HBP Manual
HBP Manual
HBP Series
Blower Purge Desiccant Compressed Air Dryer
R E A D A N D U N D E R S TA N D T H I S M A N UA L P R I O R TO O P E R AT I N G O R S E R V I C I N G T H I S P R O D U CT.
RATED
FLOW
MODEL
REFERENCE
HBP500
HBP600
HBP750
HBP900
HBP1050
500 SCFM
600 SCFM
750 SCFM
900 SCFM
1050 SCFM
500
600
750
900
1050
HBP1300
HBP1500
HBP1800
HBP2200
HBP2600
1300 SCFM
1500 SCFM
1800 SCFM
2200 SCFM
2600 SCFM
1300
1500
1800
2200
2600
HBP3200
HBP3600
HBP4300
3200 SCFM
3600 SCFM
4300 SCFM
3200
3600
4300
MODELS
Contents
1.0 General Safety Information............................ 1
2.0 Receiving, Storing, and Moving...................... 1
3.0 Description..................................................... 2
4.0 Installation...................................................... 2
5.0 Instrumentation............................................... 7
6.0 Operation........................................................ 11
7.0 Maintenance................................................... 28
8.0 Troubleshooting.............................................. 30
DRAWINGS
Electrical Schematic 460VAC, 3 phase............... 33
Electrical Schematic 575VAC, 3 phase............... 34
Electrical Data Fusing & Wire Sizing................... 35
P&ID Schematic - Models 500 through 600 .......... 36
P&ID Schematic - Models 750 through 4300 ........ 38
REPLACEMENT PARTS
Models 500 through 600......................................... 40
Models 750 through 1800....................................... 42
Models 2200 through 2600..................................... 44
Models 3200 through 4300..................................... 46
WARRANTY
2.2 Storing
Store the dryer indoors to prevent damage to any electrical or mechanical components. All packaging material
should be left in place until the dryer is in position.
2.3 Handling
The dryer is designed to be moved by means of the shipping skid or the base channels. The dryer may also have
lifting lugs for use with an overhead crane. Be sure to
attach all of the lift points and use appropriate spreader
bars to prevent damage to the dryer.
CAUTION Never lift the dryer by attaching hooks
or slings to the piping, or to any part other than the
lifting lugs. Severe structural damage could occur.
3.0 Description
3.1 Function
Blower purge type regenerative dryers are an economical and reliable way to dry compressed air to dew points
below the freezing point of water. Desiccant dryers lower
the dew point of compressed air by adsorbing the water
vapor present in the compressed air onto the surface of
the desiccant. Adsorption continues until equilibrium is
reached between the partial pressure of the water vapor
in the air and that on the surface of the desiccant.
These dryers continuously dry compressed air by using
two identical towers, each containing a desiccant bed.
While one tower is on-stream drying, the other tower is
off-stream being regenerated (reactivated, i.e. dried out).
The towers are alternated on- and off-stream so that dry
desiccant is always in contact with the wet compressed
air. In this way a continuous supply of dry air downstream
of the dryer is possible. The switching from one tower
to the other is controlled by a solid-state controller on
either a fixed time basis (standard) or a demand basis
(optional).
When a tower is placed off-line, it is slowly depressurized and the desiccant is regenerated. First, a blower
draws in ambient air which is heated. The heated air
flows through the desiccant bed, desorbs the moisture
from the desiccant, and carries the desorbed water out
of the dryer. The blower and heater are turned off when
the desiccant bed is fully heated. When configured for
cooling, a portion of the dry compressed air is diverted
from the main air flow and throttled to near atmospheric
pressure. This extremely dry, low pressure air passes
through the hot off-line tower, partially cooling the desiccant bed and reducing the dew point spike after tower
change over. At the end of the cooling stage, the tower
is repressurized to full line pressure. This prevents desiccant bed movement and downstream pressure loss when
the tower goes back on-line.
4.0 Installation
4.1 System Arrangement
Locate the dryer under cover in an area where the ambient air temperature will remain between 35F (2C) and
120F (49C).
