Powe and Energy Lab Manual - M.tech (PEES) - II Sem Lab
Powe and Energy Lab Manual - M.tech (PEES) - II Sem Lab
DEPARTMENT OF
ELECTRICAL AND ELECTRONICS ENGINEERING
PREFACE
The significance of the Power & Energy System Lab is renowned in the various fields
of engineering applications. For an Electrical Engineer, it is obligatory to have the practical
ideas about the Power systems. By this perspective we have introduced a Laboratory manual
cum Observation for Power & Energy System Lab.
The manual uses the plan, cogent and simple language to explain the fundamental
aspects of Power & Energy System Lab in practical. The manual prepared very carefully
with our level best. It gives all the steps in executing an experiment.
ACKNOWLEDGEMENT
It is one of lifes simple pleasures to say thank you for all the help that one has
extended their support. I wish to acknowledge and appreciate Associate Professor Mr.Saleem
Pasha, Assistant Professors Mr.N.Ramchander, Mr.G.Naresh Kumar, and Lab Technician
K. Srinivas Raju, P. Prabhu Dass, Foremen for their sincere efforts made towards developing
the Power & Energy System Lab. I wish to thank students for their suggestions which are
considered while preparing the lab manual.
Dr. N. BHOOPAL
HOD - EEE
DOS:1. Proper dress has to be maintained while entering in the Lab. (Boys Tuck in and shoes, girls
with apron)
2. All students should come to the Lab with necessary tools.
3. Students should carry observation notes and record completed in all aspects.
4. Correct specifications of the equipment have to be mentioned in the circuit diagram.
5. Student should be aware of operating equipment.
6. Students should be at their concerned experiment table, unnecessary moment is restricted.
7. Student should follow the indent procedure to receive and deposit the equipment from the
Lab Store Room.
8. After completing the connections Students should verify the circuits by the Lab Instructor.
9. The reading must be shown to the Lecturer In-Charge for verification.
10. Students must ensure that all switches are in the OFF position, all the connections are
removed.
11. All patch cords and stools should be placed at their original positions.
DONTs:-
AIM: To measure the load and power factor for the electrical utilities.
APPARATUS:
S.NO Name of the equipment
Wattmeter
Rheostats
Connecting wires
4
5
6
CIRCUIT DIAGRAM:
Range
Type
Qty
Theory:
Power factor is the percentage of electricity that is being used to do useful work. It is defined
as the ratio of active or actual power used in the circuit measured in watts or kilowatts (W
or KW), to the apparent power expressed in volt-amperes or kilo volt-amperes (VA or
KVA).
The apparent power also referred to as total power delivered by utility company has two
components. 1) Productive Power that powers the equipment and performs the useful work.
It is measured in KW (kilowatts) 2) Reactive Power that generates magnetic fields to
produce flux necessary for the operation of induction devices (AC motors, transformer,
inductive furnaces, ovens etc.). It is measured in KVAR (kilovolt-Ampere-Reactance).
Reactive Power produces no productive work. An inductive motor with power applied and no
load on its shaft should draw almost nil productive power, since no output work is being
accomplished until a load is applied. The current associated with no-load motor readings is
almost entirely "Reactive" Power. As a load is applied to the shaft of the motor, the
"Reactive" Power requirement will change only a small amount.
The Productive Power is the power that is transferred from electrical energy to some other
form of energy (i.e. such as heat energy or mechanical energy). The apparent power is always
in always in excess of the productive power for inductive loads and is dependent on the type
of machine in use. The working power (KW) and reactive power (KVAR) together make up
apparent power, which is measured in kilovolt-amperes (KVA).
The cosine of the phase angle between the KVA and the KW components represents the
power factor of the load. KVAR represents the non-productive reactive power and is
lagging phase angle.
The Relationship between KVA, KW and KVAR is non-linear and is expressed
KVA2 = KW2 + KVAR2 .
A power factor of 0.72 would mean that only 72% of your power is being used to do useful
work. Perfect power factor is 1.0, (unity); meaning 100% of the power is being used for
useful work.
FORMULAE:
PF = cos
where
PF = power factor
= phase angle between voltage and current
Procedure:
1) Connect the circuit as shown in the figure.
2) Ammeter is connected in series with wattmeter whose other end is connected to one of
the loads of the balanced loads.
3) The Y-phase is directly connected to one of the nodes of the 3-ph supply.
4) A wattmeter is connected across R-phase & Y-phase as shown in fig. The extreme of
Bphase
is connected to the third terminal of the balanced 3-ph load.
