MAM Technical Specification
MAM Technical Specification
MAM Series
Technical Data
Dimensional Data
Installation Diagram
10
11
Operating Sequence
12
Specifications
13
MAM220906
-1-
Technical Data
SUPPLY AIR DATA
CFM
ESP
400
0.3
ELECTRICAL DATA
V/Ph/Hz
Compressor (Nominal TR)
RLA (Amps)
LRA (Amps)
Blower Motor (HP)
FLA (Amps)
Minimum Ampacity (Amps)
Maximum Fuse Size (Amps)
Power Consumption (kW)
115/1/60
1.25
13.0
75.0
1/8
2.4
19
30
1.3
PERFORMANCE DATA
Air Temp
40% RH
F
lb/h
Smbh
70
1.0
10.1
74
1.6
10.3
78
2.5
10.5
82
2.6
11.0
86
2.8
11.4
90
3.5
11.9
93
4.7
12.0
96
4.9
12.3
100
5.2
13.7
Tmbh
11.1
12.0
13.1
13.8
14.4
15.6
16.9
17.5
19.1
208-230/1/60
1.25
7.0
34.2
1/8
1.0
10
15
1.3
lb/h
2.5
3.0
3.6
4.0
4.5
5.9
6.2
7.0
7.3
50% RH
Smbh
9.1
9.4
9.7
10.1
10.5
10.6
10.8
11.0
12.2
Tmbh
11.8
12.5
13.5
14.3
15.2
16.8
17.4
18.4
19.9
lb/h
3.2
4.5
5.1
5.7
6.9
7.7
8.7
-
60% RH
Smbh
8.4
8.6
8.8
9.2
9.2
9.4
9.5
-
Tmbh
12.4
13.3
14.1
15.1
16.5
17.5
18.6
-
lb/h
5.0
5.8
6.5
7.3
8.6
9.6
-
70% RH
Smbh
7.6
7.8
8.0
8.0
8.1
8.5
-
Tmbh
7.6
13.8
14.8
15.7
17.2
18.6
-
AIR CONDITIONING
Total Heat of Rejection = 19940 Btu/h
Air Cooled:
Condenser
Model
CCA-002
CCA-002
Air on
OACC F
90
95
Total System
Charge (lb. R22)
24*
24*
CCA-002
100
24*
Water Cooled:
Flow
gpm
0.7 - 4.3
P
psi
0.5 - 2.8
Water Temp
Range F
45 - 90
Total System
Charge (lb R22)
3.5
Allows the unit to dehumidify and supply air reheated up to room temperature. Ideal for applications where the MAM
replaces an existing Air Conditioner.
4 Row
Allows the unit to reject all the compressor heat into the space. Ideal for small spas and whirlpools.
*The receiver is sized for a maximum of 50 linear ft. refrigerant line lengths and/or not more than 6 feet below the MAM unit.
