Inertia constant=5 kW-seconds per kVA; Load damping constant, B=1 %; frequency, f=50 Hz; and Speed regulation, R=2.5 Hz / p.u MW. If there is a 1.5 %
increase in the load, find the frequency drop
(a) without governor control
(b) with governor control.
[8+8]
?????
R07
Set No. 4
[8+8]
3. Design a static var compensator for a low voltage distribution system with the
following specifications:
System voltage = 440 V
System frequency = 50 Hz
Coil inductance, L=5.37 mH
The inductor saturates at 950 A and settles to a value of 1.8 mH at 1800 A.
Compensation is required over a range of -80 kVAR to +30 kVAR per phase. [16]
4. Two control areas have the following characteristics:
Area-1:
Speed regulation
Damping co-efficient
Rated MVA
Area-2: Speed regulation
Damping co-efficient
Rated MVA
=
=
=
=
=
=
0.02 pu
0.8 pu
1500
0.025 pu
0.9 pu
500
Determine the steady state frequency change and the changed frequency following
a load change of 120MW occurs in area-1. Also find the tie-line power flow change.
[16]
5. Obtain the dynamic response of load frequency controller with integral control
action in two area load frequency control system.
[16]
6. A 80 MVA synchronous generator operates on full load at a frequency of 50Hz. The
load is suddenly reduced to 40 MW. Due to time lag in the governor system, the
steam valve begins to close after 0.3 secs. Determine the change in frequency that
occurs in this time. H=4 KW-s/KVAof generator capacity.
[16]
R07
Set No. 4
7. Two generating stations A & B have full load capacities of 300 MW and 250 MW
respectively. The inter connector connecting the two stations has a motor-generator
set (Plant C) near station A of full load capacity of 100 MW. Percentage changes
of speed of A, B and C are 5, 4 and 3 respectively. The loads on bus bars A and
B are 200 MW and 100 MW respectively. Determine the load taken by set C and
indicate the direction in which the energy is flowing.
[16]
8. A single area consists of two generators with the following parameters:
Generator 1 = 1200 MVA; R=6 % (on machine base)
Generator 2 = 1000 MVA; R=4 % (on machine base)
The units are sharing 1800 MW at normal frequency 50 Hz. Unit supplies 1000
MW and unit 2 supplies 800 MW. The load now increased by 200 MW.
(a) Find steady state frequency and generation of each unit if B=0.
(b) Find steady state frequency and generation of each unit if B=1.5.
?????
[8+8]
R07
Set No. 1
R07
Set No. 1
8. Two generating stations A and B have full load capacities of 200 MW and 75 MW
respectively. The inter connector connecting the two stations has an induction
motor/synchronous generator (plant C) of full load capacity of 25 MW. Percentage
changes in speeds of A, B and C are 5, 4 and 3 respectively. The loads on the bus
bars of A and B are 75 MW and 30 MW respectively. Determine the load taken
by the set C and indicate the direction in which the energy is flowing.
[16]
?????
R07
Set No. 3
[8+8]
3. Draw flow chart for economic scheduling with out considering line losses.
[16]
[16]
5. Two control areas connected by a tie line have the following characteristics.
Area 1
R=0.01 pu
D=0.8 pu
Base MVA=2000
Area 2
R=0.02 pu
D=1.0 pu
Base MVA=500
A load change of 100 MW (0.2 pu) occurs in area 1. What is the new steady
state frequency and what is the change in the tie flow? Assume both areas were at
nominal frequency (60 Hz) to begin.
[16]
6. Discuss the merits of proportional plus integral load frequency control of a system
with a neat block diagram.
[16]
7. A system consists of 4 identical 250 MVA generators feeding a load of 510 MW
The inertia constant H of each unit is 2.5 on the machine base. The load varies by
1.4% for a 1 % change in frequency. If there is a drop in load of 10 MW, determine
the system block diagram expressing H and B on the base of 1000 MVA. Give the
expression for speed deviation, assuming there is no speed governor.
[16]
8. In a two plant operation system, the hydro plant is operation for 10 hrs, during
each day and the steam plant is to operate all over the day. The characteristics of
the steam and hydro plants are
CT = 0.04 PGT 2 +30 PGT + 10 Rs/hr
WH =0.12 PGH 2 +30 PGH m3 / sec
When both plants are running, the power flow from steam plant to load is 150 MW
R07
Set No. 3
and the total quantity of water is used for the hydro plant operation during 10 hrs
is 150106 m3 . Determine the generation of hydro plant and cost of water used.
Neglect the transmission losses.
[16]
?????