Wind Design
Wind Design
John Holmes
Andrew King
Warreen Publishing
ii
Wind Actions
ISBN: 0-646-44705-X
Printed by:
Design and Print Services
University of Canterbury
Christchurch
New Zealand
Cover Design:
Justin Sharpe, Lucy Holmes and John Holmes
1Chapter 5: Examples
5.1 Example 1 - Single-storey house in an urban area
Design wind loads are required for a single-storey house in the Sydney metropolitan area.
The relevant information is as follows :
Location: western suburbs of Sydney (Region A2).
Terrain: Suburban terrain for all directions.
Topography: ground slope less than 1 in 20 for greater than 5 kilometres in all directions.
Dimensions: average roof height : 4.35metres
Horizontal dimensions, including entrance porch on south side (Figure 5.1):
24 metres x 12 metres
Porch : 2.4 X 14.5 m
Gable roof with 15 degrees pitch. Hip on west end. 0.6 m eaves.
Building orientation: major axis is East-West.
Timber frame construction. Wall studs are spaced at 0.4m. Roof trusses are spaced at
1.2m.
The building walls are considered equally permeable.
8
9
'
This house is used as an example in the Guide to the Use of the Wind Load provisions of
ASCE 7-02[21]. Its use in the present Design Guide allows for a comparison of the two
Standards for this building.
= 45 m l s
(Region A)
Wind direction multipliers for Sydney (Region A2) are given in Table 3.2. Values range from
0.80(N, NE, E) to 1.0 (W).
~ h 4 . 3 m,
5 For Terrain Category 3, MZ,,,= M4,35,caU
= 0.83 (Table 4.1(A))
Shielding
Since the building is surrounded by suburban development, assume a Shielding Multiplier,
Topography
Topographic Multiplier, M, = M,
1 .O
Chapter 5
21
1
i
For all wind directions, site wind speeds are calculated in the following table.
NE
E
SE
S
sw
W
NW
45
0.80
45
45
45
45
45
0.80
0.80
0.95
0.90
0.95
45
45
1.00
0.95
I
I
0.83
0.83
0.83
0.83
0.83
0.83
0.83
0.83
I
I
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85
1.0
1.o
1.o
1.o
1.o
1.o
1.o
1.0
25.4
25.4
25.4
30.2
28.6
30.2
31.7
30.2
In this case, the building is orientated exactly N-S and E-W, and the design wind speeds,
Vdes,B
can be obtained by inspection from VsitBin the above table, for the four wind directions
orthogonal to the building walls:
1
i
Vdes,N
= 30.2 m/s (largest from NW to NE sector)
j
j
Vdes,B
= 30.2 m/s (largest from NE to SE sector)
j
Vdes,S
= 30.2 m/s (largest from SE to SW sector)
Vdes,W
= 3 1.7 m/s (largest from SW to NW sector)
j
i
1
~
External pressures
I
j
Leeward walls :
(normal to long axis): -0.3 (Table 5.2(B))
(normal to short walls): -0.3
I!
/
j
Side walls
(first 4.35 m from windward edge): -0.65 (Table 5.2(C))
(4.35 m to 8.7 m): -0.5
(8.7 m to 13.05 m): -0.3
(beyond 13.05 m): -0.2
I
I
i
j
Roof
upwind slope (normal to long axis: h/d = 4.35/12=0.36): -0.59, -0.13 (Table 5.3(B))
downwind slope and hip end (normal to long axis: h/d = 4.35/12=0.36): -0.5 (Table 5.3(C))
upwind slope (normal to short walls: h/d = 4.35/24=0.18): -0.5,O.O (Table 5.3(B))
downwind slope (normal to short walls: h/d = 4.3Y244.18): -0.5 (Table 5.3(C))
crosswind slope, R (normal to short walls: first 4.35 m from w.e): -0.9,0.4 (Table 5.3(A))
crosswind slope, R (normal to short walls: 4.35 m to 8.7m from w.e): -0.5,O.O (Table 5.3(A))
crosswind slope, R (normal to short walls: 8.7 m to 13.05 m from w.e): -0.3, M.1 (Table 5.3(A))
crosswind slope, R (normal to short walls: beyond 13.05 m from w.e): -0.2, M.2 (Table 5.3(A))
....,...(............... .....
....... .,..,,..../
A Guide to ASINZS 1170.2: 2002
jr
...,
...
,.,
..
,
.l
j
l
.
'
1..
.
1
.
1
.
1
....... .,.....,.........
l..........,......,.~.~
,.,.
II
I//
North wall
As windward wall (north wind direction):
Cfig(external) = +0.7 (1 .O) (1 .O) = 0.7
~ ~ ) CfigCdF= (0.5)(1.2) (30.2)2(0.7)(1.0) = 383 Pa = 0.38 kPa
p,,, = ( 0 . 5 ~ Vdes,i
Cfig(internal) = -0.3 (1 .O) = -0.3
pin,= (0.5 psi) Vdes,iCfigCdY,= (0.5)( 1.2) (30.2)2(-0.3)( 1.O) = -164 Pa = -0.16 kPa
Net pressure across windward wall surface = 0.38-(-0.16) = 0.54 kPa
Chapter 5
23
East wall
As windward wall (east wind direction):
Cfig(external) = +0.7 (1 .O) (1 .O) = 0.7
p,,, =. (0.5 pa,,>Vdes,iCfigCdyn= (OS)( 1.2) (30.2) (0.7)( 1.O) = 383 Pa = 0.38 kPa
Cfig(internal) = -0.3 (1.0) = -0.3
p,,, = (0.5pal,>Vdes,: CfisCdyn= (0.5)(1.2) (30.2) (-0.3)(1.0) = -164 Pa = -0.16 kPa
Net pressure across wall surface = 0.38-(-0.16) = 0.54 kPa
West wall
As windward wall (west wind direction):
Cfig(external) = 44.7 (1.O) (1 .O) = 0.7
peXt= (0.5 paiJ
Vda,iCfiPCdyn
= (0.5)( 1.2) (3 1.7)2 (0.7)( 1.O) = 422 Pa = 0.42 kPa
Cfig(internal) = -0.3 (1.O) = -0.3
pint= (0.5pai$V;,
C, Cdyn
= (0.5)(1.2) (31.7)2(-0.3)(1.0) = -181 P a = -0.18 kPa
Net pressure across wah surface = 0.42-(-0.18) = 0.60 kPa
As side wall - northwind direction:
For 0 to Ih (0 to 4.35 m) from north edge - same as east wall: -0.36 kPa
p,,, = 0 kPa
Net pressure across wall surface = -0.36 kPa (acting outwards)
1
l
1
1
'
I
I
Roof
north wind direction
north roof slope (surface 8).
Cfig(external) = -0.59 (1.O) (1.O) = -0.59
p,,, = (0.5 pa,$Vdes,; CfigCdyn
= (0.5)( 1.2) (30.2)2 (-0.59)( 1.O) = -323 Pa = -0.32 kPa
Cfig(internal) = 0.0 (1 .O) = 0.0
P,,, = 0 kPa
Net pressure across roof surface = -0.32-(0.0) = -0.32 kPa
South roof slope (surface 9) and hip end (surface 7).
Cfig(external) = -0.5 (1.0) (1.0) = -0.5
p,,, = (0.5pa,,>Vdes,; CfigCdyn= (0.5)(1.2) (30.2)2 (-OS)(l.O) = -274 Pa = -0.27 kPa
P,,, = 0 kPa
Net pressure across roof surface = -0.27-(0.0) = -0.27 kPa
east wind direction
east roof slope (surface 10).
Cfig(external) = -0.59 (1.O) (1.O) = -0.59
p,,, = (0.5 pa,,>Vdes,lCfigCdyn= (0.5)(1.2) (30.2)2 (-0.59)( 1.O) = -323 Pa = -0.32 kPa
Cfig(internal) = 0.0 (1.O) = 0.0
p,,, = 0 kPa
Net pressure across roof surface = -0.32-(0.0) = -0.32 kPa
west roof slope (surface 11).
CfiU
(external) = -0.5 (1.0) (1.0) = -0.5
P,,, = (0.5 pa,,>Vdes,; CfigCdyn
= ( O S ) ( 1.2) (30.2)2 (-0.5)( 1.O) = -274 Pa = -0.27 kPa
pi,, = 0 kPa
Net pressure across roof surface = -0.27-(0.0) = -0.27 kPa
south wind direction
south roof slope (surface 9).
Cfig(external) = -0.59 (1.O) (1 .O) = -0.59
p,,, = (0.5 pa,,>
Vdes,; CfigCdyn= (0.5)(1.2) (30.2)2 (-0.59)(1.0) = -323 Pa = -0.32 kPa
Cfig(internal) = 0.0 (1.O) = 0.0
P,,, = 0 kPa
Net pressure across roof surface = -0.32-(0.0) = -0.32 kPa
north roof slope (surface 8) and hip end (surface 7).
Cfig(external) = -0.5 (1.O) (1 .O) = -0.5
p,, = (0.5 pa,$Vde,,; Cfi8Cdyn
= (0.5)( 1.2) (30.2)2 (-0.5)(1 .O) = -274 Pa = -0.27 kPa
p,,, = 0 kPa
Net pressure across roof surface = -0.27-(0.0) = -0.27 kPa
crosswind roof slopes (surfaces I O and 11).
For length 0 to l h (0 to 4.35 m) from windward edge:
Cfig(external) = -0.9 (1 .O) (1.O) = -0.9
p,,, = (0.5 pa,$Vdes,; CfigCdyn= (0.5)( 1.2) (30.2)2(-0.9)( 1.O) = -493 Pa = -0.49 kPa
P,,, = 0 kPa
Net pressure across roof surface = -0.49-(0.0) = -0.49 kPa
For length l h to 2h (4.35m to 8.7m)from windward edge:
Cfiv(external) = -0.5 (1.0) (1.0) = -0.5
p,,;= (0.5 pa,)Vdes,; CfigCdyn
= (0.5)( 1.2) (30.2)2 (-0.5)( 1.O) = -274 Pa = -0.27 kPa
pi,, = 0 kPa
..,...i..,,.......I........~.,,.. ..,.,
.l.l.l.'