5) Another wattmeter is connected across Y & B phase; the extreme of B-phase is connected
to the third terminal of the balanced three phases load.
6) Verify the connections before switching on the 3-ph power supply.
7) Calculate the power factor by the give formulae at different loads as mentioned.
TABULAR FORM:
Power =
S.NO
SPEED(rpm)
Load
Hp.
Load
1 hp = 745.7 W.
PRECAUTIONS:
1. Avoid making loose connections.
2. Readings should be taken carefully without parallax error.
RESULT: The load and power factor for the electrical utilities is calculated.
Full Load
Solar cell,
Rheostat,
Ammeter,
Voltmeter,
Illumination source,
Variac and
Connecting wires.
THEORY:
A solar cell is illuminated by light having photon energy greater than the band gap energy of
the solar cell. Then, using a proper circuit, the open circuit voltage, short circuit current and
power drawn from the solar cell are measured.
I. Introduction
1. Solar cell is basically a two terminal p-n junction device designed to absorb photon
absorption through the electrical signal or power in the external circuits. Therefore it is
necessary to discuss the physics of semiconductor p-n junction diode, which converts
the optical energy into electrical signals.
2 It is well known that doped semiconductors are of two types, p and n- types
semiconductors depending upon the nature of the charge carriers. In n-type
semiconductor the free carriers are electrons and in p-type semiconductor, the positive
charge carriers are holes. Since the semi conduct- ors are electrically neutral, in a doped
semiconductor the number of free carriers is equal to the lattice ions present in the
semiconductor. The nature of the semiconductor can be defined from the location of Fermi
energy level (EF) in the band structure of the semiconductor as shown in Fig.1. (The Fermi
energy level is defined as the highest filled energy level at 0 K). In p-type semiconductor the
Fermi level lies just above the valence band (EV) and in n-type semiconductor it lies just
below the conduction band (EC) as shown in Fig. 1. When these two types of
semiconductors come in contact, the free carriers flow in opposite direction and neutralize
each other. This process will continue until the Fermi energy levels of the two
semiconductors come to the same level as shown in Fig. 2.
The region surrounding the junction thus only contains the uncovered positive ions in n-side
and uncovered negative ions in p-side. This region is known as the depletion region (W)
and there are no free carriers available in this region (Figure 3a). In the depletion region, the
nature of Fermi energy level is most important from device point of view.
The variation of different parameters across the depletion region is also shown in Fig. 3(b-e).
p-type semiconductor
n-type semiconductor
Figure 1. Location of Fermi energy level in p and n type semiconductors.
Figure 2. Energy bend band diagram of p-n junction diode under no bias condition.
4. When a radiation of photon energy greater than the band gap energy of the
semiconductor falls up on the surface across the junction (i.e., region surrounding the
depletion region), it produces new electron hole (e-h) pairs. Since there exists a junction
potential difference as shown in Fig 3, the new carriers flow in opposite directions depending
on their nature of charge. Under this condition eq. (1) can be modified as follows:
Where, gop is the optical generation rate of e-h pairs per (cm3- sec) and V is the applied
reverse bias across the p-n junction diode. The second part of the equation is the current due
to optical genera-tion of e-h pairs (Iop).
Figure 3. Schematic diagram of p-n junction showing different parameters exist across the junction.
Following eq.(2), when the device is short circuited (V=0), there is a short circuit current
from p to n equal to Iop. The usual (i.e., under dark conditions) V-I characteristic for
diode is shown in Fig. 4 by the dashed line that passes through the origin (see eq. (1)).
Figure 4. V-I characteristic curves of a photo-diode under dark (------) and illuminated ( ___ ) conditions.
Under this condition the Fermi levels will again change the nature in depletion region.
From the difference of the Fermi levels in n and p-type semiconductors one can express the
open circuited voltage as shown in Fig . 5.
Figure 5. Illuminated I-V characteristics for solar cell for two different illuminations
5. When we need to use the photodiode as detector application, we usually operate it in the
3rd quadrant. If power is to be extracted from the device, the fourth quadrant is used. The
equivalent circuit for the purpose is shown in Fig. 6. in the experimental section. The
maximum power delivered through the load RL is when the series resistance RS is
equivalent to the value of RL as given in the procedure. Again to receive maximum power
from solar cell, it is designed with large surface area coated with appropriate materials to
reduce the reflection of the incident light and to reduce the recombination. Therefore in solar
cell device the junction depth from the surface must be less than the recombination length of
electron and holes from both sides, so that the optically generated carriers can reach the
depletion region before recombination with the majority carriers in the semiconductors. In
most of the cases the incident photons penetrate the n and p regions and are absorbed in the
depletion region.