NOTE: If dryer is installed in ambients below 35F
(2C), low ambient protection requiring heat tracing
and insulation of the prefilter bowls, auto drains and/
or sumps, and lower piping with inlet switching and
purge/repressurization valves is necessary to prevent
condensate from freezing. If installing heat tracing, observe electrical class code requirements for type of duty
specified. Purge mufflers and their relief mechanisms
must be kept clear from snow and ice buildup that could
prevent proper discharge of compressed air.
Compressor
Aftercooler
Separator
Receiver
Prefilters
Desiccant Dryer
Afterfilters
Receiver
Figure 1
Typical System Configuration
2.
Dryer bypass piping may be installed to allow uninterrupted airflow during servicing. If the downstream application cannot tolerate unprocessed air for short periods,
install a second dryer in the bypass line.
(MAX)
(MAX)
SIDE VIEW
TOP VIEW
(MAX)
AIR INLET
AIR OUTLET
(TYP 4 PLACES)
R SLOTS
VIEW I
500 600 scfm
A
(MAX)
(MAX)
SIDE VIEW
TOP VIEW
GAS OUTLET
(MAX)
(TYP 4 PLACES)
R SLOT
VIEW II
750 through 2600 scfm
GAS INLET
FACE OF CUSTOMER
DRY GAS OUTLET
CONNECTION
FACE OF CUSTOMER
WET GAS INLET
CONNECTION
(MAX)
(MAX)
SIDE VIEW
TOP VIEW
GAS OUTLET
(MAX)
SLOT
(TYP 4 PLACES)
GAS INLET
CENTERLINE OF
CUSTOMER WET GAS
INLET CONNECTION
CENTERLINE OF
CUSTOMER DRY GAS
OUTLET CONNECTION
VIEW III
3200 through 4300 scfm
55
47.9/16
53
46.3/4
1.1/4
23.3/8
13.3/16
862
WT/KGS
76
2 NPT
2 NPT
578
1156
1491
22 X 32
594
32
335
1187
2664
1346
335
76
500
MODEL
VIEW REF.
322
1208
1,900
WT/LBS
2462
1397
2 NPT
600
2 NPT
2,200
7/8 X 1.1/4
108
998
2 NPT
2 NPT
22 X 32
360
2753
2551
578
1156
1531
604
32
2 NPT
2 NPT
7/8 X 1.1/4
14.3/16
105
13.3/16
100.7/16
22.3/4
12.11/16
96.15/16
22.3/4
60
45.1/2
59
45.1/2
23.13/16
1.1/4
VIEW REF.
600
500
MODEL
1,134
3 FLANGE
3 FLANGE
22 X 32
400
2903
2557
341
203
32
679
1359
1734
677
32
1338
1524
II
750
2,500
3 FLANGE
3 FLANGE
7/8 X 1.1/4
15.3/4
114
100.11/16
13.7/16
1.1/4
26.3/4
53.1/2
68
26.5/8
1.1/4
52.11/16
60
II
750
1,179
3 FLANGE
3 FLANGE
22 X 32
400
2903
2557
341
203
32
679
1359
1734
677
32
1338
1524
II
900
2,600
3 FLANGE
3 FLANGE
7/8 X 1.1/4
15.3/4
114
100.11/16
13.7/16
1.1/4
26.3/4
53.1/2
68
26.5/8
1.1/4
52.11/16
60
II
900
1,361
3 FLANGE
3 FLANGE
22 X 32
425
2870
2535
335
203
83
679
1359
1580
750
32
1434
1626
II
1050
3,000
3 FLANGE
3 FLANGE
7/8 X 1.1/4
16.3/4
113
99.13/16
13.3/16
3.1/4
26.3/4
53.1/2
62
29.9/16
1.1/4
56.7/16
64
II
1050
5,400
3 FLANGE
3 FLANGE
7/8 X 1.1/4
20.3/4
116
101.7/8
15.5/8
5.15/16
26.3/4
53.1/2
79
34.7/8
1.1/4
69.13/16
