C441 Ethernet Module User Manual
C441 Ethernet Module User Manual
Contents
Description
Page
1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 Mounting and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.1 C441R and C441T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.2 C441U and C441V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 Connections and switch settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.1 Connecting To an Ethernet Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.2 Setting the IP Address Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.3 Connecting To The Modbus Serial Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.4 Connecting the I/O points and power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.5 S811+ to C441U and C441V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.6 Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.7 Configuration Reset Button. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5 Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.1 Configuration using a web browser. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.2 Configuration using an EDS file. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6 EtherNet/IP Protocol Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.1 Supported Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.2 EtherNet/IP Object Model for C441 Motor Insight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.3 EtherNet/IP Object Model for C440 overload relay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.4 EtherNet/IP Object Model for S611 Soft Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6.5 EtherNet/IP Object Model for S811+ Soft Starter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.6 EtherNet/IP Object Model Stand Alone I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7 Modbus TCP and Modbus Serial Protocol Support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
7.1 Supported Function Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
7.2 Register Definitions for the C441 Motor Insight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
7.3 Register Definition for the C440 Overload Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
7.4 Register Definition for the S611 Soft Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.5 Register Definitions for S811+ Soft Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.6 Register Definitions for use as stand alone I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
1 Introduction
2 Ratings
The following ratings apply to the C441R, C441T, C441U and C441V
The device can also be used stand alone as an Ethernet I/O block.
Rating
Media
Wire
10/100 MB
yes
# of Ports
The table below describes the products covered in this manual and
their primary usage
Table 3. Environmental Ratings of the Module
Description
Catalog #
Description
Use With
C441R
C441T
C441Motor Insight
S611 Soft Starter
C441U
C440 Overload
As I/O Block
S811+ Soft Starter
C441V
C440 Overload
As I/O Block
S811+ Soft Starter
Rating
Transportation and
Storage
Temperature
-40C 85C
Humidity
Operating
Temperature
Humidity
Altitude
Shock
IEC 60068-2-27
Vibration
IEC 60068-206
Pollution Degree
Electrical/EMC
Rating
Surge (IEC61000-4-5)
+/- 2 kV line-to-ground
RF Conducted (IEC61000-4-6)
10 V, 0.15 80 MHz
IP20
EN55011 Class A
Agency Certifications
UL 508
cUL (CSA C22.2 No. 14)
CE (Low Voltage Directive)
ODVA EtherNet/IP Certified
Requirement
Voltage Range
18 30 Vdc
50 mA
NNote: Any UL Listed power supply with an isolated 24Vdc voltage output can
be used provided that a UL listed or recognized fuse rated no more then 4A
maximum is installed
Warning
Only apply 24Vdc to the Motor Insight Communication module
power supply connector. Use of any other voltage may result
in personal injury, property damage and damage to the module.
The C441R and C441U provide connection for four AC Input points
the ratings for these inputs are:
Table 6. AC Input Ratings
Specification
Value
Number of Inputs
Nominal voltage
120 Vac
Nominal Current
15 mA
Operating Range
80 140 Vac
Operating Frequency
50/60 Hz
30 ms
Input Type
The C441T and C441V provide connection for four DC Input points.
The ratings for these inputs are:
Table 7. DC Input Ratings
Specification
Value
Number of Inputs
Nominal voltage
24 Vdc
Nominal Current
5 mA
Type
Current Sinking
Input Type
All units provide two output relays. The ratings of the relay outputs
are:
Table 8. Relay Output Ratings
Specification
Value
Num Contacts
Thermal Contact
5A
300 Vac
120 Vac
5A
Electrical Life
1105 Operations
Mechanical Life
1106 Operations
Front View
P1
Status
Indicators
Configuration
Reset
I/O
Indicators
RS485 Port
(Modbus)
Top
View
Bottom
View
IP Address
Switch
I/O and
Supply
Ethernet Switch
PLC
P1
P1
P1
P2
P2
P2
P1
P1
P1
P2
P2
P2
PLC
Some PLC systems and external switches provide support for ring
network topologies. In these systems a closed ring is formed and
a special algorithm is used to allow communications to continue
even if a cable becomes disconnected or one of the ring devices is
removed.
While the Motor Insight does NOT directly execute these algorithms,
it has been designed to be included in these two types of rings. The
figure below depicts three Motor Insight units connected in a ring
with a PLC that supports a ring algorithm.
PLC
P1
P1
P1
P2
P2
P2
(With
Ring
Support)
Though the Ethernet Module has two Ethernet Ports, it only has one
IP address that is used to target communications to the device. The
dip switch accessible on the top of the module is used to establish
the IP address Mode. The switch settings and the resulting behaviors are depicted in the table below.
Mode
Restore
Static
(HW)
254
Static
(NV)
DHCP
P1
1-253
255
10
P2
Setting
Default
Range
Address
Address
Baud Rate
1 1
Stop
StopBits
Bits
Parity
Parity
Mode
11
Even
RTUEven
1 to 247
1 to 247
9600, 19.2K,
9600, 19.2K. 57.6K,
57.6K,
115.2K
115.2K
1 or 2
1 or 2
Even or Odd
RTU
or ASCH
Even
or Odd
Setting
Baud Rate
D0
D1
Default
19.2K
19.2K
Mode
RTU
Range
RTU or ASCII
RS485
24VDC
Power Supply
AC/DC
D1
D0
24
0V
I1
I1
I2
I2
I3
I3
I4
I4
Ethernet
ON
OFF
NO
Q1
NO
Q1
NO
Q2
NC
Q2
1
2
4
8
16
32
64
128
On
AC/DC
Pin 12
RS485
24VDCISO
AC/DC
AC/DC
D1
D0
Ethernet
24
0V
I1
I1
I2
I2
I3
I3
ON
I4
I4
OFF
NO
Q1
NO
Q1
NO
Q2
NC
Q2
1
2
4
8
16
32
64
128
On
Pin 12
eaton corporation www.eaton.com
11
NO
Q2
NC
Q2
32
64
128
AC/DC
Pin 12
RS485
24VDCISO
AC/DC
AC/DC
Pin 12
12
D1
D0
Ethernet
24
0V
I1
I1
I2
I2
I3
I3
ON
I4
I4
OFF
NO
Q1
NO
Q1
NO
Q2
NC
Q2
1
2
4
8
16
32
64
128
On
RS485
24VDC
Power Supply
120VAC
AC/DC
AC/DC
D1
D0
Ethernet
24
0V
I1
I1
I2
I2
I3
I3
ON
I4
I4
OFF
NO
Q1
NO
Q1
NO
Q2
NC
Q2
1
2
4
8
16
32
64
128
On
Pin 12
13
On
D1
1
2
4
8
16
32
S2
S1
D0
24VDC
Power Supply
Ethernet
RS485
OR
Pin 1
24VDC
Power Supply
D1
D0
24
0V
I1
I1
I2
I2
I3
I3
I4
I4
NO
Q1
NO
Q1
NO
Q2
NC
Q2
ON
OF
F
1
2
4
8
16
32
64
128
On
Pin 12
Module Status
MS
The Module Status Indicator states are described in the table below
Table 10. Module Status Indicator
Indicator State
Summary
Requirement
Steady Off
No Power
Steady Green
Device
Operational
If the device is operating correctly, the module status indicator shall be steady green.
Flashing Green
Standby
Flashing Red
Minor Fault
Steady Red
Major Fault
Flashing Green/
Red
Self-test
NS
Network Status
I/O Status
I1
I2
I3
I4
O1
O2
Indicator
State
Steady Off
Summary
Requirement
Flashing Green
No
Connections
Steady Green
Connected
Flashing Red
Connection
Time-out
Steady Red
Duplicate IP
Flashing Green
and Red
Self-test
Description
Steady Off
Not Powered, No IP
Address
Flashing Green
No Traffic
Flashing Yellow
The Input Status Indicator states are described in the table below
Table 13. Input Status (I1-I4) Indicator
Indicator State Description
Off
On Solid
The Output Status Indicator states are described in the table below.
Table 14. Output Status (O1-O2) Indicator
Indicator State
Description
Off
On Solid
Action Taken
15
5 Configuration
The web pages have been validated for use with Internet Explorer.
To use the web page open your Internet Explorer browser and enter
the IP address assigned to the Ethernet module:
http:// IP Address
The web page provides five levels of authorization as shown in the
chart below:
Default
User Name
Default
Password
Open
<none>
<none>
readonly
Control
control
control
Description
Config
Super_
User
superuser
superuser
Exclusive Owner
Listen Only
Input Only
Level
Read_Only readonly
Object
# of
Instances
0x01
(hex)
Identity
0x02
Message
Router
0x04
Assembly
Object
(See
assembly
object
details)
0x06
Connection 1
Manager
0x08
Discrete
Input Point
0x09
Discrete
Output
Point
0x29
Control
Supervisor
0x2C
Overload
0x93
Voltage
Monitor
Vendor Specific object for monitoring motor voltage. See details below.
0xF5
TCP/IP
Interface
0xF6
Ethernet
Link
Object Details
Identity Object
Class: 1 (0x01)
16
Description
Service
Name
Service
Data
Description
0x05
Reset
0x05
Reset
101
0x05
Reset
0x0E
Get_
n/a
Attribute_
Single
0x10
Set_
value
Attribute_
Single
NV
Access
Data
Type
Name
Description
Get
UINT
CIP
Vendor
ID
Get
UINT
CIP
Device
Type
Get
UINT
Product
Code
Get
UINT
Get
WORD
Device
Status
Serial
Number
Assembly Object
Class: 4 (0x04)
Table 17. C441 Motor Insight Assembly Object Instance
Attributes
Attrib
NV
Access
Set/Get
Data
Type
Array of
BYTE
Name
Description
Data
Instance
Usage
Name
Output
Poll
Output
105
Poll
Input
50
Poll
Fault Status
Input
51
Poll
Input
100
Poll
Input
107
Poll
Input
110
Poll
Input
115
Poll
General Monitoring
Input
121
Poll
Word
Offset
Size
(bytes)
Name
Description
Basic
Output
Overload
NV
Set/Get
UDINT
Get
SHORT_ Product
STRING Name
Byte
Offset
Word
Offset
Size
(bytes)
Name
Description
Get
USINT
Fault Status
Bit 0: Faulted.
Device
State
176
NV
Set/Get
177
Get
UINT
C441
DSP FW
Version
178
Get
UINT
UI
User Interface Firmware Version
Firmware
Version
179
NV
Set/Get
UINT
C441
Unit ID
Word
Offset
Size
(bytes)
Name
Description
Extended
Input
Overload
Bit 0: Faulted
Bit 1: Warning
Unit ID
0x00BA (186) - C441BA
0x00BB (187) - C441BB
0x00CA (202) - C441CA
0x00CB (203) - C441CB
0x00DA (218) - C441DA
0x00DB (219) - C441DB
0x00EA (234) - C4410109(x)
0x00EB (235) - C4410590(x)
17
Assembly includes general status, motor current, line voltage and Input states.
