Pipe Friction Lab Report
Pipe Friction Lab Report
Summary/ Abstract:
We investigated the effect of pipe friction on head loss in different types of flow. To achieve
this objective, we used a hydraulic bench with a hydraulic motor, test-pipe with a constant
diameter and a head tank with stilling material inside it. It reflected that beyond a certain flow
velocity, the type of flow changed from laminar to turbulent. There was found to be a linear
relationship between Reynolds Number and Fanning friction factor.
Introduction:
Pressure drop or head loss in pipes is due to eddy currents caused by friction
between the pipes inner surface, as a result of its roughness, and the fluid it
contains. The frictional force acts tangential to the motion of the fluid and
results in a decrease in the overall energy of the fluid in motion. The study of
the frictional force between a moving fluid and the walls of a pipe and the
energy loss associated with it has numerous engineering applications in industry
The results of this experiment could be used in the oil pipe system design and
pump design industries where knowledge of different magnitudes of pressure
drop for different types of fluid flow is imperative to their work. In pipe system
design, the pressure drop between two locations determines the minimum
acceptable cross-sectional area of the pipeline given the flow rate requirements
for a desired output in a system.
Engineers in the oil pipe system design industry also use their knowledge of
pressure drops in piping networks to produce the most economical balance
between installation costs of the piping system and operational costs of the
pumps system.
In oil pump design, the knowledge of pressure drop is crucial to determining the
size of the pumps. After engineering calculations to find out the type of oil flow
using the dimensionless Reynolds Number, the pressure drop or head loss
between two points is determined. This value of pressure drop is then accounted
for by the pumps as the amount of power loss due to frictional losses in the pipe
is the power required to be added to the system by the booster pumps. These
booster pumps will be placed at points in the pipe system where maximum
pressure drops occur.
This pipe friction experiment aims to investigate the magnitude of pressure drop
for a broad range of flow rates that represent laminar, transitional and fully
turbulent types of flow and to calculate an estimate for the critical Reynolds
number where the flow changes from laminar to turbulent in nature.
Theory:
The type of fluid flow in a system is found by calculation of the dimensionless Reynolds
Number (ratio between inertial forces and viscous forces):
R eD=
VD
Laminar flow
Transient or transitional Flow
Turbulent
Laminar flow occurs mainly in pipes with small-cross-sectional area, at low fluid flow
velocities or with fluids of relatively high density. It is the flow in which viscous forces
dominate inertial forces. Laminar flow is a smooth steady flow of a fluid where its particles
move in layers that do not mix and are parallel to the wall. Shear stress depends solely on
viscosity and is independent of density. Occurs below Re=2000
Turbulent flow occurs generally at high flow rates, in pipes with larger cross-sectional areas
or with fluids of relatively low density. It is the flow in which inertial forces dominate
viscous forces. Eddies and wakes mean the layers of particles are now mixed and the flows
behavior is unpredictable. Shear stress for turbulent flow is directly related to the fluids
density. Occurs above Re= 2000
Transient flow occurs when turbulent and laminar flows occur simultaneously with
turbulence in the middle of the flow and laminar flow at the sides. This occurs around Re=
2000.
The energy loss due to friction between the pipes inner surface and the fluid it contains can
be derived from the Bernoullis Equation which describes the different forms of energy
involved in the fluid:
2
p1 V 1
p V2
+ +Z 1 = 2 + 2 +Z 2 + h
2g
2g
)(
Where:
= Elevation in pipe in m
The value of Z (Z2 Z1), the length of the tube, is 510mm which will be a
constant throughout the experiment. The change in fluid velocity is
negligible, therefore, V2-V1= 0. Factoring these conditions into the
Bernoullis Equation and rearranging to make h L the subject of the
formula will give us an expression to calculate the total head loss:
h L=
p1 p 2
Z
In turbulent flow, the surface roughness of the pipe has a significant effect
on the head loss but in turbulent flow, the surface roughness of the pipe
has negligible effect on the head loss.
Through experimental observations, Darcy and Weisbach developed an
expression to calculate the energy loss in both laminar and turbulent flow:
f=
h L = Head loss in m
LV
2 Dg
= Diameter of pipe in m
Equipment:
1)Stopwatch- To
measure time
taken for water
to be
collected.
2)Measuring
Beaker- To
measure
volume of
water
collected
3) Hydraulic Bench:
A vertical piping
system with 3
valves in the rear
to switch
between
different types of
flow. A hydraulic
motor pumps
water up the
pipe and into the
head tank with
the stilling
matter for
laminar flow. The
motor is
connected
directly to the
test pipe by
adjusting the
valves to obtain
a higher flow
rate. (Turbulent
flow)
To obtain a laminar flow for the test, adjust the 3 valves at the back of
the bench. Engage Valve V1 and close valve V2 to allow the water to
flow to the reservoir.
Set the over flow tube at the required water level in the head tank.
Open valve V3 to allow the fluid to flow through the stilling material
and into the test pipe.
Control the volumetric flow rate using valve V4. Start the stopwatch
when the valve V4 is opened.
Close V4 and stop the timer simultaneously.
Record readings on the mercury manometer, reflecting pressure loss in
the test pipe between the 2 test points, and the water level reading on
the measuring water.
Repeat 4,5 and 6 for other rates of flow.
Turbulent Flow:
Disengage valves V2 and V3 and open valve v2 to allow water to flow
directly from the hydraulic bench into the test pipe to obtain a higher
rate of water flow.