MAM0604
-2-
Technical Data
SUPPLY AIR DATA
CFM
ESP
485
0.3
ELECTRICAL DATA
V/Ph/Hz
Compressor (Nominal TR)
RLA (Amps)
LRA (Amps)
Blower Motor (HP)
FLA (Amps)
Minimum Ampacity (Amps)
Maximum Fuse Size (Amps)
Power Consumption (kW)
208-230/1/60
2.0
13.6
63.0
1/8
1.0
18
30
2.1
208-230/3/60
2.0
6.6
50.0
1/8
1.0
10
15
2.1
PERFORMANCE DATA
Air Temp
40% RH
F
lb/h
Smbh
70
2.6
16.0
74
3.5
16.3
78
4.9
16.4
82
4.7
17.2
86
5.5
17.6
90
6.4
18.2
93
8.0
17.7
96
8.3
18.6
100
9.5
19.0
Tmbh
18.7
19.9
21.5
22.1
23.4
24.9
26.1
27.3
28.9
50% RH
Smbh
14.5
14.9
15.2
15.8
16.3
16.4
16.6
-
lb/h
4.7
5.7
6.3
7.2
8.1
9.9
10.5
-
460/3/60
2.0
3.4
25.0
1/3
1.2
6
15
2.1
Tmbh
19.4
20.8
21.8
23.3
24.8
26.8
27.6
-
Lb/h
6.7
7.7
8.9
9.5
11.3
13.0
-
60% RH
Smbh
13.4
13.7
13.8
14.1
14.2
14.4
-
Tmbh
20.5
21.8
23.2
24.1
26.1
28.0
-
lb/h
8.7
9.7
10.9
12.1
14.5
-
70% RH
Smbh
12.4
12.5
12.7
12.7
12.9
-
Tmbh
21.5
22.6
24.1
25.4
28.1
-
AIR CONDITIONING
Total Heat of Rejection = 30726 Btu/h
Air Cooled:
Condenser
Model
CCA-002
CCA-002
CCA-002
Air on
OACC F
90
95
100
Total System
Charge (lb. R22)
27*
27*
27*
Water Cooled:
Flow
P
gpm
psi
1.1 7.0
0.8 6.6
Water Temp
Range F
45 - 90
Total System
Charge (lb. R22)
5.7
Allows the unit to dehumidify and supply air reheated up to room temperature. Ideal for applications where the MAM
replaces an existing Air Conditioner.
6 Row
Allows the unit to reject all the compressor heat into the space. Ideal for small spas and whirlpools.
*The receiver is sized for a maximum of 50 linear ft. refrigerant line lengths and/or not more than 6 feet below the MAM unit.
MAM0405
-3-
Technical Data
SUPPLY AIR DATA
CFM
ESP
600
0.3
ELECTRICAL DATA
V/Ph/Hz
Compressor (Nominal TR)
RLA (Amps)
LRA (Amps)
Blower Motor (HP)
FLA (Amps)
Minimum Ampacity (Amps)
Maximum Fuse Size (Amps)
Power Consumption (kW)
208-230/1/60
2.3
15.0
72.5
1/4
1.5
21
35
2.5
208-230/3/60
2.3
10.0
63.0
1/4
1.5
14
20
2.5
PERFORMANCE DATA
Air Temp
40% RH
F
lb/h
Smbh
70
3.1
20.0
74
4.2
20.6
78
6.0
20.6
82
5.9
21.7
86
6.8
22.1
90
7.7
22.7
93
8.5
22.7
96
10.2
23.3
100
10.7
23.4
Tmbh
23.2
25.0
26.9
27.9
29.3
30.7
31.6
34.0
34.6
50% RH
Smbh
18.3
18.5
19.3
19.7
20.5
20.9
21.1
-
lb/h
6.0
7.0
8.0
8.8
10.0
11.9
13.2
-
460/3/60
2.3
5.0
31.0
1/3
1.2
8
15
2.5
Tmbh
24.6
25.9
27.7
28.9
31.0
33.3
34.9
-
Lb/h
8.2
9.5
10.9
12.1
14.3
16.1
-
60% RH
Smbh
16.7
17.2
17.3
18.0
18.8
19.0
-
Tmbh
25.3
27.1
28.7
30.7
33.8
35.9
-
lb/h
10.7
12.0
13.4
15.3
17.6
-
70% RH
Smbh
15.4
15.5
15.7
16.1
16.9
-
Tmbh
26.6
28.1
29.7
32.2
35.4
-
AIR CONDITIONING
Total Heat of Rejection = 37750 Btu/h
Air Cooled:
Condenser
Model
CCA-002
CCA-003
CCA-003
Air on
OACC F
90
95
100
Total System
Charge (lb R22)
27*
30*
30*
Water Cooled:
Flow
P
gpm
psi
1.3 7.1
1.0 5.1
Water Temp
Range F
45 - 90
Total System
Charge (lb R22)
6.3
Allows the unit to dehumidify and supply air reheated up to room temperature. Ideal for applications where the MAM
replaces an existing Air Conditioner.