Word Size (bytes): 2
All data is little endian (low byte first).
Byte
Offset
Word
Offset
Size
(bytes)
Byte
Offset
Word
Offset
Size
(bytes)
Name
Description
Device
Status
Current I1
Current I2
Current I3
Trip
Reason
10
Current
Average
12
Voltage
L1-L2
14
Voltage
L2-L3
16
Voltage
L3-L1
18
Voltage
Average
Name
Description
Device
Status
Word
Offset
Size
(bytes)
Name
Description
Basic Overload
w/Relay
Word
Offset
Size
(bytes)
Name
Description
Extended
Overload
Input w/
IO
18
Word
Offset
Size
(bytes) Name
Device
Status
Current I1
Current I2
Current I3
10
Word
Offset
Size
(bytes) Name
32
16
34
17
Overload
Status
Overload Status
- 0x0001: Overload Trip
- 0x0002: Ground Fault Trip
- 0x0004: High Power Trip
- 0x0080: Relay Closed
36
18
Error Code
Warning/Alarm Indications
0x0001 (1) - Low Voltage Warning
0x0002 (2) - High Voltage Warning
0x0004 (4) - Voltage Unbalance Warning
0x0008 (8) - Low Power Warning
0x0010 (16) - Reverse Phase Warning
0x0020 (32) - Current Unbalance Warning
0x0040 (64) - Voltage Single Phase
Warning
0x0080 (128) - Current Single Phase
Warning
0x0100 (256) - GND Fault Warning
38
19
Thermal
Thermal Capacity
Pile
0% Cold Motor
Percentage 100% Will Cause an Overload Trip (%)
40
20
Description
Current
Average
12
Voltage
L1-L2
14
Voltage
L2-L3
16
Voltage
L3-L1
18
Voltage
Average
20
10
Motor
Power
Motor Power
x0.1kW when external CTs are used
x0.01kW otherwise (scale)
22
11
Voltage
Max Deviation from Average Voltage
Unbalance Divided by Average Voltage (%).
Percentage
24
12
Current
Max Deviation from Average Current
Unbalance Divided by Average Current (%).
Percentage
26
13
Apparent
Power
Factor
28
14
Residual
Ground
Current
30
15
Line
frequency
Description
19
Instance Count: 2
Instance List: 1, 2
Byte
Offset
Word
Offset
Size
(bytes)
Name
Description
Device
Status
Current
Average
Voltage
Average
Trip
Reason
Aux
Relay
Trip
Reason
NV
3
101
20
NV
Access
Data
Type
Name
Description
Get
BOOL
Input
Set/Get
UDINT
Field Inputs
Debounce
NV
Access
Data
Type
Name
Description
Set/Get
BOOL
Field Relay
Outputs
NV
Set/Get
BOOL
Field Relay
Fault Action
NV
Set/Get
BOOL
Field Relay
Fault State
NV
Set/Get
BOOL
Field Relay
Idle Action
NV
Set/Get
BOOL
Field Relay
Idle State
Service
Data
0x0E
Get_Attribute_Single
n/a
0x10
Set_Attribute_Single
value
0x05
Reset
n/a
Description
Data
Type
10
Get
11
12
13
Attrib NV Access
Data
Type
BOOL
Fault
Status
106
NV Set/Get
Get
BOOL
Warning
Status
Set/Get
BOOL
Fault
Reset
107
Get
UINT
Fault
Queue
Set/Get
BOOL
Force
Fault
101
Get
WORD
Device
Status
104
105
Description
103
Name
17
102
Get
Get
Get
NV Set/Get
UINT
UINT
UINT
BOOL
Trip
Reason
Overload
Status
Overload Status
- 0x0001: Overload Trip
- 0x0002: Ground Fault Trip
- 0x0004: High Power Trip
- 0x0080: Relay Closed
Error
Code
Warning/Alarm Indications
0x0001 (1) - Low Voltage Warning
0x0002 (2) - High Voltage Warning
0x0004 (4) - Voltage Unbalance Warning
0x0008 (8) - Low Power Warning
0x0010 (16) - Reverse Phase Warning
0x0020 (32) - Current Unbalance
Warning
0x0040 (64) - Voltage Single Phase
Warning
0x0080 (128) - Current Single Phase
Warning
0x0100 (256) - GND Fault Warning
Motor
Ctrl Idle
Loss Act
Disable
Name
Description
BOOL
Motor
Ctrl Com
Idle
Action
Val
NV Set/Get
BOOL
Motor
Ctrl Com
Loss Act
Disable
108
NV Set/Get
BOOL
Motor
Ctrl Com
Loss
Action
Val
109
Get
UINT
Fault
Queue
110
Get
UINT
Fault
Queue
Entry 1
111
Get
UINT
Fault
Queue
Entry 2
112
Get
UINT
Fault
Queue
Entry 3
113
Get
UINT
Fault
Queue
Entry 4
114
Get
UINT
Fault
Queue
Entry 5
115
Get
UINT
Fault
Queue
Entry 6
116
Get
UINT
Fault
Queue
Entry 7
117
Get
UINT
Fault
Queue
Entry 8
118
Get
UINT
Fault
Queue
Entry 9
119
Set/Get
BOOL
Clear
0->1 = Fault Entry Cleared
Last Fault 0 = No action
Entry
From
Queue
120
NV Set/Get
UINT
Enable/
Disable
Trip
21
Data
Type
121
WORD
122
123
124
125
(0x7D)
22
NV Set/Get
NV Set/Get
NV Set/Get
Get
WORD
UINT
WORD
Set/Get
BOOL
Name
Description
Aux
Relay
Config
Byte 1
Aux
Relay
Config
Byte 2
Aux
Reset
Delay
Aux
0x0002 - Relay Turned Off (Network/UI)
Relay Trip 0x0004 - Contactor Failure
Reason
0x0008 - Under Current Trip
0x0010 - Overload Trip
0x0020 - GND Fault Trip
0x0040 - Current Unbalance Trip
0x0080 - Current Single Phase
0x0100 - Mains Freq Fault
0x0200 - High Power Trip
0x0400 - Over Voltage Trip
0x0800 - Under Voltage Trip
0x1000 - Voltage Unbalance Trip
0x2000 - Over Current Trip
0x4000 - Low Power Trip
0x8000 - Phase Reversal Trip
Reset
Aux
Relay
Overload Object
Class 44 (0x2C)
Instance Count: 1
Instance List: 1
Table 31. Overload Object Instance Attributes
Attrib NV
Data
Access Type
Name
Description
NV
Set/Get USINT
Overload
Trip Class
Get
INT
Current
Average
Get
USINT
Current
Max deviation from average current
Unbalance divided by average current (%).
Percentage
Get
USINT
Thermal
Thermal Capacity
Pile
0% Cold Motor
Percentage 100% Will Cause and Overload Trip
(%)
Get
INT
Current I1
Get
INT
Current I2
10
Get
INT
Current I3
11
Get
INT
Residual
Ground
Current
101
NV
Set/Get UINT
Run Time
Hours
102
Get
103
NV
Set/Get UINT
CT
Multiplier
105
NV
Set/Get UINT
Overload
FLA
106
Get
UINT
Apparent
Power
Factor
107
Get
UINT
Motor
Power
Motor Power
x0.1kW when external CTs are used
x0.01kW otherwise (scale)
108
Get
UINT
Remaining
Normal
Restart
Delay
109
Get
UINT
110
NV
Set/Get UINT
Load Fault
Hold-off
Time
111
NV
Set/Get UINT
Load Fault
Number of
Restarts
112
NV
Set/Get UINT
UINT
Data
Access Type
113
Set/Get UINT
NV
Name
Description
114
NV
Set/Get UINT
Run
Transition
Time
115
NV
Set/Get UINT
Run
Transition
Percent
Ground
Fault Trip
Mode
Ground
Fault Trip
Delay
116
117
NV
NV
Set/Get UINT
Set/Get UINT
118
NV
Set/Get UINT
Ground
Fault Pickup Level
119
NV
Set/Get UINT
Current
Unbalance
Trip Delay
Data
Type
Name
Description
Get
UINT
Voltage L1-L2
Get
UINT
Voltage L2-L3
Get
UINT
Voltage L3-L1
Get
UINT
Voltage Average
Get
UINT
Voltage
Unbalance
Percentage
Get
UINT
Line Frequency
NV Set/Get
UINT
Voltage Faults
Trip Mode
NV Set/Get
UINT
Under Voltage
Pick-up Level
NV Set/Get
UINT
Under Voltage
Trip Delay
10
NV Set/Get
UINT
Over Voltage
Pick-up Level
11
NV Set/Get
UINT
12
NV Set/Get
UINT
Voltage
Unbalance
Pick-up Level
120
NV
Set/Get UINT
Current
Unbalance
Pick-up
Level
121
NV
Set/Get UINT
Jam Trip
Delay
122
NV
Set/Get UINT
123
NV
Set/Get UINT
Current
Pickup Delay for Current Phase Loss
Phase Loss (sec)
Trip Delay
13
NV Set/Get
UINT
Voltage
Unbalance
Trip Delay
124
NV
Set/Get UINT
High KW
Trip Time
14
NV Set/Get
UINT
Phase Order
125
NV
Set/Get UINT
High KW
Trip limit
Phase Order
- 0 (Trip Disabled)
- 1 ACB
- 2 ABC
126
NV
Set/Get UINT
15
NV Set/Get
UINT
Supply Fault
Hold-off Time
127
NV
Set/Get UINT
16
UINT
128
NV
Set/Get UINT
Under
Under Current Trip Delay (sec)
Current Trip
Delay
129
NV
Set/Get UINT
Under
Current
Pick-up
Level
130
NV
Set/Get UINT
Overload
Reset
131
NV
Set/Get UINT
Load Fault
Reset
Delay Calc
Get
23
Object Details
Class 1 (0x01): Identity Object
Instance Count: 1
Instance List: 1
Table 33. C440 Identity Object Instance Attributes
Attrib
Data
NV Access Type
Get
UINT
CIP
ODVA assigned Vendor Identification
Vendor ID number.
