Ats
Ats
1.1. This guide describes about the method of the adjustment of ExEq which has the voltage
regulator with parallel operation(droop compentation) equipment in 3 phases brushless
alternator being produced in HHI.
1.2. Here we describe about ExEq for low voltage alternators(HFx5,HFx6 series) only.
For the medium voltage alternators(3.0/3.3kV, 6.0/6.6 kV HSR series), all description is same
7
8
1.3. This guide for adjustment can be important reference for the trouble-shooting during operating
on the field.
reference value
AVR.
droop compensator
current transformer
bypass resistor
rectifier transformer
steady rectifier
thyristor
Main stator
reactor
capacitor
exciter field
stator part
rotor part
Main rotor
main
AA4100=2
rotating rectifier
exciter rotor
exciter
1/12
A4(210297)
2.2. Rotor:
(1) Main field(rotating field of main machine)
(2) Rotating rectifier
(3) Armature (Exciter rotor) of exciter machine
The three-phase current(A.C.) generated in the rotor winding of the exciter is rectified to direct
current(D.C.) by rotating rectifiers(three-phase bridge circuit) and applied to the rotating pole
winding of the main generator which produces the magnetic flux required to generate the
voltage(electric power) at Main winding.
2.3.1 Exciting current (current required to produce about 115% of no-load rated output voltage)
proportional to the no-load voltage of Main stator is transferred to the Rectifier Transformer
(T6) via Reactor(L1).
2.3.2 Exciting current (current required to produce about 110% of full load rated output voltage by
compensating armature reaction and armature reactance) proportional to the load voltage of
Main stator is transferred to the Rectifier Transformer(T6) via Current transformers
(T1.T2.T3).
2.3.3 The exciter currents transferred to the Rectifier Transformer(T6) via Reactor(L1) and current
transformer(T1,T2,T3) are magnetically combined and transferred to the steady rectifier(V1
for HFx5, V29 for HFx6).
2.3.4 The Steady rectifier transforms A.C power transferred via rectifier transformer(T6) to D.C
power and this D.C power is supplied to the exciter field.
2/12
AA4100=2
2/12
A4(210297)
2.3.5 AVR compares the terminal voltage (sensing voltage) compensated by droop compensator and
the reference voltage set by reference value setter and transforms the difference between
sensing voltage and reference voltage to the pulse. That pulse turns on the gate of thyristor.
2.3.6 By turning on Thyristor gate, the excess current (transferred from rectifier transformer(T6)
over the current required to keep proper output voltage bypasses through the bypass
resister(R1 for HFx5((6GA2 490-0A AVR), R48 for HFx6(6GA2 491-1A AVR)). By controlling the
bypass current the output terminal voltage of main stator can be kept required proper voltage
value.
Load current
100[%]
3/12
AA4100=2
3/12
A4(210297)
Ja.Xp
ep
Ja.Ra
Ua
Jf(total)
Ja
Jf(current)
Jf(Reactor)
4/12
AA4100=2
4/12
A4(210297)
voltage at the constant value under same condition by supplying additional exciting current
required to compensate the voltage drop due to armature reaction and armature reactance.
5/12
AA4100=2
5/12
A4(210297)
6/12
AA4100=2
6/12
A4(210297)
Fig. (5) Bypassing the exciting current by bypass resistor(HFx5 Type generator)
w
u
Ju
A.V.R. (A1)
Jb
R1
Jua
Js
F1
Jef
F2
Jb
Jef = Js - Jb
Jua = Ju - Jb
Jef = exciter field current
Js = total current of rectifier bridge (-) line
Jb = bypass current
Jua = u phase current of rectifier bridge
Ju = total current of u phase
7/12
AA4100=2
7/12
A4(210297)
5.3 Check voltage hunting and setting of rated voltage by adjusting the reference
value setter
5.3.1 For HFx5 series generator
Confirm that the output voltage could be smoothly adjusted by turning the reference value
setter from anticlockwise to clockwise and then adjust the reference value setter to set the
output voltage to the rated value. If the hunting on the output voltage or exciting current
would be seen, remove it by adjusting the potentiometers(Vr, Tn) on AVR(A1).
The standard position of potentiometers during shop test are Vr = 3.0 and Tn = 6.0.
5.3.2 For HFx6 series generator
Confirm that the output voltage could be smoothly adjusted by turning the reference value
setter from anticlockwise to clockwise and then adjust the reference value setter to set the
output voltage to the rated value. If the hunting on the output voltage or exciting current
would be seen, remove it by adjusting the potentiometers(K, T, R47) on AVR(A1).