6 Row
Allows the unit to reject all the compressor heat into the space. Ideal for small spas and whirlpools.
*The receiver is sized for a maximum of 50 linear ft. refrigerant line lengths and/or not more than 6 feet below the MAM unit.
MAM0304
-4-
Technical Data
SUPPLY AIR DATA
CFM
ESP
745
0.3
ELECTRICAL DATA
V/Ph/Hz
Compressor (Nominal TR)
RLA (Amps)
LRA (Amps)
Blower Motor (HP)
FLA (Amps)
Min. Ampacity (Amps)
Max. Fuse Size (Amps)
Power Consumption (kW)
208-230/1/60
2.75
17.9
88.0
1/4
1.5
24
40
2.9
PERFORMANCE DATA
Air Temp
40% RH
F
lb/h
Smbh
70
3.6
24.7
74
5.0
25.0
78
7.1
25.2
82
6.8
26.6
86
7.9
27.2
90
9.0
27.8
93
11.8
28.5
96
12.7
28.8
100
13.7
29.3
Tmbh
28.5
30.2
32.6
33.8
35.5
37.3
40.9
42.1
43.7
lb/h
7.0
8.6
9.4
10.5
11.6
14.2
15.0
-
208-230/3/60
2.75
11.4
77.0
1/4
1.5
16
25
2.9
50% RH
Smbh
22.4
22.9
23.6
24.1
24.8
24.9
25.3
-
460/3/60
2.75
5.7
39.0
1/3
1.2
9
15
2.9
Tmbh
29.7
32.0
33.5
35.2
37.0
39.9
41.1
-
Lb/h
10.0
11.4
13.0
14.3
16.8
19.5
-
575/3/60
2.75
4.71
31.0
1/2
1.6
8
15
2.9
60% RH
Smbh
20.7
20.9
21.1
21.9
21.9
22.1
-
Tmbh
31.2
32.9
34.7
36.9
39.5
42.6
-
lb/h
12.8
14.5
16.3
18.0
20.8
-
70% RH
Smbh
18.7
18.8
19.2
19.4
19.6
-
Tmbh
32.1
34.1
36.4
38.3
41.4
-
AIR CONDITIONING
Total Heat of Rejection = 45580 Btu/h
Air Cooled:
Condenser
Model
CCA-003
CCA-004
CCA-004
Water Cooled:
Flow gpm
1.6 9.2
Air on
OACC F
90
95
100
Total System
Charge (lb R22)
32*
31*
31*
P
psi
1.5 6.0
Water Temp
Range F
45 - 90
Total System
Charge (lb R22)
8.0
Allows the unit to dehumidify and supply air reheated up to room temperature. Ideal for applications where the MAM
replaces an existing Air Conditioner.
6 Row
Allows the unit to reject all the compressor heat into the space. Ideal for small spas and whirlpools.
*The receiver is sized for a maximum of 50 linear ft. refrigerant line lengths and/or not more than 6 feet below the MAM unit.
