Fault - Current XR Relation React-Resist
Fault - Current XR Relation React-Resist
Home
TOC
<<
>>
Index
1.2-5
X/R Ratio
X
X
X
X
9 (7 14)
15 (12 17)
80 (40 120)
80 (40 120)
20 (13 32)
30 (10 60)
16 (16 50)
30 (10 60)
.75X
.75X
1.5X
1.0X
20 (13 35)
30 (10 60)
1.5X
1.0X
17 (15 25)
30 (15 40)
3.0X
1.2X
17 (15 25)
15 (2 40)
Neglect
Neglect
As Specified
or Calculated
15 (5 15)
As Specified
or Calculated
80 (40 120)
OA to 10 MVA, 69 kV
OA to 10 MVA, above 69 kV
Transformers
FOA 12 to 30 MVA
8.0
8.0 to 10.5
Depends on
Primary
Windings BIL
Rating
18 (7 24)
18 (7 24)
20 (7 30)
38 (32 44)
Table 1.2-3. Typical System X/R Ratio Range (for Estimating Purposes)
Type of Circuit
X/R Range
Remote generation through other types of circuits such as transformers rated 10 MVA
or smaller for each 3-phase bank, transmission lines, distribution feeders, etc.
15 or less
15 40
30 50
30 50
Synchronous machines connected through transformers rated 100 MVA and larger.
40 60
40 120
CA08104001E
1.2-6
Home
TOC
<<
>>
January 2003
Index
130
130
120
120
120
110
110
90
90
80
80
80
30
40
40
30
5-CYCLE
BREAKER
20
20
20
10
10
10
1.0
1.1
1.2
1.3
NT
AC
50
30
GT
IME
60
50
5-CYCLE
BREAKER
PA
RT
IN
70
60
CO
40
70
CO
50
Ratio X/R
60
NT
AC
T P
ART
ING
70
Ratio X/R
TIME
90
100
12
100
10
110
130
100
Ratio X/R
1.4
5-CYCLE
BREAKER
1.0
1.1
1.2
1.3
1.4
January 2003
Home
TOC
<<
>>
Index
1.2-7
V max
E
------- I -------------- KI
Vo
X2
KI
= Maximum symmetrical
interrupting capacity
2.4
4.16
6.6
12
13.8
50 VCP-W 250
10.1 kA
0%
1
1.5
2
1.5
2
2.5
2.5
3
3
3.75
3.75
5
5
7.5
7.5
10 1
10
10
10
12 1
12
15
15
20
20 1
20
25
30
Reclosing Duty
50 VCP-W 250
12 kA
50 VCP-W 250
36 kA
50 VCP-W 350
49 kA
50 VCP-W 250
33.2 kA
50 VCP-W 350
46.9 kA
75 VCP-W 500
41.3 kA
50 1
1
Transformer impedance 6.5% or more, all other transformer impedances are 5.5% or more.
(1,000 m)
CA08104001E
Altitude in
Feet (Meters)
Correction Factor
Current
Voltage
1.00
0.95
0.80
1.2-8
Home
TOC
<<
>>
Index
January 2003
Ref. No. 0042
E
I 3-Phase = ----X
Given a circuit breaker interrupting and momentary rating in the table below,
verify the adequacy of the ratings for a system without motor loads, as shown.
Table 1.2-6. Short Circuit Duty
Type
Breaker
V Max.
Max. KI
4.76
----------- (29) = 33.2 kA I1
4.16
LG Symmetrical Interrupting Capability
29 kA
36 kA
36 kA
Note: Interrupting capabilities I1 and I2 at operating voltage must not exceed maximum
symmetrical interrupting capability Kl.
Check capabilities I1, I2 and I3 on the following utility system where there is no
motor contribution to short circuit.
24,200 Watts Load Losses
= 15
R
375 MVA
Available
2
2
2
2X
Z = X + R = R -------2- + 1
R
1
1
13.8 kV
3750 kVA
X
X = ----- ( R ) = 15 (.066) = .99%
R
Transformer Standard 5.5% Impedance
has a 7.5% Manufacturing Tolerance
4.16 kV
50VPC-W250
I
I 3-Phase = ----BX
where X is per unit reactance
IB is base current
13.8 kV
3.75 MVA
Base current I B = = .52 kA
3 ( 4.16 kV )
I
.52
I 3-Phase = ----1- = ------------------ = 8.6 kA Sym.
X
.0604
X
System = 9 (is less than 15)
R
would use 1.0 multiplying factor for
short circuit duty, therefore, short
circuit duty is 8.6 kA sym. for 3-phase
fault I1 and momentary duty is 8.6 x
1.6 = 13.7 kA I3.
