0% found this document useful (0 votes)
224 views

Instrumentation Control Cable Specification

The document specifies requirements for instrumentation cables used to supply power and signals. It states that the contractor must supply and install the cables along with associated civil and mechanical works. The cables must be able to withstand transportation, installation, and operation under normal and short circuit conditions of the systems they connect to. Cable joints for instrument signals and power supply cables are not permitted. Cables will be directly laid on trays, in trenches, conduits, or ducts, or directly buried in the ground. The contractor must also supply materials for cable termination such as junction boxes and glands.

Uploaded by

sachinrmishra
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
224 views

Instrumentation Control Cable Specification

The document specifies requirements for instrumentation cables used to supply power and signals. It states that the contractor must supply and install the cables along with associated civil and mechanical works. The cables must be able to withstand transportation, installation, and operation under normal and short circuit conditions of the systems they connect to. Cable joints for instrument signals and power supply cables are not permitted. Cables will be directly laid on trays, in trenches, conduits, or ducts, or directly buried in the ground. The contractor must also supply materials for cable termination such as junction boxes and glands.

Uploaded by

sachinrmishra
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Instrumentation Cables (Power Supply and Signal Cables)

a) Contractor shall include in his scope the supply and laying, of instrumentation
signal & instrument power supply cables and associated civil/mechanical work
required for completing the system.
b) Cables shall be capable of satisfactorily withstanding without damage,
transportation to site, installation at site, and operation under normal and short
circuit conditions of the various systems to which the respective cables are
connected when operating under the climatic conditions prevailing at the site as
indicated in this specification. Cables shall be capable of operating satisfactorily
under a power supply system voltage variation of 15%, and frequency variation of
5%.
c) Cable joints in instrument signals and instrument power supply cables shall not
be permitted.
d) Cables shall be directly laid on trays, in trenches, conduits, and ducts and
directly buried in the ground as necessary.
e) The Contractor shall also supply the necessary materials such as junction boxes,
glands, lugs etc required for termination of cables.
Cables for Digital Signals (D.C.) and D.C. Power Supply to Instruments
660V/1100 V grade multicore cables, multistranded high conductivity annealed 1.0
sq.mm. stranded tinned copper conductor, extruded PVC insulated, overall shielded
with aluminium Mylar tape, ATC drain wire run continuously in contact with
aluminium tape, inner sheathed with extruded PVC, armoured with galvanised steel
wire overall sheathed with extruded PVC conforming to IS: 1554 & IEC: 189 Part II.
Cables for analog signals
660 V/1100 V annealed, tinned, high conductivity 1.0 sq mm stranded copper
conductor extruded PVC insulated two cores twisted into pair, laid up collectively,
individual pair shielded and overall shielded with aluminium Mylar tape, ATC drain
wire run continuously in contact with aluminium side of the tape, inner sheathed
with extruded PVC, armoured with galvanised steel wire, overall sheathed with
extruded PVC conforming to IS: 1554 & IEC: 189 Part ll.
Power supply cables
Cables shall be rated for 1100 V and shall conform to the latest edition of IS: 1554.
Cable shall be insulated with extruded PVC type 'A. The inner sheath over laid up
covers and outer sheath over the armour shall be of extruded PVC compound type
ST1. 230 V AC power supply cable for panel shall be of 2.5 sq mm stranded, tinned,
annealed copper conductor. 24 V DC power supply cable for the panel shall be of 25
sq mm stranded, tinned, annealed copper conductor.
Testing on Cables
Check details are in accordance with the specification

Check for physical damage


Megger test between each core and armor/sheath
Continuity Check