The standard positions of potentiometers during shop test are K = 3.0, T = 50 and R47 =
20.
8/12
AA4100=2
8/12
A4(210297)
6.2.3 If the rated load current cannot be loaded due to the low supply power, the droop should be
set to the lower value proportional to the possible load comparing to rated load.( 5[%] droop
at 100[%] rated current)
(ex.) rated current = 2000 [A], rated voltage = 450 [V], possible load current = 1600 [A]
Droop setting value [%] = 5[%] * (1600 / 2000) = 4.0[%], output voltage =
(1 - 0.04) * 450 = 432 [V]
9/12
AA4100=2
9/12
A4(210297)
rectifier(+, -) terminals
Opened circuit(misconnection) with the cables or pins between the input terminals(U1,V1,W1) of
(2UV, 2VV, 2WV) of rectifier transformer(T6) and the terminals(U, V, W) of static rectifier(V1 or
V29).
The failure(open or short) of the diode for steady rectifier(V1 or V29)
The failure(open or short) of the diode for rotating rectifier(V2)
Insulation failure between turns on the primary winding of rectifier transformer(T6)
Insulation failure between turns on the secondary winding of current transformers(T1, T2, T3)
1.3 Voltage increases rapidly according to load current increase or sudden load
Setting too low turn number(too large secondary current) of secondary winding of current
transformer(T6)
Setting too large turn number(too large output current) of input winding for no-load tap of rectifier
transformer(T6)
10/12
AA4100=2
10/12
A4(210297)
terminals(2.2) of current transformers(T1, T2, T3) and the input terminals(2U, 2V, 2W) of
rectifier transformer(T6).
Insulation failure between turns on the secondary winding of current transformers(T1, T2, T3)
Insulation failure between turns on the secondary winding of rectifier transformer(T6)
1.6 Generator voltage not adjustable or too narrow control range by reference value setter
or A1(Usoll for HFx5 series or U for HFx6 series).
No wiring for reference value setter or S/W off for reference value setter
Incorrect position of Micro switch(S1-3) on ) for HFx6 series (normal : S1-3 to be OFF position).
Opened circuit(misconnection) with one or several cables or pins between the terminals 17, 18, 19
on AVR and secondary winding(2.1, 2.2) of sensing(step down) transformers(T7, T8) or between
main bus and primary winding(1.1, 1.2) of sensing transformer for HFx5 series
Sensing of higher than normal U-W phase voltage by incorrect wiring or polarity of sensing(step
series
Opened circuit or incomplete connection of the cable(1, 5) for bypass cables of AVR for HFx5
Opened circuit or incomplete connection for bypass plug connector(X3) on AVR for HFx6 series
Setting of bypass resistor(R1 or R48) at too high resistance value
Failure of thyristor(V28) for HFx6 series
Failure of AVR
1.7 Hunting of output voltage or exciting current with load or without load
Hunting of speed of Engine governor
Incomplete contact of connecting pins or cable
Loosened locking nut of potentiometers(VR & R2) on AVR for HFx5 series
Incorrect adjusting of potentiometers(Vr, Tn for HFx5 series, K, T, 47 for HFx6 series) on AVR
11/12
AA4100=2
11/12
A4(210297)
The wiring cable between AVR and reference value setter is too long or the reference value would
be infected by external magnetic noise.
The resistance value with bypass resistor(R1 or R48) is too low.
External power for initial charging is connected to the auxiliary terminals(+F1, -F2) for exciter
field.
Out of control by AVR because of too low no-load exciter current
Failure of AVR
active load(KW) sharing due to different speed variation ratio of each prime
mover(engine governor).
Incorrect reactive load(KVAR) sharing due to different no load voltage setting by reference setter.
Voltage droop values by droop potentiometer(R2 or S on A1) are different from each other.
The accurate load sharing is impossible if the voltage droop values by droop potentiometer(R2 or S
1.9 The circuit breaker is opened due to high circulation current between generators during
synchronizing(break on for parallel operation).
High variation of active power due to instability of governor of prime mover
Different voltage droop setting from each other paralleling generator
Incorrect tap setting of current transformers(T1,T2,T3) or rectifier transformer(T6).
2. You can use Brief Troubleshooting sheet for electric trouble of the generator as shown in
attachments.
12/12
AA4100=2
12/12
A4(210297)