User Manual Module HGM400 Series
User Manual Module HGM400 Series
(HGM410/HGM420)
USER MANUAL
Smartgen Technology
Chinese trademark
English trademark
Note
Original release.
Modify typical application.
INSTRUCTION
Highlights an essential element of a procedure to ensure
NOTE
correctness.
Indicates a procedure or practice, which, if not strictly observed,
CAUTION! could result in damage or destruction of equipment.
ISSUE 2012-03-15
Version 1.1
Page 3 of 30
Table of Contents
1
SUMMARY....................................................................................5
SPECIFICATION ..........................................................................6
OPERATION .................................................................................7
4.1 PANEL KEYS ............................................................................................ 7
4.2 PANEL DESCRIPTION ............................................................................. 8
4.3 AUTOMATIC START/STOP OPERATION ................................................ 8
4.4 MANUAL START/STOP OPERATION .................................................... 10
PROTECTION ............................................................................10
5.1 WARNINGS ............................................................................................ 10
5.2 SHUTDOWN ALARM...............................................................................11
CONNECTIONS .........................................................................12
SENSOR SELECT......................................................................24
10 COMMISSIONING ......................................................................25
11 TYPICAL APPLICATION.............................................................26
12 INSTALLATION ...........................................................................27
12.1 FIXING CLIPS ......................................................................................... 27
12.2 OVERALL DIMENSION AND PANEL CUTOUT ..................................... 28
ISSUE 2012-03-15
Version 1.1
Page 4 of 30
1 SUMMARY
HGM400 series automatic controller, integrating digital, intelligent and network
techniques, is used for automatic control system of generator. It can achieve automatic
start/stop, data measuring and three remote functions (SG485 module is needed).
The controller uses LCD display, optional Chinese, English, Spanish and Russian
display interface with easy and reliable operation.
HGM400 series automatic controller uses micro-processing technique which can carry
out precision measuring, constant value adjustment, timing and threshold setting and
etc.. All the parameters can be adjusted from front panel or through programmable
interface (USB to LINK, can use SG72 adaptor) via PC. It can be widely used in all
types of generator automatic control system for compact structure, simple connections
and high reliability.
Generator
Line Voltage (Uab, Ubc, Uca)
Phase Voltage (Ua, Ub, Uc)
Frequency (HZ)
Load
Current (IA, IB, IC)
Active Power (KW)
Reactive Power (KVar)
Apparent Power (KVA)
Power Factor (PF)
Accumulated Energy (kWh)
For mains: Over/under voltage, lack of phase; for generator: over/under voltage,
over/under frequency, over current;
Precision measure and display engine parameters,
HGM400 Series Genset Controller
ISSUE 2012-03-15
Version 1.1
Page 5 of 30
Temperature (WT),
C/ F both are display
Oil pressure (OP),
kPa/Psi/Bar all be display
Speed (SPD),
RPM (unit)
Voltage of Battery (VB) V (unit)
Voltage of Charger (VD)
V (unit)
Hours counter (HC): Max. 999999 hours.
Start times: Max.999999 times.
Control protection: Automatic start/stop, switch on/off (ATS control) and fault
display;
With ETS, idle control, pre-heat control, acceleration and deceleration control, all
are relay output;
Parameters setting: Allow user to modify parameters and store them in internal
FLASH, which cannot be lost even when power off. All the parameters can be
adjusted from the front panel, or by PC via an SG72 adaptor;
Types of temperature and pressure sensor can be directly used and user defined;
Conditions of crank disconnect can be selected.(magnetic pickup, oil pressure,
generator);
Power supply range is (8~35)VDC, accommodating to different starting voltage;
All parameters use digital modulation, abandoning analog modulation of
conventional potentiometer, more reliability and stability;
Modular design, flame retardant ABS shell, plug-in terminals, embedded mounting,
compact structure, easy installation.