Name
Description
Class
Object
# of
Instances
Description
0x01
(hex)
Identity
Get
UINT
0x02
Message
Router
CIP
Device
Type
Get
UINT
0x04
Assembly
Object
Product
Code
Get
UINT
0x06
Connection 1
Manager
Get
WORD
Device
Status
0x08
Discrete
Input Point
0x09
Discrete
Output
Point
0x29
Control
Supervisor
0x2C
Overload
0xF5
TCP/IP
Interface
0xF6
Ethernet
Link
NV Set/Get UDINT
Serial
Number
Get
SHORT_ Product
STRING Name
Get
USINT
176
177
Get
UINT
C441
DSP FW
Version
178
Get
UINT
UI
User Interface Firmware Version
Firmware
Version
24
Device
State
Data
NV Access Type
179
NV Set/Get UINT
Name
Description
C441
Unit ID
Unit ID
0x00BA (186) - C441BA
0x00BB (187) - C441BB
0x00CA (202) - C441CA
0x00CB (203) - C441CB
0x00DA (218) - C441DA
0x00DB (219) - C441DB
0x00EA (234) - C4410109(x)
0x00EB (235) - C4410590(x)
Word
Offset
Size
(bytes)
Name
Description
Basic
Overload
Output w/IO
Table 40. C440 Assembly Instance 120 (0x78): Status, Faults and
Measurements
NV
Access
Set/Get
Data
Type
Array of
BYTE
Name
Description
Data
Assembly includes the C440 status, faults, current and thermal value.
Word Size (bytes): 2
All data is little endian (low byte first).
Byte
Offset
Word
Offset
Size
(bytes)
Name
Description
Device
Status
Latched
Faults
Scaled 3
Phase Ave
Current
Thermal
Memory
Percentage
Instance
Usage
Name
Output
Poll
Input
50
Poll
Fault Status
Output
105
Poll
Input
107
Poll
Input
120
Poll
Input
130
Poll
Word
Offset
Size
(bytes)
Name
Description
Basic
Bit 2: Fault Reset
Overload
Output
Word
Offset
Size
(bytes)
Name
Description
Fault
Status
Bit 0: Faulted
Word
Offset
Size
(bytes)
Name
Description
Basic
Overload
Output w/
Relay
25
Table 41. C440 Assembly Instance 130 (0x82): Full Status and
Measurements
Assembly includes a full list of the most commonly used values.
Word Size (bytes): 2.
All data is little endian (low byte first).
Byte
Word Size
Offset Offset (bytes)
Name
Description
Attrib
Device Status
Scaled Current
Phase A RMS
Scaled Current
Phase B RMS
Scaled Current
Phase C RMS
10
Current as
Percentage of
FLA
12
Phase
Imbalance
Percent
14
Line Frequency
16
Thermal
Memory
Percentage
18
Latched Faults
20
10
Feature States
22
11
Device
Temperature
24
12
Scaled Ground
Current RMS
26
13
Ground Fault
Percent
26
NV
101
NV
Access
Data
Type
Name
Description
Get
BOOL
Inputs
0 = Off
1 = On
Set/Get
UDINT
Field
Inputs
Debounce
Data
Access Type
Name
Description
Set/Get BOOL
Field
Relay
Outputs
NV
Set/Get BOOL
Field
Relay
Fault
Action
NV
Set/Get BOOL
Field
Relay
Fault
State
NV
Set/Get BOOL
Field
Relay
Idle
Action
NV
Set/Get BOOL
Field
Relay
Idle
State
Data
Access Type
Name
Description
10
Get
BOOL
Fault Status
12
Set/Get BOOL
Fault Reset
17
Set/Get BOOL
Force Fault
101
Get
WORD Device
Status
Latched
Faults
102
Get
UINT
103
Get
105
NV
Set/Get BOOL
Motor Ctrl
When this value is TRUE the motor
Idle Loss Act state will be unchanged after a
Disable
communication idle event. A FALSE
value will cause the Motor Control
Communication Idle Value to be
applied on a com idle event.
106
NV
Set/Get BOOL
Motor Ctrl
Com Idle
Action Val
107
NV
Set/Get BOOL
Motor Ctrl
Com Loss
Act Disable
108
NV
Set/Get BOOL
Motor Ctrl
Com Loss
Action Val
Data
Access Type
Name
Description
130
Get
UINT
Feature
States
131
Get
INT
Device
Temperature
132
Get
UINT
Line
Frequency
27
Instance Count: 1
Instance List: 1
NV
Access
Data
Type
Get
Get
Name
Description
USINT
Phase
Imbalance
Percent
USINT
Thermal
Memory
Percentage
Object
# of
Instances
0x01
(hex)
Identity
Description
100
Get
USINT
0x02
Message
Router
105
Get
UINT
Scaled FLA
Setting
0x04
Assembly
Object
140
Get
UINT
Scaled 3Phase
Ave Current
0x06
Connection
Manager
141
Get
UINT
0x08
Discrete Input 4
Point
142
Get
UINT
0x09
Discrete
Output Point
143
Get
UINT
0x29
Control
Supervisor
144
Get
UINT
Scaled Ground
Current RMS
0x2C
Overload
0x2D
SoftStart
150
Get
UINT
Scaled Max
FLA
This is the max FLA setting possible in this device. The value is
scaled by the multiplier. (Amps)
0x93
Voltage
Monitor
Vendor Specific object for monitoring motor voltage. See details below.
0xF5
Get
UINT
Scaled Min
FLA
This is the min FLA setting possible in this device. The value is
scaled by the multiplier. (Amps)
TCP/IP
Interface
151
0xF6
Ethernet Link
Current Scale
Value
152
Get
UINT
153
Get
UINT
Current as
Percentage
of FLA
154
Get
USINT
Ground Fault
Percent
28
Object Details
Class 1 (0x01): Identity Object
Instance Count: 1
Instance List: 1
Table 46. S611 Identity Object Instance Attributes
Attrib
NV
Access
Data
Type
Get
3
4
Name
Description
UINT
CIP
Vendor
ID
Get
UINT
CIP
Device
Type
Get
UINT
Product
Code
Get
UINT
NV
Access
Data
Type
Get
WORD
Name
Description
Device
Status
NV
Set/Get
UDINT
Serial
Number
Get
SHORT_
STRING
Product
Name
Get
USINT
Device
State
176
NV
Set/Get
SHORT_
STRING
177
Get
UINT
C441
DSP FW
Version
178
Get
UINT
UI
User Interface Firmware Version
Firmware
Version
179
NV
Set/Get
UINT
C441
Unit ID
Instance
Usage
Name
Output
Poll
Basic Softstarter
Input
60
Poll
Input
100
Poll
Output
105
Poll
Output
106
Poll
Input
107
Poll
Extended Overload w/ IO
Input
108
Poll
Input
121
Poll
Input
131
Poll
Input
133
Poll
Word
Offset
Size
(bytes)
Name
Description
Basic
Basic Softstart Assembly.
Softstarter Bit 0 = Run 1
Bit 2 = Fault Reset
Word
Offset
Size
(bytes)
Name
Description
Basic
Softstarter
Input
Basic Softstart.
Bit 0 = Faulted
Bit 2 = Running1
Bit 7 = Bypass (at Reference)
Table 51. S611 Assembly Instance 100 (0x64): Status and Current
Assembly includes the status overview and motor current levels.
Word Size (bytes): 2
All data is little endian (low byte first).
Byte
Offset
Word
Offset
Size
(bytes)
Instance Count: 10
Instance List: 3, 60, 100, 105, 106, 107, 108, 121, 131, 133
Unit ID
0x00BA (186) - C441BA
0x00BB (187) - C441BB
0x00CA (202) - C441CA
0x00CB (203) - C441CB
0x00DA (218) - C441DA
0x00DB (219) - C441DB
0x00EA (234) - C4410109(x)
0x00EB (235) - C4410590(x)
Attrib
NV
Access
Set/Get
Data
Type
Array of
BYTE
Name
Description
Data
Name
Description
29
Word
Offset
Size
(bytes)
Name
Description
Basic
Basic Overload with Relays
Overload w/ Bit = Description
Relay
Bit 0 = Relay Output 1
Bit 1 = Relay Output 2
Bit 2 = Fault Reset
Word
Offset
Size
(bytes)
Name
Description
Device
Status
Average
Current
Average
Voltage
Trip
Reason
Bit = Description
0 = Overload
1 = Jam
2 = Stall
3 = Current Imbalance
4 = Load Disconnect
5 = Phase Loss
6 = Mains Fault
7 = Phase Reversal
8 = Shorted SCR
9 = SCR Not Firing
10 = Pole Overtemp
11 = Bypass Dropout
12 = SCR Overcurrent
13 = Contactor Overcurrent
14 = Communication Fault
15 = Other Device Fault
Word
Offset
Size
(bytes)
Name
Description
Word
Offset
Size
(bytes)
Name
Description
Table 55. S611 Assembly Instance 108 (0x6C): Motor Ctrl Status
w/IO
Byte
Offset
Word
Offset
Size
(bytes)
Name
Description
Motor
Ctrl
Status
w/IO
30
Word
Offset
Size
(bytes) Name
Device Status
Phase A RMS
Current
Phase A RMS
Current
Phase B RMS
Current
Phase B RMS
Current
Phase C RMS
Current
Phase C RMS
Current
Overload
Thermal
Memory
Thermal Capacity
0% Cold Motor
100% Will Cause an Overload Trip (%)
Field Inputs
10
Average
Current
12
Vab RMS
Voltage
10
14
Vbc RMS
Voltage
Average
Current
12
16
Vca RMS
Voltage
Vab RMS
Voltage
14
18
Average
Voltage
Vbc RMS
Voltage
16
Vca RMS
Voltage
18
Average
Voltage
20
10
Total Kilowatts
22
11
Voltage
Unbalance
24
12
Current
Unbalance
26
13
28
14
Residual
Ground Fault
Current
30
15
Line Frequency
Byte
Offset
Word
Offset
Size
(bytes) Name
Device Status
Description
Description
31
Word
Offset
Size
(bytes) Name
32
16
34
17
Description
Trip Reason
Motor Status
Bit = Description
0 = Overload
1 = Jam
2 = Stall
3 = Current Imbalance
4 = Load Disconnect
5 = Phase Loss
6 = Mains Fault
7 = Phase Reversal
8 = Shorted SCR
9 = SCR Not Firing
10 = Pole Overtemp
11 = Bypass Dropout
12 = SCR Overcurrent
13 = Contactor Overcurrent
14 = Communication Fault
15 = Other Device Fault
Motor Control Status Bits:
Bit = Description
0 = Run
2 = In Bypass
5 = Fault
11 = Relay 1 State
12 = Relay 2 State
13 = Control From Network
14 = Permissive State
36
18
Pole Temp
38
19
Power Sign
40
20
Current Scale
Factor
42
21
Overload
Thermal
Memory
Thermal Capacity
0% Cold Motor
100% Will Cause an Overload Trip (%)
NV
Access
101
NV
Set/Get
32
Data
Type
Name
Description
NV
Access
Data
Type
Name
Description
Set/Get
BOOL
Field
Relay
Outputs
NV
Set/Get
BOOL
Field
Relay
Fault
Action
NV
Set/Get
BOOL
Field
Relay
Fault
State
NV
Set/Get
BOOL
Field
Relay
Idle
Action
NV
Set/Get
BOOL
Field
Relay
Idle
State
NV
Access
Data
Type
Name
Description
Set/Get
BOOL
Run1
Get
BOOL
Running1
10
Get
BOOL
Fault Status
12
Set/Get
BOOL
Fault Reset
13
Get
UINT
Fault Code
15
Get
BOOL
Control from
Net
101
Get
102
103
Get
Get
UINT
UINT
Trip Reason
Motor Status
105
NV
Set/Get
UINT
Network
Timeout
106
NV
Set/Get
UINT
Communication
Loss Behavior
1 = Fault
2 = Hold last state
3 = Stop (1)
NV
Access
Data
Type
Name
Description
107
NV
Set/Get
BOOL
Motor Ctrl
Com Loss Act
Disable
108
NV
Set/Get
BOOL
109
Get
UINT
Fault Code
110
Get
UINT
Fault Code
Entry 1
111
Get
UINT
Fault Code
Entry 2
112
Get
UINT
Fault Code
Entry 3
113
Get
UINT
Fault Code
Entry 4 .