80
II
1500
1,633
3 FLANGE
3 FLANGE
22 X 32
451
2997
2662
335
203
83
679
1359
1862
761
32
1456
1676
II
1300
2,449
3 FLANGE
3 FLANGE
22 X 32
527
2946
2588
397
203
151
679
1359
2009
886
32
1773
2032
II
1500
DIMENSIONS IN MILLIMETERS
3,600
3 FLANGE
3 FLANGE
7/8 X 1.1/4
17.3/4
118
104.13/16
13.3/16
3.1/4
26.3/4
53.1/2
73
30
1.1/4
57.5/16
66
II
1300
DIMENSIONS IN INCHES
2,495
4 FLANGE
4 FLANGE
22 X 32
527
2946
2588
397
203
151
679
1359
2009
886
32
1773
2032
II
1800
5,500
4 FLANGE
4 FLANGE
7/8 X 1.1/4
20.3/4
116
101.7/8
15.5/8
5.15/16
26.3/4
53.1/2
79
34.7/8
1.1/4
69.13/16
80
II
1800
3,674
4 FLANGE
4 FLANGE
22 X 32
565
3246
2943
438
184
111
756
1511
2186
980
32
1864
2159
II
2200
8,100
4 FLANGE
4 FLANGE
7/8 X 1.1/4
22.1/4
128
115.7/8
17.1/4
7.1/4
4.3/8
29.3/4
59.1/2
86
38.9/16
1.1/4
73.3/8
85
II
2200
3,719
4 FLANGE
4 FLANGE
22 X 32
565
3246
2943
438
184
111
756
1511
2256
980
32
1864
2159
II
2600
8,200
4 FLANGE
4 FLANGE
7/8 X 1.1/4
22.1/4
128
115.7/8
17.1/4
7.1/4
4.3/8
29.3/4
59.1/2
89
38.9/16
1.1/4
73.3/8
85
II
2600
4,264
6 FLANGE
4 FLANGE
22 X 32
673
3246
2942
370
403
19
756
1511
2708
929
32
2106
2159
III
3200
9,400
6 FLANGE
4 FLANGE
7/8 X 1.1/4
26.1/2
128
115.13/16
14.9/16
15.7/8
3/4
29.3/4
59.1/2
107
36.9/16
1.1/4
82.7/8
85
III
3200
4,491
6 FLANGE
6 FLANGE
22 X 32
699
3404
3100
421
403
127
756
1511
2955
929
32
2106
2159
III
3600
9,900
6 FLANGE
6 FLANGE
7/8 X 1.1/4
27.1/2
134
122.1/16
16.9/16
15.7/8
29.3/4
59.1/2
116
36.9/16
1.1/4
82.7/8
85
III
3600
5,602
6 FLANGE
6 FLANGE
22 X 32
775
3313
3010
413
403
51
806
1613
3132
1062
32
2372
2769
III
4300
12,350
6 FLANGE
6 FLANGE
7/8 X 1.1/4
30.1/2
130
118.1/2
16.1/4
15.7/8
31.3/4
63.1/2
123
41.13/16
1.1/4
93.3/8
109
III
4300
When using Table 1 you will find the desiccant quantities listed in layers. Each layer will vary in depth
due to the type, quantity and purpose of the desiccant. Layer 1 must be installed first at the bottom of
the vessel followed by layer number 2 etc., until the
complete charge of desiccant has been installed.
Layer #1
(lbs.) (p/n)
Layer #2
(lbs.)
(p/n)
Layer #2
(lbs.)
(p/n)
500
354
AA-4
600
453
AA-4
750
590
AA-4
900
590
AA-4
1050
710
AA-4
1300
48
AA-25
876
AA-4
1500
92
AA-25
1167
AA-4
1800
92
AA-25
1167
AA-4
2200
161
AA-25
1706
AA-4
2600
161
AA-25
1706
AA-4
3200
258
AA-25
2119
AA-4
3600
258
AA-25
2353
AA-4
4300
719
TS-50
146
AA-25
2679
AA-4
AA = Activated Alumina
TS = Tabular Support
5.0 Instrumentation
The following instrumentation helps in monitoring dryer
operation and performance. Instruments which are
available as options are so noted.