1.1..1....1.1..
.".I
I.......'..I...
~..,~
.,,.,
.
,
.
l
.
.
.
l
.,.. .,.,..
~
Chapter 5
27
For windows (or doors) more than 1.44 m2 in area on west wall:
Cfig(external) = +0.7 (1.O) (1.O) = +0.7 (positive case)
p,,, = (0.5 pa,)Vdes,: CfigCdyn= (OS)( 1.2) (3 1.7)2 (+0.7)( 1.O) = +422 Pa = +0.42 kPa
Cfig(internal) = -0.3 (1.0) = -0.3
pi,, = ( 0 . 5 ~ ~Vdcs,:
~ ) CfigCdyn
= (0.5)(1.2) (31.7)2 (-0.3)(1.0) = -181 P a = -0.18 kPa
Net pressure across window = +0.42-(-0.18) = +0.60 kPa
For windows or doors up to 5.76 m2 in area on east and west walls within a distance of 2.4 m
from south and north corners, or on north or south wall within 2.4 m from east corners:
Cfiu(external) = -0.65 (1.O) (1.5) = -0.975 (negative case)
p,,p= ( 0 . 5 ~ ~
Vdes,i
~ ) CfigCdyn
= (0.5)(1.2) (30.2)2(-0.975)(1.0) = -534 Pa = -0.53 kPa
pin, = 0 kPa
Net pressure across window = -0.53-(0.0) = -0.53 kPa
..
~,.,.
Wind Actions
Chapter 5
For windows or doors up to 5.76 m2 in area on north and south walls within a distance of 2.4
m from west corners:
Cfig(external) = -0.65 (1 .O) (1.5) = -0.975 (negative case)
p,,, = (0.5 psi) Vdes,: CfiPCdyn= (0.5)( I .2) (3 1.7)2(-0.975)(1.O) = -588 Pa = -0.59 H a
pint= 0 kPa
Net pressure across window = -0.59-(0.0) = -0.59 kPa
For any other windows or doors, loads for major framing members apply.
For roof cladding elements less than 5.76 m2 in area, on roof surfaces 8 and 9, up to 2.4 m
from east edge of roof, and on roof surfaces 10 and 11, up to 2.4 m from south edge of roof:
Cfig(external) = -0.9 (1.0) (1.5) = -1.35
p,, = (OSp,,,)Vdes,;CfigCdyn= (0.5)(1.2) (30.2)(-1,35)(1.0) = -739 Pa= -0.74 kPa
pi,, = 0 kPa
Net pressure across element = -0.74-(0.0) = -0.74 kPa
For roof cladding elements less than 5.76 m2 in area, on roof surfaces 8 and 9, up to 2.4 m
from west edge of roof :
Cfig (external) = -0.9 (1.0) (1.5) = -1.35
p,,, = ( 0 . 5 ~ Vdes,:
~ ~ ) CfiPCdyn= (0.5)(1.2) (31.7)2(-1.35)(1.0) = -814 Pa = -0.81 kPa
pint= 0 kPa
Net pressure across element = -0.81-(0.0) = -0.81 kPa
For roof cladding elements less than 1.44 m2 in area, on roof surfaces 8, 9,lO and 11, up to
1.2 m from windward edge of roof :
Cfig(external) = -0.59 (1.O) (2.0) = -1.18 (negative case)
p,,, = (0.5 paiJVdes,tCfigCdy,,= (0.5)(1.2) (30.2)2(-1. IS)( 1.O) = -646 Pa = -0.65 kPa
pint= 0 kPa
Net pressure across element = -0.65-(0.0) = -0.65 kPa
For roof cladding elements less than 1.44 m2 in area, on roof surface 7, up to 1.2 m from west
edge of roof:
Cfig(external) = -0.59 (1 .O) (2.0) = - 1.18 (negative case)
p,,,=(0.5p,i,)Vdes,~CfisCdyn=
(0.5)(1.2) (31.7)2(-1.18)(1.0)=-711 Pa=-0.71 kPa
pin, = 0 kPa
Net pressure across element = -0.71-(0.0) = -0.71 kPa
For roof cladding elements less than 5.76 m2 in area, on roof surfaces 8, 9,lO and 11, up to
2.4 m from windward edge of roof:
Cfig(external) = -0.59 (1.O) (1.5) = -0.89 (negative case)
p,,, = (0.5 paiJVd,,i CfigCdyn= (0.5)(1.2) (30.2)2(-0.89)(1.O) = -487 Pa = -0.49 kPa
pint= 0 H a
Net pressure across element = -0.49-(0.0) = -0.49 kPa
For roof cladding elements less than 5.76 m2 in area, on roof surface 7, up to 2.4 m from west
edge of roof :
Cfig(external) = -0.59 (1.0) (1.5) = -0.89
p,,, = (O.5paiJVdes,tCfigCdYn
= (0.5)(1.2) (31.7)2(-0.89)(1.0) = -537 Pa = -0.54 kPa
pint= 0 kPa
Net pressure across element = -0.54-(0.0) = -0.54 kPa
Loading on battens should be applied as moving 'patch' loads, with a tributary area equal to
the batten spacing times the truss rafter spacing, with the appropriate local pressure factor for
that area. For example, in this case, if the batten spacing is 0.6 m, the tributary area would be
1.2 X 0.6 = 0.72 mz. Since this area is less than 0.25a2,the local pressure factor would be 1.O,
1.5 or 2.0, depending on the distance of the centre of the 'patch' from the roof edge. Over the
remainder of the batten, K, should be taken as 1.O; i.e. the loading should be the same as used
for major structural members.
I
I
Shielding
Since there are no surrounding buildings, Ms = 1.O
Topography
Prohle through topography for the south, south-east and south-west directions are shown in
Figure 5.2 (a), (b) and (c) respectively.
.............
I ...I.
I
.,.,...
~.-.,
....
I I.....
I......._I..
I.
...lj
.....
'
..I..
"...X..."..".I.~~
..-.,,..--. ................,.....
~
Chapter
Actions
5
N-s/
section
- wm
~ 6 0 m
/*m
section
36 m
NW-SE
section
x = lOm
-=0.83
H
2-4,
The house is within the separation zone (Figure 4.4).
L, = greater of 0.36Lh or 0.4H = max{ 13.0 m, 24 m} = 24 m
L,= 10 x 2 4 m = 2 4 0 m
(Equation 4.4(3))
Lu=45 x=16m.
-= 0.67
244
60
3.5 (4.3 5 + 30.6)
(Equation 4.4(2))
= 36.9 m/s
31
Wind Actionq
32 /Chnpter5
For all wind directions, site wind speeds are calculated in the following table.
~.-'..
A Guide to ASlNZS 1170.2: 2002
WindChapter
Actions
5
= -418
Pa = -0.42 kPa
pint= 0 kPa
Net pressure across wall surface = -0.42 kPa (ignore - leeward wall case governs)
East wall
As windward wall (east wind direction):
Cfig(external) = +0.7 (1.0) (1.0) = 0.7
p,, = (0.5 pai$Vdes,iCfigCdyn= (0.5)(1.2) (48.2) (0.7)(1.0) = 976 Pa = 0.98 kPa
Cfig(internal) = -0.3 (1.0) = -0.3
pint= ( 0 . 5 ~ ~
Vdes,i
~ ) CfigCdyn= (0.5)(1.2) (48.2) (-0.3)(1.0) = -418 Pa = -0.42 kPa
Net pressure across wall surface = 0.98-(-0.42) = 1.40 kPa
As side wall - north wind direction:
Forfirft 4.35 mfiorn north edge:
Cfig(external) = -0.65 (1 .O) (1 .O) = -0.65
p,,, = (0.5pai,) Vdes,: CfigCdyn= (0.5)(1.2) (38.9) (-0.65)(1.0) = -590 Pa = -0.59 kPa
Cfig(internal) = 0.0 (1 .O) = 0.0
pint= 0 kPa
Net pressure across wall surface = -0.59 kPa (ignore - leeward wall case governs)
33
West wall
As windward wall (west wind direction):
Cfig(external) = +0.7 (1 .O) (1 .O) = 0.7
p,,, = (0.5 pair)Vdes,: CfigCdyn= (0.5)( 1.2) (64.6)2(0.7)( 1.O) = 1753 Pa = 1.75 kPa
Cfig (internal) = -0.3 (1 .O) = -0.3
pi,, = (0.5 pair)Vdes,: CfigCdyn= (0.5)( 1.2) (64.6)2(-0.3)( 1.O) = -75 1 Pa = -0.75
Net pressure across wall surface = 1.75-(-0.75) = 2.50 kPa
j
wind direction:
As side wall Forjrst 4.35 m from north edge - same as east wall: -0.59 kPa.
South wall
As windward wall (south wind direction):
C,. (external) = +0.7 (1.O) (1 .O) = 0.7
p,,, = (0.5 pair)Vdes,: CfigCdy,= (0.5)( 1.2) (64.6)2 (0.7)(1.O) = 1753 Pa = 1.75 kPa
Cfig(internal) = -0.3 (1 .O) = -0.3
pin,= (0.5 pair)Vdes,; CfigCdyn= (0.5)( 1.2) (64.6)2 (-0.3)( 1.O) = -75 1 Pa = -0.75 kPa
Net pressure across wall surface = 1.75-(-0.75) = 1.50 kPa
..~....
A Guide to ASlNZS 1170.2: 2002
Wind Actions
Chapter 5
Roof
north wind direction
north roof slope (surface 8).
