Rules For Fire Alarm System
Rules For Fire Alarm System
3.
GENERAL REQUIREMENTS:
3.1
3.2 SIGNS:
3.2.1 Pucca walls to be shown by double lines, doors and windows
being clearly marked.
3.2.2 Perfect party walls to be indicated by the sign T at each
end of the wall, or have the letters P.P.W along side of
across them at regular intervals and marked in distinctive
colour.
3.2.3 Fire proof doors and/or shutters to be marked as follows:
Single Fire Proof Door and/or Shutter S.F.D
Double Fire Proof Door and/or shutter D.F.D
3.5
3.6
3.7
3.8
3.9
OF
ZONES
(PROTECTED
WITH
4.2.1 The floor area of a single zone shall not exceed 2000 m 2.
4.2.2 The search distance i.e. the distance that has to be travelled
by a searcher inside the zone to determine visually the
position of the fire, shall not exceed 30M.
Remote indicator lamps outside doors of rooms, cabins etc.,
within a zone may be useful, if doors are likely to be locked.
Making an area easier to search, the use of remote indicator
lamps reduce the need for a large number of smaller zones.
4.2.3 If the total floor area of a building is 300 m 2 or less, it may be
considered
as a single zone even though there may be
more than one storey.
4.2.4 Where the total floor area of a building is greater than 300
m2, all zones shall be restricted to a single storey.
Note 1 If the total floor area of a fire compartment is 300 m 2
or less, and if any communication with other fire
compartments is only at the lowest level of the
building, such fire compartment may be considered
as a single 00.zone even though there may be more
than one stories within it;
6.
SPACING
POINTS:
AND
SITING
OF
DETECTORS
AND
MANUAL
CALL
6.1 GENERAL
A well laid out detection system can perhaps do nothing to reduce
the incidence of fire but can certainly help to lessen the resultant
loss by reducing the delay between ignition and the start of
effective fire fighting.
Heat and smoke sensitive detectors depend on the convective
movement of the combustion products from the fire to the
detector.
The spacing and siting requirements for these detectors are based
on the needs to restrict the time taken for movement of
combustion products to ensure that these combustion products
reach the detectors fitted in the ceiling in adequate concentration
within a reasonable time lag.
6.2 SPACING OF DETECTORS:
6.2.1 For the open areas under flat horizontal ceilings, the
horizontal distance from any point in the area to the detector
(point type) shall not exceed 5.3M for heat detectors or 7.5
m for smoke detectors.
Incase of line type detectors, spacing of not more than 18 M
between two projected beams and not more than half that
spacing from an external wall parallel to the beam may be
used.
Spacing
(area
coverage)
1.00
0.95
0.91
0.83
0.74
0.64
0.50
0.38
(1.00)
(0.91)
(0.83)
(0.70)
(0.55)
(0.40)
(0.25)
(0.15)
Vertical
b)
c)
d)
e)
f)
b) Certain
flame detectors respond to the instantaneous
level of radiation received while others depend upon the
level received over a period.
In either case the response will depend on the distance
between the flame detector and the fire, since the
radiation level received is inversely proportional to the
square of this distance. Increased distance from the fire
will, therefore, lead to an increase in the size of the fire at
detection.
c) A clear line of sight to the area being protected is of great
importance but at the same time care must be exercised
to avoid a direct line of sight to likely sources of non-fire
radiation to prevent false alarms.
6.4.2 SPACING GUIDE-LINE:
a)
b)
c)
d)
e)
f)
c)