0% found this document useful (1 vote)
379 views

01 - Fresh Air Unit Esp Calculation

This document provides details on ductwork for a fresh air duct system in Riyadh, including duct material specifications, dimensions for 9 duct sections, and pressure loss calculations for each section and fittings. The total static pressure of the system is 452.9 Pa, with 132.9 Pa from duct sections and 320 Pa from fittings. Flow rates through the ducts range from 7,308 m3/h to 36 m3/h. Key specifications include the duct material being sheet metal with fittings every 2 meters, an operating altitude of 630 meters, and standard atmospheric properties for calculations.

Uploaded by

mefaisal75
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
379 views

01 - Fresh Air Unit Esp Calculation

This document provides details on ductwork for a fresh air duct system in Riyadh, including duct material specifications, dimensions for 9 duct sections, and pressure loss calculations for each section and fittings. The total static pressure of the system is 452.9 Pa, with 132.9 Pa from duct sections and 320 Pa from fittings. Flow rates through the ducts range from 7,308 m3/h to 36 m3/h. Key specifications include the duct material being sheet metal with fittings every 2 meters, an operating altitude of 630 meters, and standard atmospheric properties for calculations.

Uploaded by

mefaisal75
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

AFFAIR

RIYADH BANK

4/6/2013
Rev. - 00

DUCT NAME

Fresh Air Duct

FILE NAME : FAHU-G1-1/2

GENERAL DATA

SITE

RIYADH

DUCT MATERIAL
ROUGHNESS COEF.
SHEET THICKNESS
ALTITUDE
ALTITUDE COEF.
AIR DENSITY
KINEMATIC VISCOSITY

:S. SHEET + 1 FITTING EVERY 2 M.


: 0.09
mm
: 8/10 DE MM
: 630 metres
: 0.93
: 1.11 kg/m2
15.06 cts

DUCTS PRESSURE LOSSES BOARD


1

FLOW (L/s)

SECTION

2030

1092

914

584

552

177

149

48

10

FLOW (m3/h)

7308

3931

3290

2102

1987

637

536

173

36

WIDTH (mm)

750

400

400

350

350

250

250

200

100

HEIGHT (mm)

500

500

450

400

350

200

150

100

100

LENGTH (m)

9.0

29.0

2.7

1.2

9.0

11.0

16.0

5.3

5.6

10

11

12

13

14

15

16

17

10

11

12

13

14

15

16

17

DIAMETER (mm)

KSI
ELBOW 30

0.18

ELBOW 45

0.24

ELBOW 90

0.4

TEE 45

0.3

TEE 90

END TEE

1.5

BRANCH TEE

0.05

TRANSITION

0.25

CONTRACTION

0.05

AIR OUTLET
E.M.G.

1.1
0.44

AIR INLET

0.5
1

SPECIAL FITTINGS PRESSURE DROPS


DESIGNATION

PD(PA)

QTY

TOTAL

FIRE DAMPER

25

DAMPER

25

100

SUPPLY GRILLE

20

20

RETURN GRILLE

15

FRESH AIR GRILLE

20

REJECT AIR GRILLE

30

100

100

PLANE FILTER

80

OIL FILTER

150

SAND FILTER

100

ELECTRICAL COIL

VAV

110

VAVH

150

SOUND ATTENUATOR

100

TOTAL

model rev. 2.0

320

AFFAIR

RIYADH BANK

4/6/2013
Rev. - 00

DUCT NAME

Fresh Air Duct

FILE NAME : FAHU-G1-1/2

RESULTS BOARD
N

FLOW

Spd.

DIAM.

HEIGHT

WIDTH

OR

PD

PD

DUCTS

PRESSURE

per METER

x LENGTH

PD

DROPS

EQUIV.
DIAM.
m

m3/h

m/s

mm

mm

mm

Pa/m

Pa

Pa

Pa

9.00

7,308

5.41

666.02

750

500

0.5

4.2

49.6

53.8

29.00

3,931

5.46

488.12

400

500

0.7

19.5

12.4

31.9

2.70

3,290

5.08

463.59

400

450

0.6

1.7

1.4

3.1

1.20

2,102

4.17

408.80

350

400

0.5

0.6

1.0

1.6

9.00

1,987

4.51

382.61

350

350

0.6

5.7

1.7

7.4

11.00

637

3.54

244.06

250

200

0.7

7.8

3.8

11.6

16.00

536

3.97

209.99

250

150

1.1

17.3

1.3

18.6

5.30

173

2.40

152.34

200

100

0.7

3.5

0.3

3.8

9
10
11
12
13
14
15
16
17

5.60
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

36
0
0
0
0
0
0
0
0

1.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

109.32
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

100
0
0
0
0
0
0
0
0

100
0
0
0
0
0
0
0
0

0.2
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

1.1
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

1.1
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

61.4

71.6

132.9

TOTAL
88.80

STATIC PRESSURE :

452.9

included
*DUCTS PRESSURE DROP :

132.9

*FITTING PRESSURE DROP :

320.0

model rev. 2.0