3 SPECIFICATION
Items
Contents
Working Voltage
Power Consumption
AC voltage Input:
3 Phase 4 Wire
2 Phase 3 Wire
Single phase 2 Wire
3 Phase 3 Wire
Alternator Frequency
50Hz/60 Hz
10,000 Hz (max)
ISSUE 2012-03-15
Version 1.1
Page 6 of 30
Overall Dimensions
Panel Cutout
110mm x 90mm
CT Secondary Current
5A (rated )
Working Condition
Temperature: (-25~70)C;
Storage Condition
Temperature: (-30~+80)C
Protection Level
Insulation Intensity
Weight
0.26kg
Humidity: (20~93)%RH
4 OPERATION
4.1 PANEL KEYS
Stop/ Reset
Start
Manual
Pressing this and up key
Automatic
Set/Confirm
Up/Increase
Down/Decrease
Pressing this key will set the module into auto mode.
Enter into Set menu after pressing this key;
Shift cursor to confirm.
Turning pages up;
In parameter setting, shift cursor and increase values.
Turning pages down;
In parameter setting, shift cursor and decrease values.
ISSUE 2012-03-15
Version 1.1
Page 7 of 30
ISSUE 2012-03-15
Version 1.1
Page 8 of 30
Start Sequence,
1) HGM420: when mains is abnormal (over/under voltage, lack of phase), enter into
Mains Abnormal Delay and LCD displays count-down timer. When the delay is
over, Start Delay begins.
2) HGM410: genset enters into Start Delay when Remote Start is active.
3) Count- down timer of Start Delay is displayed in LCD.
4) When start delay is over, preheat relay is outputting (if configured), Preheat Delay
XX s is displayed in LCD.
5) When preheat delay is over, fuel relay is outputting 1s and then start relay outputs; if
genset failed to start during Start Time, fuel and start relays stop outputting and
enter into Crank Rest Time and wait for next cranking.
6) If genset failed to start within specified start times, the fourth line of LED will turn
black and Fail to Start alarm will be displayed.
7) Whatever time to start successfully, genset will enter into Safety on Run Time.
During this period, alarms of low oil pressure, hi-temperature, under speed, charge
failure and auxiliary input (be configured) are disabled. As soon as this delay is over,
genset will enter into Start Idle Delay (if configured).
8) During start idle delay, alarms of under speed, under frequency, under voltage are
disabled. As soon as this delay is over, genset will enter into Warming Up Delay (if
configured).
9) When Warming Up Delay is over, the indicator is illuminating if gens normal. If
engine voltage and frequency reach the load demand, closing relay outputs, genset
takes load and indicator illuminates; if engine voltage and frequency appear
abnormal, controller will alarm to shutdown (alarm is displayed in LCD).
Stop Sequence,
1) HGM420: during genset running, if mains normal, enters into Mains Normal Delay.
When mains indicator illuminates, Stop Delay begins.
2) HGM410: genset enters into Stop Delay when Remote Start is inactive.
3) When stop delay is over, genset enters into Cooling Delay. Gens closing relay is
open. After switch Transfer Rest Delay, mains closing relay outputs, mains will take
load, power indicator of gens eliminates while indicator of gens illuminates.
4) When entering Stop Idle Delay (if configured), Idle relay is energized to output.
5) When entering ETS delay, ETS relay is energized to output, fuel relay is open.
6) When entering Genset at Rest, automatically judge whether genset is stopped or
not.
HGM400 Series Genset Controller
ISSUE 2012-03-15
Version 1.1
Page 9 of 30
7) When genset has stopped, enters into standby mode; if failed to stop, controller will
alarm (Fail to Stop alarm will be displayed in LCD).
4.4
key, choose Manual Test Mode. Under the two modes, press
key to
start genset, it can automatically judge crank disconnect and accelerate to hi-speed
running. If high temperature, low oil pressure, over speed and abnormal voltage
occur during genset running, controller can effectively protect genset to stop (detail
procedures please refer to No.4~9 of Auto start operation). Under Manual Mode
if mains normal, load switch wont transfer; if mains abnormal, load switch will transfer
to gens. Under Manual Test Mode, after genset normally runs in high speed, no
matter mains normal or not, load will be transferred to gens.