CIRCUIT DIAGRAM:
PROCEDURE:
1. Complete the circuit as shown in circuit diagram (figure 6.)
2. Illuminate the solar cell. Adjust the rheostat position for resistance so that the volt meter
reads zero. This is the short circuit connection. Adjust the variac 119 (maximum
up to 230 V) such that ammeter reads a value of about 500 mA. Note down the value of
the current as short circuited current, Isc .
3.
Increase the resistance by varying the rheostat slowly and note down the readings of
current and voltage till a maximum voltage is read. Ensure to take at least 15 20
readings in this region.
4. Disconnect the rheostat and note down the voltage. This is the open circuit voltage,
Voc
5. Repeat the experiment for another intensity of the illumination source.
6. Tabulate all readings in Table 1. Calculate the power using the relation, P = V x
7. Plot I vs. V with Isc on the current axis at the zero volt position and Voc on the voltage
axis at the zero current (see Figure 5.)
8.
9. To see the performance of the cell calculate fill factor (FT) of the cell, which can be
expressed by the formula, FF = [ Pm/Isc Voc ].
RESULT:
VIVA QUESTIONS:
1. What is a semiconductor? What are p and n type semiconductors? Give one example of
each.
2. What are the advantages of using doped semiconductor rather than pure
semiconductors? Why are semiconductor diodes preferred to valve diodes?
3. What is the meaning of valence and conduction band in semiconductor? How is the Fermi
energy level in a semiconductor defined?
4. Why do the Fermi energy levels come to the same level when p and n-types of
semiconductors come in contact?
5. What is the depletion region? Assuming majority carrier concentration in n-type
semiconductor is higher than p-type, discuss about the width of the depletion region about the
physical contact layer.
6. What is the meaning of recombination, recombination length, and life time of carriers in
doped semiconductor?
7. What is reverse saturation current in p-n diode? If you increase the reverse bias voltage,
what will be the nature of the 3rd quadrant part of the dotted line in figure 4?
8. Give some practical uses of the solar cell
3. Lead-Acid Batteries
THEORY:
Methods of charging
Some of the methods of charging are constant-current method, constant-voltage method,
modified constant-voltage method, float charging method, and trickle charging method.
Constant-current charging method
In the constant-current method, a fixed current is applied for a certain time to the battery to
recharge it. The charging current is set to a low value to avoid the voltage across the battery
from exceeding the gassing voltage as the battery charge approaches 100%. Consequently,
this results in long charge times (usually 12 hours or longer). Figure below (A) shows the
charging characteristic curves obtained with the constant-current method (single step).
Multiple decreasing current steps can also be used to shorten charge times obtained using the
constant-current charging method as shown in Figure below (B) Though it is used for
charging some small lead-acid batteries, the constant current charging method is not widely
used for lead-acid batteries, because of the gassing which is likely to occur when charging a
battery too long. The risk of gassing is more important when charging a battery which is only
partially discharged.
Constant-current is also used in trickle charging, another charging method described later in
this discussion.
b
Constant-voltage charging method
In the constant-voltage charging method, a fixed-voltage is applied to the battery to recharge
it. The initial charging current (current at the beginning of the battery charge) is at its
maximum and can even reach higher values (even exceeding the maximum charge current
prescribed by the battery manufacturer) when the battery depth of discharge is high. For this
reason, purely constant-voltage charging is seldom used to charge lead-acid batteries that are
used in cyclic charge-discharge applications (e.g., battery in an electric vehicle). However,
constant-voltage charging is often used to maintain the charge of lead-acid batteries used in
standby applications (e.g., as in uninterruptable power supplies), in which case the charge
process is referred to as float charging (another charging method described later in this
discussion). Figure below shows
the charging characteristic curves obtained with the constant-voltage charging method. The
waveform difference between the charger output voltage and the battery cell voltage at the
beginning of the charge cycle is caused by the internal resistance of the battery.
CIRCUIT DIAGRAM:
PROCEDURE:
The Procedure is divided into the following sections:
RESULT:
PROCEDURE:
The performance of a solar cell is measured in terms of its efficiency at converting
sun light into electricity. Only sunlight of certain energy will work efficiently to create
electricity.
ADVANTAGES:
1. Absence of moving parts.
2. Modular in nature in which desire currents, voltage and power levels can be achieved by
more integration.
3. They consume no fuel to operate on solar energy
4. Maintenance cost is low.
5. Easy to operate
6. Solar cells can be used in combination with power conducting circuits to feed powerv into
utility grid.