MAM0304
-5-
Technical Data
SUPPLY AIR DATA
CFM
ESP
850
0.3
ELECTRICAL DATA
V/Ph/Hz
Compressor (Nominal TR)
RLA (Amps)
LRA (Amps)
Blower Motor (HP)
FLA (Amps)
Min. Ampacity (Amps)
Max. Fuse Size (Amps)
Power Consumption (kW)
208-230/1/60
3.3
20.0
104.0
1/3
2.2 - 2.5
28
45
3.5
PERFORMANCE DATA
Air Temp
40% RH
F
lb/h
Smbh
70
4.5
28.3
74
5.8
28.6
78
8.3
28.8
82
8.0
30.4
86
9.6
31.4
90
10.9
32.1
93
13.8
32.8
96
14.9
33.4
100
15.8
34.1
Tmbh
33.0
34.7
37.5
38.8
41.5
43.6
47.3
49.1
50.7
lb/h
8.1
9.9
10.9
12.5
13.8
16.8
18.8
-
208-230/3/60
3.3
13.9
88.0
1/3
2.2 - 2.5
20
30
3.5
50% RH
Smbh
25.6
26.2
27.0
27.9
28.7
28.9
30.5
-
460/3/60
3.3
6.4
44.0
1/3
1.2
10
15
3.5
Tmbh
34.1
36.6
38.4
41.0
43.2
46.5
50.3
-
Lb/h
11.3
13.2
15.5
16.5
19.8
22.3
-
575/3/60
3.3
5.4
34.0
1/2
1.6
9
15
3.5
60% RH
Smbh
23.3
24.0
24.5
25.0
25.1
25.2
-
Tmbh
35.2
37.8
40.7
42.3
45.9
48.7
-
lb/h
14.8
17.0
19.0
21.2
24.5
-
70% RH
Smbh
21.4
21.9
22.2
22.5
22.7
-
Tmbh
37.0
39.8
42.2
44.7
48.4
-
AIR CONDITIONING
Total Heat of Rejection = 53300 Btu/h
Air Cooled:
Condenser
Model
CCA-004
CCA-005
CCA-005
Water Cooled:
Flow gpm
1.6 10.0
Air on
OACC F
90
95
100
Total System
Charge (lb R22)
31
46
46
P
psi
1.2 5.2
Water Temp
Range F
45 - 90
Total System
Charge (lb R22)
8.6
Allows the unit to dehumidify and supply air reheated up to room temperature. Ideal for applications where the MAM
replaces an existing Air Conditioner.
6 Row
Allows the unit to reject all the compressor heat into the space. Ideal for small spas and whirlpools.
*The receiver is sized for a maximum of 50 linear ft. refrigerant line lengths and/or not more than 6 feet below the MAM unit.
MAM0304
-6-
Technical Data
SUPPLY AIR DATA
CFM
ESP
960
0.3
ELECTRICAL DATA
V/Ph/Hz
Compressor (Nominal TR)
RLA (Amps)
LRA (Amps)
Blower Motor (HP)
FLA (Amps)
Min. Ampacity (Amps)
Max. Fuse Size (Amps)
Power Consumption (kW)
208-230/1/60
3.8
21.4
137.0
1/3
2.2 - 2.5
29 - 30
50
4.0
PERFORMANCE DATA
Air Temp
40% RH
F
lb/h
Smbh
70
5.7
33.1
74
7.4
33.4
78
10.2
33.5
82
9.7
35.2
86
11.6
36.3
90
13.2
37.2
93
16.7
37.5
96
17.9
37.9
100
19.1
38.7
Tmbh
39.1
41.2
44.2
45.3
48.4
51.0
55.0
56.7
58.8
lb/h
10.3
11.8
13.0
15.0
16.5
20.0
21.6
-
208-230/3/60
3.8
16.4
91.0
1/3
2.2 - 2.5
23
35
4.0
50% RH
Smbh
30.0
30.4
31.2
32.3
33.2
33.3
33.5
-
460/3/60
3.8
6.6
46.0
1/3
1.2
10
15
4.0
Tmbh
40.8
42.8
44.9
48.1
50.6
54.3
56.1
-
Lb/h
13.6
15.6
18.3
19.9
23.4
26.5
-
575/3/60
3.8
5.3
30.0
1/2
1.6
9
15
4.0
60% RH
Smbh
27.5
27.8
28.4
29.3
29.6
29.9
-
Tmbh
41.8
44.2
47.6
50.2
54.2
57.7
-
lb/h
17.4
19.9
22.4
24.8
29.3
-
70% RH
Smbh
24.9
25.7
25.9
26.1
26.2
-
Tmbh
43.2
46.6
49.4
52.1
57.0
-
AIR CONDITIONING
Total Heat of Rejection = 62170 Btu/h
Air Cooled:
Condenser
Model
CCA-005
CCA-006
CCA-006
Water Cooled:
Flow gpm
1.9 12.7
Air on
OACC F
90
95
100
Total System
Charge (lb R22)
48*
52*
52*
P
psi
1.2 7.4
Water Temp
Range F
45 - 90
Total System
Charge (lb R22)
10.8
Allows the unit to dehumidify and supply air reheated up to room temperature. Ideal for applications where the MAM
replaces an existing Air Conditioner.
