Specification For Supply & Installation of Window Type Air Conditioning Units & Accessories
This document provides specifications for the supply and installation of window type air conditioning units and accessories with cooling capacities less than 36,000 BTU. It includes details on the nature of bids, power supply requirements, calibration standards, literature on equipment, warranties, and testing procedures. The air conditioning units must be ASHRAE Energy Efficiency Class A with a COP over 4.4. Components like compressors and enclosures are also specified.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
163 views
Specification For Supply & Installation of Window Type Air Conditioning Units & Accessories
This document provides specifications for the supply and installation of window type air conditioning units and accessories with cooling capacities less than 36,000 BTU. It includes details on the nature of bids, power supply requirements, calibration standards, literature on equipment, warranties, and testing procedures. The air conditioning units must be ASHRAE Energy Efficiency Class A with a COP over 4.4. Components like compressors and enclosures are also specified.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9
SPECIFICATION FOR
SUPPLY & INSTALLATION OF WINDOW TYPE AIR
CONDITIONING UNITS & ACCESSORIES
(FOR THE COOLING CAPACITY LESS THAN 36,000 BTU SPECIFIED OPERATING POINT AS PER THE SPECIFICATION)
WINDOW TYPE AIR CONDITIONING UNITS SPECIFICATION FOR INSTALLATION OF WINDOW TYPE AIR CONDITIONING UNITS AND ACCESSORIES
TABLE OF CONTENTS
Page Number 1.1 Nature of Bid 6ap - 2 1.2 Surplus Stock 6ap - 2 1.3 Power Supply 6ap - 2 1.4 Calibration of Instrument & Meters 6ap - 2 1.5 Literature on Equipments & Materials 6ap - 3 1.6 Local Materials to be used in work 6ap - 3 1.7 Installation, Testing & Commissioning 6ap - 3 1.8 Calculation of Operational Cost 6ap - 3 1.9 Warranty period 6ap - 3 2.1 General Specifications 6ap 4 2.2 Compressor Specifications 6ap - 4 2.3 Air Condition Unit Enclosure 6ap - 5 2.4 Room Conditions 6ap 6 2.5 Installation, Testing & Commissioning 6ap 6 2.6 Maintenance Period 6ap 7 2.7 Technical Literature 6ap 7 2.8 Specific Specifications 6ap 7 NWSDB/ Specification for Window type Air Conditioner 6ap - 1 CAPC : MPC : DPC : PPC : RPC :- J une 2013
SPECIFICATION FOR INSTALLATION OF WINDOW TYPE AIR CONDITIONING UNITS AND ACCESSORIES
GENERAL SPECIFICATIONS 1.1 NATURE OF BID
The Contractor shall carefully study the drawings mentioned under scope of work and fill in the price in the attached bill of quantities. It is to be distinctly understood that the total quantity Bided for is to be complete and comprehensive of all minor deficiencies if any, in the brief description. No variation or extras will be allowed except in respect of alterations, which are specially authorized in writing. No alterations shall be made without the written permission of the Engineer.
1.2 SURPLUS STOCK
No compensation shall be paid by the Board on completion of the work for any surplus stock of pipes, specials, fittings etc. and materials obtained for the purpose of this Contract. However, on completion of the Contract, the Engineer may retain any surplus stock, which would be useful for the maintenance of the above Air Conditioning Unit and pay at prices agreed upon at that time by the Engineer and the Contractor.
1.3 POWER SUPPLY
The necessary 400 / 230 V, 3 phases / single phase and neutral 50Hz electric power will be made available at the power distribution panel of the building. The power required for the distribution panel for air conditioning units shall be from the afore said electrical power distribution point and all cabling and accessories shall be provided and fixed by the Contractor.
All electrical equipment & wiring shall conform to the standards set by the I.E.E., UK as well as Sri Lanka regulations and be acceptable to the Ceylon Electricity Board, Sri Lanka.
1.4 CALIBRATION OF INSTRUMENT & METERS
All instruments & meters shall be calibrated in the Metric Units as follows;
(a) Pressure shall be indicated in kg/ cm 2
(b) Temperature in C. (c) Voltage in V. (d) Time shall be indicated in Hours (e) Amperage shall be indicated in Amperes. (f) Relative humidity in RH % with dry bulb temperature.
NWSDB/ Specification for Window type Air Conditioner 6ap - 2 CAPC : MPC : DPC : PPC : RPC :- J une 2013
1.5 LITERATURE ON EQUIPMENT AND MATERIALS
The Bidder shall supply detailed literature and specifications from the manufacturers in respect of all equipment and materials included in his offer and give the names of all such manufacturers and the countries of origin of the materials and equipment.