APPLICATIONS:
1. Home lightening system
2. Traffic control system
3. Street lightening system
4. Battery charging
RESULT:
WORKING:
A solar photo voltaic water pumping system consist of photo voltaic array mounted on a
stand and one of the following motor pump sets compatible with the photo voltaic array. This
array converts the solar energy into electricity, which is used for running the motor pump set.
The pumping system draws water from the open well, bore well, streme, pond, cannel, etc.
The system components of solar photovoltaic water pumping systems are photo voltaic array,
motor pump, interface voltaic, connecting cables, switches and pipes etc.
The SPV water pumping system is used in agriculture, horticulture, animal husbandry,
poultry forming high valve crops, fish culture, salt farming, drinking water etc..
The water pumping systems are available in different types to meet various needs and
applications:
SURFACE PUMPS: These pumps are suitable for lifting and pumping water from a
maximum depth of 20 meters (total head)
SUBMERSIBLE PUMPS: These pumps can be used in areas where water is available at a
greater depth and where open wells are not available. The maximum recommended depth
these systems can pump is 50 meters
SOLAR HAND PUMP: These pumps are exclusively designed by Balaji Industrial and
agricultural casting to meet both the requirements of surface and submersible pumps. It has a
manual operation mode where the system can be used manually when sufficient sunshine is
not available to drive the pump.
WORKING: When the su ray falls on the solar collector, black body absorbs the sun rays
and water in the tubes get heated up and circulates to the heat exchanger. Through the heat
exchanger, hot water is again pumped back in the solar collector with the help of pump. The
organic fluid in the other tube senses the heat produced in the heat exchanger and converts
its phase into vapor. Ground water is pumped with the help of a pump, which is coupled
with the heat engine.
OBSERVATION TABLE:
Result:
CIRCUIT:
Square wave inverters were the original electronic inverter. The first versions use a
mechanical vibrator type switch to break up the low voltage DC into pulses. These pulses are
then applied to a transformer where they are stepped up. With the advent of semiconductor
switches the mechanical vibrator was replaced with solid state transistor switches.
Nowadays, the most common circuit topology, which is used to produce a square wave
output, referred to as push-pull. Square wave inverters run simple electric motors, but not
much else, and will require a lot of energy to do so. Also, this kind of inverters is low quality.
The price of better quality inverters is low enough to make the use of these unattractive.
Modified Square Wave Inverters
Modified square wave inverters (often referred to as modified sine wave inverters) use a
push-pull topology as well as square wave inverters, with the addition of a few extra parts in
their design. However, some modified square wave inverters use another one topology, which
is called H-Bridge. Their output has the shape of the waveform of the next page (see figure
2).
These inverters are a good choice for a 'whole home' inverter since their high surge capacity
lets them start motors whilst their high efficiency lets them run small appliances
economically. Most loads will run without trouble from a modified sine wave. It is suitable
for a variety of applications such as induction motors (i.e. refrigerators, drill presses);
resistive loads (i.e. heaters, toasters); universal motors (i.e. hand tools, vacuum cleaners) as
well as microwaves and computers. However, some appliances will not operate or will run
noticeably less well if not on a pure sine wave.
Problem loads: e.g. many laser printers, copiers, some computers, light dimmers and some
variable speed tools may not operate; some TV's and some audio equipment will pick up
interference or background buzz; some digital clocks may not keep time; microwave ovens
will have longer cooking times; and some small battery chargers may fail. Central heating
ignition systems can be problematic.
Sine Wave Inverters
A sine wave inverter puts out an AC equal to what you get from utility grid, a smooth sine
wave. A 'mains' quality pure sine wave output is necessary for some applications such as
running electronics or audio equipment. Two common tolopogies that are used to produce
sine wave output are push-pull and H-Bridge. True sine wave inverters can run all types of
load and are now available which are powerful, efficient and affordable! Their disadvantage
is their cost, which is higher than the cost of the other kinds of inverters.
B. GRID-CONNECTED INVERTERS
Grid-connected inverters are supply driven - they provide all the power supplied from a DC
source to the grid or mains. Therefore, in grid-connected systems, the solar inverter is the
connecting link between the solar generator and the AC grid, while the characteristics of the
inverter have a decisive influence on the performance of the grid connected photovoltaic
system.
Generally, grid-connected inverters operate at a higher DC voltage than stand alone inverters.
Grid-connected inverters should NOT be connected to batteries and stand-alone inverters
should NOT be connected directly to PV or the grid. Smaller systems with few appliances
may have only DC power, but recent advances in inverter design, efficiency, and reliability
have increased the potential of solar systems considerably.