C,. (external) = -0.59 (1.O) (1.O) = -0.59
p,, = ( 0 . 5 ~ Vdes,:
~ ~ ) CfigCdyn= (0.5)(1.2) (38.9) (-0.59)(1.0) = -536 Pa = -0.54 kPa
Cfig(internal) = 0.0 (1 .O) = 0.0
pint= 0 kPa
Net pressure across roof surface = -0.54-(0.0) = -0.54 kPa
1
/
j,
1j
1;
I
I
1
j
1
]
~
I
j
= -2254 Pa = -2.25 H
1i
j
I
j
I
Chapter
Actions5 37
.........
.......,.,.........................."..l.l.*..."...........~...l.*-_,.
11, I/.
"
r._......__
~,*
WindChapter
Actions5
For windows (or doors) more than 1.44 m2 in area on east wall:
C,. (external) = +0.7 (1.O) (1 .O) = +0.7 (positive case)
Vdes,: CfigCdyn= (0.5)(1.2) (48.2)2(+0.7)( 1.O) = +976 Pa = M.98 kPa
p,,, = (0.5 paiJ
Cfig(internal) = -0.3 (1.O) = -0.3
pi,, = (0.5 pa,,)Vdes,: CfigCdyn= (0.5)(1.2) (48.2)2(-0.3)(1.0) = -418 Pa = -0.42 kPa
Net pressure across window = +0.98-(-0.42) = +1.40 kPa
For windows (or doors) more than 1.44 m2 in area on south and west walls:
= +0.7 (positive case)
p,,, = (0.5 paiJVdes,iCfigCdyn= (0.5)(1.2) (64.6)2(+0.7)(1.0) = +1753 Pa = +1.75 kPa
C,. (internal) = -0.3 (1.O) = -0.3
pint= ((0.5 pa,>Vdes,iCfigCdyn= (0.5)( 1.2) (64.6)2(-0.3)( 1.O) = -75 1 Pa = -0.75 kPa
Net pressure across window = +1.75-(-0.75) = +2.50 kPa
For windows up to 5.76 m2 in area on east and west walls within a distance of 2.4 m from
north corners:
Cfig(external) = -0.65 (1.O) (1.5) = -0.975 (negative case)
p,,, = (0.5 pa,,>Vdes,iCfigCdyn= (0.5)(1.2) (38.9)2(-0.975)(1.0) = -885 Pa = -0.89 kPa
pint= 0 kPa
Net pressure across window = -0.89-(0.0) = -0.89 kPa
For windows up to 5.76 m2 in area on north and south walls within a distance of 2.4 m from
east corners:
Cfig(external) = -0.65 (1.O) (1.5) = -0.975 (negative case)
p,,, = (0.5 pa,$Vdes,iC,. Cdy, = (0.5)( 1.2) (48.2)2(-0.975)( 1.O) = -1359 Pa = -1.36 kPa
pin,= 0 kPa
Net pressure across window = -1.36-(0.0) = -1.36 kPa
For windows up to 5.76 m2 in area on east and west walls within a distance of 2.4 m from
south comers, and on north and south walls within a distance of 2.4 m from west corners:
Cfig(external) = -0.65 (1.0) (1.5) = -0.975 (negative case)
p,,, = (0.5 paJVdes,: CfigCdy, = (0.5)( 1.2) (64.6)2(-0.975)( 1.O) = -2441 Pa = -2.44 kPa
pi,, = 0 kPa
Net pressure across window = -2.44-(0.0) = -2.44 kPa
For any other windows or doors, loads for major framing members apply.
Design loadings for roof cladding and battens ultimate limit states
(note: for permissible stress design - divide loads by 1.5)
For roof cladding elements less than 1.44 m2 in area, on roof surfaces 8 and 9, up to 1.2 m
from east edge of roof:
Cfig(external) = -0.9 (1.O) (2.0) = -1.8
p,,, = (0.5 pa,,>Vdes,: CfigCdyn= (0.5)(1.2) (48.2)2(-1.8)( 1.O) = -2509 Pa = -2.5 1 kPa
pint= 0 @a
Net pressure across element = -2.5 1-(0.0) = -2.5 1 kPa
For roof cladding elements less than 1.44 m2 in area, on roof surfaces 8 and 9, up to 1.2 m
from west edge of roof, and on roof surfaces 10 and 11, up to 1.2 m from south edge of roof :
Cfig(external) = -0.9 (1 .O) (2.0) = -1.8
p,,, = (0.5 psi,) Vdes,: C,. Cdyn= (0.5)(1.2) (64.6)2(-1.8)(1.O) = -4507 Pa = -4.5 1 kPa
pi,, = 0 kPa
Net pressure across element = -4.5 1-(0.0) = -4.5 1 kPa
39
For roof cladding elements less than 5.76 m2 in area, on roof surfaces 8 and 9, up to 2.4 m
from east edge of roof:
Cfig(external) = -0.9 (1.0) (1.5) = -1.35
p,,, = ( 0 . 5 ~Vdes,t
~ ~ )CfigCdyn= (0.5)(1.2) (48.2)2(-1.35)(1.0) = -1882 Pa = -1.88 kPa
pint= 0 kPa
Net pressure across element = -1.88-(0.0) = -1.88 kPa
For roof cladding elements less than 5.76 m2 in area, on roof surfaces 8 and 9, up to 2.4 m
from west edge of roof, and on roof surfaces 10 and 11, up to 2.4 m from south edge of roof:
Cfis
(external) = -0.9 (1.0) (1.5) = -1.35
-.p,,, = (O.5pai) Vdes,;CfiPCdyn= (0.5)(1.2) (64.6)2(-1.35)(1.0) = -3380 Pa = -3.38 kPa
pTn,= 0 kPa
Net pressure across element = -0.81-(0.0) = -3.38 kPa
For roof cladding elements less than 1.44 m2 in area, on roof surface 8, up to 1.2 m from
north edge of roof :
Cfig(external) = -0.59 (1.0) (2.0) = -1.18 (negative case)
p,,,= ( 0 . 5 ~Vdes,t
~ ~ )CfigCdyn= (0.5)(1.2) (38.9)2(-1.18)(1.0) = -1071 P a = -1.07 kPa
pi,, = 0 kPa
Net pressure across element = -1.07-(0.0) = -1.07 kPa
For roof cladding elements less than 1.44 m2 in area, on roof surface 7, up to 1.2 m from west
edge of roof, and on roof surface 9, up to 1.2 m from south edge of roof :
Cfig(external) = -0.59 (1.0) (2.0) = -1.18 (negative case)
p,,, = (O.5pai) Vdes,; CfigCdyn= (0.5)(1.2) (64.6)2(-1.18)(1.0) = -2955 P a = -2.95 kPa
pint= 0 kPa
Net pressure across element = -2.95-(0.0) = -2.95 kPa
For roof cladding elements less than 5.76 m2 in area, on roof surface 8, up to 2.4 m from
north edge of roof :
Cfig(external) = -0.59 (1.O) (1.5) = -0.89 (negative case)
p,,, = ( 0 . 5 ~ Vdes,t
~ ~ ) C,,, Cdy, = (0.5)(1.2) (38.9)2(-0.89)(1.0) = -808 Pa = -0.81 kPa
pint= 0 kPa
Net pressure across element = -0.81-(0.0) = -0.81 kPa
For roof cladding elements less than 5.76 m2 in area, on roof surface 7, up to 2.4 m from west
edge of roof, and on roof surface 9, up to 2.4 m from south edge of roof:
Cfig(external) = -0.59 (1.O) (1S ) = -0.89
p,,, = (0.5 pa,>Vdes,: CfigCdyn= (0.5)(1.2) (64.6)2(-0.89)(1.O) = -2228 Pa = -2.23 E a
pint= 0 kPa
Net pressure across element = -2.23-(0.0) = -2.23 kPa
Loading on battens should be applied as moving 'patch' loads with a tributary area equal to
the batten spacing times truss rafter spacing, with the appropriate local pressure factor for
that area. For example, in this case, if the batten spacing is 0.6 m, the tributary area would be
1.2 X 0.6 = 0.72 m2. Since this area is less than 0.25a2,the local pressure factor could be 1.O,
1.5 or 2.0, depending on the distance of the centre of the 'patch' from the roof edge. Over the
remainder of the batten, K, should be taken as 1.O; i.e. the loading should be the same as used
for major structural members.
Wind Actions
Chapter 5
Figure 5.3
= 45 m l s
(Region A)
Wind direction multipliers for Auckland (Region A6) are given in (Table 3.2). Values range
from 0.85 (N, S) to 1.O (E, W).
Terrain-height
z=h=6.2 m, for Terrain Category 3, MZ,,t= M6,2,aat3
= 0.83 (Table 4.1(A))
for Terrain Category 2, Mz,cat
= M6,Z,aa
= 0.93 (Table 4.1 (A), by interpolation)
41
Shielding
The building has other industrial development to the north and west, assume a Shielding
Multiplier, Ms, of 0.85 for N, W, NW directions. Take Ms =1.0 for other directions.
Topography
Topographic Multiplier, M, = M,
~ ~1
N
NE
E
SE
S
SW
W
NW
m/s)
45
45
45
45
45
45
45
45
1.O
~ ~1
0.85
0.95
1.oo
0.95
0.85
0.95
1.oo
0.95
0.83
0.83
0.83
0.83
0.93
0.93
0.83
0.83
0.85
1.o
1.o
1.o
1.o
1.o
0.85
0.85
1.o
1.o
1.o
1.o
1.o
1.o
1.o
1.o
m/s)
27.0
35.5
37.4
35.5
35.6
39.8
31.7
30.2
Wind Actions
Chapter 5
Roof
(0 to 6.2 m from windward edge): -0.9, -0.4 (Table 5.3(A))
(6.2 m to 12.4 m): -0.5
(12.4 m to 18.6 m): -0.3, +0.1
(beyond 18.6 m): -0.2, +0.2
Area reductionfactors (Table 5.4)
For wall loads on end frame columns (as side wall): tributary areas 5.85 X 2.5 = 14.6 m2
Ka = 0.97 (Table 5.4 by interpolation)
For wall loads on central frame columns (as side wall): tributary areas 5.85 X 5 = 29.25 m2
K, = 0.89
For roof loads on end frame rafters: tributary areas 15 x 2.5 = 37.5 m2.