1.6 LOCAL MATERIALS TO BE USED IN WORK
All materials and fittings which are manufactured locally by State sponsored Corporations and other local agencies and which are up to the required standards will not be allowed to be imported and no foreign exchange will be given for the same.
1.7 INSTALLATION, TESTING AND COMMISSIONING
Refer the specific specifications for window type Air conditioning units and Accessories.
1.8 CALCULATION OF OPERATIONAL COST
In the evaluation of bidders of the capacity more than 18,000 Btu / hr Air Conditioning units with the capacity present worth of operational cost will be considered and followings will be used in calculation of operational cost.
a. Overall efficiency of the Air conditioning unit / COP b. Economic life of equipment - 07 years c. Annual operational hours of each unit (As per the specific specifications for Air Conditioning units and Accessories) d. Cost of Electrical Energy Rs 9.30 (present rate can be used) per kWh. e. Discounting Rate - 12%
1.9 WARRANTY PERIOD
The supplier should provide a warranty period of minimum 05 years for trouble free operation of the Compressor. One year trouble free warranty for all equipments and accessories supplied under this contract.
During first year of warranty period all the works describe under the maintenance period have to be attended. This should include at least six free services within warranty period.
The contractor should provide required materials, labour and spare parts during the warranty period without any charged to NWS&DB. The warranty period commenced from the completion date as per the completion certificate. The contractor has to assure that he is equipped with sufficient resources to attend any maintenance or major breakdowns immediately after inform by NWS&DB. NWSDB/ Specification for Window type Air Conditioner 6ap - 3 CAPC : MPC : DPC : PPC : RPC :- J une 2013
2. SPECIFICATION FOR INSTALLATION OF WINDOW TYPE AIR CONDITIONING UNITS AND ACCESSORIES
2.1 GENERAL SPECIFICATION
The Air Conditioning Units shall be of the window type suitable for indoor installation with wall brackets, power connection, condensate water drain piping using suitable PVC piping to the nearest common drain line. The product shall be ASHREA Energy efficiency Class A with COP not less than 4.4 .
The unit shall be housed in a Galvanized steel fabricated box with acoustic, heat insulation and vibration protected painted with corrosion resistive paints suitable for Tropical climate.
This installation shall facilitate in such a way to permit the removal of the units when the repairs to be carried out.
a. The unit shall be with fully hermitic compressor. b. Operate on a Refrigerant, free of halocarbons. c. Condenser with inbuilt fan. d. Evaporator with Squirrel Cage Fan. e. Fresh Air changing facility with facility for control for efficient operation. f. Remote Control device.
Original performance curves of the Air Conditioning units certified by the manufacturer should be furnished and photocopies will be accepted which are duly certified by the local agent.
A dimensioned drawing of the Air Conditioning Units complete with materials of manufacture shall be provided with the Bid.
The brand of the Compressor shall be provided with performance efficiency , power supply and capacity details.
2.2 COMPRESSOR SPECIFICATION
Compressor :
The Compressor shall be energy efficient fully hermitically sealed type rotary / reciprocating, 230 V / 400V +/ - 10 %, single / three phase, 50Hz. Operating on Refrigerant R 410A. NWSDB/ Specification for Window type Air Conditioner 6ap - 4 CAPC : MPC : DPC : PPC : RPC :- J une 2013
The compressor Motor shall be suitably protected against overloading using a removable suitably sized over load protection. These shall be mounted on resilient mountings for quite operation.
2.3 AIR CONDITION UNIT ENCLOSURE
2.3.1 General
The control panels shall be completely designed, fabricated assembled, wired, checked and tested at the factory as per standards and per descriptions given below.
Modern Architectural design arrangement and finish suitable for luxury living environment shall be elegant and workmanship shall be of a high order with flushed and concealed type front cover. The unit shall be wall mounted and locked on to the steel enclosure made out of Galvanized steel with protective paints suitable for tropical climate. The enclosure shall be ensure earthing. The units and all electrical components should be suitable for the operation on 230 volts +10% 01 phase 02 wire, 50Hz, AC power Supply.
2.3.2 Construction
The panels shall be of sheet metal, wall mounted as per the specification The design shall be totally enclosed, dust and rain splash-proof as per IP 55 of IEC publication 34- 5. The housing of the panel shall be fabricated of 14 SWG. The outer and inner surface of the panels shall be primed and painted with corrosive resist PVC ,Epoxy or plastic, marine grade special coating , colour as specified.