114
Get
UINT
Fault Code
Entry 5
115
Get
UINT
Fault Code
Entry 6
116
Get
UINT
Fault Code
Entry 7
117
Get
UINT
Fault Code
Entry 8
118
Get
UINT
Fault Code
Entry 9
119
Set/Get
BOOL
Clear Fault
Queue
120
NV
Set/Get
UINT
Fault Enable
Bits
150
Set/Get
UINT
Motor Control
151
NV
Set/Get
UINT
Start Input
Behavior
152
NV
Set/Get
UINT
Fault Relay
Config
33
NV
Access
Data
Type
153
NV
Set/Get
UINT
154
155
156
157
34
NV
NV
NV
Set/Get
Set/Get
Set/Get
Set/Get
UINT
UINT
UINT
UINT
Name
Description
Auxiliary Relay
Configuration
User Interface
Display Config
UI Edit Lock
Command
Register
Communication
Loss Timeout
NV
Data
Access Type
NV
Get
USINT Current
Unbalance
Get
USINT Overload
Thermal
Memory
Thermal Capacity
0% Cold Motor
100% Will Cause an Overload
Trip (%)
101
Get
UINT
102
Get
UINT
Number of
Starts
105
NV
Set/Get UINT
106
Get
UINT
107
Get
UINT
Total Kilowatts
119
NV
Set/Get UINT
Current
Unbalance Trip
Delay
120
Get
Current
Unbalance
121
NV
Set/Get UINT
122
NV
Set/Get UINT
123
NV
Set/Get UINT
130
NV
Set/Get UINT
Reset Mode
Method of Reset.
0 = Manual
1 = Auto
140
Get
UINT
141
Get
UINT
Phase A RMS
Current
142
Get
UINT
Phase B RMS
Current
143
Get
UINT
Phase C RMS
Current
144
Get
UINT
Residual
Ground Fault
Current
152
Get
UINT
Current Scale
Factor
170
NV
Set/Get UINT
171
NV
Set/Get UINT
172
NV
Set/Get UINT
173
NV
Set/Get UINT
174
NV
Set/Get UINT
175
Get
Power Sign
176
NV
Set/Get UINT
Residual GF
Start Delay
UINT
INT
Name
Description
Instance Count: 1
Instance List: 1
Access
Data
Type
Name
Description
Get
BOOL
At Ref
NV
Set/Get
NV
Set/Get
UINT
13
NV
Set/Get
14
NV
Set/Get
UINT
Kick Start
Initial
Torque
16
NV
Set/Get
UINT
Object
# of
Instances
0x01
(hex)
Identity
0x02
Message
Router
0x04
Assembly
Object
16
0x06
Connection
Manager
0x08
Discrete
Input Point
0x09
Discrete
2
Output Point
0x0A
Analog Input 1
Point
0x29
Control
Supervisor
Description
101
Get
INT
Phase A
Power Pole Temperature. Scaled = x10
Pole Temp (°C)
102
Get
INT
Phase B
Power Pole Temperature. Scaled = x10
Pole Temp (°C)
103
Get
INT
Phase C
Power Pole Temperature. Scaled = x10
Pole Temp (°C)
104
Get
INT
0x2C
Overload
0x20
SoftStart
105
NV
Set/Get
UINT
Initial
Motor
Torque
0x93
Voltage
Monitor
Vendor Specific object for monitoring motor voltage. See details below.
106
NV
Set/Get
UINT
Pump
If supported, the amount of time to
Stop Time use for the pump stop ramp behavior.
(seconds)
0xF5
TCP/IP
Interface
0xF6
Ethernet
Link
107
108
NV
NV
Set/Get
Set/Get
UINT
UINT
Start
Method
Phase
Sequence
Object Details
Class 1 (0x01): Identity Object
Instance Count: 1
Instance List: 1
Table 64. S811+ Identity Object Instance Attributes
Attrib
NV
Access
Data
Type
Get
3
4
Name
Description
UINT
CIP
Vendor
ID
Get
UINT
CIP
Device
Type
Get
UINT
Product
Code
Get
UINT
35
NV
Access
Data
Type
Get
WORD
Name
Description
Device
Status
NV
Set/Get
UDINT
Serial
Number
Get
SHORT_
STRING
Product
Name
Get
USINT
Device
State
176
NV
Set/Get
SHORT_
STRING
177
Get
UINT
C441
DSP FW
Version
Instance Count: 14
Instance List: 5, 60, 61, 101, 102, 110, 111, 120, 121, 130, 131, 140, 141, 150
Attrib
NV
Access
Set/Get
Get
UINT
UI
User Interface Firmware Version
Firmware
Version
179
NV
Set/Get
UINT
C441
Unit ID
Unit ID
0x00BA (186) - C441BA
0x00BB (187) - C441BB
0x00CA (202) - C441CA
0x00CB (203) - C441CB
0x00DA (218) - C441DA
0x00DB (219) - C441DB
0x00EA (234) - C4410109(x)
0x00EB (235) - C4410590(x)
Array of
BYTE
Name
Description
Data
Type
Instance
Usage
Name
Output
5 (0x05)
Poll
Input
60 (0x3C)
Poll
Input
61 (0x3D)
Poll
Output
101 (0x65)
Poll
Input
102 (0x66)
Poll
Device Status
Input
110 (0x6E)
Poll
Input
111 (0x6F)
Poll
Input
120 (0x78)
Poll
Input
121 (0x79)
Poll
Input
130 (0x82)
Poll
Input
131 (0x83)
Poll
Input
140 (0x8C)
Poll
Input
141 (0x8D)
Poll
Input
150 (0x96)
Poll
S811 Status
Word
Offset
Size
(bytes)
Data
Type
178
36
Name
Description
Extended
Softstarter
Byte Offset
Word
Offset
Size
(bytes)
Name
Description
Basic
Softstarter
Input
Word
Offset
Size
(bytes)
Name
Description
Device
Status
Word
Offset
Size
(bytes)
Name
Description
Byte Offset
Word
Offset
Size
(bytes)
Name
Description
Extended
Softstarter
Word
Offset
Size
(bytes) Name
3Ph RMS
Line Current
(deciamps)
Word
Offset
Size
(bytes)
Name
Description
Device
Status
Description
37
Includes the Motor status, motor Ave Current scaled in Amps and Thermal value
Word Size (bytes): 2
Includes the Motor status, motor Ave Current scaled in 0.1A and Thermal value
Word Size (bytes): 2
Byte
Offset
Word Size
Offset (bytes) Name
Byte
Offset
Word
Offset
Size
(bytes)
Name
Description
Device
Status
3Ph Ave
Line Current
(amps)
% Thermal
Pile used
3Ph Ave
Scaled RMS average of the 3phase line curLine
rent - This is the actual current flowing to
Current
the motor in 0.1A.
(deciamps)
4
6
Motor
Control
Faults
Description
38
Assembly includes the status overview, motor current levels scaled in Amps, Pole
Voltages & Thermal.
Word Size (bytes): 2
Assembly includes the status overview, motor current levels scaled in 0.1A, Pole Voltages
& Thermal.
Word Size (bytes): 2
Byte
Word
Offset Offset
Size
(bytes) Name
Description
Word
Offset
Size
(bytes)
Name
Description
Device
Status
Device
Status
3Ph RMS
Scaled RMS 3phase line current - This is
Line Current the actual current flowing to the motor in
(amps)
1.0A.
3Ph RMS
Scaled RMS 3phase line current - This is the
Line Current actual current flowing to the motor in 0.1A.
(deciamps)
% Thermal
Pile used
% Thermal
Pile used
10
Average
current as
% FLA
Average of the 3 phase current as a percentage of the Motor Nameplate fla setting
10
Average
current as
% FLA
Average of the 3 phase current as a percentage of the Motor Nameplate fla setting
12
3Ph RMS
Mains
Voltage
12
3Ph RMS
Mains
Voltage
Byte
Offset
39
Word Size
Offset (bytes)
Name
Description
Device
Status
3Ph RMS
Line Current
(amps)
3Ph Ave
Line Current
(amps)
10
Average
Average of the 3 phase current as a
current as % percentage of the Motor Nameplate fla
FLA
setting
12
% Thermal
Pile used
14
3Ph RMS
Mains
Voltage
20
10
22
11
24
12
Field Inputs
26
13
Power Pole
Temperature
32
16
Line
Frequency
34
17
Motor
Control
Faults
40
Word Size
Offset (bytes)
36
18
38
44
Name
Description
Motor
Control
Warnings
19
Active Fault
List
22
Total Motor
Starts
Device
Status
Description
3Ph RMS
Line Current
(deciamps)
3Ph Ave
Line Current
(deciamps)
10
Average
Average of the 3 phase current as a percurrent as % centage of the Motor Nameplate fla setting
FLA
12
% Thermal
Pile used
14
3Ph RMS
Mains
Voltage
20
10
Ave 3Ph
Real Power
(kW)
22
11
24
12
Field Inputs
26
13
32
16
Line
Frequency
34
17
Motor
Control
Faults
Description
36
18
Motor
Control
Warnings
38
19
Active Fault
List
44
22
Total Motor
Starts
41
Includes S811 status,motor faults, motor warnings, & Active fault codes
Word Size (bytes): 2
Instance Count: 4
Instance List: 1, 2, 3, 4
Byte
Offset
Word Size
Offset (bytes) Name
Device
Status
Motor
Control
Faults
Description
Attrib
NV
Access
Data
Type
3 (0x03)
Get
BOOL
101
(0x65)
NV
Set/Get
UDINT On/Off
The debounce time applied to the
debounce input. The debounce applies to both
rising
Motor
S811+ Motor Control Warning Bit Field
Control
Bit Warning
Warnings 0 Phaseloss
1 Phase Imbalance
2 Thermal Pile
3 Overcurrent
4 Breaker Fault
5 GND Fault
6 Motor Stall
7 Motor Jam
8 OverTemp
9 UnderLoad
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Other
Active
Will display up to 3 faults/warnings that are
Fault List actively pesent
12
20
Fault
Queue
42
Name
Description
Input
State
NV
Access
Data
Type
3 (0x03)
Set/Get
BOOL
5 (0x05)
NV
Set/Get
BOOL
Com
When a communication fault occurs
Fault
the output can execute two types of
Action behavior.