K, = 0.88
For roof loads on central frame rafters: tributary areas 15 X 5 = 75 m2.
K, = 0.83
Local pressure factors (Table 5.6)
a = minimum of 0.2 X 15 m, 6.2 m = Min(3.0 m, 6.2 m} = &
limiting tributary areas for local pressure factors : 0.25a2=2.25 m2
a2= h2
= 0.8
Case (c) is applicable, for all wind directions, to positive pressures on downwind end of roof
with negative internal pressures: Kc = 0.8
Case (d) in Table 5.5 is applicable to external negative roof and leeward wall pressures
and positive internal pressures, for SW winds: K, = 0.95. However, Kc= 0.8 from Case (b)
governs for external roof and leeward pressures.
Otherwise, Kc = 1.O
= 470
Pa = +0.47 kPa
j
j
I
Endframes
= -336 Pa
= -201
=-0.34 kPa
Pa =-0.20 kPa
Centralframes
Same as end frames (combined Ka K, for roof pressures is equal to 0.8)
-0.20 kPa
-0.34 kPa
-0.60 kPa
@
+0.47 kPa
-0.34 kPa
Figure 5.4 Load case I
- NE wind
Chapter
Actions5
End frames
= -380 Pa =-0.38
= -228 Pa
kPa
=-0.23 kPa
Centralframes
Same as end frames (combined KaKcfor roofpressures is equal to 0.8)
-1.32 kPa
-1.02 kPa
-0.87 kPa
-0.14 kPa
-1.02 kPa
45
-0.48 kPa
4
-0.38 kPa
-0.38 kPa
+0.22 kPa
+0.22 kPa
.*.,.........n,.".ll..n ..._.__-_-_.
...I
....
-11__1I
.
"
"
_..Y.Y.
*-Y."
-.-....--.>...,.=.
~
"rnl.
Wind Act
Chapter 5
4
-0.53 kPa
= -663
Pa = -0.66 kPa
-0.66 kPa
4
-0.53 kPa
First inboard frame from NWend (downward roof load case, roller door closed, Cp,i= -0.3)
The tributary areas for this frame are between 17.5 m and 22.5m from the windward end. i.e.
between 2.81 and 3.6h from the windward (SE) end.
Fraction of area in 2h to 3h zone (1.115) = 0.22
Fraction of area in >3h zone (3.915) = 0.78
side walls (south west and north east walls):
Cfig(external) = Cp,,K, K, = (-0.222)(0.89)(1.O) = -0.20
p,,, = (O.5paJ Vdes,iCfigC,,, = (0.5)(1.2) (37.4)' (-0.20)(1.0) = -168 Pa = -0.17 kPa
Cfig (internal) = -0.3 (1 .O) = -0.30
pin,= (0.5 pa,>Vdes,iCfigCdy,= (0.5)(1.2) (37.4)' (-0.30)(1.0) = -252 Pa = -0.25 kPa
Net pressure across wall surface = -0.17-(-0.25) = +0.08 kPa
roof
Cfig(external) = Cp,,K, K, = (+0.178)(0.83)(0.8/0.83) = +0.14
p,,, = ( 0 . 5 ~ Vdes,i
~ ~ ) CfigCdY,= (0.5)(1.2) (37.4)' (+0.14)(1.0) = +117 Pa = +0.12 kPa
Cfig(internal) = -0.3 (0.8) = -0.24
pint= (0.5 paiJVdes,: CfigCdyn= (0.5)( 1.2) (37.4)2 (-0.24)(1.O) = -201 Pa = -0.20 kPa
Net pressure across wall surface = +0.12-(-0.20) = +0.32 kPa
ind Actions
48 /6,,ter5
+0.32kPa
+0.32kPa
+0.08kPa
+0.08kPa
Figure 5.9 Load case 6 - SE wind
- inboard frame
Design wind pressures for doors and windows ultimate limit states
(note: for permissible stress design - divide loads by 1.5)
-...,. ..-..
.
.
W
.
"
.
I*
.
-.-.
1
1
I--.
Wind Act
Chapter 5
Design wind pressures for wall and roof claddings and supporting
structure - ultimate limit states
(note: for permissible stress design - divide loads by 1.5)
Wall cladding
For cladding on north west or south east walls Area< 2.25 m2, between 0 and 1.5 m from the
north east comers: (NE Wind)
Cfig(external) = -0.65 (1.0) (2.0) = -1.3
p,,, = ( 0 . 5 ~ Vdes,t
~ ~ ) CogCdyn= (0.5)(1.2) (37.4)*(-1.3)(1.0) = -1091 Pa = -1.09 kPa
pin,= 0 kPa
Net pressure across element = -1.09-(0.0) = -1.09 kPa
For cladding on north west or south east walls Area< 2.25 m2,between 0 and 1.5 m from the
north east corners: (SW Wind with roller door open)
Cfig(external) = -0.30 (1 .O) (1.O) = -0.3
p,,, = (0.5 paiJVdes,tCfigCdyn= (0.5)(1.2) (39.8)*(-0.3)(1.0) = -285 Pa = -0.29 kPa
pint= ( O S ) ( 1.2) (39.8)2 (+0.70)(1.O) = +665 Pa = +0.67 kPa
Net pressure across element = -0.29-(+0.67) = -0.96 kPa
(NE wind case is dominant)
For cladding on north west or south east walls Area< 2.25 m2,between 0 and 1.5 m from the
south west comers: (SW Wind with roller door open)
Cog(external) = -0.65 (1 .O) (2.0) = -1.3
peXt= (0.5paiJVdes,iCogCdy,= (0.5)(1.2) (39.8)2(-1.30)(1.0) = -1236Pa = -1.24 kPa
pint= ( O S ) ( 1.2) (39.8)2 (+O.70)(1.O) = +665 Pa = W.67 kPa
Net pressure across element = -1.24-(W.67) = -1.91 kPa
For cladding on north west or south east walls Area< 9 m2,between 0 and 3.0 m from the
north east comers: (NE Wind)
Cog(external) = -0.65 (1.0) (1.5) = -0.975
p,,, = (O.5pai) Vdes,iCfigCdyn= (0.5)(1.2) (37.4)2(-0.975)(1.0) = -818 Pa = -0.82 kPa
pint= 0 kPa
Net pressure across element = -0.82-(0.0) = -0.82 kPa
For cladding on north west or south east walls Area< 9 m', between 0 and 3.0 m from the
north east comers: (SW Wind with roller door open)
(same as cladding with Area <2.25 m2 calculated previously)
Net pressure across element = -0.29-(+0.67) = -0.96 kPa
(in this case, SW wind is dominant)
For cladding on north west or south east walls Area< 9 m2,between 0 and 3.0 m from the
south west comers: (SW Wind with roller door open)
Cfig(external) = -0.65 (1 .O) (1.5) = -0.975
p,,, = (0.5 pai$
Vdes,: CfiPCdyn= (OS)( 1.2) ( 3 9 ~ 3(-0.975)(
)~
1.O) = -927 Pa = -0.93 kPa
pint= (0.5)(1.2) (39.8)2 (+0.70)(1.0) = +665 Pa = +0.67 kPa
Net pressure across element = -0.93-(+0.67) = -1.60 kPa
For cladding on south west walls Area< 2.25 m2 , between 0 and 1.5 m from the south east
comers: (SE Wind)
Cfig(external) = -0.65 (1 .O) (2.0) = -1.3
p,,, = (0.5pa,>Vdes,: CfigCdyn= (0.5)(1.2) (37.4)' (-1.3)(1.0) = -1091 P a = -1.09 kPa
pint= 0 kPa
Net pressure across element = -1.09-(0.0) = -1.09 kPa
For cladding on south west walls Area <9 m2,between 0 and 3.0 m from the south east
comers: (SE Wind)
Cfig(external) = -0.65 (1.O) (1.5) = -0.975
pa,, = (0.5 psi$ Vdes,: CfigCdyn= (0.5)(1.2) (37.4)' (-0.975)(1.0) = -818 Pa = -0.82 kPa
pi,,,= 0 kPa
Net pressure across element = -0.82-(0.0) = -0.82 kPa
For cladding on north east walls any area:
(SW Wind with roller door open)
CfiP(external) = -0.50 (1 .O) (1 .O) = -0.5
p,,, = (0.5 pa,$Vdcs,: CfigCdyn= (0.5)(1.2) (39.8)' (-OS)(l,O)
pint= ( O S ) ( 1.2) (39.8)2 (+0.70)(1.O) = +665 Pa = +0.67 Wa
Net pressure across element = -0.48-(0.67) = -1.15 Wa
For cladding on north west or south east walls Area< 2.25 m2 ,between 0 and 1.5 m from the
south west comers: (SW Wind with roller door open)
Cfig(external) = -0.65 (1 .O) (2.0) = -1.3
p,,, = ( 0 . 5 ~Vdes,:
~ ~ )CfigCdyn
= (0.5)(1.2) (39.8)' (-1.3)(1.0) = -1236 Pa = -1.24 kPa
pint= (0.5)(1.2) (39.8)2 (+0.70)(1.0) = +665 Pa = +0.67 kPa
Net pressure across element = -1.24-(0.67) = -1.91 kPa
For cladding on north west or south east walls Area< 9 m2,between 0 and 3.0 m from the
south west comers: (SW Wind with roller door open)
CfiP(external) = -0.65 (1 .O) (1.5) = -0.975