2) HGM410: Manual Mode is activated when press
Then press
accelerate to hi-speed running. If hi-temperature, low oil pressure, over speed and
abnormal voltage occur during genset running, controller can effectively protect
genset to stop (detail procedures please refer to No.4~9 of Auto start operation).
Controller will send closing signal when genset runs in high speed.
3) Manual stop: pressing
5 PROTECTION
5.1 WARNINGS
When controller detects the warning signal, only alarm and not stop genset. The alarms
are displayed in LCD.
Warnings as following,
No
Items
Description
Loss Of Speed When controller detected engine speed is 0 (the delay is 0),
1
Signal
a warning alarm signal will be sent and displayed in LCD.
When controller detected gens current above the pre-set
Gens
Over
2
value (the delay is 0), a warning alarm initiates and displayed
Current
in LCD.
3 Fail To Stop
When generator cannot stop after the stop delay, controller
HGM400 Series Genset Controller
ISSUE 2012-03-15
Version 1.1
Page 10 of 30
No
Items
Charge Failure
Battery
Voltage
Under
Battery
Voltage
Over
Low
Level
Liquid
Temp.
Open
Sensor
10
Oil
Press
Sensor Open
Description
will send warning alarm signal and it will be displayed in
LCD.
When controller detected the fuel level is lower than
threshold, controller will send warning alarm signal and it will
be displayed in LCD.
When controller detected the charger voltage is lower than
threshold, controller will send warning alarm signal and it will
be displayed in LCD.
When controller detected the battery voltage is lower than
threshold, controller will send warning alarm signal and it will
be displayed in LCD.
When controller detected the battery voltage is higher than
threshold, controller will send warning alarm signal and it will
be displayed in LCD.
When controller detected low water level input is active,
controller will send warning alarm signal and it will be
displayed in LCD.
When temperature sensor opens circuit and the warning
input is active, controller will send a warning alarm signal and
it will be displayed in LCD.
When oil pressure sensor opens circuit and the warning input
is active, controller will send warning alarm signal and it will
be displayed in LCD.
ISSUE 2012-03-15
Version 1.1
Page 11 of 30
No
Items
Description
Gens
Voltage
Over
Gens
Voltage
Under
Gens
Current
Over
10
Fail To Start
11
Over Frequency
12
Under
Frequency
13
Genset Failed
14
15
Low
Level
Liquid
16
Temp.
Open
Sensor
17
Oil
Pressure
Sensor Open
LCD.
When controller detected genset voltage is over the preset, it
will send a stop alarm signal and it will be displayed in LCD.
When controller detected genset voltage is under the preset,
it will send a stop alarm signal and it will be displayed in
LCD.
When controller detected genset current is over the preset
and delay is not 0, it will send a stop alarm signal and it will
be displayed in LCD.
During the start attempt times, if genset start failed, it will
send a stop alarm signal and it will be displayed in LCD.
When controller detected genset frequency is over the
preset, it will send a stop alarm signal and it will be displayed
in LCD.
When controller detected genset frequency is under the
preset, it will send a stop alarm signal and it will be displayed
in LCD.
When controller detected genset frequency is 0, it will send a
stop alarm signal and it will be displayed in LCD
When controller detected genset fuel level low input is active,
it will send a stop alarm signal and it will be displayed in
LCD.
When controller detected genset water level low input is
active, it will send a stop alarm signal and it will be displayed
in LCD.
When temperature sensor opens circuit and the input is
active, controller will send a stop alarm signal and it will be
displayed in LCD.
When oil pressure sensor opens circuit and the input is
active, controller will send a stop alarm signal and it will be
displayed in LCD.