Blower Purge Air dryers are rated NEMA 4 and include
the following:
Solid State Controls
Chamber Pressure Gauges
Purge Flow Pressure Gauge
Energy Management (Option A)
5.1 Controls
ENERGY MANAGEMENT
SENSOR LOCATION
(OPTIONAL)
PURGE INLET
CHECK VALVE
TOP VIEW
HEATER TEMP
THERMOCOUPLE
(CENTER END IN PIPE)
(OPPOSITE SIDE)
PURGE
HEATER WITH
INSULATION
TOWER INLET
VALVE
PURGE SUCTION
FILTER SILENCER
PURGE BLOWER
AND MOTOR
REAR VIEW
REPRESS VALVE
ASME RELIEF VALVE
OUTLET CHECK VALVE
PURGE
PRESSURE GAUGE
DESICCANT
FILL PORT
RIGHT TOWER
PRESSURE GAUGE
CONTROL
ENCLOSURE
LEFT TOWER
PRESSURE GAUGE
HIGH TENSION
ENCLOSURE
PRESSURE REGULATOR
& PILOT AIR FILTER
TOWER
INSULATION
(OPTIONAL)
DEWPOINTER
(OPTIONAL)
DESICCANT
DRAIN PORT
TOWER PURGE
EXHAUST VALVE
FRONT VIEW
Figure 3
General Layout Drawing
(Models 500 through 600)
ENERGY MANAGEMENT
SENSOR LOCATION (OPTIONAL)
REPRESS VALVE
TOP VIEW
HOT PIPE INSULATION
HEATER TEMP
THERMOCOUPLE
(CENTER END IN PIPE)
(OPPOSITE SIDE)
PURGE
HEATER WITH
INSULATION
PURGE SUCTION
FILTER SILENCER
CHAMBER INLET
VALVE
PURGE BLOWER
AND MOTOR
REAR VIEW
ASME RELIEF VALVE
RIGHT TOWER
PRESSURE GAUGE
CONTROL
ENCLOSURE
LEFT TOWER
PRESSURE GAUGE
HIGH TENSION
ENCLOSURE
PRESSURE REGULATOR
& PILOT AIR FILTER
TOWER
INSULATION
(OPTIONAL)
DEWPOINTER
(OPTIONAL)
DESICCANT
DRAIN PORT
TOWER PURGE
EXHAUST VALVE
FRONT VIEW
Figure 3a
General Layout Drawing
(Models 750 through 2600)
HEATER INLET
TEMPERATURE SWITCH
ENERGY MANAGEMENT
SENSOR LOCATION
(OPTIONAL)
TOP VIEW
ASME RELIEF VALVE
HOT PIPE
INSULATION
REPRESS
VALVE
PURGE INLET
CHECK VALVE
HEATER TEMP
THERMOCOUPLE
(CENTER END
IN PIPE)
(OPPOSITE SIDE)
HEATER
OVERTEMP RTD
PURGE
HEATER WITH
INSULATION
PURGE SUCTION
FILTER SILENCER
TOWER
INLET VALVE
PURGE BLOWER
THROTTLING VALVE
PURGE BLOWER
AND MOTOR
REAR VIEW
PURGE PRESSURE
GAUGE
DESICCANT
FILL PORT
RIGHT TOWER
PRESSURE GAUGE
CONTROL
ENCLOSURE
LEFT TOWER
PRESSURE GAUGE
HIGH TENSION
ENCLOSURE
PRESSURE REGULATOR
& PILOT AIR FILTER
TOWER INSULATION
(OPTIONAL)
DEWPOINTER
(OPTIONAL)
DESICCANT
DRAIN PORT
TOWER PURGE
EXHAUST VALVE
TOWER
DEPRESS VALVE
FRONT VIEW
Figure 3b
General Layout Drawing
(Models 3200 through 4300)
10
6.0 Operation
6.1 Controls
A solid-state controller controls valve and heater operation, monitors all critical operating conditions, and indicates operating status on a 2-line LCD display operator
interface. The controller receives input data from pressure switches, temperature sensors and the operator
interface. The operator interface displays information
about the dryer operating status and is used to change
the dryer operating mode.