p,, = (0.5 p&) Vdes,: CfigCdyn= (OS)( 1.2) (39.8)2 (-0.975)(1.O) = -927 Pa = -0.93 kPa
pint= (OS)( 1.2) (39.8)2 (+0.70)(1.O) = +665 Pa = +0.67 kPa
Net pressure across element = -0.93-(0.67) = -1.60 kPa
For cladding on south west walls Area< 2.25 m2between 0 and 1.5 m from the north west
comers: (NW Wind)
Cfig(external) = -0.65 (1.0) (2.0) = -1.3
p,,, = (0.5 psi$ Vdes,iCfigCdyn
= (0.5)(1.2) (3 1.7)2(-1.3)( 1.O) = -784 Pa = -0.78 kPa
pint= 0 P a
Net pressure across element = -0.78-(0.0) = -0.78 kPa
A Guide to ASlNZS 1170.2: 2002
Chapter
Actions
5 51
For cladding on south west walls Area< 9 m2 between 0 and 3.0 m from the north west
corners: (NW Wind)
Cfig(external) = -0.65 (1 .O) (1.5) = -0.975
p,,, = (0.5 psi$ Vdes,: CfigCdyn= (0.5)(1.2) (31.7)2(-0.975)(1.0) = -588 Pa = -0.59 kPa
pint= 0 kPa
Net pressure across element = -0.59-(0.0) = -0.59 kPa
Roof cladding
For roof cladding elements area< 2.25 m2, on roof between 0 and 1.5 m from north east, or
south east, edges of roof: (NE or SE Wind)
Cfig(external) = -0.9 (1.0) (2.0) = -1.8
peXt= ( 0 . 5 ~ Vdes,:
~ 3 CfipCdyn=(0.5)(1.2) (37.4)2(-1.8)(1.0) = -1511 P a = -1.51 kPa
pint= 0 kPa
Net pressure across element = -1.51-(0.0) = -1.51 kPa
For roof cladding elements between 2.25 and 9 m2 in area, on roof between 0 and 3.0 m from
north east, or south east, edges of roof:
Cfig(external) = -0.9 (1.0) (1.5) = -1.35
p,,,=(0.5pai,)Vdes,~
CfipCdyn=
(0.5)(1.2) (37.4)2(-1.35)(1.0)=-1133 Pa=-1.13 kPa
pi,, = 0 kPa
Net pressure across element = - 1.13-(0.0) = - 1.13 kPa
For roof cladding elements area< 2.25 m2, on roof between 0 and 1.5 m from south west edge
of roof: (SW Wind with roller door open)
Cfig(external) = -0.9 (1.0) (2.0) = -1.8
pext=(0.5pai,)Vdes,~CfigCdyn=
(0.5)(1.2) (39.8)2(-1.8)(1.0)= -1711 Pa=-1.71 Wa
pint= (0.5)(1.2) (39.8)2 (+0.70)(1.0) = +665 Pa = +0.67 kPa
Net pressure across element = -1.71-(0.67) = -2.38 Wa
For roof cladding elements between 2.25 and 9 m2,on roof between 0 and 3.0 m from south
west edge of roof: (SW Wind with roller door open)
Cfig(external) = -0.9 (1.0) (1.5) = -1.35
p,,, = ( 0 . 5 ~ Vdes,:
~ ~ ) CfigCdyn= (0.5)(1.2) (39.8)2(-1.35)(1.0) = -1283 Pa = -1.28 kPa
pin,= (0.5)( 1.2) (39.8)2 (+0.70)(1.0) = +665 Pa = +0.67 kPa
Net pressure across element = -1.28-(0.67) = -1.95 kPa
For roof cladding elements all areas, on roof between 3.0 and 6.2 m from south west edge of
roof: (SW Wind with roller door open)
Cfig(external) = -0.9 (1 .O) (1.O) = -0.9
pext= (0.5 pair)Vdes,: CfigCdyn= (0.5)(1.2) (39.8)2(-0.9)(1.0) = -855 Pa = -0.86 kPa
pint= (0.5)(1.2) (39.8)2 (+0.70)(1.0) = +665 Pa = +0.67 kPa
Net pressure across element = -0.86-(0.67) = -1.53 kPa
For roof cladding elements all areas, on roof between 6.2 and 12.4 m from south west edge
of roof: (SW Wind with roller door open)
Cfig(external) = -0.5 (1.0) (1.0) = -0.5
p,,, = (0.5 pa;$Vdes,: CfigCdyn= (0.5)(1.2) (39.8)2(-0.5)(1.0) = -475 Pa = -0.475 kPa
pint= (0.5)(1.2) (39.8)2 (+0.70)(1.0) = +665 Pa = +0.665 kPa
Net pressure across element = -0.475-(0.665) = -1.14 kPa
For roof cladding elements all areas, on roof between 12.4 and 15 m from south west edge of
roof: (SW Wind with roller door open)
Cfig(external) = -0.5 (1.O) (1.O) = -0.3
p,,, = (0.5 pa,$Vdes,: CfigCdp = (0.5)(1.2) (39.8)2(-0.3)(1.0) = -285 Pa = -0.29 kPa
p,,, = (0.5)(1.2) (39.8)2 (+0.70)(1.0) = +665 Pa = +0.67 kPa
Net pressure across element = -0.29-(0.67) = -0.96 kPa (cases above govern for this zone)
For roof cladding elements area< 2.25 m2, on roof between 0 and 1.5 m from north west edge
of roof: (NW Wind)
Cfig(external) = -0.9 (1.O) (2.0) = -1.8
p,,, = (OSp,,,) Vdes,iCfigCdyn= (0.5)(1.2) (31.7)2(-1.8)(1.0) = -1085 Pa= -1.09 kPa
pint= 0 kPa
Net pressure across element = -1.09-(0.0) = -1.09 kPa (cases above govern for this zone)
For roof cladding elements between 2.25 and 9 m2,on roof between 0 and 3.0 m from north
west edge of roof:
Cfig(external) = -0.9 (1.0) (1.5) = -1.35
p,,, = (O.5paJVdes,: CfiPCdyn=(0.5)(1.2) (31.7)2(-1.35)(1,0) = -814 Pa= -0.81 kPa
pint= 0 kPa
Net pressure across element = -0.81-(0.0) = -0.81 kPa (cases above govern for this zone)
Governing design pressures for roof cladding elements, less than 2.25m2in area, are shown
in Figure 5.10
1.5 m
-1.1
,
;I.
I
For other wall and roof cladding elements, use loads for portal frames, with positive loads
multiplied by 1.25 (K,) for elements less than 2.25 m2 in area.
Loading on roof purlins should be applied as moving 'patch' loads with the appropriate local
pressure factor for that area. For example, in this case, if the purlin spacing is 0.6 m, the
tributary area for a patch 2.5 m long (equal to one half the frame spacing) would be 2.5 X 0.6
= 1.5 mz. Since this area is less than 0.25a2,the local pressure factor could be 1.0, 1.5 or 2.0,
depending on the distance of the centre of the 'patch' from the roof edge. Over the remainder
of the purlin, Kpshould be taken as 1.0 for that load case; i.e. the loading should be the same
as that used for major structural members.
...I..I
............ .............
.j......
1
.
1
.
1
,
,
/
.
~
j
~
.
*
l
.
,
l
.
~
I
.
l
.
.....
~I.... I__I,."..YY..I.~*L...~..~,~~.~,
................,,..
/~
Wind Actions
Chapter 5
/
Figure 5.11
This building was used as an example in the Guide to ASCE 7-02 [21]. Its use in the present
Design Guide allows for a comparison of the two Standards for this building.
=
=
F,. 66 d s (Region C)
(1.05)(66) = 69.3 m / s
= 0.95
for overturning forces and major structural system for all directions
Terrain-heig h t multiplier
z=h=48 m, For Terrain Category 3, Mz,cat
= M48,cat3
= 1.28 (Table 4.I(B) by interpolation)
Shielding
There are no other buildings of greater height in any direction. Take Ms, equal to 1.O for all
directions.
Topography
Topographic Multiplier, M, = M,
= 1.O
Vdes,B
= VsitB= 84.3 d s (for overall loads and main structure design)
= 88.7 d
s (for cladding)
Kc= 1.0
M,t3
of
sector
(m)
44
35
25
15
5
1.266
1.20
1.10
0.95
0.80
windward
qz.C,
(kPap
leeward
qh,Cfig
(kPa)
windward
q,.C,g.Cdyn.A
(kN)
3.337
2.998
2.519
1.879
1.332
-2.132
-2.132
-2.132
-2.132
-2.132
1601.7
1798.8
1511.5
1127.4
799.5
leeward
moment
qZ.Cfig.Cdyn.Acontribution
(kN)
(MN.m)
- 1023.3
-1279.2
-1279.2
- 1279.2
- 1279.2
115.5
107.7
69.8
36.1
10.4
Vdes,i
Total along-wind base bending moment obtained by summing contributions from last column
of table = 340 MN.m
Wind normal to 30 m wall
Height
Mz,&3
of
sector
(m)
44
35
25
15
5
windward
qz.c,
(kPa!