Value = Description
0 = Apply Fault Value
1 = No Change
6 (0x06)
NV
Set/Get
BOOL
Com
Fault
Value
7 (0x07)
NV
Set/Get
BOOL
Idle
When a communication idle state
Action occurs the relay can execute two types
of behavior.
Value = Description
0 = Apply Idle Value
1 = No Change
8 (0x08)
NV
Set/Get
BOOL
Idle
Value
Name
Description
Instance Count: 1
Instance List: 1
Instance Count: 1
Instance List: 1
Attrib
NV
3 (0x03) V
8 (0x08) V
100
(0x64)
101
(0x65)
NV
Access
Data
Type
Get
USINT
Get
Get
Set/Get
Set/Get
USINT
USINT
USINT
Description
102
(0x66)
NV
103
(0x67)
NV
104
(0x68)
NV
Set/Get
USINT
105
(0x69)
NV
Set/Get
UINT
Set/Get
USINT
Name
USINT
Attrib
NV
Access
Data
Type
Name
3 (0x03)
Set/Get
BOOL
Run1
4 (0x04)
Set/Get
BOOL
Run2
7 (0x07)
Get
BOOL
Running1
8 (0x08)
Get
BOOL
Running2
9 (0x09)
Get
BOOL
Ready
10 (0x0A)
Get
BOOL
Faulted
Fault present
Warning present
Description
11 (0x0B)
Get
BOOL
Warning
12 (0x0C)
Set/Get
BOOL
Fault Reset
Reset Fault
15 (0x0F)
Get
BOOL
Control From
Net
22 (0x16)
Get
100 (0x64)
NV
Set/Get
101 (0x65)
NV
Set/Get
102 (0x66)
NV
Set/Get
103 (0x67)
NV
Set/Get
104 (0x68)
NV
Set/Get
105 (0x69)
NV
Set/Get
106 (0x6A) NV
Set/Get
107 (0x6B) NV
Set/Get
108 (0x6C) NV
Set/Get
Entry 1
109 (0x6D) NV
Set/Get
Entry 2
110 (0x6E)
NV
Set/Get
Entry 3
111 (0x6F)
NV
Set/Get
Entry 4
112 (0x70)
NV
Set/Get
UINT
Custom fault
code 1
Entry 1
113 (0x71)
NV
Set/Get
UINT
Custom fault
code 2
Entry 2
114 (0x72)
NV
Set/Get
UINT
Custom fault
code 3
Entry 3
115 (0x73)
NV
Set/Get
BOOL
Terminal Block
control enable
116 (0x74)
Get
BOOL
Run1 logic
sense
117 (0x75)
NV
Set/Get
BOOL
wiring config
118 (0x76)
NV
Set/Get
BOOL
Pending start
warning
119 (0x77)
NV
Set/Get
UINT
Power up start
delay
120 (0x78)
NV
Set/Get
UINT
Start delay
121 (0x79)
NV
Set/Get
UINT
Get
UINT
Auto Reset
Count
122 (0x7A) V
43
NV
Access
123 (0x7B) NV
Set/Get
Data
Type
Name
Description
124 (0x7C) NV
Set/Get
UINT
Auto Reset
Delay Time
125 (0x7D) NV
Set/Get
UINT
Auto Reset
Attempt Limit
126 (0x7E)
Set/Get
NV
127 (0x7F)
NV
Set/Get
UINT
128 (0x80)
NV
Set/Get
UINT
Motor Control
Command
Timeout
129 (0x81)
130 (0x82)
44
NV
Set/Get
Set/Get
BOOL
Alarm - No Trip
Enabled
Attrib
NV
Access
Name
4
(0x04)
NV
Set/Get
7
(0x07)
Get
USINT % Thermal
Pile used
100
(0x64)
Set/Get
UINT
Motor
Nameplate
FLA in 0.1A
101
(0x65)
Get
UINT
3Ph Ave
Line Current
(deciamps)
102
(0x66)
Get
UINT
3Ph RMS
Line Current
(deciamps)
Scaled RMS 3phase line current This is the actual current flowing to
the motor in 0.1A (L1).
103
(0x67)
Get
UINT
3Ph RMS
Line Current
(deciamps)
Scaled RMS 3phase line current This is the actual current flowing to
the motor in 0.1A (L2).
104
(0x68)
Get
UINT
3Ph RMS
Line Current
(deciamps)
Scaled RMS 3phase line current This is the actual current flowing to
the motor in 0.1A (L3).
105
(0x69)
Get
UINT
Average
Average of the 3 phase current as a
current as % percentage of the Motor Nameplate
FLA
fla setting
106
(0x6A)
Get
UINT
3Ph Ave
Line Current
(amps)
107
(0x6B)
Get
UINT
3Ph RMS
Line Current
(amps)
Scaled RMS 3phase line current This is the actual current flowing to
the motor in 1.0A (L1).
108
(0x6C)
Get
UINT
3Ph RMS
Line Current
(amps)
Scaled RMS 3phase line current This is the actual current flowing to
the motor in 1.0A (L2).
109
(0x6D)
Get
UINT
3Ph RMS
Line Current
(amps)
Scaled RMS 3phase line current This is the actual current flowing to
the motor in 1.0A (L3).
110
(0x6E)
Get
UINT
Ave 3Ph
Real Power
(kW)
111
(0x6F)
Get
INT
112
(0x70)
NV
Set/Get
113
(0x71)
Set/Get
BOOL
114
(0x72)
NV
Set/Get
115
(0x73)
NV
Set/Get
116
(0x74)
NV
Set/Get
UINT
117
(0x75)
NV
Set/Get
118
(0x76)
NV
Set/Get
Enable
Overload
During Start
Description
Undercurrent Amount of time a low current condiTrip Duration tion must exist before a trip; 0.0
- 60.0 (in 0.1secs)
Attrib
NV
Access
Name
119
(0x77)
NV
Set/Get
120
(0x78)
NV
Set/Get
121
(0x79)
NV
Set/Get
UINT
Motor
Phase Loss
Duration
Amount of time a phase loss condition must exist before a trip; 0.0
- 60.0 (in 0.1secs)
122
(0x7A)
NV
Set/Get
USINT Phase
Imbalance
Trip Enable
123
(0x7B)
NV
Set/Get
124
(0x7C)
NV
Set/Get
UINT
125
(0x7D)
NV
Set/Get
126
(0x7E)
NV
Set/Get
UINT
Ave Power
Low Trip
Threshold
127
(0x7F)
NV
Set/Get
UINT
Ave Power
High Trip
Threshold
128
(0x80)
NV
Set/Get
UINT
Ave Power
Amount of time a low or high power
Trip Duration condition must exist before a trip;
0.0 - 60.0 (in 0.1secs)
Description
NV
Access
Data
Type
Name
Description
3
(0x03)
Get
BOOL
At Ref
4
(0x04)
NV
Set/Get
7
(0x07)
NV
Set/Get
UINT
8
(0x08)
NV
Set/Get
USINT Initial
Starting
Torque
11
(0x0B)
NV
Set/Get
BOOL
Expected
Incoming
Phase
Sequence
16
(0x10)
NV
Set/Get
UINT
Stop Ramp
Time
100
(0x64)
NV
Set/Get
UINT
Pump Stop
Time
101
(0x0D)
NV
Set/Get
USINT Kickstart
Duration
102
(0x0E)
NV
Set/Get
USINT Kickstart
Starting
Torque
103
(0x65)
NV
Set/Get
USINT Ramp2
Soft Start
Method
104
(0x66)
NV
Set/Get
UINT
105
(0x67)
NV
Set/Get
106
(0x68)
NV
Set/Get
BOOL
107
(0x69)
NV
Set/Get
USINT Ramp2
Kickstart
Duration
108
(0x6A)
NV
Set/Get
USINT Ramp2
Kickstart
Starting
Torque
109
(0x6B)
NV
Set/Get
UINT
Ramp2 Stop
Ramp Time
110
(0x6C)
NV
Set/Get
UINT
111
(0x6D)
Get
INT
Power Pole
Temperature
112
(0x6E)
Get
INT
Power Pole
Temperature
113
(0x6F)
Get
INT
Power Pole
Temperature
Start Ramp
Time
Ramp2 Start
Ramp Time
Ramp2
Expected
Phase
Sequence
45
NV
Access
114
(0x70)
NV
Set/Get
Data
Type
Name
Description
USINT Temperature
Sensor Trip
Enable
115
(0x71)
NV
Set/Get
116
(0x72)
NV
Set/Get
46
Attrib NV
Access
1
(0x01)
Get
USINT Motor
status
Name
Description
2
(0x02)
Get
USINT S811
input
status
3
(0x03)
Get
USINT S811
output
status
4
(0x04)
Get
UINT
Active
Fault #1
5
(0x05)
Get
UINT
Active
Fault #2
6
(0x06)
Get
UINT
Active
Fault #3
7
(0x07)
Get
UINT
Bit field
(faults)
Table 86. Class 140 (0x8C): Device Status Object Object (Cont.)