Answer
Figure 1.2-5. Example 1 One Line Diagram
Z R
(5.09) (.65) =
25.91 .42 =
25.48
X = 5.05%
13.8 kV System
Transformer
System Total
or
X
.99%
5.05%
6.04%
.0604 pu
R
X/R
.066% 15
.65%
8
.716 % 9
.00716 pu
CA08104001E
January 2003
Home
TOC
<<
>>
Index
1.2-9
7500 kVA
X/R
.015
.001
15
X = 15
R
21 kA Sym. Available
13.8 kV
Z = 5.53%
X = 5.5%
R = 0.55%
X
= 10
R
6.9 kV
1
13.8 kV System
.628 (6.9)
X = ----------- --------------- = .015
21 (13.8)
Transformer
.055
.0055
X
= 25
R
197A FL
X''d = 20%
10
X
= 35
R
173A FL
X''d = 25%
(.628)
X = .20 ------------------- = .638 pu at 7.5 MVA base
.197
2500 hp
Ind.
Interrupting
E/X Amperes
Momentary
E/X Amperes
X
R
I3 Source Transformer
.628
.070
= 8.971
.628
.070
= 8.971
11
.628
(1.5) .638
= .656
.628
.638
= .984
.628
(1.5) .908
= .461
.628
.908
= .691
I3F =
10.088
10.1 kA
or
3-Phase
LG
3-Phase & LG
Remote
1
15 1
20
25
30
1.00
1.00
1.00
1.00
1.04
1.00
1.00
1.02
1.06
1.10
1.00
1.00
1.05
1.10
1.13
36
40
45
50
55
1.06
1.08
1.12
1.13
1.14
1.14
1.16
1.19
1.22
1.25
1.17
1.22
1.25
1.27
1.30
60
65
70
75
80
1.16
1.17
1.19
1.20
1.21
1.26
1.28
1.29
1.30
1.31
1.32
1.33
1.35
1.36
1.37
85
90
95
100
1.22
1.23
1.32
1.33
1.38
1.39
1.40
1.41
100
120
130
1.24
1.24
1.24
1.34
1.35
1.35
1.42
1.43
1.43
25
25
.638
= 39
35
35
.908
= 39
= 157
IB
.628
- = -------------- = .062
Total X = ------I 3F
10.1
X
System ----- = .062 (235) = 14.5 is a Multiplying Factor of 1.0 from Table 1.2-7
R
Table 1.2-8. Short Circuit Duty = 10.1 kA
Breaker
Type
75VCP-W500
150VCP-W500
V
Max.
8.25 kV 33 kA
15 kV
18 kA
Max. KI
41 kA
23 kA
Answer
Either breaker could be properly
applied, but price will make the type
150VCP-W500 the more economical
selection.
CA08104001E
1
R
10.647
Total 1/R = 235
x 1.6
17.0 kA Momentary Duty
Type of Fault
Ratio
X (1)
R (X)
11
.070
(33) = 39.5 kA
66 kA
15 (18) (39.1) = 23 kA
6.9
(But not to exceed KI)
37 kA
8.25
6.9
Home
TOC
<<
>>
Index
January 2003
Ref. No. 0044
Answer
Check breaker application or generator bus for the system of generators shown.
Each generator is 7.5 MVA, 4.16 kV 1040 amperes full load, I B = 1.04 kA
X
Gen ----- ratio is 30
R
1 1 1 3
1
1 1 1 3
1
= + + = and = + + =
X X X X
RS R R R R
XS
X
X
X
R
X
or X S = ----- and R S = ---- Therefore, System --------S = ----- = Gen ----- = 30
R
RS
3
3
R
G1
G2
G3
Since generator neutral grounding reactors are used to limit the I LG to I3-phase or
below, we need only check the I3 short circuit duty.
I I I 31
3(1.04)
I B Phase = ----B- + ----B- + ----B- + ----------B- = ----------------------- = 28.4 kA Symmetrical E/X Amperes
.11
X X X X
4.16 kV
X
System ----- of 30 is a Multiplying Factor of 1.04 from Table 1.2-7.
R
Short-circuit duty is 28.4 (1.04) = 29.5 kA Symmetrical
Figure 1.2-7. Example 3 One-Line Diagram
V Max.
at V Max.
Max. KI
50VCP-W250
4.76 kV
29 kA
36 kA
4.76
(29) = 33.2 kA
4.16
CA08104001E