1.266
1.20
1.10
0.95
0.80
3.337
2.998
2.519
1.879
1.332
leeward
windward
qh.CRg qZ.C,g.Cdy,.A
(kPa)
(kN)
- 1.279
-1.279
-1.279
- 1.279
-1.279
800.9
899.4
755.8
563.7
399.7
leeward
moment
qZ.Cfig.Cdyn.Acontribution
(kN)
(MN.m)
-307.0
-383.8
-383.8
-383.8
-383.8
48.7
44.9
28.5
14.2
3.9
Chapter 5 55
For 24 m to 48 m from leading edges (any orthogonal wind direction) - tributary areas
greater than 1OOm2:
Cfig(external) = -0.7 (0.8) (1.0) = -0.56
p,,, = (0.5paiJ Vdes,: CfigCdyn= (0.5)(1.2) (84.3)2(-0.56)(1.0) = -2388 Pa = -2.39 kPa
Cfig(internal) = 0.0 (1.0) = 0.0
pint= 0 kPa
Net pressure across roof surface = -2.39-(0.0) = -2.39 kPa
For 48 m to 60 m from leading edges (wind directions normal to 30m walls) - tributaly areas
greater than 1OOm2:
Cfig(external) = -0.5 (0.8) (1.O) = -0.40
p,,, = (0.5pair)Vdes,: CfigCdyn= (0.5)(1.2) (84.3)2 (-0.40)(1.0) = -1706 Pa = -1.71 kPa
Cfig(internal) = 0.0 (1.O) = 0.0
pi,, = 0 kPa
Net pressure across roof surface = -1.7 1-(O.O) = - 1.7 1 kPa
Cladding pressures
(note: for permissible stress design - divide loads by 1S )
Wall elements
For elements (WA1) less than 9 m2 in area on walls at height z:
Cfip(external) = +0.8 (1.O) (1.25) = +1 .O (positive case)
p,,, = (0.5 pa,>Vdes,: CfigCdy, = (0.5)(1.2) (88.7)2(MZ,ca,3/1.28)2
(+lW.O)
= +4721(MZ,cao/l
.28)2 Pa = +4.72(,Z,cat3/1
.28)2 kPa
Cfig(internal) = -0.2 (1.O) = -0.2
pint= (0.5pair)Vdes,: CfigCdyn= (0.5)(1.2) (88.7)2 (-0.2)(1.0) = -944 Pa = -0.94 kPa
Net pressure across element = 4.72(Mz,cat3/1
.28)2+ 0.94 kPa
For elements (SA5) less than 9 m2 in area on walls within a distance of 3 m from corners:
Cfig(external) = -0.65 (1.O) (3.0) = -1.95 (negative case)
p,,, = (0.5pa,,>Vdes,: CfigCdyn= (0.5)(1.2) (88.7)2 (-1.95)(1.0) = -9205 P a = -9.21 kPa
pint= 0 kPa
Net pressure across element = -9.21-(0.0) = -9.21 kPa
For elements (SA4) less than 36 m2 in area on walls within a distance of 6 m from comers:
Cfig(external) = -0.65 (1.O) (2.0) = -1.3 (negative case)
p,,, = (OSp,,,) Vdes,: CfigCdyn= (0.5)(1.2) (88.7)2 (-1.3)(1.0) = -6137 Pa = -6.14 kPa
pi,, = 0 kPa
Net pressure across element = -6.14-(0.0) = -6.14 kPa
For elements (SA3) less than 9 m2in area on walls greater than a distance of 6 m ikom my comer:
Cfig(external) = -0.65 (1.O) (1S)= -0.975 (negative case)
p,,, = (0.5 pair)Vdes,: CfigCdyn= (0.5)(1.2) (88.7)2(-0.975)(1.0) = -4603 Pa = -4.60 kPa
pint= 0 kPa
Net pressure across element = -4.60-(0.0) = -4.60 kPa
For elements greater than 9 m2 in area on walls greater than a distance of 6 m from any corner:
Cfig(external) = -0.65 (1.O) (1.O) = -0.65 (negative case)
p,,, = (0.5 pair)
Vdes,;CfigCdyn= (0.5)(1.2) (88.7)2 (-0.65)(1.0) = -3068 Pa = -3.07 kPa
pint= 0 kPa
Net pressure across element = -3.07-(0.0) = -3.07 H a
Roof elements
For elements (RA2) less than 9 m2 in area on roof, less than a distance of 3 m from edges:
Cfig(external) = -1.3 (1.0) (2.0)(0.8) = -1.6
(negative case; K, of 0.8 included; note limit of -2.0 on K,.Cp,)
A Guide to ASINZS 1170.2: 2002
Wind Actions
Chapter 5
p,,, = ( 0 . 5 ~ Vdes,t
~ ~ ) CfigCdyn= (0.5)(1.2) (88.7)2(-1.6)(1.0) = -7553 P a = -7.55 kPa
pint= 0 kPa
Net pressure across element = -7,55-(0.0) = -7.55 kPa
For elements (RA1) less than 36 mz in area on roof, less than a distance of 6 m from edges:
Cfig(external) = -1.3 (1.0) (1.5)(0.8) = -1.56 (Ka<l.O canbeusedforA> 10 m)
p,,, = (0.5 psi$ Vdes,; CfigCdy, = (0.5)(1.2) (88.7)2 (-1.56)(1.0) = -7364 Pa = -7.36 kPa
pi,, = 0 kPa
Net pressure across element = -7.36-(0.0) = -7.36 kPa
Other roof elements, less than a distance of 24 m from edges:
Cfig(external) = -1.3 (1.0) (l.O)(l.O) = -1.3
(Ka 4 . 0 can be used for A> 10 m2;no reduction due to parapet in this case)
~ ~ ) CfigCdY,= (0.5)(1.2) (88.7) (-1.3)(1.0) = -6137 Pa = -6.14 kPa
p,,, = ( 0 . 5 ~ Vdes,i
pint= 0 kPa
Net pressure across element = -6.14-(0.0) = -6.14 kPa
3P57&
46 m
This building (known as the CAARC building)
was used as an example in the Commentary to
AS1170.2-1989 [4]. Its use in the present Design
Guide allows for a comparison of the two Standards
for this building.
183 m
= 60 d s
Terrain-height multiplier
z=h=183 m, For Terrain Category 3, Mz,cat
= M,83,ca0
= 1.23 (Table 4.I(A) by interpolation)
Shielding
There are no other buildings of greater height in any direction. Take Ms, equal to 1.0 for all
directions.
Topography
Topographic Multiplier, M, = M,
1.O
= 70.1
VsitB
= 60( 1.O)( 1.23)(1.0)(1.O)
= 73.8 m/s
(Equation 2.2)
Vdes,B
- Vsitp
= 70.1 m/s
= 34.4 d s
(for accelerations)
= 73.8 m/s
(for cladding)
am2
wind Actions
Chapter 5
Action combinationfactor
K,= 1.0
Lh
I+
I76
\j[
gR = ~ ~ = ~ 2 1 ~ g , ( 6 0 0 ( 0 . =3.OY
2 0 ) )
3..5nah(I 4- g v I h )] [ I + 4nabOh(1+gvihl]
[I+
vdes,8
vdes ,8
Forb = 46 m,
I
3.j(0.2) ( 183)( 1+ (3.7)( 0.143)) I
"[I,
70.1
1
=0.146
[3.794][1.8031
li
Wind Actions
6o Chapter 5
Forb = 30 m,
1
3.5(0.2)(183)(1+(3.7)(0.143))
s=[l+
70.1
1
=0.173
[3.794][1.524]
4(0.2)(30)(1+(3.7)(0.143))
70.1
XN
Et =
( 1+ 70.8N2
),"
~(0.768)
5/6
(Equation 6.2(4))
=0.106
( 1+ 70.8(0.768)2)
Forb = 46 m,
(1.0)(3.09)' (0.146)(0.106)
0.05
1L
1
J
( I f 2(3.7)(0.143))
cdyn =
- 1 fO.2864-
2.058
=m
Forb = 30 m,
(1.0)(3.09)2(0.1 73)(0.106)
0.05
J
(1 + 2(3.7)(0.143))
Cdyn =
1 + 0.286,/-
2.058
=m
Wind Actions
Chapter 5
Height of
sector
(m)
171.5
150
130
110
90
70
50
30
10
windward
Mz,ca,3
leeward
%Cfi
1.223
1.210
1.190
1.170
1.144
1.110
1.070
1.ooo
0.830
(kPay
2.332
2.283
2.208
2.135
2.041
1.921
1.785
1.560
1.074
windward
(kPap
-1.474
- 1.474
- 1,474
- 1.474
- 1.474
-1.474
-1.474
-1.474
-1.474
leeward
qz.CRg.Cdyn.Aqz.Cfig.C .A
(kN)dyn
(kN)
q,.C,
2374
202 1
1955
1889
1806
1701
1580
1380
95 1
-1500
-1305
-1305
-1305
-1305
-1305
-1305
-1305
-1305
moment
contribution
(MN.m)
664
499
424
35 1
280
210
144
81
23
Total along-wind base bending moment obtained by summing contributions from last column
= 2680 MN.m
Height of
sector
windward
Mz,ca,3
(m)
171.5
150
130
110
90
70
50
30
10
1.223
1.210
1.190
1.170
1.144
1.110
1.070
1.000
0.830
leeward
qz,c,
qh.Cfig
(kPa!
2.332
2.283
2.208
2.135
2.041
1.921
1.785
1.560
1.074
(kPa)
-1.150
-1.150
-1.150
-1.150
-1.150
-1.150
-1.150
-1.150
-1.150
windward
leeward
moment
qz.Cfig.Cdyn.A qZ.Cfig.Cdy,.Acontribution
(kN)
1569
1335
1292
1248
1194
1124
1044
912
628
(kN)
-773
-672
-672
-672
-672
-672
-672
-672
-672
(MN.m)
402
301
255
211
168
126
86
48
13
(The values of base bending moment obtained here are slightly lower than those in [4],
calculated using AS1 170.2-1989. The reason for this is the inclusion of the wind direction
multiplier, M,, of 0.95 in the new calculations.)
Cross-wind response
Turbulence intensity at z= 2W3 (122 m) = 0.159
v,
logloCfi= -2.346
cji =
&IO
= 0.159,
= 0.20
loglo" =
= 0.159,
logloCfi= -2.930
(Equation 6.3(2))
= 1.5(3.09)(
")
(4)
(Equation 6.3(1))
W e , ( 4 = 0.5p,,(Vdes,,8)2.d.(C/igCdy")
= 0.6(70.1)230.(.0.00631z)=558
= 0.006312
v"""
Height of
sector, z
Forcehnit
height
(m)
171.5
150
130
110
90
70
50
30
10
(kN/m)
95.70
83.70
72.54
61.38
50.22
39.06
27.90
16.74
5.58
Sector
height
(m)
23
20
20
20
20
20
20
20
20
contribution
2201
1674
1451
1228
1004
78 1
558
335
112
(MN.m)
377.5
251.1
188.6
135.0
90.4
54.1
27.9
10.0
1.1
Chapter 5
lNind
M, = 0.5gRb
"'f]
h2
o:puir
(3
)Km q.?