Access to all equipment mounted inside shall be from the front.
Switch gears and earth , main connections and auxiliary wiring shall be arranged and marked in general compliance with relevant British standards.
2.3.3. Earthing
A suitable earth terminal should be provided to facilitate the connection of the main earth. Earthing arrangement should be complies with BS 7430 and earth resistance of the main earth should not be exceed 5 .
2.3.4 Wiring
Control wiring shall be concealed by taking through neatly arranged PVC Spiral wire protectors and all control wires shall be terminated with cable lugs or compression type terminals. All Current carrying bolts and nuts shall be of high conducting material.
NWSDB/ Specification for Window type Air Conditioner 6ap - 5 CAPC : MPC : DPC : PPC : RPC :- J une 2013
2.3.5 Control Panel Equipment, Remote Controls and Protections
The equipment to be mounted on the control panel / Remote controller of Air Conditioning Unit shall consist of the following and starting method as per the specification.
a DOL Starting of the Compressor. b Over Load protection for the all Motor. c Thermostatic expansion and flow control of the refrigerant. d Room temperature sensor. e Fan speed control, three minimum speeds. f Compressor loading control, high / low and economical. g. With facility of on / off, room temperature indication etc.
2.4 ROOM CONDITIONS
a Please refer the room lay out and the locations suggested for the installation of the Air Conditioning units. b Room with out Air conditioning Temperature shall be 40 C with Relative humidity 90%
2.5 INSTALLATION TESTING AND COMMISSIONING
All installation work shall be carried out in accordance with relevant International Standards and codes of practice.
When all installation work is satisfactorily completed, the contractor shall inform the Engineer in writing that equipment are ready for handing over and the Engineer shall then fix a date for taking over.
At the taking over all equipment shall be tested for a period as per the application to determine the following. a Power consumption b Room Temperature and Relative Humidity at full load as given. c Vibration and Noise
If the Engineer is not satisfied with the performance of the equipment or other installation, he may refuse to take over the equipments until necessary improvements are effected. Any time necessary for this additional work will be considered as contractors delay.
NWSDB/ Specification for Window type Air Conditioner 6ap - 6 CAPC : MPC : DPC : PPC : RPC :- J une 2013
2.6 MAINTENANCE PERIOD
The Air Conditioning units and other equipment shall be satisfactorily maintained for a period of 24 months from the date of taken over. During the maintenance period, the contractor should attend to
a. All periodical service shall not be less than six. Schedule of periodical service should be submitted with the bid.
b. Maintain a maintenance record (format of maintenance record shall be submitted with bid)
c. Attending to all the repairs and replacements to avoid any failure of the system with in a time period not less than 05 working days from the date the contractor has been notified.
d. In addition to the equipment which fails, the equipments that do not give satisfactory performance during the period of maintenance shall be replaced by the contractor with in 3 weeks from the date the contractor has been notified.
e. In order to cut down the down time in the event of any major failure of unit the supplied should provide the spare unit till such time the unit is replaced after repairs.
The expenses involved in this connection shall be born by the contractor who should take this in to consideration when biding.
If the contractor is not attended to the repair within the time specified as above, the engineer has the right to rectify the fault and claim the cost thus incurred from the contractor.
2.7 TECHNICAL LITERATURE
The following technical literature for the Air conditioning units, Remote Controls, and accessories, shall be forwarded along with offer.
a) Technical Specification of the Air conditioning units (Features, dimensions, cross Sectional drawing of the Air Conditioning unit showing materials, etc.)
2.8 SPECIFIC SPECIFICATIONS
The Air conditioning unit / units shall be provided the following room conditions and requirements
NWSDB/ Specification for Window type Air Conditioner 6ap - 7 CAPC : MPC : DPC : PPC : RPC :- J une 2013
2.8.1 Number of Occupants .. 2.8.2 Number of Air changes per hour not less than 6 Nos 2.8.3 Floor Area - .. m 2 and room height .. m 2.8.4 Walls Brick / thickness 2.8.5 Type of Ceiling / Floor Slab -.. 2.8.6 Number of Windows - . 2.8.7 Electrical Equipment inside the Room and the heat out put
a. Room Lighting b. Printers .. c. Computers .. d. Photo copiers .. e Any other Heat sources.
2.8.8 Room after Air Conditioning shall be 20C with Relative Humidity 65% 2.8.9 Noise level at full load condition shall be less than 55dB ( A )
NWSDB/ Specification for Window type Air Conditioner 6ap - 8 CAPC : MPC : DPC : PPC : RPC :- J une 2013