With the use of modern high efficiency AC lighting the majority of, if not all, loads can be
operated on AC especially in larger installations. We can use both AC & DC where each is
most effective and economical - many DC appliances use less power than their AC
equivalents (especially refrigeration, lighting & electronics) - but DC appliances tend to be
harder to find and more expensive.
PROCEDURE FOR MEASURING EFFICIENCY:
EFFICIENCY MEASUREMENT CONDITIONS:
EFFICIENCY CALCULATIONS:
RESULT:
Pyrheliometer:
The receiver of the instrument consists of two thin strips of manganin, made as identical in
every way as possible. One strip is exposed to the sun radiation, while the other one is
screened from the sun. Through the screened strip an electric current is passed, the intensity
of which is regulated so that heating of the two strips is the same.
To secure this thermo junctions connected through a sensitive galvanometer are attached to
the central points at the back side of the two strips. A current through the screened strip is
adjusted, so that the galvanometer shows no deflection.
PROCEDURE:
The power incident on a PV module depends not only on the power contained in the sunlight,
but also on the angle between the module and the sun. When the absorbing surface and the
sunlight are perpendicular to each other, the power density on the surface is equal to that of
the sunlight (in other words, the power density will always be at its maximum when the PV
module is perpendicular to the sun). However, as the angle between the sun and a fixed
surface is continually changing, the power density on a fixed PV module is less than that of
the incident sunlight.
The amount of solar radiation incident on a tilted module surface is the component of the
incident solar radiation which is perpendicular to the module surface. The following figure
shows how to calculate the radiation incident on a tilted surface (S module) given either the
solar radiation measured on horizontal surface (Shoriz) or the solar radiation measured
perpendicular to the sun (Sincident).
CALCULATIONS:-
RESULT:-
First rule: all the strings of modules connected to the input of an inverter (or a MPPT input),
should be homogeneous: identical modules, same number of modules in series, same
orientation.
Exceptions may sometimes be acceptable - as far as only differences in the current of strings
are
concerned - for example strings of different orientations (cf Heterogeneous planes ).
PVsyst now allows the construction of heterogeneous systems with several different
subfields.
For a given subfield: you have to define your requirements, and PVsyst will automatically
propose a suited arrangement.
The basic requirements for a sub-field (i.e. the parameters you should input) are:
- The desired nominal power, or alternatively the available area for installing modules,
- The inverter model, chosen in the database,
- A PV module model, chosen in the database.
Then the program will choose the required number of inverters, according to a pre-defined
Pnom array/inverter ratio of 1.25. It will then propose a number of modules in series, and a
number of strings in order to approach the desired power or available area.
The acceptable choices for the number of modules in series/parallel are mentioned on the
dialog. They should meet the following requirements:
- The minimum array voltage in worst temperature conditions (60C) should not be under the
inverter's voltage range for MPPT,
- The maximum array voltage in worst temperature conditions (20C) should not be above
the inverter's voltage range for MPPT,
- The maximum array voltage in open circuit should not exceed the absolute maximum
voltage at the input of the inverter,
- The maximum array voltage in open circuit should not exceed the allowed system voltage
specified for the PV module.
The inverter power sizing is a delicate and debated problem. PVsyst proposes a
methodology based on the predicted overload losses. This usually leads to Pnom ratios far
below those recommended by inverter's providers, but we think that they are closer to an
economical optimum. All these conditions are explicitly displayed on a system sizing graph,
(button "Show sizing").
Design temperatures:
These conditions involve design temperatures, which are part of your project and may be
changed according to your climate in the definition of the project, option "Site and Meteo" /
"Next". The default values (for each new project) may be redefined in the Hidden Parameters,
topic "System design parameters". These are:
- Maximum cell temperature in operating conditions, default 60C,
- Summer usual operating conditions, not used for sizing constraints, default 50C,
- Winter minimum cell temperature in operating conditions, default 20C,
- Absolute Cell lower temperature for determining the Maximum possible voltage of the
array. The default is set to -10C for most European countries (best practice rule). For this
limit, the cell temperature is considered as the ambient temperature (worst case when the sun
suddenly appears on the field).
System sizing
As with any usual system, you are advised to start by specifying the required power for your
subfield (or the available area). After that you have to choose a PV module. When choosing a
SolarEdge inverter, the system sizing dialog will change to a suited dialog for the SolarEdge
architecture, and predefine the number of required inverters for your system size. You have
first to choose the Power Box to be used in your system (in the PV module group). Then in
the Array design part, please define the Power Box input configuration, i.e. the number of PV
modules connected to each Power Box (according to number of available inputs).