I+gvIh)
k+2
Vdes,O
neb( 1+ gvIh )
70.I
= 7.64
(0.2).30.( I + (3.7)O.143)
= 0.159,
= 1.5(3.09)(
E)
log,,Cfi = -1.556
= 0.159,
,/-
I
(1)
46 ( I + (3.7)(0.I 43))2
= 0.006792
6.3(1))
w,(4 = 0.5 P , , r < V ~ ~ ~ , ~ > z . d . ( c ~ ~ c ~(Equation
~)
=0.6(70.1), X 46 X (O.O0679z)= 920 z N/m = 0.920 z (kN/m)
63
Equivalent cross-wind load per unit height is evaluated in the following table
1j
10
9.2
20
184
I .8
Total cross-wind base bending moment obtained by summing contributions from last column
= 1870MN.m
Alternatively, using Equation 6.3(3)
Calculation of accelerations
To calculate accelerations for assessment of serviceability of the building, Appendix G is used.
Mass per unit height, mo = 160 x 46
30 Kglm = 2.21
lo5Kglm
h1.3I mo = 183l.' l(2.21 x lo5)= 0.00395. Since this exceeds 0.0016, cross-wind
accelerations may be excessive (Equation G1) and should be checked.
Forb=46m,
I
3.5(0.2)(183)(1+(3.7)(0.143)) I + 4(0.2)(46)(1+(3.7)(0.143))
34.4
34.4
Wind Actions
Chapter 5
Forb = 30 m,
1
3.5(0.2)(183)(1+(3.7)(0.143)) I
s = [l+
34.4
1
= 0.0723
[6.694][2.067]
4(0.2)(30)(1+ (3.7)(0.143))
34.4
Reduced frequency,
(O.2)( 1 7 6 )[1 + ( 3 . W .W ]
) __
= 1.565
N = naLh ( I + g,I
34.4
vdes .Q
Et =
(Equation 6.2(4))
( 1+ 70.8N2 ),I6
z (1.565)
5/6
= 0.0666
( 1+ 70.8(1.565)2)
(1+2gvI h )
For b = 46 m,
(1.0)( 3.09)2 (0.0567)(0.0666)
- 2(0.143)/[
0.01
Cdyn,res
( 1+ 2(3.7)(0.143))
0.286$3.606]
2.058
==
Forb = 30 m,
2(0.143)
cdyn,res -
0.286J[4.5981
-
2.058
I L
(1.0)(3.09)2 (0.0723)(0.0666)
0.01
( I + 2(3.7)(0.143))
= 0.298
I..._
~
'
'
..Y..
Forb = 46 m,
Resonant base moment = 2680.
Forb = 30 m,
Resonant base moment = 1610.
Peak along-wind accelerations:
Forb = 46 m,
3
3
x 177.1x106m/s2
x,, = -x resonant peak base moment =
moh2
2.21~1~
0 ~1 8 3 ~
(liy
Forb = 30 m,
,,x
=- 3
m,h2
3
2.21~1X
0~
XI
I
18.5x106m/s2
~
= 0.0480 m / s 2 = 0 . 0 4 8 0 ~F ) m g = 4.9 mg
= 0.12
-3.0+ 0.0637Vn2-0.00037Vn4
1-O.02Vn2 +0.000124Vn4
= 0.159,
-1.648
= -= -2.975
0.580
-1
(Equation G3(1))
ionsl
WindChapter
Act 5
0.6(34.4)2
(1 + (3.7)(0. 143))2
](l)/T
~(0.00097) m/s2
(i;)
W n d normal to 30 m face
For wind normal to 30 m face (b=30 m), reduced velocity,
Building dimensions are 6 :1 : 1.5
For 6 : 1 : 2 and I,, = 0.12 from Equation 6.3(11),
10gloC = 0.000475 V,- 0.0226V: + 0.396V0- 4.093 = . 9a
For 6 : 1 : 2 and I,,, = 0.20 from Equation 6.3(12),
10g,,Cfi = O.O0038V,- 0.0197V: + 0.363Vn- 3.82 = -2.716
By interpolation for 6 : 1 : 2 and I,, = 0.159, log,, Cfi= -2.811
For 6 : 1 : 1 and I,, = 0.12 from Equation 6.3(7),
10gloCfi= 0.000406V: - 0.0165Vn3+0.201 V, - 0.6O3yr -2.76 = -2.985
For 6 : 1 : 1 and I,,,, = 0.20 from Equation 6.3(8),
lOg,,C = 0.000334Vi - O.O125V;+ 0.141 V, - 0.384Vn -2.36 = -2.410
By interpolation for 6 : 1 : 1 and I,,, = 0.159, logloCfi= -2.705
By interpolation for 6 : 1.5 : 1 and I,,
= 0.159,
(Equation G3(1))
- 1.5(30)(3.09)
2.21 X lo5
~(0.00175)m/s2
0.01
The peak cross-wind accelerations are considerably greater than the along-wind accelerations,
but are within accepted human comfort criteria, at the natural frequency of 0.2 Hertz [4].
Cladding pressures
(note: for permissible stress design - divide loads by 1.5)
For elements less than 9 m2 in area on walls at height z:
Cfig(external) = +0.8 (1 .O) (1.25) = + I .O (positive case)
fig
dy,
= (05)(1*2)(738)2(M~,@3/123)2
(+l*o)(lo)
p,,,, = (O Pair)
= +3268(M5c,,/1.23)2 Pa = +3.27(MZ,c,/1.23)2 kPa
Cfig(internal) = -0.2 (1.0) = -0.2
pint= (OSp,,) Vdm,iCfigC,,,,, = (0.5)(1.2) (73.8), (-0.2)(1.0) = -654 Pa = -0.65 k P a
Net pressure across element = 3.27(MzcaJ1.23)2+ 0.65 kPa
For elements less than 9 m2 in area on walls within a distance of 3 m from comers:
67
j
~
Wind Actions
Chapter 5
Figure 5.13
= 41
m/s (Region A)
For calculation of serviceability deflections for broadcasting antennas, a gust wind speed that
is exceeded for 0.1% of the time is used [12, Appendix E]. For most locations in Australia a
value of 20 m/s is appropriate [ 121.
Hence, take V,
= 20
m/s
Terrain-height multiplier
Mz,catis adjusted according to the height of each tower section.
For z=h=100 m, For Terrain Category 2, Mz,cat
= M1m,caQ
= 1.24 (Table 4.1(A))
Shielding
There are no other structures of greater height in any direction. Take M , equal to 1.O for all
directions.
Topography
Topographic Multiplier, M, = M,
1.O
= 45.8 m / s
(Equation2.2)
For all wind directions, site wind speeds at ~ 1 0 m0 are calculated in the following table.
1
I
41
0.95
1.24
1.o
1.o
48.3
Design windspeeds
The largest value Vdes,B
at z equal to 100 metres for a wind normal to any face, and the largest
along any diagonal can be obtained by inspection from VsitBin the above table,:
Height range
Wind on to face
(m)
C,
0-20m
20 -40 m
40-60m
60-80111
j
.m
Wind on to corner
3.01
2.65
2.30
1.80
3.41
3.05
2.75
2.30
1i
Cross-wind response is not significant for lattice towers. Significant cross-wind excitation for
the UHF antenna is a possibility, but is not covered for unusual sections in AS/NZS 1170.2;
specialist advice should be sought.
iI
1
II
Background factor, BS =
J[0.26(100 - '
)
0
i
,............
I....I..
151
I
.
I
.
.
+ 0.46(10)']
I.
I
.
.
.
,
...
I
_
.
_
I
.
.
I
.
Y~
= 0.746
(Equation 6.2(2))
Bs =
+ 0.46(10)2]
d[0.26(100-0)2
1+
= 0.746
151
H s = 1.0
For bo, = 10 m,
1
1+ (3.7)(0.131))
s=[ I + 3.5(0.7)(1OO)(50.8
[8.1601[1.8181
Et =
= 0.0674
ZN
( I + 70.8N 2
5/6
~(3.089)
5/6
(Equation 6.2(4))
= 0.0425
( I + 70.8(3.089)2)
Fors = 0 m,
Cdyn =
(1.0)(3.48f (0.0674)(0.0425)
0.05
J
(1+2(3.7)(0.131))
I + 0.262,/[10.21 3 + 0.6941
I . 969
==
'
r . ~
'"
.*.
I....
Forb,
= 6 m,
B, =
= 0.830
,/[0.26(100-40)2 +0.46(6j2]
i
j
I+
IS1
i
1
~~
( I .I 6)(3.48)2(0.0674)(0.0425)
0.os
C+n =
-
(I+2(3.7)(0.131))
I +0.262,/-
=m
I . 969
B, =
I+
,/[0.26(100 -
+ 0.46(2)2
= 0.936
I51
(1.64)(3.48)2 (0.0674)(0.0425)
0.05
cdyn =
( I i-2(3.7)(0.131))
j1
j
~
j
j
I + 0 . 2 6 2 d m
1.969
= 1.005
Wind Actions
Chapter 5
95
85
2
2
1.90
1.90
1.236
1.228
2.923
2.885
55.4
54.7
5.26
4.65
25
15
5
15
17
19
2.65
3.01
3.01
1.10
1.05
0.91
3.229
3.342
2.510
114.9
91.6
76.9
2.87
1.37
0.38
1.90
1.90
1.236
1.228
2.885
44.3
43.7
85
1.6
5
7
9
11
13
15
17
19
75
65
55
45
35
25
15
5
2.30
2.30
2.75
2.75
3.05
3.05
3.41
3.41
I
I
1.22
1.204
1.188
1.17
1.14
1.10
1.05
0.91
3.447
3.358
3.908
3.791
3.992
3.716
3.786
2.844
81.6
111.3
116.6
138.2
122.9
132.0
103.6
87.0
(MN.m)
4.2 1
3.72
6.12
7.23
6.4 1
6.22
4.30
3.30
1.55
0.43
+ AC, = C, = Cd,.KaiKi,.(A8/A)
C, can be obtained from Table F l (hemispherical bowl), or from Table F4 inAS3995-1994 [12].