CONNECTIONS
ISSUE 2012-03-15
Version 1.1
Page 12 of 30
Description
Connect battery negative.
Connect battery positive. If longer than
30m, parallel connection with 2 cables.
Recommend using maximum 20A fuse.
Plant Supply B+ from pin 2, 5 A rated.
DC Power Supply B+
1.5mm2
Programmable
Output 1
1.0mm2
1.0mm2
Programmable Relay
Output 2
Programmable Relay
Output 3
Auxiliary Input 1
Auxiliary Input 2
Auxiliary Input 3
Auxiliary Input 4
Temperature
Sensor
Input
1.0mm2
1.0mm2
1.0mm2
1.0mm2
1.0mm2
1.0mm2
12
1.0mm2
13
CT A Phase Sensing
1.5mm2
5
6
7
8
9
10
11
Relay
1.0mm2
ISSUE 2012-03-15
Version 1.1
Page 13 of 30
Pin
Cable
Size
Function
Description
14
CT B Phase Sensing
1.5mm2
15
CT C Phase Sensing
1.5mm2
16
CT Common
1.5mm2
2
17
0.5mm
18
Charger D+ Input
1.0mm2
19
20
21
22
23
24
25
26
27
28
29
Programmable
Output 4
Programmable
Output 5
Relay
1.0mm2
Relay
1.0mm2
Common Port
1.5mm2
Generator U Phase
Sensing
Generator V Phase
Sensing
Generator W Phase
Sensing
Generator N2 Output
Mains
R
Phase
Sensing
Mains
S
Phase
Sensing
Mains
T
Phase
Sensing
1.0mm2
Mains N1 Sensing
1.0mm2
1.0mm2
1.0mm2
1.0mm2
1.0mm2
1.0mm2
1.0mm2
ISSUE 2012-03-15
Version 1.1
Page 14 of 30
No
1
Items
Mains
Delay
Mains
Delay
Range
Normal
Abnormal
Mains
Voltage
Under
Mains
Voltage
Over
Transfer
Time
Rest
(0-3600)s
Default
10
(30-620)V
184
(30-620)V
276
(0-99.9)s
1.0
Start Delay
(0-3600)s
Stop Delay
(0-3600)s
Start Times
(1-10)times
Preheat Time
(0-300)s
10
Crank Time
(3-60)s
11
(3-60)s
10
12
Safety
Time
(1-60)s
10
13
(0-3600)s
14
Warm Up Time
(0-3600)s
10
Run
On
Description
ISSUE 2012-03-15
Page 15 of 30
No
Items
Range
Default
15
Cooling Time
(3-3600)s
10
16
Stop Idle
ETS
Solenoid
Hold
(0-3600)s
(0-120)s
20
18
(0-120)s
19
Switching On
(0-10)s
5.0
20
Flywheel Teeth
(10-300)
118
21
Generator
Abnormal Delay
(0-20.0)s
10.0
22
Generator
Voltage
(30-620)V
264
23
Generator Under
Voltage
(30-620)V
196
24
Under Speed
(0-6000)RPM
1200
25
Over Speed
(0-6000)RPM
1710
26
Under Frequency
(0-75.0)Hz
45.0
27
Over Frequency
(0-75.0)Hz
57.0
17
Over
ISSUE 2012-03-15
Description
Delay of cooling time before
stopping.
Idle running time when stopping.
Its the delay for energizing to
stop.
When set ETS solenoid hold as
0s, from idle delay over to over
stop timer; if not 0s, its from ETS
delay over to genset at rest.
Pulse width of mains or closing
gens. When it is 0s, output is
continuous.
Used
for
judging
crank
disconnect and detecting rotating
speed. See INSTALLATION in
this manual.
Gens high voltage and low
voltage alarm delay.
When voltage is over the point,
Gens Over Voltage is active.
When the point is 620V, Gens
Over Voltage is disabled.
When voltage is under the point,
Gens Under Voltage is active.
