Microgrid Dynamic Performance Improvement Using A Doubly Fed Induction Wind Generator
Microgrid Dynamic Performance Improvement Using A Doubly Fed Induction Wind Generator
1, MARCH 2009
137
NOMENCLATURE
Ar
Cpopt
d, q
et
Kopt
Lm
Ls
Popt
r,
R
s, r
Te , Te opt
Manuscript received March 12, 2008; revised July 10, 2008. Current version
published February 19, 2009. Paper no. TEC-00085-2008.
M. Shahabi, M. R. Haghifam, and M. Mohamadian are with the Department of Electrical Engineering, Tarbiat Modares University, Tehran 14115-111,
Iran (e-mail: [email protected]; [email protected]; mohamadian@
modares.ac.ir).
S. A. Nabavi-Niaki is with the Department of Electrical and Computer
Engineering, Toronto University, Toronto, ON M5S 3G4, Canada (e-mail:
[email protected]).
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org.
Digital Object Identifier 10.1109/TEC.2008.2006556
opt
w
s , r
t
138
Fig. 1.
Fig. 2.
DG2 represents a variable-speed wind turbine set with rated capacity of 2 MW, which is interfaced through a DFIG with rated
capacity of 2.5 MVA. The DG1 and DG2 parameters are given
in the Appendix. The microgrid system is separated from the
rest of the MV feeder by a circuit breaker.
III. ISLANDING DETECTION AND THE SYSTEM
PROTECTION SCHEME
Under the regulation governing distribution system operation,
an islanding scenario is permitted only for loads with dedicated
generation units. As a result, DG units must be equipped with
specific islanding detection and prevention schemes to disconnect the unit within 2 s of an islanding event [12].
However, in the future, to realize the full benefit of high DG
penetration depth, the islanding operation of microgrids needs
to be considered.
In the case of future microgrid applications, with the potential
of islanding operation, a fast and reliable detection algorithm is
required to effectively distinguish between an islanding condition and other types of disturbances.
In this research, the islanding and formation of a microgrid
is assumed to be detected within 100 ms (five cycles in 50 Hz).
After detection, the islanding mode operation of the microgrid
is activated by changing the DGs control mode.
To consider the islanding operation of microgrids, a protection scheme in distribution network can be suggested as
follows. The distribution system is divided into several zones in
such a way that in each zone, there is no DG, or if there is any,
balance of generation and consumption in that zone is possible
regardless of the main grid and by using only the power generated by DGs that exist in that zone (microgrid concept) [13]
(see Fig. 2). In other words, the distribution system is divided
into two categories: the first category includes those zones that
have no DG and their loads are fully supplied through the main
grid, and the second category includes those zones that have
one or more DGs and are capable of operating in the islanded
SHAHABI et al.: MICROGRID DYNAMIC PERFORMANCE IMPROVEMENT USING A DOUBLY FED INDUCTION WIND GENERATOR
Fig. 3.
139
140
Fig. 4.
with Cpopt being the optimal power coefficient of the wind turbine for a given wind speed, Ar (in square meters) the effective
area covered by the turbine blades, w (in meters per second)
the wind speed, and (in kilograms per cubic meter) is the air
density. The calculation of the optimal power coefficient Cpopt
(2)
(3)
(4)
where r (in meters) is the blade radius and topt is the optimal
wind turbine rotor speed (in radians_mechanical per second) for
a given wind speed. From (1) and (4), an optimum (maximum)
power value Popt can be obtained as a function of the shaft speed,
referred to as the generator side of the gearbox, as follows:
Popt = Kopt r3
(5)
where Kopt = (/2)(Cpopt /3opt )r5 , r = (P/2)Gt , P being the number of poles and G the gear ratio. From (5), the
wind turbine predefined optimal extraction power curve can be
established for a given Kopt associated to a fixed blade angle.
In this research, Kopt is defined for a fixed blade angle equal
to 0 . In Fig. 5, the maximum power extraction curve adopted
for a variable-speed wind turbine is shown.