6 Row
Allows the unit to reject all the compressor heat into the space. Ideal for small spas and whirlpools.
*The receiver is sized for a maximum of 50 linear ft. refrigerant line lengths and/or not more than 6 feet below the MAM unit.
MAM0906
-7-
Technical Data
SUPPLY AIR DATA
CFM
ESP
1230
0.3
ELECTRICAL DATA
V/Ph/Hz
Compressor (Nominal TR)
RLA (Amps)
LRA (Amps)
Blower Motor (HP)
FLA (Amps)
Min. Ampacity (Amps)
Max. Fuse Size (Amps)
Power Consumption (kW)
208-230/1/60
5.0
32.1
148.0
1/2
2.8 - 3.2
43 - 44
70
5.3
PERFORMANCE DATA
Air Temp
40% RH
F
lb/h
Smbh
70
7.6
42.8
74
9.7
43.3
78
13.6
43.6
82
13.3
46.1
86
15.3
47.0
90
17.4
48.1
93
22.7
48.8
96
23.3
49.1
100
26.0
50.7
Tmbh
50.8
53.5
57.9
60.0
63.0
66.4
72.7
73.6
78.0
lb/h
13.0
15.9
17.6
19.6
22.3
26.3
27.8
-
208-230/3/60
5.0
19.3
137.0
1/2
2.8 - 3.2
27 - 28
45
5.3
50% RH
Smbh
38.9
39.9
41.0
41.9
43.6
43.9
44.0
-
460/3/60
5.0
9.1
62.0
3/4
2.7
15
20
5.3
Tmbh
52.6
56.6
59.5
62.5
67.0
71.5
73.2
-
Lb/h
18.2
20.9
23.9
26.6
30.6
33.9
-
575/3/60
5.0
7.9
50.0
1/2
1.6
12
15
5.3
60% RH
Smbh
36.2
36.6
36.9
38.5
38.8
39.7
-
Tmbh
55.3
58.6
62.0
66.5
70.9
75.3
-
lb/h
23.1
25.9
29.1
32.6
37.9
-
70% RH
Smbh
32.9
33.3
33.6
34.1
35.0
-
Tmbh
57.1
60.5
64.2
68.3
74.8
-
AIR CONDITIONING
Total Heat of Rejection = 80940 Btu/h
Air Cooled:
Condenser
Model
CCA-007
CCA-008
CCA-008
Water Cooled:
Flow gpm
2.6 16.5
Air on
OACC F
90
95
100
Total System
Charge (lb R22)
60*
68*
68*
P
psi
0.5 9.0
Water Temp
Range F
45 - 90
Total System
Charge (lb R22)
14.5
Allows the unit to dehumidify and supply air reheated up to room temperature. Ideal for applications where the MAM
replaces an existing Air Conditioner.
6 Row
Allows the unit to reject all the compressor heat into the space. Ideal for small spas and whirlpools.
*The receiver is sized for a maximum of 50 linear ft. refrigerant line lengths and/or not more than 6 feet below the MAM unit.
MAM0304
-8-
-9-
Installation
MAM Series
The receiver is sized for a maximum of 50 linear ft. refrigerant line lengths and/or not more than 6 feet below the MAM unit.
MAM0304
- 10 -
Field Wiring
MAM Series
Air-cooled
A/C only
MAM0304
- 11 -
Operating Sequence
MAM Series
MAM0304
- 12 -
Specifications
1.
GENERAL
1.1
Scope
MAM Series
.1
Unit shall be specifically designed for dehumidification and cooling. The unit shall
operate from a remote thermostat and humidistat.
