Training Fire Protection
Training Fire Protection
A309
Allan Comello
April 17, 2013
Copyright Materials
This presentation is protected by US and International Copyright laws.
Reproduction, distribution, display and use of the presentation without written
permission of the speaker is prohibited.
Course
Description
1) Illustrates the safety challenges posed by high-rise buildings
2) Describes the requirements for fire protection and prevention
3) Describes system & design requirements, as per the standards,
of Smoke Management Systems
4) Explains stair pressurization, components, and its working
5) Discusses passive fire safety elements in the building as a first line of
defense in fire emergencies
6) Proposes strict adherence to standards and quality procedures for design,
specification, installation and maintenance of stairwell pressurization components
for a safe means of egress
Learning
Objectives
1. Participants will learn about safety challenges posed by high-rise buildings
2. Participants will have an understanding of the design specifications and
systems requirements of stairwell pressurization system as per the safety
codes and standards
3. Participants will gain knowledge about stairwell pressurization as an effective
smoke management method in high-rise buildings
4. Participants will learn from the on-site experiences and examples provided
LIFE SAFETY
Engineering Means of Egress
High-rise building
"Any building greater than 23 meters (75.5 ft) in
height, where building height is measured from the
lowest level of fire department vehicle access to the
floor of the highest occupiable story.
- NFPA 101 Life Safety Code (LSC) 3.3.27.7
Poke-thru construction
Lapping
Radiated heat through flooring
HVAC ducting
The gap between the exterior panels
and interior beams
Stack effect
Stack effect is defined as "the vertical, natural air
movement throughout a high-rise building caused
by the difference in the outside and inside air
temperatures.
Influencing factors:
Airtight exterior walls
Air leakage between floors
Air temperature between floors
Differences between inside and outside
air temperature
Inadequate Systems
Smoke management systems are required to meet specific
building codes for fire resistance. Failure of these systems can
hinder fire department operations resulting in a large fire.
Active fire protection systems
Smoke detectors
Fire alarms systems
Sprinkler systems
HVAC systems
Stairwell pressurization
A type of smoke-control system in which
Components
Stair Pressurization Fans
Ductwork and Accessories
Pressure Relief Dampers
Fire Alarm Systems
Fire rated doors
Building Automation Systems (BAS)
Source: NFPA
Bypass Duct
Roof
Working of Stairwell
Pressurization
Staircase
Starter / Control
Panel
1)
2)
3)
4)
5)
Source: Trinity
Under normal conditions, the pressurization fan should not run and the dampers on the air
intake and bypass ducts shall be closed
In a fire situation, through a signal from the fire alarm panel, the damper on the air intake
shall open . An end switch on the damper actuator shall signal the fan to run when the
damper is open
A pressure sensor installed in the stairwell shall control the bypass damper to maintain a
constant pressure of 50Pa within the stairwell
The fan should be wired for manual stopping
It should be possible to override all controls and run the system through the firemans smoke
control panel
Emergency lighting
In buildings where artificial lighting is provided for
normal use and occupancy, exit lighting and the
illumination of the means of egress is required to
assure occupants can quickly evacuate the building.
All emergency lighting must be installed and tested in
accordance with NFPA 111 (Full 1 hour test annually
and 30-second test every 30 days.)
Compartmentation &
Fire resistant doors
Fire rated doors ensure adequate
compartmentation of buildings to
contain fire in the compartment in
which it starts providing a means of
escape .
Fire Doors are regulated by the
building code and NFPA throughout
design, specification, installation
and occupancy permitting.
27
There should be separate ducts for stairwell pressurization rather than using
Masonry Shaft for air to avoid air leakages and get proper pressurization.
All ducts used for Pressurization and Smoke Exhaust System shall be fire
rated, many contractors are using normal GI Ducts which defeats the
purpose.
Elevator hoist ways have proved to be readily available conduit for movement
of smoke throughout buildings in past fires. This is because the leakage
through elevator doors and elevator hoist ways. The building stack effect has
provided the driving force that has readily moved smoke into and out of the
loosely constructed elevator hoist ways. Methods of correcting this problem
include:
1) Exhaust of the fire floor
2) Pressurization of elevator lobbies
3) Construction of smoke tight elevator lobbies
4) Pressurization of the elevator hoist way
5) Closing elevator doors after automatic recall
It is paramount that local legislation imposes strict rules for the proper
installation, maintenance and service of fire safety items that are part of
the means of egress
References
Allan Comello
+971509204011