When the point is 30V, Gens
Under Voltage is disabled.
When engine speed is under the
point and holds for 10s, Gens
Under Speed is active.
When engine speed is over the
point and holds for 2s, Gens
Over Speed is active.
When generator frequency is
lower than the point and holds for
10s, Gens Under Frequency is
active.
When generator frequency is
over the point and holds for 2s,
Gens Over Frequency is active.
Version 1.1
Page 16 of 30
No
Items
Range
Default
28
High Temperature
(80-140)C
98
29
(0-400)kPa
103
30
Loss of
Signal
(0-20.0)s
5.0
31
Charge Failure
(0-30)V
6.0
32
Battery
Voltage
Over
(12-40)V
33.0
33
Battery
Voltage
Under
(4-30)V
8.0
34
CT Rate
(5-6000)/5
500
35
(5-6000)A
500
36
Over
Current
Percentage
(50-130)%
120
37
Over
Delay
(0-3600)s
1296
38
Digital Output 1
(0-17)
14
39
Digital Output 2
(0-17)
Speed
Current
ISSUE 2012-03-15
Description
When engine temperature sensor
value is over this point, send
alarm signal. Active from end of
safety run on timer. When the
value is 140, high temperature
alarm is disabled. (only suitable
for temperature sensor)
When engine oil pressure sensor
value is under this point, send
alarm signal. Active from end of
safety run on timer. Low oil
pressure alarm is disabled. (only
suitable for oil pressure sensor)
If set the delay as 0, only warn
not to stop the generator.
During generator is running,
when alternator WL/D+ voltage is
under this point and remains for
5s, generator will send shutdown
alarm.
When battery voltage is over the
point and holds for 20s, Battery
Over Voltage is active. Its a
warning alarm.
When generator battery voltage
is under the point and holds for
20s, Battery Under Voltage is
active. Its a warning alarm.
Current transformer rate
Maximum rated current, used for
calculating over current.
When the load current is over the
point, over current delay begins.
When load current is over the
pre-set value, over current is
initiated. When set delay timer as
0, only warning no shutdown,
Factory default: Fuel Relay
Output
Factory default: Energized To
Stop
Version 1.1
Page 17 of 30
No
Items
Range
Default
Description
40
41
42
Digital Output 3
Digital Output 4
Digital Output 5
(0-17)
(0-17)
(0-17)
3
5
6
43
Auxiliary Input 1
(0-15)
(0-1)
(0-20.0)s
2.0
(0-15)
(0-1)
(0-20.0)s
2.0
(0-15)
10
(0-1)
(0-20.0)s
2.0
(0-15)
11
(0-1)
(0-20.0)s
2.0
44
45
46
47
48
49
50
51
52
53
54
Auxiliary Input 1
Active
Auxiliary Input 1
Delay
Auxiliary Input 2
Auxiliary Input
Active
Auxiliary Input
Delay
Auxiliary Input 3
Auxiliary Input
Active
Auxiliary Input
Delay
2
2
3
3
Auxiliary Input 4
Auxiliary Input 4
Active
Auxiliary Input 4
Delay
55
Module Mode
(0-2)
56
Module Address
(1-254)
57
Passwords
(0-9999)
1234
58
Crank Disconnect
(0-5)
59
Engine Speed
(0-3000)RPM
360
ISSUE 2012-03-15
0: Stop Mode
1: Manual Mode
2: Auto Mode
Communication
controller.
address
of
Version 1.1
Page 18 of 30
No
Items
Range
Default
Description
When generator frequency is
over this point, starter will
disconnect.
When engine oil pressure is over
this point, starter will disconnect.
Factory default: when the
temperature is too high, alarm to
shutdown. Note 1.