Attrib NV
Access
Data
Type
8
(0x08)
Get
UINT
Name
Description
Bit field
(warnings)
9
(0x09)
Get
UINT
Most
recent
fault
10
(0x0A)
Get
UINT
next
most
recent
fault
11
(0x0B)
Get
UINT
next
most
recent
fault
next
most
recent
fault
Data
Type
Name
Description
1
(0x01)
Get
UINT
3Ph RMS
Mains
Voltage
2
(0x02)
Get
UINT
3Ph RMS
Mains
Voltage
3
(0x03)
Get
UINT
3Ph RMS
Mains
Voltage
4
(0x04)
Get
UINT
Line
Frequency
5
(0x05)
Get
USINT Incoming
Phase
Sequence
6
(0x06)
Get
UINT
DC Control
Voltage
7
(0x07)
NV Set/Get
UINT
8
(0x08)
NV Set/Get
USINT Under
Voltage Trip
Enable
9
(0x09)
NV Set/Get
USINT Under
Voltage Trip
Threshold
10
(0x0A)
NV Set/Get
UINT
13
(0x0D)
Get
UINT
next
most
recent
fault
11
(0x0B)
NV Set/Get
14
(0x0E)
Get
UINT
next
most
recent
fault
12
(0x0C)
NV Set/Get
USINT Over
Voltage Trip
Threshold
15
(0x0F)
Get
UINT
next
most
recent
fault
13
(0x0D)
NV Set/Get
UINT
Get
UINT
next
most
recent
fault
14
(0x0E)
NV Set/Get
16
(0x10)
USINT Voltage
Imbalance
Trip Level
15
(0x0F)
NV Set/Get
UINT
next
most
recent
fault
Voltage
Amount of time a voltage imbalance
Imbalance
condition must exist before a trip; 0.0 Trip Duration 60.0 (in 0.1secs)
16
(0x10)
NV Set/Get
UINT
Oldest
fault
Incoming
Line
Frequency
Rating
17
(0x11)
NV Set/Get
Clear
Fault
Queue
USINT Line
Frequency
Trip
18
(0x12)
NV Set/Get
USINT Frequency
Deviation
Trip
Threshold
19
(0x13)
NV Set/Get
UINT
20
(0x14)
NV Set/Get
USINT Phase
Phase reversal trip enable
Reversal Trip 0x00 - disable
Enable
0x01 - fault enable
0x02 - warning enable
18
(0x12)
19
(0x13)
Get
Get
Set/Get
UINT
12
(0x0C)
17
(0x11)
Get
UINT
UINT
BOOL
Under
Voltage Trip
Duration
Over Voltage Amount of time an over voltage condiTrip Duration tion must exist before a trip; 0.0 - 60.0
(in 0.1secs)
Voltage imbalance trip threshold
Frequency
Amount of time a frequency deviation
Trip Duration condition must exist before a trip; 0.0 60.0 (in 0.1secs)
47
NV
Access
Data
Type
Name
Description
Get
WORD
Device
Status
NV
Set/Get
UDINT
Serial
Number
Get
SHORT_ Product
STRING Name
Get
USINT
176
NV
Set/Get
Object
# of
Instances
0x01
(hex)
Identity
0x02
Message
Router
0x04
Assembly
Object
0x06
Connection
Manager
0x08
Discrete
Input Point
0x09
Discrete
2
Output Point
0xF5
TCP/IP
Interface
0xF6
Ethernet
Link
Description
Object Details
Class 1 (0x01): Identity Object
Instance Count: 1
Instance List: 1
Device
State
NV
Access
Data
Type
Name
Description
Get
UINT
CIP
Vendor
ID
Get
UINT
CIP
Device
Type
Get
UINT
Product
Code
Get
UINT
NV
Access
Set/Get
Data
Type
Array of
BYTE
Name
Description
Data
48
Type
Instance
Usage
Name
Input
Poll
Field Inputs
Output
32
Poll
Input
107
Poll
4In/2Out Assembly
Instance Count: 2
Instance List: 1, 2
Byte
Offset
Word
Offset
Size
(bytes)
Name
Description
Field
Inputs
NV
Access
Data
Type
Name
Description
Set/Get
BOOL
Field
Relay
Outputs
NV
Set/Get
BOOL
Field
Relay
Fault
Action
Word
Offset
Size
(bytes)
Name
Description
NV
Set/Get
BOOL
Field
Relay
Outputs
Field
Relay
Fault
State
NV
Set/Get
BOOL
Field
Relay
Idle
Action
NV
Set/Get
BOOL
Field
Relay
Idle
State
Word
Offset
Size
(bytes)
Name
Description
4In/2Out
Assembly
Access
Data
Type
Name
Description
Get
BOOL
Input
0 = Off
1 = On
Set/Get
UDINT
Field
Inputs
Debounce
101
NV
49
Read/
Register Write Name
Field Inputs
Description (Units)
Control
Voltage
The supported function codes and register maps are identical for
both the Ethernet Modbus TCP and serial Modbus RTU protocols.
Ambient
Temperature
R/W
Max Board
Temperature
65
Dip Switch
Value
R/W
Serial
Number
11
R/W
Hardware
Rev
1601
101
R/W
Field Relay
Outputs
102
R/W
Field Inputs
Debounce
110
R/W
Modbus TCP
Com Timeout
1761
111
R/W
Field Relay
Fault Action
Commands
Supported
VendorName
ProductCode
MajorMinorRefision
VendorURL
ProductName
ModelName
UserApplicationName
112
R/W
Field Relay
Fault State
1793
113
R/W
Field Relay
Idle Action
1809
50
114
R/W
Field Relay
Idle State
Start
Coil
Read/
Register Write Name
Start
Coil
Read/
Register Write Name
143
4049
254
R/W
Motor Ctrl
Com Loss
Action Val
300
Current I1
301
Current I2
302
Current I3
303
Current
Average
304
305
306
307
Voltage
Average
308
Motor Power
Motor Power
x0.1kW when external CTs are used
x0.01kW otherwise ( scale )
309
Voltage
Unbalance
Percentage
310
Current
Unbalance
Percentage
311
Apparent
Power Factor
312
Residual
Ground
Current
313
Line frequency
314
Thermal Pile
Percentage
Thermal Capacity
0% Cold Motor
100% Will Cause and Overload Trip ( % )
315
Fault Queue
325
Remaining
Supply Fault - Time to Restart ( sec )
Rapid Cycling
Restart Delay
326
Remaining
Motor Fault - Time to Restart ( sec )
Normal
Restart Delay
327
Remainng
Underload
Trip Restart
Delay
328
R/W
Run Time
Hours
144
Method of IP
Allocation
Present
Ethernet IP
Address
Description (Units)
The Method Used to Allocate an IP
Address:
0 - DHCP
1 - Upper three octets from NV and lower
octet selected by the dip switch setting.
2 - Full address taken from NV Memory.
3 - Restore (hardcoded 192.168.1.254).
The active IP address being used on the
network.
146
Present
The active subnet mask IP address being
Ethernet
used on the network.
Subnet Mask
148
Present
Ethernet
Default
Gateway
150
R/W
Stored
Ethernet IP
Address
152
R/W
Stored
The IP subnet mask used in the NV
Ethernet
address select configuration.
Subnet Mask
154
R/W
Stored
Ethernet
Default
Gateway
156
R/W
Ethernet
MAC Address
159
R/W
160
R/W
Modbus TX
mode
161
R/W
162
R/W
Modbus
Address
163
R/W
Modbus
Parity and
Stop Bits
3201
201
Intercom
Status
4001
251
R/W
Motor Ctrl
Idle Loss Act
Disable
4017
252
R/W
Motor Ctrl
Com Idle
Action Val
4033
253
R/W
Motor Ctrl
When this value is TRUE the motor state
Com Loss Act will be unchanged after a communication
Disable
loss event. A FALSE value will cause the
Motor Control Communication Loss Value
to be applied on a com loss.
Description (Units)
51
Start
Coil
Read/
Register Write Name
Description (Units)
Start
Coil
Read/
Register Write Name
329
Start Count
402
R/W
330
Trip Reason
403
R/W
CT Multiplier
404
R/W
Ground Fault
Pick-up Level
405
R/W
Under
Current Pickup Level
406
R/W
Low Power
Pick-up Level
331
332
Description (Units)
Overload
Status
Overload Status
- 0x0001: Overload Trip
- 0x0002: Ground Fault Trip
- 0x0004: High Power Trip
- 0x0080: Relay Closed
407
R/W
408
R/W
Current
Unbalance
Pick-up Level
Error Code
Warning/Alarm Indications
0x0001 (1) - Low Voltage Warning
0x0002 (2) - High Voltage Warning
0x0004 (4) - Voltage Unbalance Warning
0x0008 (8) - Low Power Warning
0x0010 (16) - Reverse Phase Warning
0x0020 (32) - Current Unbalance Warning
0x0040 (64) - Voltage Single Phase
Warning
0x0080 (128) - Current Single Phase
Warning
0x0100 (256) - GND Fault Warning
409
R/W
410
R/W
Under
Voltage Pickup Level
411
R/W
Over Voltage
Pick-up Level
412
R/W
Voltage
Unbalance
Pick-up Level
333
C441 DSP
FW Version
413
R/W
Jam Pick-up
Level
334
UI Firmware
Version
414
R/W
335
R/W
C441 Unit ID
Unit ID
0x00BA (186) - C441BA
0x00BB (187) - C441BB
0x00CA (202) - C441CA
0x00CB (203) - C441CB
0x00DA (218) - C441DA
0x00DB (219) - C441DB
0x00EA (234) - C4410109(x)
0x00EB (235) - C4410590(x)
415
R/W
Phase Order
416
R/W
417
R/W
Motor Fault
Motor Fault Reset Delay ( min )
Hold-off Time
418
R/W
Load Fault
Load Fault Reset Delay ( min )
Hold-off Time
419
R/W
Load Fault
Number of
Restarts
420
R/W
Motor Fault
Number of
Restarts
421
R/W
Ground Fault
Trip Delay
422
R/W
Under
Current Trip
Delay
423
R/W
Low Power
Trip Delay
424
R/W
Jam Trip
Delay
425
R/W
Current
Unbalance
Trip Delay
426
R/W
Under
Voltage Trip
Delay
5361
52
336
400
401
R/W
R/W
Aux Relay
Trip Reason
Command
register
Motor
Control
Phase Order
- 0 (Trip Disabled)
- 1 ACB
- 2 ABC
Start
Coil
Read/
Register Write Name
Description (Units)
Start
Coil
Read/
Register Write Name
427
R/W
Over Voltage
Trip Delay
7105
445
R/W
428
R/W
Voltage
Unbalance
Trip Delay
429
R/W
430
R/W
Current
Phase Loss
Trip Delay
433
R/W
Enable/
Disable Trip
Aux Relay
Only Available for 120 V Control Power
Config Byte 2 Models. Each bit of this configuration
parameter enables (value 1) or disables
(value 0) a fault for the auxiliary relay. The
meanings of the bits are:
0x01: Low Power
0x02: High Power
0x04: Over Voltage
0x08: Under Voltage
0x10: Phase Order
0x20: Overload
0x40: Supply Frequency Fault
446
R/W
Aux Reset
Delay
1000
R/W
Modbus
Production
List
2000
Modbus
Production
Data
3000
R/W
Modbus
Consumption
List
4000
R/W
Modbus
Consumption
Data
434
R/W
Overload
Reset
435
R/W
Voltage
Faults Trip
Mode
436
R/W
Ground Fault
Trip Mode
437
R/W
Run
Transition
Percent
438
R/W
Run
Transition
Time
439
Network
Status
Network Status
0x0001: Watchdog Enabled
0x0004: Front Panel Locked
440
R/W
C441 Comm
loss Timeout
441
R/W
443
R/W
Load Fault
Reset Delay
Calc
7089
444
R/W
Aux Relay
Only Available for 120 V Control Power
Config Byte 1 Models.