Repeat 4,5 and 6 for a range of flow rates.
h1
(cm
.Hg)
h2
h
(cm. (cm.
Hg) H20
)
Head
Loss
(m)
Volum
e
(m3)
Time(s
)
22
22.5
0.5
0.505
0.0001
14.2
23
21.4
1.6
0.494
0.0001
13.3
21
23.5
2.5
0.485
0.0001
10.5
24
20.5
3.5
0.475
0.0001
8.75
23.7
20.9
2.8
0.482
0.0001
9.56
Flow
Rate
(m3/s
)
7.042
25E06
7.518
8E-06
9.496
68E06
1.142
86E05
1.046
03E05
Velocit
y
(m/s)
Reynold
s
Number
0.9962
76
1.0636
93
2598.98
1
2774.85
2
1.3435
06
Fanning
friction
(Experimen
tal)
Fanning
Friction
(Moody
diagram
)
0.01467987
0.015
0.0125975
0.013
3504.79
8
0.007752694
0.0076
1.6168
13
4217.77
4
0.005242807
0.0049
1.4798
24
3860.41
1
0.006350632
0.0064
Laminar Flow
0
3.4
-0.5
log(f)
3.45
3.5
3.55
3.6
3.65
-1
-1.5
-2
-2.5
log(Re)
h1
(cm.H
g)
h2
(cm.H
g)
h
(cm.H2
0)
Hea
d
Los
s
(m)
Volume
(m3)
5.5
0.45
5
0.000
1
9.8
7
1.013
E-05
Time(s)
1.4333
45
Flow Rate
(m3/s)
3739.161
623
Velocity
(m/s)
0.006389
985
Reynol
ds
Numbe
r
Fanning
friction
(Experimen
tal)
0.006
2
3.572774
Fann
Fricti
(Moo
diagr
4.5
7.5
8.4
9.7
0.46
5
0.43
5
0.42
6
0.41
3
0.000
1
0.000
1
0.000
1
0.000
1
9.6
6
7.0
3
6.5
3
5.7
5
1.035
E-05
1.422
E-05
1.531
E-05
1.739
E-05
1.4645
05
2.0123
92
2.1664
81
2.4603
68
3820.447
746
5249.719
093
5651.688
396
6418.352
213
0.006255
49
0.003099
232
0.002618
726
0.001968
52
0.006
2
0.003
1
0.003
0.002
5
3.582114
3.720136
3.752178
3.807424
Turbulent Flow
0
3.55
-0.5
3.6
3.65
3.7
3.75
3.8
3.85
-1
Calculations:
The sample calculations to calculate the Fanning friction factor and
Reynolds number from the results of each test are as follows:
h=h2h1
h water=5.5 cm
h L= h Z 0.055 0.510| = 0.455m
Flow rate Q=
Volume
Time
0.0001
m3
5 m
=1.013
=1.013 10
9.87
sec
s
2.25 10
2
5
Velocity v=Q( r )=(1.013 10 )/
hL
Frictional Factor f =
L V
D 2g
0.455
=0.00639
0.51
1.433 2
4
0.003 2 9.81
VD VD 1.43335 3 103
R eD =
=
=
= 3739.161623
1.15 106
Percentage error:
Largest percentage error in friction factor (laminar flow):
100
0.0052430.0049
0.0049
100 =
7%
Largest percentage error in friction factor (turbulent flow):
f (experimental )f ( Moody Diagram)
f ( Moody Diagram)
100
0.0019690.0025
0.0025
100
21.3 %
The percentage error for turbulent flow was much larger than that of
laminar flow as the much higher velocities needed highly accurate
mechanism for time measurement, which meant that, human error had a
much greater impact on the calculation of the friction factor.
Possible Sources of Error:
1) Human Error: Parallax error while reading the levels of manometric
fluid in the manometer and the volume of water in the measuring
beaker. Delay in recording the time taken for a volume of water to be
collected.
2) Diameter of test pipe: The diameter of the test pipe might vary slightly
through its length which would greatly affect the accuracy of the
readings as the readings are very susceptible to changes in pipe
diameter. This is because the diameter affects the flow rate calculation
and in turn, the calculation for the friction factor which is directly
related to the square of the flow velocity.
3) Fluctuations in Manometer: Air bubbles coul have been formed during
the calibration of the manometer which would lead to an error in the
readings for pressure difference.
Precautions:
1)
2)
3)
4)
Improvements:
1) Place measuring beaker at an appropriate height to avoid parallax
error rather than a relatively low height in the sink.
2) Use a stand to hold the delivery tube in order to avoid causing
unwanted fluctuations in pressure difference due to varying
elevation.
Conclusion:
The head loss in the test-pipe was found to be proportional to the flow velocity of the fluid.
The findings of the experiment have shown that the head loss due to friction in laminar flow
is much larger than in turbulent flow. It reflected that beyond a certain flow velocity, the type
of flow changed from laminar to turbulent. This laboratory experiment proved that the
Fanning friction factor was directly related to the Reynolds Number for both laminar flow
and turbulent flow which was expressed in the log graphs plotted from the results. It also
showed that the friction factor for laminar flow was significantly larger than for turbulent
flow.
References:
http://www.mvsengineering.com/files/SubsurfaceBook/MVS-SVE_Chapter02.pdf
http://www.engineersedge.com/fluid_flow/pressure_drop
/pipe-friction-calculation.htm
http://www.ipt.ntnu.no/~jsg/undervisning/prosessering/
kompendium/ErrorAnalysisStrupstad.pdf