Transformer
Transformer
E2063/ Unit 8/ 1
UNIT 8
TRANSFORMER
OBJECTIVES
General Objective
TRANSFORMER
E2063/ Unit 8/ 2
INPUT
8.0
Introduction
A transformer is a device which uses the phenomenon of mutual induction to change the
values of alternating voltages and currents. In fact, one of the main advantages of alternating
current transmission and distribution is the ease with which an alternating voltage can be
increased or decreased by transformers.
Losses in transformers are generally low and thus efficiency is high. Being static
they have a long life and are very stable. Transformers range in size from the miniature units
used in electronic applications to the large power transformers used in power stations. The
transformer types are shown in Figure 8.1. The principle of operation is the same for each.
TRANSFORMER
8.1
E2063/ Unit 8/ 3
Principle of Operation
In simple form, a transformer consists of two windings connected by a magnetic core. One
winding is connected to a power supply and the other to a load. A circuit diagram symbol
for a transformer is shown in Fig. 8.2.
Primary winding
AC supply
Flux
Core
Secondary winding
N1
N2
Load
secondary thus 1 = 2 .
1
2
The induced e.m.f. per turn is constant.
Assuming no losses, E1 = V1 and E2 = V2
V
V1
V
N
= 2 or 1 = 1
V2 2
1
2
When the load is connected across the secondary winding, a current I2 flows. In an ideal
transformer losses are neglected and a transformer is considered to be 100% efficient.
TRANSFORMER
E2063/ Unit 8/ 4
Hence input powers = output power or V1 I1 = V2 I2 , the primary and secondary voltamperes are equal.
V1
I
Thus
= 2
V2
I1
Combining equations gives
V1
N1 I 2
=
=
V2
N 2 I1
Example 8.1
A transformer is to be used to provide a 60 V output from a 240 V A.C supply. Calculate (a)
the turns of ratio required and (b) the number of primary turns, if the secondary is wound
with 500 turns.
Solution to Example 8.1
V2 = 60 V
V1 = 240 V
N2 = 500
a)
V1
N1
240
=
=
V2
N2
60
so turns ratio,
b)
N1
4
= or 4 : 1
N2
1
N1
4
=
500
1
therefore, N1 = 2000
Example 8.2
TRANSFORMER
E2063/ Unit 8/ 5
Figure 8.3
V2
200
1
=
=
V1 2000 10
N2
1
=K=
N1
10
N1 = N 2 10 = 66 10 = 660 turns
(ii)
V1I1 = V2 I 2 = 20 103
20 103
I2 =
= 100 A
200
TRANSFORMER
8.2
E2063/ Unit 8/ 6
There are broadly two types of single-phase double-wound transformer construction the
core type and the shell type as shown in Figure 8.4.
Transformer ratio is the comparison between primary and secondary elements. Figure 8.5
.shows the primary and secondary elements.
Flux produced by primary winding
induces secondary winding via core
Secondary
winding
Primary
winding
Vp
Np
Ns
Vs
TRANSFORMER
E2063/ Unit 8/ 7
N s E s Vs
=
=
N p E p Vp
Where
S
P
Vs
Vp
=
=
=
=
Notes
If K < 1 i.e. Ns < Np : this transformer is called step-down transformer
If K > 1 i.e. Ns > Np : this transformer is called step-up transformer
If K = 1 i.e. Ns = Np : this transformer is called coupling transformer
Example 8.3
TRANSFORMER
E2063/ Unit 8/ 8
(a)
(b)
(c)
Ns 2000
=
= 20
Np 100
Q K > 1 step-up transformer
K=
Ns 2000
=
= 0.67
Np 3000
Q K < 1 step-down transformer
K=
Ns 100
=
=1
Np 100
Q K = 1 coupling transformer
Np
(100)
Ns
(2000)
Np
(100)
Ns
(100)
Np
(3000)
Ns
(2000)
K=
TRANSFORMER
E2063/ Unit 8/ 9
Activity 8A
8.1
8.2
8.3
8.4
8.5
8.6
8.7
A transformer has 500 primary turns and 3000 secondary turns. If the
primary voltage is 240 V, determine the secondary voltage, assuming an ideal
transformer.