NOTE: In Energy Management or Dew Point Control, as the drying time extends beyond 4 hours,
additional cooling time becomes available thus the
cooling step will frequently terminate based on temperature providing complete bed cooling.
V14
DRY GAS
OUTLET
F2
V7
V11
V8
DPA
SOL 'E'
F1
O1
V12
V13
DEWPOINTER OPTION
O2
M
V5
PR&G
V6
SET AT
100 PSIG
PI3
1TC
SET @ 370F
PI1
LEFT
CHAMBER
1PS
3PS
PI2
H1
RTD 3
SET @ 650F
SET @
45 PSIG
SET @
45 PSIG
SET @
5 PSIG
SET @
5 PSIG
RIGHT
CHAMBER
2PS
4PS
EXH.
DRYING
(RTD4/HS1)
REGEN
3
1
SET @ 176F
SOL 'C'
RTD 1
SOL 'D'
SOL 'F'
V9
RTD 2
SOL 'G'
BD1
BD2
M1
V10
M2
V3
V4
V1
SOL 'A'
V2
SOL 'B'
WET GAS
INLET
NOTES
1. SYMBOLS ARE PER ANSI Y32.10 "GRAPHIC SYMBOLS FOR FLUID POWER DIAGRAMS."
2. AS SHOWN FLOW DIRECTION IS:
LEFT CHAMBER DRYING
RIGHT CHAMBER REGEN
PILOT GAS LINE
3. SOLENOID VALVES 'B', 'D', & 'G' ARE SHOWN ENERGIZED,
SOLENOID VALVES 'A', 'C', 'E', & 'F' ARE SHOWN DE-ENERGIZED.
INDICATES OPTION
4.
Figure 4
Sequence of Operation Fixed Cycle Operation
Left Chamber Drying Right Chamber Regenerating (shown)
(continued on next page)
12
NOTE: In Energy Management or Dew Point Control, as the drying time extends beyond 4 hours,
additional cooling time becomes available thus the
cooling step will frequently terminate based on temperature providing complete bed cooling.
EMS
LEFT
TOWER
RIGHT
TOWER
Figure 5
Optional Moisture Sensing
Energy Management System (EMS)
13
14
NOTE: Jumpers JP7 and JP8 are used by the factory during final inspection to download language
text and to enable factory set-up screens.
Power On - green
Alarm - red
Service / Maintenance reminder - amber
Filters (pre, after, and pilot) service / maintenance
reminders - amber
Inlet switching and purge / repressurization valve status (On = valve open; Off = valve closed) - green
Left and right tower status (heating) - amber
Left and right tower status (drying) - green
Left and right tower pressure switch status (On =
switch closed; Off = switch open) - green
The front panel contains four momentary-contact pushbutton switches. Refer to Figure 6, Front Panel Overlay
for the appropriate icon associated with each switch.
Pushing on the overlay icon actuates the switch.
Data Display Switch
This switch is used to step through the display
screens.
Select Switch
This button is located to the left of the text display window.
Refer to the Front Panel Operation Section for additional
information.
ENTER Switch
This button is located to the right of the text display
window. Refer to the Front Panel Operation Section for
additional information.
Alarm Reset Switch
This button is normally used to reset an alarm or service
reminder. Refer to the Front Panel Operation Section
for additional information.
