0% found this document useful (0 votes)
73 views

Sizing of Power Cables For Circuit Breaker Controlled Feeders Part I

This document discusses criteria for sizing power cables for circuit breaker controlled feeders, including short circuit current withstand capacity, continuous current carrying capacity, and voltage drop. It provides equations and tables for determining minimum cable size based on short circuit duration, which is based on circuit breaker operating times. An example calculation selects a 240mm2 cable size for a 415V motor feeder based on withstanding 50kA for 160ms.

Uploaded by

javad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
73 views

Sizing of Power Cables For Circuit Breaker Controlled Feeders Part I

This document discusses criteria for sizing power cables for circuit breaker controlled feeders, including short circuit current withstand capacity, continuous current carrying capacity, and voltage drop. It provides equations and tables for determining minimum cable size based on short circuit duration, which is based on circuit breaker operating times. An example calculation selects a 240mm2 cable size for a 415V motor feeder based on withstanding 50kA for 160ms.

Uploaded by

javad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 6

Sizing of power cables for circuit breaker

controlled feeders (part 1)


Posted May 10 2012 by Asif Eqbal in Cables, Low Voltage with 21 Comments

Low voltage switchboard with circuit breakers (incomers, feeders)

The following three criteria apply for the sizing of cables for circuit breaker controlled feeders:
I. Short circuit current withstand capacity
This criteria is applied to determine the minimum cross section area of the cable, so that cable
can withstand the short circuit current.
Failure to check the conductor size for short-circuit heating could result in permanent damage to
the cable insulation and could also result into fire. In addition to the thermal stresses, the cable
may also be subjected to significant mechanical stresses.
II. Continuous current carrying capacity
This criteria is applied so that cross section of the cable can carry the required load current
continuously at the designed ambient temperature and laying condition.
III. Starting and running voltage drops in cable
This criteria is applied to make sure that the cross sectional area of the cable is sufficient to keep
the voltage drop (due to impedance of cable conductor) within the specified limit so that the
equipment which is being supplied power through that cable gets at least the minimum required
voltage at its power supply input terminal during starting and running condition both.

1. Criteria-1 Short circuit capacity
The maximum temperature reached under short circuit depends on both the magnitude and
duration of the short circuit current. The quantity I2t represents the energy input by a fault that
acts to heat up the cable conductor. This can be related to conductor size by the formula:

A = Minimum required cross section area in mm2
t = Operating time of disconnecting device in seconds
Isc = RMS Short Circuit current Value in Ampere
C = Constant equal to 0.0297 for copper & 0.0125 for aluminum
T2 = Final temp. C (max. short circuit temperature)
T1 = Initial temp. C (max. cable operating temperature normal conditions)
T0 = 234.5 C for copper and 228.1 C for aluminum
Equation-1 can be simplified to obtain the expression for minimum conductor size as given
below in equation-2:

Now K can be defined as a Constant whose value depends upon the conductor material, its
insulation and boundary conditions of initial and final temperature because during short circuit
conditions, the temperature of the conductor rises rapidly. The short circuit capacity is limited by
the maximum temperature capability of the insulation. The value of K hence is as given in Table
2.
Boundary conditions of initial and final temperature for different insulation is as given under in
Table 1 below.
Table 1
Insulation material Final temperature T
2
Initial temperature T
1

PVC 160 C 70 C
Butyl Rubber 220 C 85 C
XLPE / EPR 250 C 90 C
Table 2
Material Copper Aluminum
Insulation PVC Butyl Rubber XLPE / EPR PVC Butyl Rubber XLPE / EPR
(K) 1 Second Current
Rating in Amp/mm
2