An ideal transformer with a turns ratio of 2 : 7 is fed from 240 V supply.
Determine its output voltage.
An ideal transformer has a turns ratio of 8 : 1 and the primary current is 3 A
when it is supplied at 240 V. Calculate the secondary voltage and current.
An ideal transformer connected to a 240 V mains, supplies a 12 V, 150 W
lamp. Calculate the transformer turns ratio and the current taken from the
supply.
How many turns are required for a 36 V secondary if a 240 V primary has
600 N.
True or false ? If the primary winding of a 1:2 step-up transformer has
3 N/ V, the secondary winding will have 6 N/ V.
True or false ? The secondary flux of a transformer cancels part of the
primary flux.
TRANSFORMER
E2063/ Unit 8/ 10
Feedback to Activity 8A
8.1
8.2
8.3
8.4
8.5
8.6
8.7
1440 V
840 V
V2 = 30 volts, I2 = 24 A
turns ratio = 20, I1 = 0.625 A
90
False
True
TRANSFORMER
E2063/ Unit 8/ 11
INPUT
8.3
Suppose the maximum value of flux to be m webers and the frequency to be f hertz. From
Fig. 8.6 it is seen that the flux has to change from +m to -m in the half cycle, namely in
1
seconds.
2f
Average rate of change of flux = 2 m
1
2f
But for a sinusoidal wave the r.m.s or effective value is 1.11 times the average value,
RMS value of e.m.f induced per turn = 1.11 4 f m
Hence r.m.s value of e.m.f induced in primary is
E1 = 4.44 N1 f m volts
TRANSFORMER
E2063/ Unit 8/ 12
c)
Example 8.5
An ideal 25 kVA transformer has 500 turns on the primary winding and 40 turns on the
secondary winding. The primary is connected to 3000 V, 50 Hz supply. Calculate
(i) primary and secondary currents on full-load
(ii) secondary e.m.f. and
(iii) the maximum core flux
TRANSFORMER
K=
(i)
(ii)
N2
40
4
=
=
N1 500 50
I1 =
I2 =
I1
= 8.33 50 4 = 104.2 A
K
E2
=K
E1
E2 = KE1 = (4 50) 3000 = 240V
(iii)
E1 = 4.44 fN1m
m =
3000
= 27 10 3 wb = 27 mwb
4.44 50 500
E2063/ Unit 8/ 13
TRANSFORMER
E2063/ Unit 8/ 14
Activity 8B
8.8
A 100 kVA, 4000 V/200 V, 50 Hz single phase transformer has 100 secondary turns.
Determine :
(a)
the primary and secondary current
(b)
the number of primary turns
(c)
the maximum value of the flux
8.9
8.10
A single phase 2200/250V, 50 Hz transformer has a net core area of 36cm2 and a
maximum flux density of 6 wb/m2. Calculate the number of primary and secondary
turns.
TRANSFORMER
E2063/ Unit 8/ 15
8.8
(a)
(b)
(c)
I1 = 25 A, I2 = 500 A
N1 = 2000 turns
m = 9.01 mWb
8.9
8.10
N1 = 459, N2 = 52
TRANSFORMER
E2063/ Unit 8/ 16
INPUT
8.4
The losses which occur in a transformer on load can be divided into two groups:
(a)
Copper losses are variable and result in a heating of the conductors, due to
the fact that they possess resistance. If R1 and R2 are the primary and
secondary winding resistances than the total copper loss is I12R1 + I22R2.
(b)
Core losses due to hysteresis and eddy currents.
(i) Hysteresis loss is the heating of the core as a result of the internal
molecular structure reversals which occur as the magnetic flux alternates.
The loss is proportional to the area of the hysterisis loop and thus low
loss nickel iron alloys are used for the core since their hysteresis loop
have small areas.
(ii) Eddy current loss is the heating of the core due to e.m.f. s being induced
not only in the transformer windings but also in the core. These induced
e.m.f.s set up circulating currents call ed eddy currents. Owing to the
low resistance of the core, eddy currents can be quite considerable and
can cause a large power loss and excessive heating of the core.