Each bit of this configuration parameter
enables (value 1) or disables (value 0) a
fault for the auxiliary relay.
The meanings of the bits are:
0x01: Ground Fault
0x02: Voltage Unbalance
0x04: Current Unbalance
0x08: Under Current
0x10: Phase Loss
0x20: Jam
Description (Units)
53
Read/
Register Write
Name
Description (Units)
143
Method of IP
Allocation
144
Ambient
Temperature
Present
Ethernet IP
Address
146
R/W
Max Board
Temperature
Present
Ethernet
Subnet Mask
Dip Switch
Value
148
Configuration
CRC
Present
Ethernet
Default
Gateway
150
R/W
R/W
Stored
Ethernet IP
Address
Firmware Rev
152
R/W
11
R/W
Stored
Ethernet
Subnet Mask
1601
101
R/W
Field Relay
Outputs
154
R/W
Stored
Ethernet
Default
Gateway
102
R/W
Field Inputs
Debounce
156
R/W
3201
201
Intercom
Status
Start
Coil
Read/
Register Write
Name
Description (Units)
Field Inputs
Control
Voltage
65
110
R/W
Modbus TCP
Com Timeout
1761
111
R/W
Field Relay
Fault Action
4001
251
R/W
Motor Ctrl
Idle Loss Act
Disable
4017
252
R/W
Motor Ctrl
Com Idle
Action Val
4033
253
R/W
Motor Ctrl
Com Loss Act
Disable
4049
254
R/W
Motor Ctrl
Com Loss
Action Val
300
Motor Ctrl
State
301
302
303
304
305
Thermal
Memory
Percentage
1777
1793
112
113
R/W
R/W
Field Relay
Fault State
Field Relay
Idle Action
1809
54
114
R/W
Field Relay
Idle State
Start
Coil
Read/
Register Write
Start
Coil
Read/
Register Write
306
402
428
Firmware
Revision
429
Firmware
Build
430
Firmware
Checksum
1000
R/W
Modbus
Production
List
2000
Modbus
Production
Data
3000
R/W
Modbus
Consumption
List
4000
R/W
Modbus
Consumption
Data
Name
Description (Units)
307
Current as
Percentage
of FLA
308
Phase
Imbalance
Percent
309
Ground Fault
Percent
310
311
Scaled FLA
Setting
The present FLA setting. The potentiometer selects this value. The value is
scaled by the multiplier. ( Amps )
312
Overload
Class
313
314
315
Device
Temperature
332
R/W
Trip/Reset
Control
396
Scaled Min
FLA
397
Scaled Max
FLA
398
Current Scale
Value
399
Product Code
400
Name
Description (Units)
55
Start
Coil
Register
Read/
Write Name
143
Method of IP
Allocation
144
Present
Ethernet IP
Address
146
Present
The active subnet mask IP address being
Ethernet Subnet used on the network.
Mask
148
Present
Ethernet
Default
Gateway
150
R/W
Firmware Rev
Hardware Rev
152
R/W
Field Relay
Outputs
154
R/W
156
R/W
Ethernet MAC
Address
159
R/W
Modbus Com
Timeout
160
R/W
Modbus TX
mode
161
R/W
Modbus Baud
Rate
162
R/W
Modbus
Address
163
R/W
Modbus Parity
and Stop Bits
3201
201
4001
251
R/W
Motor Ctrl
Idle Loss Act
Disable
4017
252
R/W
Motor Ctrl Com Action to execute when a communicaIdle Action Val tion loss event occurs.
0 = Ignore (No Change)
1 = Stop
4033
253
R/W
Motor Ctrl
Com Loss Act
Disable
Start
Coil
Register
Read/
Write Name
Field Inputs
Ambient
Temperature
R/W
Max Board
Temperature
65
Dip Switch
Value
Configuration
CRC
R/W
Serial Number
11
R/W
1601
101
R/W
Description (Units)
102
R/W
Field Inputs
Debounce
110
R/W
Modbus TCP
Com Timeout
1761
111
R/W
Field Relay
Fault Action
1777
1793
112
113
R/W
R/W
Table 98. Register Definition for the S611 Soft Starter (Cont.)
Field Relay
Fault State
1809
56
114
R/W
Description (Units)
Table 98. Register Definition for the S611 Soft Starter (Cont.)
Table 98. Register Definition for the S611 Soft Starter (Cont.)
Start
Coil
Start
Coil
Register
Read/
Write Name
324
Trip Reason
Bit = Description
0 = Overload
1 = Jam
2 = Stall
3 = Current Imbalance
4 = Load Disconnect
5 = Phase Loss
6 = Mains Fault
7 = Phase Reversal
8 = Shorted SCR
9 = SCR Not Firing
10 = Pole Overtemp
11 = Bypass Dropout
12 = SCR Overcurrent
13 = Contactor Overcurrent
14 = Communication Fault
15 = Other Device Fault
325
Fault Code
Register
Read/
Write Name
Description (Units)
Description (Units)
4049
254
R/W
Motor Ctrl Com Action to execute when a communicaLoss Action Val tion loss event occurs.
0 = Ignore (No Change)
1 = Stop
300
Motor Status
301
Current Scale
Factor
302
Phase A RMS
Current
303
Phase B RMS
Current
304
Phase C RMS
Current
305
Average
Current
306
Vab RMS
Voltage
307
Vbc RMS
Voltage
335
308
Vca RMS
Voltage
336
309
Average
Voltage
337
310
Total Kilowatts
Orion UI
Firmware
338
Unit ID
399
R/W
Modbus
Change Tracker
Queue
400
R/W
Motor Control
401
R/W
Start Input
Behavior
402
R/W
Command
Register
311
Apparent
Power Factor
312
Power Sign
313
Line Frequency
314
Overload
Thermal
Memory
Thermal Capacity
0% Cold Motor
100% Will Cause an Overload Trip ( % )
315
Current
Unbalance
316
Voltage
Unbalance
317
Residual
Ground Fault
Current
318
Phase A Pole
Temp
319
Phase B Pole
Temp
403
R/W
Configuration
Reset
1 = Soft Reset
2 = Factory Defaults
320
Phase C Pole
Temp
404
R/W
Scaled
Overload FLA
321
Pole Temp
405
R/W
Rated Voltage
406
R/W
Start Method
407
R/W
Start Time
322
Number of
Starts
323
57
Table 98. Register Definition for the S611 Soft Starter (Cont.)
Table 98. Register Definition for the S611 Soft Starter (Cont.)
Start
Coil
Register
Read/
Write Name
Description (Units)
Start
Coil
Register
Read/
Write Name
408
R/W
Initial Motor
Torque
430
R/W
Under Voltage
Trip Delay
409
R/W
Stop Time
431
R/W
Over Voltage
Level
432
R/W
Over Voltage
Trip Delay
Description (Units)
410
R/W
Pump Stop
Time
433
R/W
411
R/W
Voltage
Unbalance Trip
Level
434
R/W
412
R/W
Kick Start Initial Initial Torque Value for the Kick Start.
Torque
(%)
Voltage
Unbalance Trip
Delay
413
R/W
Reset Mode
Method of Reset.
0 = Manual
1 = Auto
435
R/W
Phase
Sequence
414
R/W
Fault Enable
Bits
436
R/W
Fault Relay
Config
437
R/W
Auxiliary Relay
Configuration
438
R/W
UI Edit Lock
439
R/W
User Interface
Display Config
443
R/W
444
R/W
Communication 1 = Fault
Loss Behavior
2 = Hold last state
3 = Stop (1)
445
R/W
Network
Timeout
1000
R/W
Modbus
Production List
2000
Modbus
Production Data
415
R/W
Overload Class
416
R/W
417
R/W
418
R/W
419
R/W
Residual GF
Trip Level
420
R/W
Residual GF
Trip Delay
421
R/W
Residual GF
Start Delay
422
R/W
Current
Unbalance Trip
Level
423
R/W
Current
Unbalance Trip
Delay
424
R/W
Load
Disconnect Trip
Level
425
R/W
Load
Disconnect Trip
Delay
426
R/W
Load
Disconnect
Source
427
R/W
428
R/W
Phase Loss Trip Trip Delay applied to the Phase Loss Trip
Delay
Sense. ( seconds )
429
R/W
Under Voltage
Level
58
Table 98. Register Definition for the S611 Soft Starter (Cont.)
Start
Coil
Register
Read/
Write Name
3000
R/W
4000
R/W
Modbus
Consumption
List
Modbus
Consumption
Data
Description (Units)
Read/
Register Write
Name
Description (Units)
Field Inputs
Control
Voltage
Ambient
Temperature
R/W
Max Board
Temperature
65
Dip Switch
Value
Configuration
CRC
R/W
Firmware Rev
11
R/W
1601
101
R/W
Field Relay
Outputs
102
R/W
Field Inputs
Debounce
110
R/W
Modbus TCP
Com Timeout
1761
111
R/W
Field Relay
Fault Action
112
R/W
Field Relay
Fault State
59
Read/
Register Write
1793
113
R/W
Name
Description (Units)
Field Relay
Idle Action
1809
114
R/W
Field Relay
Idle State
130
Eth Port 1
Speed Actual
2097
132
Eth Port 1
Full Duplex
Enabled
134
Eth Port 1
Active state of the Auto-Negotiation
Autonegotiate behavior.
State
Value = State
0 = Link Inactive
1 = Auto Negotiation in Progress
2 = Auto Negotiation Failed (Defafult
used)
3 = Auto Negotiation of Duplex Failed
(speed ok)
4 = Auto Negotiation Success
5 = Auto Negotiation Disabled
6 = Port Disabled
2145
135
Eth Port 1
Enabled
137
Eth Port 2
Speed Actual
2209
139
Eth Port 2
Full Duplex
Enabled
141
Eth Port 2
Active state of the Auto-Negotiation
Autonegotiate behavior.