.2
.3
Optional
The system shall have an air-conditioning option to reject compressor heat during the
air-conditioning season.
1.2
.1
.2
.3
.4
Piping in accordance with BOCA code M-702.0 for joints and connections. All refrigerant
pipes shall be copper type "L".
.5
Manufacturer shall have an environmental and quality control test chamber. The
unit shall undergo a 15-point design review and 60-point quality control review.
.2
.3
Test report shall be available on request. Engineer reserves the right to witness
factory performance testing.
.4
Manufacturer of the packaged system for humidity control shall have a minimum of
five years experience in the production of these systems.
.5
The system shall have a limited warranty for twenty-five months from the date of
shipment.
.6
MAM0506
- 13 -
Specifications
1.3
MAM Series
Basis of Design
.1
Unit shall be base bid with specified Dectron Inc. (DRY-O-TRON) with capacities as
scheduled.
.2
An Add or Deduct Alternate (substitution) may be provided as indicated on the bid form
subject to the following conditions:
1.4
A.
Substitution shall include revised layout including details on duct, piping, and
power connections.
B.
C.
Increased operating costs due to larger blower motors, compressors and water
pumps shall be highlighted as part of the disclosure package.
D.
Submittals
.1
Submit overall dimension drawings, field wiring diagram, and product data including air
flow, static pressures, total power consumption, moisture removal capacity, moisture
removal efficiency, air leaving conditions under all operating modes, water heater
characteristics and total refrigerant charge.
.2
.3
A copy of a similarly sized units actual quality control and testing report to be submitted
for the engineers review.
1.5
.1
MAM0506
- 14 -
Specifications
2.
PRODUCTS
2.1
General
MAM Series
.1
The dehumidifiers shall be split air cooled or packaged water-cooled units. Air handling
section shall include compressor, evaporator (dehumidifying coil), hot gas reheat coil,
supply air blower, blower motor, contactors and controls in one complete enclosure.
Systems using condensing units shall not be acceptable.
.2
Air cooled units shall be field charged with R-22 refrigerant. Water cooled units are
factory charged with R-22 refrigerant.
.3
.4
Optional
The unit shall be supplied with a hot gas reheat (condenser) coil capable of rejecting
100% of the compressor heat.
.5
Optional
The unit shall be configured to reject heat to a water loop.
2.2
.1
2.3
Principle of Operation
The unit shall operate according to the following sequence. The returned humid air
passes through the dehumidifying coil and is cooled below its dew point, thereby
condensing moisture. The heat captured by this process and the heat generated by the
compressor power consumption are absorbed by a mechanical refrigeration system.
This recovered heat can then be used to reheat the air. On a call for cooling all the heat
is rejected to the remote outdoor air-cooled condenser or fluid loop.
Cabinet
.1
The base shall be constructed of 16-gauge satin coated sheet metal. Cold rolled steel
shall not be acceptable. The entire base shall be phosphate degreased and painted
with baked epoxy powder paint, providing a chlorine and pool chemistry resistant finish.
The metal shall be formed and reinforced for maximum rigidity.
.2
Removable service panels shall be furnished to provide access to all internal parts from
both sides and in both sections.
.3
The units shall be constructed of 20-gauge satin-coated sheet metal. All metal to be
phosphate degreased and then painted baked epoxy powder paint, providing a chlorine
and pool chemistry resistant finish.
.4
Each unit shall have a built-in electrical control panel in a separate compartment in order
not to disturb the air flow within the dehumidifier during electrical servicing. All electrical
MAM0506
- 15 -
Specifications
MAM Series
2.4
.1
2.5
The unit shall have a built-in air filter rack with separate hinged access door with
compression fasteners.
Insulation
Entire coil section shall be insulated to prevent condensation with 1/2-inch thick
fiberglass duct liner insulation, approved for 250F operating temperature and up to
5,000 fpm air velocity. Surface to be protected against perforation with a reinforcing
mesh. Fire resistance rating to conform with NFPA Standard 90A. Sound attenuation
coefficient shall be not less than 0.64 at a frequency of 1000 Hz as per ASTM Standard
C423. Thermal conductivity shall be not more than 0.232 Btu in/h sq. ft. F at 75F.