Factory
default:
when
oil
pressure is lower, alarm to
shutdown. Note 2
0: 3P4W; 1:2P3W
2:1P2W; 3: 3P3W Note 3
60
Engine
Frequency
(10.0-30.0)Hz 14.0
61
(0-400)kPa
200
62
(0-1)
63
Low OP Inhibit
(0-1)
64
Voltage Input
(0-3)
(0-9)
08
SGX
(0-9)
08
SGX
(2-32)
65
66
67
Temp.
Sensor
Select
Pressure Sensor
Select
Number Of Poles
68
Temperature
Sensor Open
(0-2)
69
Oil
Pressure
Sensor Open
(0-2)
70
Defined
Curve
(0-1)
Sensor
ISSUE 2012-03-15
Version 1.1
Page 19 of 30
Items
Not Used
Common Alarm
Idle Control
Preheat Control
Close Generator
Close Mains
Switching Off
Acceleration Control
Deceleration Control
10
Genset Run
11
12
13
14
15
16
17
Description
Including all shutdown alarms and warning alarms.
When there is warning alarm only, it is not self-lock;
when a shutdown alarm occurs, it is self locking until
the alarm is reset.
Suitable for genset with electromagnet and will pick up
after stop idle delay. The output will remain energized
until engine has come to a complete stop, then
de-energizes.
The designated programmable output relay will
energize when the idle delay is not zero. The output
contact would typically be connected to the idle/run
input control of an electronic governor.
The designated programmable output relay will
energize until the engine receive a crank success
signal. The preheat output is typically used for an
engine starting aid such as glow plugs.
When closing time is 0, its continuous output.
When closing time is 0, its continuous output.
(HGM410 without)
When closing time is 0, its disabled.
Pull-in during warm-up delay. Open when auxiliary
acceleration input is active.
Pull-in when entering stop idle or ETS solenoid
process, (alarm to shutdown). Open when auxiliary
deceleration input is active.
Outputting when genset in normal running and
disconnect when rotating speed is under engine speed
after started.
Close when fuel level is lower than the set threshold;
open when low fuel level warning input is inactive.
Outputting when entering into Warming Up and
disconnect when Cooling Down is over.
System
In
Auto
The controller work in automatic mode.
Mode
Fuel Relay Output
To control fuel relay output.
Reserved
Reserved
Reserved
ISSUE 2012-03-15
Version 1.1
Page 20 of 30
Items
Not Used
High Temp. Alarm
TABLE
(ACTIVE
WHEN
Description
Low OP Alarm
Auxiliary Alarm
Auxiliary Shutdown
Coolant To Stop
6
7
Generator Closed
Mains Closed
High Temp. Stop
Inhibit
Low Oil Pressure
Stop Inhibit
HGM410 without
When it is active, prohibit stopping when high
temperature occurs. Note 1
When it is active, prohibit stopping when oil low
pressure occurs. Note 2
HGM420 without
8
9
10
Low
Fuel
Warn
Low Liquid
Warn
Low
Fuel
Shutdown
Low Liquid
Shutdown
11
12
13
14
15
Level
Level
Level
Level
Temperature
Sensor
Content
0 Not used
1 Defined Res. Type
2 VDO
3 SGH(Huanghe sensor)
4 SGD(Dongkang sensor)
ISSUE 2012-03-15
Description
Defined input resistance
range
is
(0~6000).
Factory default is SGX.
Version 1.1
Page 21 of 30
No
Content
Pressure
Sensor
Description
5 CURTIS
6 DATCON
7 VOLVO-EC
8 SGX
9 Reserved
0 Not used
1 Defined Res. Type
2 VDO 10Bar
3 SGH(Huanghe sensor)
4 SGD(Dongkang sensor)
5 CURTIS
6 DATCON
7 VOLVO-EC
8 SGX
Content
Magnetic pickup
Generator
1) The crank disconnect condition has three kinds, the magnetic pickup and the
generator voltage can be used alone, oil pressure must be used with the magnetic
pickup and the generator voltage, in order to make the starter disconnect as soon
as possible.
2) Magnetic pickup is installed in the engine for testing flywheel.