Filter Service /
Maintenance LED
Filter Service /
Maintenance LED
Left Tower Drying LED
Left Tower
Heating LED
Right Tower
Heating LED
Filter Service /
Maintenance LED
Vacuum Fluorescent
Text Display
Select switch
Enter Switch
Power On LED
Maintenance / Service
Reminder LED
Communications Icon
Alarm LED
Data Display Switch
Reset Switch for Alarm
RS232
Figure 6
Front Panel Overlay
and
15
16
NOTE: Value must be set above Energy Management Maximum RH Value Set Point (screen 9).
3. Press
to increment the setting to the desired
maximum vapor pressure value.
a. Factory set point for a -40F dew point dryer is
24 MBAR (0.348 PSI) .
NOTE: Value must be set above Energy Management Maximum Vapor Pressure Set Point
(screen 9).
18
ALARM MESSAGES
LEFT TOWER ALARMS
OTHER ALARMS
ALARM HEATER
OVER-TEMPERATURE
ALARM HEATER
LOW TEMPERATURE
ALARM BLOWER
MOTOR OVERLOAD
ALARM HEATER
HIGH TEMP IN
19
21
LT DRYING
RT DEPRESSURIZE
LT DEPRESSURIZE
RT DRYING
LT DRYING
RT HEATING
LT HEATING
RT DRYING
LT DRYING
RT COOLING
LT COOLING
RT DRYING
LT DRYING
RT REPRESSURIZE
LT REPRESSURIZE
RT DRYING
LT DRYING
RT HOLDING
LT HOLDING
RT DRYING
22
Program Step
10
11
12
LT status
Drying
Drying
Drying
Drying
Drying
Drying
Off
Depress
Heat
Cool
Down
Sweep
Repress
RT status
Off
Depress
Heat
Cool
Down
Sweep
Repress
Drying
Drying
Drying
Drying
Drying
Drying
1PS
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
then Open
Open
Open
Open
Open then
Closed
2PS
Closed
Closed
then Open
Open
Open
Open
Open then
Closed
Closed
Closed
Closed
Closed
Closed
Closed
3PS
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
then Open
Open
Open
Open
Open then
Closed
4PS
Closed
Closed
then Open
Open
Open
Open
Open then
Closed
Closed
Closed
Closed
Closed
Closed
Closed
On
On
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
Off
Off
Off
Off
Off
Off
Off
On
On
On
On
On
On
Off
On
On
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
On
Off
Off
Off
Off
Off
Off
Off
Open
Open
Open
Open
Open
Open
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Open
Open
Open
Open
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Open
Open
Open
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Open
Open
Open
Open
Open
Open
Closed
Open
Open
Open
Open
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Open
Open
Open
Open
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Open
Open
Closed
Closed
Closed
Closed
Open
Open
Left
Right
Right
Right
Right
Right
Right
Left
Left
Left
Left
Left
Table 2
Cycle Sequence Steps
23
TEST7: RT DRYING
RT: XXC
XXXF
Screen 8: Step 8
TEST8: DEPR LT
LT: XXC
XXXF
Screen 3: Step 3
Screen 9: Step 9
TEST3: HEAT RT
RT: XXC
XXXF
Screen 4: Step 4
TEST4: COOL RT
RT: XXC
XXXF
Screen 5: Step 5
TEST5: SWEEP RT
RT: XXC
XXXF
TEST9: HEAT LT
LT: XXC
XXXF
Screen 10: Step 10
TEST10: COOL LT
LT: XXC
XXXF
Screen 11: Step 11
TEST11: SWEEP LT
LT: XXC
XXXF
Screen 6: Step 6
TEST6: REPR RT
RT: XXC
XXXF
NOTE: Sequence step will not advance to tower
SWITCHOVER until tower has fully
pressurized. Exception: If switching failure
is disabled then pressure condition is
ignored.
24
Screen 7: Step 7
TEST12: REPR LT
LT: XXC
XXXF
NOTE: Sequence step will not advance to tower
SWITCHOVER until tower has fully
pressurized. Exception: If switching failure
is disabled then pressure condition is
ignored.