State
Value = State
0 = Link Inactive
1 = Auto Negotiation in Progress
2 = Auto Negotiation Failed (Defafult
used)
3 = Auto Negotiation of Duplex Failed
(speed ok)
4 = Auto Negotiation Success
5 = Auto Negotiation Disabled
6 = Port Disabled
2257
60
142
143
Eth Port 2
Enabled
Method of IP
Allocation
Read/
Register Write Name
144
Present
Ethernet IP
Address
146
Present
Ethernet
Subnet Mask
148
Present
Ethernet
Default
Gateway
150
R/W
Stored
Ethernet IP
Address
152
R/W
Stored
Ethernet
Subnet Mask
154
R/W
Stored
Ethernet
Default
Gateway
156
R/W
Ethernet MAC
Address
159
R/W
Modbus Com
Timeout
160
R/W
Modbus TX
mode
161
R/W
Modbus Baud
Rate
162
R/W
Modbus
Address
163
R/W
Modbus Parity
and Stop Bits
3201
201
Intercom
Status
4033
253
R/W
Motor Ctrl
Com Idle Act
Disable
4049
254
R/W
Motor Ctrl
Com Idle
Action Val
300
Motor Control
Status
Description (Units)
Start
Coil
Register
Read/
Write Name
Description (Units)
Start
Coil
Register
Read/
Write Name
301
Active Fault
List
315
S811 Discrete
Input Status
304
Motor Control
Faults
305
Motor Control
Warnings
316
S811 Discrete
Output Status
317
Network
Outputs
318
Fault Queue
328
3Ph Average
Line Current
330
336
337
340
341
344
3Ph Average
Pole Current
306
307
% Thermal
Pile used
308
3Ph RMS
3 Phase RMS Mains voltage reading
Mains Voltage (in volts)
311
Total Motor
Starts
313
Analog Input
Value (% of
range)
314
Analog Input
Status
Description (Units)
61
Start
Coil
Register
Read/
Write Name
Start
Coil
Register
Read/
Write Name
346
501
R/W
Modbus Two
Wire Motor
Control
352
353
502
R/W
Network
Inputs
503
R/W
MODBUS
Baud Rate
504
MODBUS
Node Address
505
R/W
MODBUS
Parity
Modbus Parity
0: even (1 stop bit)
1: odd (1 stop bit)
2: no parity (2 stop bits)
Modbus parity is only updated on
power up
506
R/W
507
R/W
MODBUS
Mode (RTU /
ASCII)
600
R/W
Motor
Nameplate
FLA (float)
602
R/W
Motor
Nameplate
FLA in 0.1A
603
R/W
Overload Trip
Class
604
R/W
Motor Rated
Volts
605
R/W
Incoming Line
Frequency
Rating
9681
606
R/W
Motor Wiring
Cfg
607
R/W
Expected
Incoming
Phase
Sequence
608
R/W
Motor Start
Method
609
R/W
356
Description (Units)
357
360
Power Factor
361
362
Power Pole
Temperature
365
DC Control
Voltage
366
Device
Temperature
367
Auto Reset
Count
368
369
Incoming
Phase
Sequence
370
Fault List
380
Application
status
6081
381
Run1 Input
Level Sense
Enable
62
500
R/W
Description (Units)
Start
Coil
Register
Read/
Write Name
Description (Units)
Start
Coil
Register
Read/
Write Name
610
R/W
Start Ramp
Time
633
R/W
Discrete
Output Cfg
611
R/W
Stop Ramp
Time
612
R/W
Pump Stop
Time
613
R/W
Kickstart
Starting
Torque
614
R/W
Kickstart
Duration
615
R/W
Ramp2
Expected
Phase
Sequence
637
R/W
Custom Fault
Output Cfg
616
R/W
Ramp2 Motor
Start Method
640
R/W
Fault Reset
Mode
641
R/W
Auto Reset
Delay Time
642
R/W
Auto Reset
Attempt Limit
643
R/W
Overload Trip
Enable
10289
644
R/W
Enable
Overload
During Start
645
R/W
Phase
Reversal Trip
Enable
646
R/W
Undercurrent
Trip Enable
647
R/W
Undercurrent
Trip Level (%
FLA)
Low load current trip threshold in percent of the motor nameplate fla setting
648
R/W
Undercurrent
Trip Duration
649
R/W
Motor Jam
Trip Enable
650
R/W
Motor Stall
Trip Enable
651
R/W
Phase Loss
Trip Enable
652
R/W
Motor Phase
Current phase loss trip threshold
Loss Trip Level
653
R/W
Motor Phase
Loss Duration
617
R/W
Ramp2 Initial
Starting
Torque
618
R/W
Ramp2 Start
Ramp Time
619
R/W
Ramp2 Stop
Ramp Time
620
R/W
Ramp2 Pump
Stop Time
621
R/W
Ramp2
Kickstart
Starting
Torque
622
R/W
Ramp2
Kickstart
Duration
9953
623
R/W
Local Control
Only Enable
624
632
R/W
R/W
Discrete Input
Cfg
Analog Input
Data Range
Description (Units)
63
Start
Coil
Register
Read/
Write Name
Start
Coil
Register
Read/
Write Name
654
R/W
Phase
Current phase imbalance trip enable
Imbalance Trip 0x00 - disable
Enable
0x01 - fault enable
0x02 - warning enable
674
R/W
Analog Input
Trip High
Threshold
High analog input trip threshold (in percent of selected analog range)
655
R/W
Motor Phase
Current imbalance trip threshold
Imbalance Trip
Level
675
R/W
Analog Input
Trip Duration
656
R/W
Motor Phase
Amount of time a current imbalance
Imbalance Trip condition must exist before a trip; 0.0 Duration
60.0 (in 0.1secs)
676
R/W
Temperature
Sensor Trip
Enable
657
R/W
Voltage
Voltage imbalance trip threshold
Imbalance Trip
Level
677
R/W
658
R/W
Voltage
Amount of time a voltage imbalance
Imbalance Trip condition must exist before a trip; 0.0 Duration
60.0 (in 0.1secs)
678
R/W
SCR Shorted
Trip Enable
659
R/W
Under Voltage
Trip Enable
10849
679
R/W
Alarm - No
Trip Enabled
Description (Units)
Description (Units)
660
R/W
Under Voltage
Trip Threshold
661
R/W
Under Voltage
Trip Duration
Amount of time an under voltage condition must exist before a trip; 0.0 - 60.0
(in 0.1secs)
10865
680
R/W
Over Voltage
Trip Enable
Start Delay
Active
Warning
Enable
Enables warning when start delay timers are used. Warning is issued while
start command is pending
681
R/W
Start Delay
After Power
up
682
R/W
Start Delay
683
R/W
Start Delay
After Run
Change
User settable time delay between successive start profiles. Delay becomes
active when start profile(ramp vs ramp2)
changes between starts
684
R/W
Motor Comm
Loss Action
685
R/W
Transient
Motor Control
Timeout
686
R/W
Motor Control
Command
Timeout
10977
687
R/W
Network two
wire control
enable
688
R/W
GND Fault
Enable
689
R/W
GND Fault
Inhibit From
Start Delay
662
R/W
663
R/W
Over Voltage
Trip Threshold
664
R/W
Over Voltage
Trip Duration
Amount of time an over voltage condition must exist before a trip; 0.0 - 60.0
(in 0.1secs)
665
R/W
666
R/W
Frequency
Deviation Trip
Threshold
667
R/W
668
R/W
Ave Power
Trip Enable
669
R/W
Ave Power
Low Trip
Threshold
670
R/W
Ave Power
High Trip
Threshold
671
R/W
Ave Power
Trip Duration
672
R/W
Analog Input
Trip Enable
673
R/W
Analog Input
Trip Low
Threshold
Low analog input trip threshold (in percent of selected analog range)
64
Start
Coil
Register
Read/
Write Name
Description (Units)
Start
Coil
Register
Read/
Write
Name
Description (Units)
690
Firmware
Version List
Field Inputs
692
Hardware
Version
Hardware version
800
R/W
Modbus
Device Reset
Register
Control
Voltage
Ambient
Temperature
R/W
Max Board
Temperature
65
Dip Switch
Value
R/W
Serial
Number
11
R/W
Hardware
Rev
1601
101
R/W
Field Relay
Outputs
102
R/W
Field Inputs
Debounce
110
R/W
Modbus TCP
Com Timeout
1761
111
R/W
Field Relay
Fault Action
900
1000
R/W
R/W
Modbus User
Application
Name
Modbus
The Production and consumption
Production List Registers can be used to create custom
Modbus interface ranges. An example:
If field inputs register address 0 is
put into the first slot of the production list, the field inputs register value
will be available in the first slot of
the Modbus Production Data Register
range. Production data is data provided
by the device and Consumption data is
for data provided (written) to the device.
Note that the values must be Modbus
Register Address (i.e., Register Number
- 1) not Register Number
Web setting examples (comma separated values):
1,2 sets the first two slots as 1 and 2,
and leaves all the rest unchanged;
, , 3 sets the third slot as 3 and leaves
all the rest unchanged
2000
Modbus
Production
Data
3000
R/W
Modbus
Consumption
List
4000
R/W
Modbus
Consumption
Data
112
R/W
Field Relay
Fault State
1793
113
R/W
Field Relay
Idle Action
114
R/W
Field Relay
Idle State
65
Register
Read/
Write
Name
Description (Units)
143
Method of IP
Allocation
144
Present
Ethernet IP
Address
146
Present
The active subnet mask IP address being
Ethernet
used on the network.
Subnet Mask
148
Present
Ethernet
Default
Gateway
150
R/W
Stored
Ethernet IP
Address
152
R/W
Stored
The IP subnet mask used in the NV
Ethernet
address select configuration.
Subnet Mask
154
R/W
Stored
Ethernet
Default
Gateway
156
R/W
Ethernet
MAC Address
1000
R/W
Modbus
Production
List
2000
Modbus
Production
Data
3000
R/W
Modbus
Consumption
List
4000
R/W
Modbus
Consumption
Data
66
Notes:
67
Licenses
This product includes embedded software that incorporates or interfaces with the following third party software:
---------------------------------------------------------------lwIP is licensed under the BSD license:
Copyright (c) 2001-2004 Swedish Institute of Computer Science.
All rights reserved.
Redistribution and use in source and binary forms, with or without modification, are permitted provided that the following conditions are
met:
1. Redistributions of source code must retain the above copyright notice, this list of conditions and the following disclaimer.
2. Redistributions in binary form must reproduce the above copyright notice, this list of conditions and the following disclaimer in the documentation and/or other materials provided with the distribution.
3. The name of the author may not be used to endorse or promote products derived from this software without specific prior written permission.
THIS SOFTWARE IS PROVIDED BY THE COPYRIGHT HOLDER ``AS IS'' AND ANY EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO,
THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE AUTHOR
BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO,
PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON
ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT
OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
--------------------------------------------------------------www.FreeRTOS.org
Eaton Corporation
Electrical Sector
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
Eaton.com
2012 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. MN04200002E / TBG000757
August 2012