Insulation shall be securely fastened by spot welding to become an integral component
of the enclosure and held on by mechanical fasteners. Adhesives shall not be
acceptable.
Evaporator (Dehumidifier Coil)
.1
Shall not be less than four rows deep on MAM-016, or six rows deep on MAM-024 to
MAM-060 for maximum moisture removal capacity. Air velocity not to exceed 300 fpm,
with 3/8-inch OD seamless copper tubing mechanically expanded to assure high heat
transfer with maximum twelve aluminum fins per inch on MAM-016 or ten aluminum fins
per inch on MAM-024 to MAM-060.
.2
Shall be HyPoxy coated fins for maximum corrosion resistance. Untreated fin material
shall not be acceptable. Coating shall comply with ASTM B117/D1654 and ASTM
D2126 for corrosion resistance.
.3
.4
Coil shall be factory tested at air pressures not less than 400 psig in a water bath.
.5
Optional
Coil shall have an optional third-to-fifth year extended warranty underwritten by the
dehumidifier manufacturer. Third party coverage shall not be acceptable.
.6
Optional
Coil shall have an optional third-to-tenth year extended warranty underwritten by the
dehumidifier manufacturer. Third party coverage shall not be acceptable.
MAM0506
- 16 -
Specifications
MAM Series
Shall be sized to transfer no less than 20F reheat from the compressor heat of rejection
into the air if necessary with 3/8-inch OD seamless copper tubing mechanically
expanded to assure high heat transfer with maximum twelve facetized aluminum fins per
inch. Systems using sources other than compressor hot gas for reheat shall not be
acceptable.
.2
Shall be HyPoxy coated fins for maximum corrosion resistance. Untreated fin material
shall not be acceptable. Coating shall comply with ASTM B117/D1654 and ASTM
D2126 for corrosion resistance.
.3
.4
Coil shall be factory tested at air pressures not less than 400 psig in a water bath.
.5
Optional
Shall be sized to transfer 100% of the compressor heat of rejection into the air if
necessary with 3/8-inch OD seamless copper tubing mechanically expanded to assure
high heat transfer with maximum twelve facetized aluminum fins per inch. Systems
using sources other than compressor hot gas for reheat shall not be acceptable.
.6
Optional
Coil shall have an optional third-to-fifth year extended warranty underwritten by the
manufacturer. Third party coverage shall not be acceptable.
.7
Optional
Coil shall have an optional third-to-tenth year extended warranty underwritten by the
manufacturer. Third party coverage shall not be acceptable.
2.7
Drain Pan
.1
The air handling section shall be equipped with a non-trapping drain pan under the
entire evaporator coil and prevent condensate carryover. Drain pans susceptible to
water pooling and subsequent bacteria growth shall not be acceptable.
.2
The drain pan shall be made of 20-gauge, 304-type stainless steel, insulated with
1/8-inch closed cell insulation on the bottom and sides of the drain pan.
2.8
.1
Blower
Shall be double width, double inlet, multi-blade forward curved centrifugal type blower
wheel, dynamically and statically balanced and tested, mounted on a solid steel shaft
coated with silicon.
MAM0506
- 17 -
Specifications
.2
2.9
MAM Series
Shall have a galvanized steel wheel and galvanized steel casing painted with a baked
enamel finish.
Blower Motor
.1
Shall be open drip-proof, multi-speed, induction type, 40C ambient, pre-lubricated ball
bearings.
.2
2.10
Compressor
.1
Shall be hermetic compressor, suction gas cooled, suitable for refrigerant R-22,
equipped with internal thermal overload protection and resilient type external mounting.
.2
Compressor manufacturer must have a wholesale outlet for replacement parts in the
nearest major city.
