Structural Lightning Protection Design Considerations
Structural Lightning Protection Design Considerations
[ To top of page ]
Down conductors
Down conductor siting and distancing is often dictated by architectural
circumstances. There should be one down conductor for every 20m or part
thereof of the building perimeter at roof or ground level (whichever is greater).
These should be evenly spaced and distances apart of more than 20m avoided
if possible.
If the building is above 20m in height or of an abnormal risk this distance
should be reduced to 10m.
They should be routed as directly as possible from the air termination network
to the earth termination network to avoid risks of side flashing. Re-entrant
loops are also to be avoided. BS 6651 recommends that the length of
conductor forming the loop should not exceed eight times the width of its open
side.
BS 6651 allows the use of 'natural conductors' such as rebars and structural
steelwork, provided that they are electrically continuous and adequately
earthed.
Lightning Protection Scheme to BS 6651 using the reinforced concrete
within the structure for down conductors
[ To top of page ]
Earth termination network
Each down conductor must have a separate earth termination. Moreover
provision should be made in each down conductor, for disconnection from the
earth for testing purposes. This is achieved with a test clamp (see below).
BS 6651 stipulates that the resistance to earth of the lightning protection
Oblong test or
junction clamp
[ To top of page ]
Bonding
All metal work, including water pipes, gas pipes, handrails, air conditioning
units, metal cladding, metal roofs etc, in the vicinity of the LPS must be bonded
to it, to avoid the danger of side flashing.
For the same reason, the LPS earth should be bonded to the main electrical
earth, as well as any other earthing system present in the structure.
Example of side flashing
If the lightning protection system on a structure is hit by
lightning, then the current flowing through the system and the
resistance/impedance offered by the conductor path will
determine themagnitude of the potential difference seen by the
lightning conductors with respect to true earth.
The lightning conductors can, instantaneously, have a potential
magnitude of megavolts (1,000,000V) with respect to true
earth.
Typically, at instant of discharge:
Potential difference at A = 1,500,000V
Potential difference at B = 0V
[ To top of page ]
Corrosion
BS 6651 contains tables of materials suitable for use in lightning protection
system components. Adherence to these requirements is vital to avoid
corrosion problems.
The correct choice of material and installation design should ensure a life span
of 30 years for the earth electrode system.
[ To top of page ]
Inspection, testing, records and maintenance
The code adequately details the requirement for inspecting a lightning
protection system, the testing required and the detailed records that should be
maintained.
Observance of clauses 32 to 34 of the code will highlight any maintenance of
the system required. Of particular importance is the regular detailed
examination of the complete lightning protection system for any evidence of
corrosion. If this check is not carried out then vital components within the LPS,
which may have suffered from corrosion and which could exhibit a high
resistance could be missed. This will have a detrimental effect on the whole
lightning protection system making it an unattractive high impedance path for
the lightning current to follow.
To minimise this problem, along with regular inspections, the selection of the
correct materials should be made in accordance with the recommendation of
BS6651.