Since the maximum value of the flux in a normal transformer does not vary by more than
about 2 per cent between no load and full load, it is usual to assume the core loss constant at
all loads.
Hence, if Pc = total core loss, total losses in transformer are
Pc + I21R1 + I22R2
and
output power
output power
=
Efficiency =
input power
input power + losses
Efficiency =
I 2V2 p.f.
2
I 2V2 p.f. + Pc + I 1 R1 + I 2 R2
TRANSFORMER
E2063/ Unit 8/ 17
=1-
losses
input power
Example 8.6
The primary and secondary windings of a 500 kVA transformer have resistances of 0.42
and 0.0019 respectively. The primary and secondary voltages are 11 000 V and 400 V
respectively and the core loss is 2.9 kW, assuming the power factor of the load to be 0.8.
Calculate the efficiency on :
(a) full load
(b) half load
Solution of Example 8.6
(a)
TRANSFORMER
E2063/ Unit 8/ 18
From equation,
=1-
losses
input power
6.74
= 1
= 0.983 per unit
406.74
3.86
Example 8.7
In a 50 kVA transformer, the iron loss is 500 W and full-load copper loss is 800W. Find the
efficiency at full-load and half-load at 0.8 p.f. lagging.
Solution of Example 8.7
Full-load, 0.8 p.f
Full-load output
Total Full-load losses
Full-load input
Full-load
Half-load, 0.8 p.f
Output at half-load
Total loss at half-load
Input at half-load
Full-load
= 50 0.8 = 40 kW
= 500 + 800 = 1300 W = 1.3 kW
= 40 + 1.3 = 41.3 kW
40
=
100 = 96.85 %
41.3
= (50 1/2) 0.8 = 20 kW
= 500 + (1 /2)2 800 = 700 W = 0.7 kW
= 20 + 0.7 = 20.7 kW
20
100 = 96.6 %
=
20.7
TRANSFORMER
E2063/ Unit 8/ 19
These two tests enable the efficiency and the voltage regulation to be a calculated without
actually loading the transformer and with an accuracy far higher than is possible by direct
measurement of input and output powers and voltages.Also, the power required to carry out
these tests is very small compared with the full-load output of transformer.
Open-circuit test.
(a)
The transformer is connected as in Fig 8.7 to a supply at the rated voltage and frequency,
namely the voltage and the frequency given on the nameplate.The ratio of the voltmeter
readings, V1 / V2, gives the ratio of the number of turns. Ammeter A gives the no-load
current, and its reading is a check on the magnetic quality of the ferromagnetic core and
joints. The primary current on no load is usually less than 5 per cent of the full-load current,
so that the I2R loss on no load is less than 1/400 of the primary I2R loss on full load and is
therefore negligible compared with the core loss. Hence the wattmeter reading can be taken
as the core loss of the transformer.
(b)
Short-circuit test
The secondary is short-circuited through a suitable ammeter A2, as shown in Fig.8.8 and the
low voltage is applied to the primary circuit. This voltage should, if possible, be adjusted to
circulate full-load current in the primary and secondary circuits. Assuming this to be the
case, the I2R loss in the windings is the same as that on full load. On the other hand, the core
loss is negligibly small, since the applied voltage and therefore the flux are only about onetwentieth to one-thirtieth of the rated voltage and flux, and the core loss is approximately
proportional to the square of the flux. Hence the power registered on wattmeter W can be
taken as the I2R loss in the windings.
TRANSFORMER
E2063/ Unit 8/ 20
Auto-transformer
TRANSFORMER
E2063/ Unit 8/ 21
flux and of the flux density, the I2R loss in the auto transformer is lower and the efficiency
higher than in the two winding transformer.
Auto transformer are mainly used for interconnecting systems that are operating at roughly
the same voltage and starting cage-type induction motors. Should an auto transformer be
used to supply a low voltage system from a high voltage system, it is essential to earth the
common connection, for example, B in Fig 8.9 otherwise there is a risk of serious shock. In
general, however, an auto transformer should not be used for interconnecting high voltage
and low voltage systems.
8.6.1
TRANSFORMER
E2063/ Unit 8/ 22
Activity 8C
8.11
8.12
8.13
Why are the core losses negligible during the short-circuit test?