- The number of Power Boxes in Series. The limits described above are shown on the right of
the edit box. The nominal power corresponding to a whole string is shown, as well as the part
of the inverter capacity (in percent). This very important information indicates how many
identical strings you can connect on one inverter. For example if more that 50%, only one
string of that length can be connected to each inverter.
- The number of Strings in Parallel. When one only string is allowed per inverter, this will be
limited to the number of inverters. Below 50% capacity, this will be 2 times this number or
more You are of course advised to use the "Show Sizing" tool for visually checking the
sizing of this sub-field.
Systems with different strings
When you have strings with different lengths, you should define different sub-arrays, one for
each length to be defined. In this case within a subfield, only a part of the inverter will be
used for each string. Therefore you should define "Uses fractional Input" option, and define
the inverter fraction to be used for this string. When several inverters are used, this will be the
fraction for one inverter times the number of inverters. This will allow the use of the
complement of each inverter within another subfield, with the suited fraction (for example
70% in one subfield and 30% in another one). The total number of inverters defined in the
whole system appears in the "Global system summary" table at the top right of the dialog.
When inverter inputs are connected to strings of different lengths, the program is not able to
check the full Compatibility of your system. You should check by yourself that the defined
fractions are compatible with the foreseen strings.
Simulation
With distributed SolarEdge architecture:
- there are no mismatch losses,
- the near shadings should be defined as "Linear", i.e. without string partition.
Linear shading is a good approximation for the shadings in SolarEdge architecture. As
opposed to the
option "according to module strings", that is used for the upper bound of electrical losses
with regular inverters. The most exact way for SolarEdge simulation would be to define a
string partition with rectangles corresponding to the number of PV modules in series at the
input of one Power Box. These very little rectangles will reduce drastically the usual
electrical shading losses observed with full strings, except in very regular cases like shed
arrangement, where each module of the lower row becomes unproductive as soon as the
bottom cell is shaded.
project.
Theory: Solar Photovoltaic (PV) systems convert Sunlight directly into Electricity. This PV
systems vary greatly in size and cost, calculating the economics of a solar system is key to
knowing whether a solar system is right for your home, business or farm. Knowing the
economics of solar PV systems will be one of the most important considerations when
deciding on solar energy. Here you should view your solar PV system as an investment; this
decision should be made after determining the feasibility of installing a solar system at
specific site. This experiment focuses on grid-tied PV systems. These economic calculations
will be similar for off-grid systems.
Procedure:
1. Determine if you have a viable site (facing south )
2. Determine the total installed cost of a system from the local solar installer, Work with
the installer to estimate annual production from solar array.
3. Determine your cost of electricity, Check state net metering laws, and check local
utilities net metering policy.
4. Calculate simple payback period.
5. Determine eligibility for local, state and federal grants and tax credits.
6. Include inflation estimate in your calculations.
7. Calculate Internal Rate of return and Net Present value using a spread sheet.
CALCULATIONS:
Example:
ASSUMPTIONS:
Capacity
Cost of Project (Rs )
Project cost excluding land (Rs)
Technical Inputs:
Capacity Utilization factor
Degredation for Ist year
Degredation year on year
Generation 1st year
Length of transmission line
Lossess per Km
Total loss
Sale of Power:
PPA tariff
PPA tariff year on year escalation
APPC rate
APPC tariff year on year escalation
Rate of REC
Rate valid upto years
REC rate after the years
CDM Benefits:
Grid Emission factor
CER rate
%of revenue available to the owner
CDM benefit start year
No of years of CDM benefit
VCU rate
Project Financing:
Debt
Debt
Equity
Subsidy
Interest on term loan
period of loan
Moratorium
Operating Expenses:
1 MW
70230000 Per MW cost
66690000
70230000
19.50%
2%
0.70%
1674036
5 Km
0.05%
0.25%
0
0.00%
3
5.00%
3.5
3
3.5
Rs per unit
Rs per unit
Rs per unit
years
Rs per unit
70% %
49161000 Rs in lakhs
21069000 Rs in lakhs
Rs in lakhs
12.50%
10 years
1 years
O&M Charges
O&M charges escalation
Insurance
Working Capital Requirment:
O&M charges
Accounts Receivable
Spares
Interest
Taxation:
MAT rate
Income tax rate
80 I/A holiday starts from
Depreciation
Use WDV book depreciation at 15.33% ?