3) When choosing magnetic pickup, ensure the number of flywheel teeth is same as
the set, otherwise over speed or under speed shutdown may appear.
4) If the generator is not installed with magnetic pickup, please don't select
corresponding item.
5) If the generator has no oil pressure sensor, please don't choose corresponding.
6) If the generator is not selected, controller will not measure and display relative
parameters (This can be applied to the pump set), if not choose magnetic pickup,
the speed signal will come from the generating AC signal.
HGM400 Series Genset Controller
ISSUE 2012-03-15
Version 1.1
Page 22 of 30
8 PARAMETERS SETTING
After controller powered on, press
below:
Fig1
1
2
3
4
Set Parameters
Information
Set Language
Mode Select
Set Parameters
When entering password interface, inputting 1234 can set part of the parameter
items in table 1; inputting 0318 can set all the items. (Table 1) If there is need to
set more parameters, please contact the factory.
NOTES:
1. For HGM410, there are no items from 1 to 5 in table 1; there are no digital outputs
about mains in auxiliary output 1-5.
2. Please modify the parameters (such as crank disconnection, auxiliary input/output
and various timers) in standby mode, otherwise alarm to shutdown or other
abnormal conditions may happen.
3. The over-voltage threshold must be greater than the under-voltage threshold;
otherwise over-voltage and under-voltage will occur at the same time.
4. The over-speed threshold must be greater than under-speed threshold, otherwise
over speed and under speed will occur at the same time.
5. Set the frequency (crank disconnect) as low as possible, in order to separate the
starter quickly when crank disconnect.
6. Auxiliary input 1-4 cannot be set as the same item, or will cause incorrect functions.
But auxiliary output 1-5 can be set as the same item.
7. If need to shut down after cooling, please set any auxiliary input as Coolant To
Stop, then connect this input to GND.
Information
LCD will display software version, issue date of the controller.
Note: Pressing
ISSUE 2012-03-15
Version 1.1
Page 23 of 30
Set Language
Chinese, English, Spanish and Russian interface can be selected.
Mode Select
The controller can be set as Manual Test Mode, Manual Mode or Auto Mode.
Note: Pressing
key at any time will quit the setting and return to the previous
setting menu.
9 SENSOR SELECT
1) When choosing sensor, standard of sensor curve will be needed. If set
temperature sensor as SGH (120C resistance type), sensor curve should be SGH
(120oC resistance type); If set as SGD (120C resistance type), sensor curve
should be SGD curve.
2) If there is difference between standard sensor curve and chosen sensor, select
"defined sensor", and then input defined sensor curve.
3) When inputting sensor curve, X value (resistance) must be in accordance with the
order of higher to lower, otherwise errors will occur.
4) When select sensor "Not used", temperature, pressure and fuel level will be
display as" - - -" in LCD.
5) If there is no pressure sensor, but only has low pressure alarm switch, then you
must set pressure sensor as "Not used", otherwise oil pressure low alarm
shutdown may appear.
6) Can set several points of forehand or backmost as the same ordinate, like the
following picture:
ISSUE 2012-03-15
Version 1.1
Page 24 of 30
1Pa
1kgf/cm2
1bar
1psi
1N/m2 (pa)
1kgf/cm2
1bar
1
9.8x104
1x105
6.89x103
1.02x10 5
1
1.02
7.03x10 2
1x10 5
0.98
1
6.89x10 2
(1b/in2) psi
1.45x10
14.2
14.5
1
10 COMMISSIONING
Before operation, the following checking should be carried out:
1) Check and ensure all the connections are correct and wires diameter is suitable.
2) Ensure that the controller DC power has insurance; battery positive and negative
have correctly connected.
3) Emergence stop input must be connected to positive of starting battery via normally
close contact of emergency stop.
4) Take proper actions to prevent engine to disconnect crank (for example, to remove
the connections of fuel value). If checking is OK, connect start battery, select Manual
Mode, controller will execute the program.