Thus:
for wind blowing towards the bowl of the dish, Cda= 1.4
for wind blowing towards the rear of the dish, Cda= 0.4
for wind blowing obliquely to the dish, C, = 1.O
45
35
11
13
Height of
section
(m)
45
b
(m)
35
Height of
section
(m)
95
85
75
65
55
45
2.315
2.730
d
'e
1.17
1.14
Mz,cat*
3.171
3.468
qz%J
(kW
11
13
2.790
3.122
1.17
1.14
3.852
4.092
b
(m)
Cd*
Mz,cat2
%Cfi
( k 4
2
2
5
7
9
11
1.90
1.90
1.80
1.80
2.30
2.315
1.236
1.228
1.22
1.204
1.188
1.17
2.928
2.890
2.702
2.632
3.274
3.196
115.8
106.9
5.24
3.85
qZ.Cfig.CdY,.A moment
contribution
(kN)
(MN.m)
140.5
126.0
6.32
4.41
moment
qz'Cfig'Cdyn*A
contribution
(kN)
(MN.m)
56.9
56.2
65.7
89.5
100.2
119.6
5.41
4.77
4.92
5.82
5.51
5.38
m n d alona diaaonal:
55
45
9
11
2.75
2.790
1.188
1.17
3.915
3.852
119.8
144.2
6.59
6.49
Heightof
section
(m)
95
85
Cd
Mz,cat*
q z G
1.90
1.90
1.236
1.228
2.928
2.890
(m)
2
2
qZ.Cflg.Cdy,.A moment
contribution
(kN)
(MN.m)
0.88
58.8
0.29
58.1
"... ..,.."...........
"
'
"'_
" Y 1..,..l.-..'......*
..I..
,...--.-
Terrain-height multiplier
Mz,cat
is adjusted according to the height of each section.
= M50,catZ
= 1.18
For z=h=50 m, For Terrain Category 2, Mz,cat
For Terrain Category 3, Mz,cat
= MSO,caO
= 1.07 (Table 4. I@))
Shielding
There are no other structures of greater height in any direction. Take Ms, equal to 1.O for all
directions.
Topography
j
Topographic Multiplier, M, = M,
1j
j
For all wind directions, site wind speeds at z=50 m are calculated in the following table.
S
SW
W
NW
45
45
45
45
1.O
0.85
0.95
1.oo
0.95
1.18
1.18
1.18
1.07
1.o
1.o
1.o
1.o
1.o
1.o
1.o
1.o
45.1
50.4
53.1
45.7
Wind Actions
Chapter 5
1
1+
(Equation 6.2(2))
,/0.26(h - s ) +~ 0.46bsh2
~3.43
][
4n0boh (1 + gvlh i ]
Vdes,O
N=
Vdes,O
53.1
ZN
E, =
7c(2237)
5/6
(Equation 6.2(4))
= 0.0526
(1+70.8(2.237)2)
= 2.237
Fors=Om,
,d
(3.7)2 (0.833) +
1+ 2(0.15 1)
IL
c4n=
1+0.302,/-
=m
2.117
Forb,
i
I
II
1I
(1 -I-2(3.7)(0.15 1))
I =
1
(1 .0)(3.43)2 (0.227)(0.0526)
0.02
(1 .25)(3.43)2 (0.227)(0.0526)
0.02
C+n=
1+ 0.302,/[12.444+ 8.781
2.117
I
Calculation of along-wind bending moment at s = 0
Summaries of the calculations are given in the following table.
1
1
Height of
section
(m)
47.5
42.5
37.5
32.5
27.5
22.5
17.5
12.5
7.5
2.5
b
(m)
1.o
1.o
1.o
1.o
1.o
1.0
1.o
1.o
1.35
2.05
%at2
qz.cfi
(kPaP
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
1.176
1.168
1.150
1.130
1.110
1.090
1.065
1.025
0.955
0.910
0.840
0.829
0.803
0.776
0.749
0.722
0.689
0.638
0.554
0.503
Vds,i
I
I
moment
qZ.Cfig.Cdy,.A
contribution
(kN)
(MN.m)
I
1
4.56
4.49
4.36
4.21
4.06
3.91
3.74
3.46
4.06
5.59
216.4
191.0
163.4
136.7
111.6
88.1
65.4
43.3
30.4
14.0
Total along-wind base bending moment obtained by summing contributions from last column
= 1060 kN.m
Mz,cat*
qzJ%
(kPaP
qZ.Cfig.C.A
1.o
0.5
1.176
0.840
4.74
moment
contribution
(MN.m)
106.7
1.o
1.o
1.0
0.5
0.5
0.5
1.150
1.130
1.110
0.803
0.776
0.749
4.54
4.38
4.23
56.7
32.8
10.6
(m)
~~
37.5
32.5
27.5
Cd
Height of
section
(m)
47.5
(kNy
1.20x1.02
Kb, - 0.50x1.0
= 0.012m
41.89
=x-
This occurs at an average wind speed of about 5.nc.b,= 5 XO.6X 1.0= 3.0 d s
The maximum deflection of 12 mm is very small and will produce negligible stresses
in comparison to those produced by the along-wind response. Therefore no remedial
action is necessary.
- Cricket sightscreen
5.8 Example 8
A cricket sightscreen has been proposed for a cricket ground in Rockhampton, Queensland
(Region C). Design wind loads are required to be determined.
(Region C)
Terrain-height multiplier
z=h=6.1m, For Terrain Category 3, Mz,cat
= M6,,,cat3
= 0.82 (Table 4.1(B))
Shielding
Structure is shielded by the grandstand for all directions.
For this case take Ms= 0.80
Topographic Multiplier
M, = 1.0
Site wind speed, VsitB= 69.3(0.95)(0.82)(0.8)(1.0)= 43.2 m/s for all@(Equation 2.2)
ionSI
WindChapter
Act 5
U
1.44kPa
Q
1.44 kPa
= Fc.45 = 45
m/s
= 28.4
m/s
81
I
~
5.9
'
Design wind loads are required for a pitched-free roof over a minerals storage area near
Hobart, Tasmania. The relevant information is as follows :
Location: Tasmania (Region A3)
Upwind terrain: Suburban-industrial terrain for 1 km in all directions, except for 300 metres
of open water starting at 200 metres from the site for the southwest to northwest quadrant.
Topography: ground slope less than 1 in 20 for greater than 5 kilometres in all directions.
Dimensions: average roof height : 15 metres
Horizontal dimensions: 20 metres x 40 metres (rectangular planform).
Roof pitch: 10 degrees.
Orientation: the main axis of the structure is orientated NNW-SSE
= 45
m l s (Region A)
Terrain-height multiplier
z=h=l5 m, Assume full Terrain Category 3 multipliers for west through north to south,
M W = M15,m3= 0.89
For south through west directions, account should be taken of the open water terrain, using
Section 4.2.3. Since structure height is 15 metres, the terrain-height multipliers should be
averaged from a distance xi to (lOOO+xJ upwind of the structure (see Figure 4. I ) .
By Equation (4.2), the lag distance, xi
1.25
0.3) (0.2)
The terrain for lOOOm beyond 20Om upwind for SW, W, NW consists of 300m of Terrain
Category 2 followed by 700 metres of Terrain Category 3,
Mz,cat =
Wind Actions
Chapter 5
Shielding
There are no other buildings of greater height in any direction. Take M , equal to 1 .O for all
directions.
Topography
Topographic Multiplier, M, = M,
1.O
= 34.0 m/s
(Equation 2.2)
For all wind directions, site wind speeds are calculated in the following table.
e4
45.0
40.0
s5 35.0
0
30.0
-0
c 25.0
i5
20.0
NW
NE
SE
SW
NW
Vdes,ENE
= 33.0 m/s (largest from NNE to ESE sector)
Vdes,SSE
= 34.0 m / s (largest from ESE to SSW sector)
Vdcs,WSW
= 40.1 m/s (largest from SSW to WNW sector)
Vdes,NNW
= 42.2 m/s (largest from WNW to NNE sector)
83
For wind parallel to the ridge, pressure coefficients are obtained from Table D4(B)
For blocked under case :
Cp,,= -1.0 for first 15m from leading edge; -0.8 for 15-30m from leading edge;
Cp,,= -0.4 for 30-40m from leading edge.
= -926 Pa
= -695
Pa
Wind Actions
Chapter 5
= -342 Pa
Design wind pressure for cladding elements and purlins ultimate limit states
For areas between lm2 and 4m2within a distance of 2 m from WSW roof edge or the ridge.
Cfig= Cp,,Ka K,= +0.4 (1.O) (1.5) = 0.6
p, = ( 0 . 5 ~ Vdes,i
~ ~ ) CfigCdyn= (0.5)(1.2) (40.1)2 (0.6)(1.0) = 579 Pa
Net downward pressure across cladding = 0.58 kPa
Cfig=Cp,,KaK,=-1.2(1.0)(1.5)=-1.8
p, = (0.5pai,)Vdes,iCfigCdy,= (0.5)(1.2) (40.1) (-1.8)(1.0) = -1737 Pa
Net upward pressure across cladding = - 1.74 H a
For areas of lmZor less within a distance of 1 m from WSW roof edge, or the ridge.
Cfig= Cp,,K, K,= +0.4 (1.0) (2.0) = 0.80
p, = (0.5 paiJVdes,iCfiPCdyn= (0.5)( 1.2) (40. 1) (0.80)(1.0) = 772 Pa
Net downward pressure across cladding = 0.62 kPa
Cfig= Cp,,K, K,= -1.2 (1.O) (2.0) = -2.4
p, = (0.5p,,) Vdes,tCfigCdyn= (0.5)(1.2) (40.1)2(-2.4)(1.0) = -2316 Pa
Net upward pressure across cladding = -2.32 kPa
85