(y/n)
Use accelerated Dep (y/n)
Accelerated Dep in 1st year
Standalone project
Other Parameters:
Exchange rate ( Euro)
Exchange rate ( Dollar)
Discounting rate for NPV
Feasibility
Indicators:
Project Pay Back
Equity Pay Back
Project NPV
Equity NPV
Project IRR
Equity IRR
DSCR
No of years
No of years
Rs
Rs
%
%
500000 per MW
5%
0.50% Of COP
1
1.5
10.0%
12%
Months
Months
(% of O&M)
% p.a
20.96%
32.45%
4 year
y
y
80% ( 40% or 80%)
n
( y/n)
90 Rs
62 Rs
12%
6.80
10.14
8578530
9110076
15%
18%
1.24
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Particulars
Cost of land & boyndary wall etc
Cost of land ( in Acres)
Conveyancing charges
Boundary wall (mt)
Site development
Sub Total
Plant & Machinery:
Modules
Inverters
Module mounting structures
Cables & connectors
SJB
Lightning arresters
Transformer & HT panels
Evacuation line
Civil Construction:
Inverter & control Room (Sqft)
Trenches
Internal roads
Sub Total
SCADA
Metering panels
Misc approvals etc
per unit
cost
Nos
4
15%
600
1
400000
2000
500000
1000000
2
55
1
12
10
1
5
36
2000000
70000
2500000
80000
50000
6000000
1200000
1200
1
1
2400
300000
500000
1
1
1
1000000
200000
2000000
Cost per
MW ( Rs in
lakhs)
1600000
240000
1200000
500000
3540000
36000000
4000000
3850000
2500000
960000
500000
6000000
6000000
59810000
2880000
300000
500000
3680000
1000000
200000
2000000
3200000
70230000
Total cost (
Rs in lakhs)
3540000
36000000
4000000
3850000
2500000
960000
500000
6000000
6000000
3680000
1000000
200000
2000000
70230000
66690000
Geographical Site
Situation
Time defined as
Narsapur, Medak
Meteo data :
Latitude 17.7N
Legal Time Time zone UT+6
Albedo 0.20
Narsapur, Medak, Synthetic Hourly data
Simulation variant :
No shading effects
Simulation date
Country
Longitude
Altitude
India
78.3E
560 m
21/02/14 23h59
Simulation parameters
Collector Plane Orientation
Tilt
Horizon
Free Horizon
Near Shadings
No Shadings
17
Azimuth
PV Array Characteristics
PV module
Si-poly
Model
Manufacturer
Number of PV modules
In series
Total number of PV modules
Nb. modules
Array global power
Nominal (STC)
Array operating characteristics (50C)
U mpp
Total area
Module area
SIRIUS-250
SIRIUS SOLAR ENERGY
20 modules
In parallel
400
Unit Nom. Power
100 kWp
At operating cond.
534 V
I mpp
644 m
Inverter
RefuSol 20K
REFU Elektronik GmbH
480-800 V
Unit Nom. Power
5 units
Total Power
Characteristics
Inverter pack
Model
Manufacturer
Operating Voltage
Number of Inverter
20 strings
250 Wp
88 kWp (50C)
165 A
19.2 kW AC
96.0 kW AC
1.5 % at STC
2.0 %
2.0 % at MPP
0.05
User's needs :
55 mOhm
1 - bo (1/cos i - 1)
Loss Fraction
Loss Fraction
Loss Fraction
bo Parameter
PVSYST V5.14
Simulation variant :
No shading effects
System type
tilt
Model
Nb. of modules
Model
Nb. of units
Unlimited load (grid)
Produced Energy
Performance Ratio PR
Grid-Connected
17
SIRIUS-250
400
RefuSol 20K
5.0
157 MWh/year
75.4 %
azimuth
Pnom
Pnom total
Pnom
Pnom total
Specific prod.