5) Set controller as Manual Mode, press start button to start genset. If failed within the
setting crank times, controller will send Failed to Start signal; then press Reset to
reset controller.
6) Recover actions of preventing engine to disconnect crank (e. g. Connect wire of fuel
value), press start button again, genset will start. If everything goes well, genset will
normal run after idle running (if configured). During this period, watch for engines
running situations and voltage and frequency of alternator. If abnormal, stop genset
and check all connections according to this manual.
7) Select the Auto Mode from front panel, connect to mains signal. After the mains
normal delay, controller will transfer ATS (if configured) and into mains load. After
cooling, controller will stop genset and into standby state until mains abnormal again.
8) When mains abnormal again, genset will start automatically and into normal running,
send signal to make gens close, transfer ATS and make genset take load. If not like
this, please check connections of ATS according to this manual.
9) If there are any other questions, please contact our technical personnel.
ISSUE 2012-03-15
Version 1.1
Page 25 of 30
11 TYPICAL APPLICATION
HGM410 Typical wiring diagram
ISSUE 2012-03-15
Version 1.1
Page 26 of 30
CAUTION! Recommend expanding relay with high capacity in start and fuel
output.
CAUTION! Use expansion relay in mains/gens closing outputs.
12 INSTALLATION
12.1 FIXING CLIPS
The module is held into the panel fascia using the supplied fixing clips.
1) Withdraw the fixing clip screw (turn anticlockwise) until it reaches proper position.
2) Pull the fixing clip backwards (towards the back of the module) ensuring four clips
are inside their allotted slots.
3) Turn the fixing clip screws clockwise until they make contact with the panel.
Note: Care should be taken not to over tighten the screws of fixing clips.
ISSUE 2012-03-15
Version 1.1
Page 27 of 30
ISSUE 2012-03-15
Version 1.1
Page 28 of 30
connected to terminal 1 and terminal 17. At full speed, output voltage range is
1-24VAC (RMS). Recommend using 12VAC (rated speed) voltage. During
installing, make the speed sensor contact the flywheel firstly, then pour out 1/3
laps, finally lock nut on the sensor.
3) Output And Expansion Relay
All outputs of the controller are relay contact outputs, if expansion relay is needed,
please add free-wheeling diode at both ends of the relay coil (expansion relay coil
links DC) or increase RC loop (expansion relay coil links AC) in order to prevent
from interfering controller or other equipment.
4) AC Input
HGM400 series controller must externally connect current transformer, CT
secondary current must be 5A. Besides, the phase of CT and input voltage must
be correct, or the sampling current and active power may be incorrect.
CAUTIONICOM must connect battery anode of the controller.
WARNING! When there is load current; the CT secondary side cannot open
circuit.
5) Withdraw Voltage Test
When the controller has been installed in the control panel, during the test please
disconnect all the terminals, lest high voltage damages the controller.
13 FAULT FINDING
Symptom
Controller inoperative
Genset stops
Emergency shutdown
Possible Remedy
Check starting battery;
Check connections of the controller;
Check the DC fuse.
Check if water/cylinder temperature too high.
Check alternator voltage.
Check the DC fuse.
Check if an emergency stop button is fitted; Ensure
battery positive is connected to the emergency stop
input.
Check if connection is open circuit.
ISSUE 2012-03-15
Version 1.1
Page 29 of 30
Symptom
Possible Remedy
High Temp. alarm (after
Check temperature sensor and connections.
crank success)
Check switch and connections according to information
Shutdown Alarm During
on LCD.
Running
Check configuration inputs.
Check connections of fuel solenoid.
Check starting battery.
Crank Not Disconnect
Check speed sensor and its connections.
Refer to engine manual.
Check connections of starter;
Starter Inoperative
Check starting battery.
Genset Running but ATS Check ATS;
Not Transfer
Check connections between ATS and controller.
ISSUE 2012-03-15
Version 1.1
Page 30 of 30