2.11
Refrigeration Circuit
.1
Shall have an in-line solder type liquid line filter drier, liquid and moisture indicator
visible from outside the unit, thermostatic expansion valve, head pressure control and
receiver with fusible plug on water cooled units or receiver with pressure relief valve on
air cooled units.
.2
Tamper proof, hermetically sealed non-adjustable high and low pressure controls and
refrigeration service valves shall be installed using Schraeder type valves.
.3
.4
Suction line shall be fully insulated with not less than 1/2-inch closed cell insulation.
2.12
Control Panel
.1
.2
.3
.4
MAM0506
- 18 -
Specifications
MAM Series
.5
Color coding and wire numbering shall be provided for easy troubleshooting.
.6
.7
.8
The unit shall be controlled by both a remote thermostat and humidistat. Each controller
can independently control unit operation without interfering with unit performance.
2.13
.1
2.14
Air Filters
Shall be 1-inch disposable type suitable for commercial application, to handle average
dust loading. Initial resistance of 0.08-inch W.G. and average arrestance efficiency of
80% based on 500-fpm air velocity.
OPTIONAL - Water-Cooled Air Conditioning
.1
Unit shall be completely packaged design equipped with air conditioning feature to reject
all compressor heat to a water-cooled condenser.
.2
The cooling water heat exchanger shall be coaxial, for maximum heat transfer from
refrigerant to cooling water. Heat exchanger shall be corrosion resistant, copper water
circuit, self-draining counter flow design. Water circuit shall be supplied with self-aligning
union fittings for easy connection. Heat exchanger shall be UL Listed or Recognized
and/or CSA Certified.
.3
3.
3.1
.1
Cabinet including base shall be constructed of 18-gauge satin coated sheet metal.
Service panel shall be furnished to provide access to all internal parts. Cabinet shall
have two coats of baked enamel finish. Fan outlet and air intake grilles shall be PVC
coated. Cabinet shall have mounting legs.
MAM0506
- 19 -
Specifications
MAM Series
.2
.3
Unit shall have dynamically balanced fan in conjunction with the dual venturi (inlet and
outlet venturies with insulation in-between) to optimize air flow with reduced air noise.
.4
Fan motor shall be permanently lubricated ball bearing type with built-in overload
protection. CCA-002 through CCA-007 motor shall not exceed 825 RPM (1-phase), 900
RPM (3-phase) for low operating decibel level. CCA-008 motor shall not exceed 1075
RPM (1-phase), 1140 RPM (3-phase). Motor shall be factory wired to a unit mounted
control panel with motor contactor, control transformer and terminal strip.
The receiver is sized for a maximum of 50 linear ft. refrigerant line lengths
and/or not more than 6 feet below the MAM unit.
4.
EXECUTION
4.1
Unit Selection
.1
4.2
.1
Handle unit carefully to prevent damage, breaking, denting and scoring. Damaged units
or damaged components shall not be installed. Replace all damaged parts with new
parts from the manufacturer.
.2
If unit is to be stored prior to installation, store in a clean, dry place. Protect from
weather, dirt, fumes, water, construction and physical damage.
.3
Comply with manufacturer's rigging and installation instructions for unloading the unit
and moving it to the final location.
MAM0506
- 20 -
Specifications
4.3
.1
4.4
MAM Series
Installation
Execute the work in accordance with the specifications and in accordance with the
manufacturer's instructions and only by workmen experienced in this type of work.
Warranty*
.1
.2
.3
.4
OPTION: An extended third-to-fifth year of parts coverage on the air side coils.
.5
* Please refer to the Dectron Warranty for full Terms & Conditions.
4.5 Start-Up
.1
Start-up for the dehumidification/heat recovery unit shall be provided by the authorized
factory representative. The agency responsible for start-up shall be factory trained and
certified. The installing contractor, if not factory certified shall not be authorized to carry
out the start-up.
.2
The agency responsible for start-up shall submit a copy of their training certificate with
the submittals.
.3
MAM0506
- 21 -