The speed controller is controlling the electromechanical
torque (Te ). The reason for such control is that the torque is
directly dependent on the quadrature component of the rotor
current (iq r ), when stator resistant is neglected [16]. The following relation between torque and iq r holds, in which et is the
terminal voltage:
Te =
Fig. 5.
Lm et
iq r .
Ls + Lm
(6)
(7)
SHAHABI et al.: MICROGRID DYNAMIC PERFORMANCE IMPROVEMENT USING A DOUBLY FED INDUCTION WIND GENERATOR
Fig. 6.
141
control will control the rotor speed and operate until the wind
cutoff speed limit is reached. A typical pitch control can be found
in [15]. The input speed reference for a pitch control is defined
according to if Pm ec > Pm ax , and then r -ref = (Pm ax /Tm ec ).
Fig. 7.
e2t
s (Ls + Lm )
(9)
where the direct component of the rotor current has been split
into a part that magnetizes the generator, idr,m agn , and a part
that determines the net reactive power exchange with the grid,
idr,gen . The direct component of the rotor current necessary to
magnetize the generator itself has the following value:
Qgrid =
Lm
Ls + Lm
idr,m agn =
e2t
.
s Lm
(10)
The value of idr ,gen determines whether the net reactive power
is generated or consumed. The terminal voltage will increase
when more reactive power is delivered to the grid. The voltage
controller should have the following features.
1) In the grid-connected mode operation of the microgrid,
the DFIG should be operated at unity power factor.
2) Terminal voltage of the DFIG should be adjusted appropriately when the microgrid switches to islanding mode.
A voltage controller that satisfies the aforementioned features
is proposed and depicted in Fig. 8.
From Fig. 8, it can be seen that during the grid-connected
mode of operation, idr,ref provides the required magnetization
current for the DFIG. Also, in the islanding mode of operation,
in addition to providing the required magnetizing current, the PI
controller regulates idr,ref in a way that it provides the required
reactive power.
142
Fig. 9.
Fig. 10.
SHAHABI et al.: MICROGRID DYNAMIC PERFORMANCE IMPROVEMENT USING A DOUBLY FED INDUCTION WIND GENERATOR
Fig. 11.
DFIG.
Fig. 13.
DFIG.
143
During the fault, bus voltages drop severely [see Fig. 12(d)].
After the islanding detection, fast control actions of the DG
units terminal voltage controllers eventually return the voltages
to their normal range. Fig. 13 illustrates the system response
when the DFIG primary frequency control is disabled.
From Figs. 12 and 13, it is observed that the primary frequency
control responds quickly and helps to improve the system frequency response slightly.
A better damping performance is obtained for the case where
DFIG has a primary frequency control capability, as shown in
Fig. 12(a), because after islanding detection, the DFIG participating in the primary frequency control leads to an increase
in active power injection. This fact makes it possible for DG1
(synchronous generator unit) to respond by injecting less active
power into the microgrid, thereby improving the system frequency smoothly. It can be seen that when power increases, the
DFIG rotor active power also increases, and consequently, the
rotor speed tends to fall a little more after islanding detection
balancing the total active power (stator plus rotor active power)
injected by the DFIG, as illustrated in Figs. 12(b) and 13(b).
Fig. 12.
DFIG.
VII. CONCLUSION
In this paper, the impact using a DFIG with capability to
contribute to primary frequency control and terminal voltage
regulation in a microgrid system was addressed. Two control
modes were adopted for DGs in a microgrid system, and both
planned and unplanned islanding scenarios were examined to
evaluate the control approach. The microgrid is supplied by
two DG units, i.e., a synchronous machine and a variable-speed
wind turbine with DFIG technology. The latter unit includes
144
C. Control parameters:
APPENDIX
REFERENCES
[1] M. W. Davis, Distributed resource electric power systems offer significant advantages over central station generation and T&D power systems,
part I, in Proc. 2001 IEEE Transmiss. Distrib. Conf. Expo., pp. 54
61.
[2] N. D. Hatziargyriou and A. P. S. Meliopoulos, Distributed energy sources:
Technical challenges, in Proc. 2002 IEEE PES Winter Meeting, pp. 1017
1022.