8.14
TRANSFORMER
E2063/ Unit 8/ 23
Feedback to Activity 8C
8.10
8.11
8.12
8.13
0.96
core
Because the primary voltage is very low.
7W
TRANSFORMER
E2063/ Unit 8/ 24
SELF-ASSESSMENT 8
You are approaching success. Try all the questions in this self-assessment section and
check your answers with those given in the Feedback on Self-Assessment 8 given on the
next page. If you face any problems, discuss it with your lecturer. Good luck.
Question 8-1
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(i)
(j)
What is a transformer ?
Draw the circuit diagram symbol for a transformer.
How is a transformer rated.
Name two types of transformer construction.
A transformer has 600 primary turns connected to a 1.5 kV supply. Determine the
number of secondary turns for a 240 V output voltage, assuming no losses.
An ideal transformer with a turns ratio of 2 : 9 is fed from 220 V supply. Determine
its output voltage.
A step-down transformer having a turns ratio of 20 : 1 has a primary voltage of 4 kV
and a load of 10kW. Neglecting losses, calculate the value of the secondary current.
An ideal transformer has a turns ratio of 12 : 1 and is supplied at 192 V. Calculate the
secondary voltage.
A transformer primary winding connected across a 415 V supply has 750 turns.
Determine how many turns must be wound on the secondary side if an output of 1.66
kV is required.
An ideal transformer has a turns ratio of 12 : 1 and is supplied at 180V when the
primary current is 4A. Calculate the secondary voltage and current.
TRANSFORMER
E2063/ Unit 8/ 25
Question 8-2
(a)
(b)
The net cross-sectional area of the core of 400/3000V, 50Hz transformer is 600cm2.
If the maximum flux density in the core is 1.3 wb/m2, find the number of primary
and secondary turns.
(c)
(d)
A single phase, 50 Hz transformer has 40 primary turns and 520 secondary turns. The
cross sectional area of the core is 270 cm2. When the primary winding is connected to
a 300 V supply, determine :
(i)
the maximum value of flux density in the core
the voltage induced in the secondary winding
(ii)
(e)
A 3.3 kV/110 V, 50 Hz, single phase transformer is to have an approximate e.m.f per
turn of 22 V and operate with a maximum flux of 1.25 T. Calculate
(i)
the number of primary and secondary turns
(ii)
the cross sectional area of the core
Question 8-3
(a)
A 200 kVA rated transformer has a full loaded copper loss of 1.5 kW and an iron
loss of 1 kW. Detemine the transformer efficiency at full load and 0.85 power factor.
(b)
A 400 kVA transformer has a primary winding resistance of 0.5 and a secondary
winding resistance of 0.001. The iron loss is 2.5 kW and the primary and
secondary voltage are 5 kV and 320 V respectively. If the power factor of the load is
0.85, determine the efficiency of the transformer :
on a full load
i.
on half load
ii.
TRANSFORMER
(c)
E2063/ Unit 8/ 26
A single phase transformer has a voltage ratio of 6 : 1 and the h.v winding is supplied
at 540 V. The secondary winding provides at full load current of 30 at a power factor
of 0.8 lagging. Neglecting losses, find :
i.
a rating of the transformer
ii.
the power supplied to load
iii.
the primary current.
TRANSFORMER
E2063/ Unit 8/ 27
FEEDBACK TO SELF-ASSESSMENT 8
(a)
(b)
Np
Ns
(d)
N s E s Vs
=
=
N p E p Vp
i. core type ii. shell type
(e)
96
(f)
990 V
(g)
50 A
(h)
16 V
(i)
3000 turns
(j)
15 V, 48 A
(c)
K=
TRANSFORMER
E2063/ Unit 8/ 28
(a)
(b)
24; 198
(c)
(i)
(d)
(i)
1.25 T (ii)
3.90 kV
(e)
(i)
150, 5 (ii)
792.8 cm2
800
(a)
(b)
(c)
0.9855 or 98.55 %
i.
97.91 %
i.
2,7 kVA
ii.
ii.
97.87 %
2.16 kW
iii.
5A