115 134 143 76 89 94
(K) 3 Second Current
Rating in Amp/mm
2

66 77 83 44 51 54

In the final equation-2 we have determined the value of constant K. Now the value of t is to
be determined. The fault current (ISC) in the above equation varies with time. However,
calculating the exact value of the fault current and sizing the power cable based on that can be
complicated. To simplify the process the cable can be sized based on the interrupting capability
of the circuit breakers/fuses that protect them.
This approach assumes that the available fault current is the maximum capability of the
breaker/fuse and also accounts for the cable impedances in reducing the fault levels.
The fault clearing time (tc) of the breakers/fuses per ANSI/IEEE C37.010, C37.013, and UL
489 are:
For medium voltage system (4.16 kV) breakers, use 5-8 cycles
For starters with current limiting fuses, use cycle
For low voltage breakers with intermediate/short time delay, use 10 cycles
For low voltage breakers with instantaneous trips, use 1 cycle
Alternatively let us consider that feeder is for any large motor which is being fed from LV 415V
or 400V switchgear having a circuit breaker with separate multifunction motor protection relay
(For this calculation it is assumed to be SIEMENS made 7SJ61).
The instantaneous protection feature of this relay will be turned ON as and when any fault
occurs. However, the selected cable shall have the capacity to withstand the maximum fault
current for a finite duration (that is fault clearing time of the circuit breaker).
The minimum faults withstand duration necessary (for the instantaneous setting) for cable
is calculated as under:
Si. No. Parameters
Time in
ms
Source/Back up
1 Relay sensing/pickup time 20 SIEMENS 7SJ61 technical data
2 Tolerance/Delay time 10 SIEMENS 7SJ61 technical data
3 Breaker operating time 40
L&T make C-Power breaker have typical
opening
time of 40 ms and closing time of 60ms)
4 Relay overshoot 20 GEC handbook Network Protection &
automation
Guide
5 Safety Margin 30
TOTAL TIME IN MILI
SECONDS
120

Therefore the cable selected for a circuit breaker controlled motor feeder in 415V or
400V switchgear shall be suitable to withstand the maximum rated fault current of 50kA for at
least 120msec. However taking allowance of 40 Mili seconds in the opening time of circuit
breaker due to aging, frequent number of operation, increase in contact resistance of circuit
breaker and finally to cover the variation due from manufacturer to manufacturer.
Hence the cable selected for a circuit breaker controlled motor feeder in 415V or 400V
switchgear shall be suitable to withstand the maximum rated fault current of 50kA for at least
(120+40) 160msec. Many consultants recommend for use operating time of disconnecting device
as 200msec also. Value of t more than 160 seconds is a conservative design.
A = (Isc x t)/K = (50000 x 0.16)/94 = 212.766mm
2

Next standard cable size: = 240 mm
2

Although it may appear that selection of minimum cross sectional area of cable conductor as
240 mm
2
is only just large enough for the duty, the actual fault current in the motor circuit is
generally less than the switchboard fault withstand rating of 50kA, hence the selection of cable
of cross sectional area 240 mm2 in practice offers sufficient design margin.
The minimum cross sectional area of cable required for 415V or 400V switchgear motor feeder
from fault withstand point of view shall be 240mm
2
.
We have considered for circuit breaker controlled motor feeder and analyzed the duration of
short circuit/fault withstanding time in seconds for the same. Exactly the Same holds true for
Circuit breaker controlled (Please see the below figure) outgoing transformer feeder.
However operating time of disconnecting device is slightly different for circuit breaker
controlled incomer and tie feeders. Duration of fault withstanding/operating time of
disconnecting device for incomer and tie feeder is 1 and 0.5 second respectively. This is because
of additional presence of inverse definite minimum time delay protection relays along with
instantaneous protection. The inverse definite time delay protection has time settings greater than
0.5 for incomer feeders and about 0.5 for tie feeders.
For all different type of feeders the operating time of disconnecting device is indicated in figure
below:

Typical value of t (fault clearing time). All the connecting cables has to be sized for short circuit
duration (t) indicated in the diagram above

The final cable size shall be selected considering the other two criteria that is continuous
current carrying capacity & voltage drop criteria which would be continued in part-2 and part-3.

You might also like