[3] C. L. Smallwood, Distributed generation in autonomous and nonautonomous microgrid, in Proc. 2002 IEEE Rural Elect. Power Conf.,
pp. D1-1D1-6.
[4] H. You, V. Vittal, and Z. Yang, Self-healing in power systems: An approach using islanding and rate of frequency decline-based load shedding,
IEEE Trans. Power Syst., vol. 18, no. 1, pp. 174181, Feb. 2002.
[5] R. Fulton and C. Abbey, Planned islanding of 8.6 MVA IPP for BC
Hydro system reliability, in Proc. 2004 First Int. Conf. Integr. RE DER,
pp. 19.
[6] F. Katiraei, M. R. Iravani, and P. W. Lehn, Micro-grid autonomous operation during and subsequent to islanding process, IEEE Trans. Power
Del., vol. 20, no. 1, pp. 248257, Jan. 2005.
[7] F. Katiraei, M. R. Iravani, and P. W. Lehn, Small-signal dynamic model
of a microgrid including conventional and electronically interfaced distributed resources, IET Gener. Transmiss. Distrib., vol. 1, no. 3, pp. 369
378, May 2007.
[8] The European Wind Energy Association (EWEA). (1999). Green peace
and wind industry unveil global energy blue print [Online]. Available:
http://www.ewea.org/src/press.htm
[9] S. K. Salman and A. Teo, Windmill modeling consideration and factors
influencing the stability of a grid-connected wind power-based embedded
generator, IEEE Trans. Power Syst., vol. 18, no. 2, pp. 793802, May
2003.
[10] J. Ekanayake and N. Jenkins, Comparison of the response of doubly fed
and fixed-speed induction generator wind turbines to changes in network
frequency, IEEE Trans. Energy Convers., vol. 19, no. 4, pp. 800802,
Dec. 2004.
[11] W. J. Rowen, Simplified mathematical representations of heavyduty gas turbines, ASME J. Eng. Power, vol. 105, pp. 865869,
1983.
[12] IEEE Standard for Interconnecting Distributed Resources with Electric
Power Systems, IEEE Standard 1547, Jul. 2003.
[13] S. M. Brahma and A. A. Girgis, Development of adaptive protection
scheme for distribution systems with high penetration of distributed
generation, IEEE Trans. Power Del., vol. 19, no. 1, pp. 5663, Jan.
2004.
[14] S. A. Papathanassion and M. P. Papadopoulos, Dynamic behavior of
variable speed wind turbines under stochastic wind, IEEE Trans. Energy
Convers., vol. 14, no. 4, pp. 16171623, Dec. 1999.
[15] J. G. Slootweg, H. Polinder, and W. L. Kling, Dynamic modeling of a
wind turbine with doubly fed induction generator, in Proc. 2001 IEEE
Power Eng. Soc. Summer Meeting, pp. 644649.
[16] S. Heier, Grid Integration of Wind Energy Conversion Systems. Chicester,
U.K.: John Wiley, 1998.
[17] H. Knudsen and J. N. Nielsen, Introduction to the modeling of wind
turbines, in Wind Power in Power Systems, T. Ackerman, Ed. Chicester,
U.K.: Wiley, 2005, pp. 525585.
[18] Database of wind characteristics located at DTU, Denmark. (2006).
[Online]. Available: http://www.winddata.com
SHAHABI et al.: MICROGRID DYNAMIC PERFORMANCE IMPROVEMENT USING A DOUBLY FED INDUCTION WIND GENERATOR
M. R. Haghifam (M98SM06) received the B.Sc. degree from Tabriz University, Tabriz, Iran, in 1988, the M.Sc. degree from Tehran university, Tehran,
Iran, in 1990, and the Ph.D. degree from Tarbiat Modares University, Tehran,
in 1995.
In 1995, he joined Tarbiat Modares University, where he is currently a
Professor of electric power systems. His current research interests include power
system reliability, electric distribution systems, and soft computing application
in power systems.
Prof. Haghifam is a Research Fellow of the Alexander Von Humboldt
Foundation.
145