0.6
Performance Ratio PR
0.7
0.5
0.4
0.3
0.2
0.1
1565 kWh/kWp/year
Performance Ratio PR
0
250 Wp
100 kWp
19 kW ac
96 kW ac
Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
Sep
Oct
Nov
0.0
Dec
Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
Sep
Oct
T Amb
GlobInc
GlobEff
EArray
E_Grid
EffArrR
EffSysR
kWh/m
kWh/m
kWh/m
kWh
kWh
January
160.1
22.88
190.7
185.5
15046
14725
12.25
11.99
February
165.8
25.97
188.4
183.3
14125
13822
11.64
11.39
March
204.5
31.17
215.0
209.0
15632
15304
11.29
11.06
April
207.1
29.91
202.9
196.8
15217
14896
11.65
11.40
May
203.6
32.18
189.1
182.8
13996
13686
11.50
11.24
June July
158.6
27.87
145.7
140.6
11244
10985
11.98
11.71
August
145.1
26.27
136.7
131.7
10919
10671
12.41
12.13
September
139.9
26.31
135.3
130.8
10748
10503
12.34
12.06
October
144.6
26.26
145.6
141.0
11488
11232
12.26
11.98
November
150.2
24.35
160.8
156.0
12844
12573
12.41
12.15
December
151.5
24.81
177.3
172.1
13810
13523
12.10
11.84
154.2
22.62
189.4
183.8
14907
14596
12.23
11.97
1985.1
26.72
2077.0
2013.5
159975
156514
11.96
11.70
Year
Legends:
GlobHor
EArray
T Amb
Ambient Temperature
E_Grid
GlobInc
EffArrR
GlobEff
EffSysR
Nov
Dec
PVSYST V5.14
Simulation variant :
No shading effects
System type
tilt
Model
Nb. of modules
Model
Nb. of units
Unlimited load (grid)
Grid-Connected
17
SIRIUS-250
400
RefuSol 20K
5.0
azimuth
Pnom
Pnom total
Pnom
Pnom total
0
250 Wp
100 kWp
19 kW ac
96 kW ac
It is incredible that about 20% of electricity is used for lighting worldwide and that, for some
municipalities, up to 40% of the electricity bills are calculated for street lighting. In todays
environmentally- and budget conscious society, engineers have combined two existing technologies
to help reduce energy costs as well as CO2 emissions. This most recent generation of solar LED street
lights provides a mature optical design, thoroughly chosen and dimensioned components, and
optimized, robust electronics. Subject to these premises, the combination of photovoltaic and LED
technology allows for street lighting, pedestrian lighting, park lighting, etc., and shows numerous
advantages over conventional systems: lowered maintenance costs, reduced light pollution, reduced
CO2 emissions, and an enhanced green image for cities, which attracts new investors, companies,
and inhabitants
Benefits of new solar lighting solutions include significant cost savings, less fire risk from
Kerosene type lanterns, and no direct carbon footprint and the use of a sustainable natural
commodity, sunlight or manpower to generate electricity. In addition there are economic and social
benefits from being able to undertake activities in the evening hours. Other products and services
could involve crank able torches, woodstove and water purifiers.
Advantages of LEDs in (solar) street lighting
There are numerous advantages for LED technology:
Directed light output system efficiency/homogeneous illumination
Low voltages best fit for solar-powered street lighting
Long and predictable service intervals reduced maintenance costs
Reliability and long lifetime increased road safety
Dimming adjusting to specific ambient light levels
Small package size flexible, flat and compact luminaries design
High-color rendering appearance and safety
LED contains no polluting materials easy lamp recycling
Higher light output even at low temperatures.
Especially for PV applications, the LED is the perfect product choice. The low DC forward voltage of
LEDs can be applied with an electronic circuit to the battery power. Alternatively an electronic boost
converter can easily be used to achieve a higher DC voltage and to drive more LEDs in series.
Total Cost of Ownership (TCO):
The LED + PV solution requires a higher investment in the beginning, but the digging work for the
power cable and the energy costs are not applicable. With the long LED lifetime, expensive
maintenance work can be decreased, resulting in a benefit for LED over traditional lighting.
Product
Price/Unit
Price
11
Solar Streetlights
2480/-
27280/-
11
Foundation
300/-
3300/-
44
Batteries
200/-
8800/-
22
LED modules
240/-
5280/44660/-
Total
Traditional Streetlights
9
Street Lights
1600/-
14400/-
15058/-
15058/-
36
Illuminants
51
1836/-
Electricity
32248/-
32248/-
Total
63542/-
This results in a relaxed budget for the municipalities as an average city spends about 40% of its
electrical bill on street lighting. The zero-energy consumption of the solar lights additionally helps to
fulfill the strong targets of CO2 reduction.
Conclusion:
Improvements in recent years in LED technology and photovoltaic technology allow for attractively
designed street lighting products and adequate light output for most requirements, even under winter
conditions with poor solar input. The preconditions are a well-designed optical
System that guarantees good light distribution with minimal losses, and the usage of the best, most
efficient, high-quality components available. Regarding TCO, this combination is competitive today.
Replacing line driven streetlights with solar streetlights would be a valuable contribution to energy
saving and CO2 reduction. Considering the research results of recent laboratory samples of PV cells
and LEDs, we can expect a bright future for these two combined technologies.