6.6 Start-up
6.6.1 Controller Settings
Purge exhaust valves are normally closed, pneumatically piston-actuated, Y-angle poppet valves. A yellow
indicator can be seen through a clear window at the top
of the actuator housing when the valve is in the open
position.
6.7.2 Alarms
26
,
x
,
xx
,
xxxxx
comma character
ASCII representation of the cycle type
,
xxx
,
xxx
,
xxx
,
xxx
,
xxx
,
xxx
,
xxxx ASCII representation of the dew point reading
(F)
,
xxxx ASCII representation of the filter time to service (hours)
,
xxxx ASCII representation of the desiccant time to
service (hours)
,
xxxx ASCII representation of the valve time to
service (hours)
,
x
ASCII representation of programming jumpers
,
1 or 0 Is the unit alarmed? 1 = alarm
,
1 or 0 Is service required? 1 = service
,
xx
ASCII representation of the energy savings
(%)
,
x
Reserved for future use, always 1 for now
,
ETX end of text character OxO3
CR carriage return
LF
line feed
JUMPERS:
The programming jumpers are as follows (0=off,
1=on):
JP Bit
1 0
2 1
3 2
4 3
5 4
6 5
7 6
8 7
7.0 Maintenance
WARNING - This equipment is a pressure-containing
device. Depressurize before servicing.
NOTE: The Dryer Controller is equipped with Service
Reminder functions for filters, desiccant and valves.
28
7.3 Valves
1. Process and pilot valves should be checked frequently for leaks and proper operation.
2. Purge pressure adjustment valve should be checked
frequently for proper adjustment.
29
8.0 Troubleshooting
WARNING - A POTENTIAL ELECTRICAL SHOCK
HAZARD EXISTS. Some of the troubleshooting
checks may require gaining access to the dryers
electrical enclosure(s) while the power supply is
energized and should be performed by a qualified
electrical technician.
WARNING - Before performing any electrical or
mechanical repairs or maintenance, or removing
or disassembling any component, be sure to deenergize and depressurize the dryer.
SYMPTOM
Indicator lights not illuminated
POSSIBLE CAUSE(S)
CORRECTIVE ACTION
1. No power to unit.
3. Blown fuse.
3. Replace fuse.
4. Board malfunction.
4. Replace board.
4a. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air filter is fully closed, ensure pilot air filter
cartridge is not clogged, ensure pilot air shut-off valve is
open
4b. Check for inlet pilot air solenoid valve failure. Check valve
operation. Repair or replace as necessary.
4c. Check for drying tower Inlet Valve failure - examine valve
and actuator for damage. Repair or replace as necessary.
5a. Check for air flow out of drying tower Purge Valve or exhaust piping indicating valve is not completely closed.
5b. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air filter is fully closed, ensure pilot air filter
cartridge is not clogged, ensure pilot air shut-off valve is
open
5c. Check for purge pilot air solenoid valve failure. Check valve
operation. Repair or replace as necessary.
5d. Check for drying tower Purge Exhaust Valve failure - examine valve and actuator for damage. Repair or replace as
necessary.
30
SYMPTOM
High Pressure Alarm
Left Tower or Right Tower Regenerating
POSSIBLE CAUSE(S)
CORRECTIVE ACTION
5a. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air filter is fully closed, ensure pilot air filter
cartridge is not clogged, ensure pilot air shut-off valve is
open.
5b. Check for purge pilot air solenoid valve failure. Check valve
operation. Repair or replace as necessary.
5c. Check for regenerating tower Purge Exhaust Valve failure examine valve and actuator for damage. Repair or replace
as necessary.
6a. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air filter is fully closed, ensure pilot air filter
cartridge is not clogged, ensure pilot air shut-off valve is
open.
6b. Check for Repressurization Valve (V11) failure. Check valve
operation. Repair or replace as necessary.
2a. Check for air flow out of regenerating tower Purge Valve or
exhaust piping indicating valve is not completely closed.
2b. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air filter is fully closed, ensure pilot air filter
cartridge is not clogged, ensure pilot air shut-off valve is
open
2c. Check for purge pilot air solenoid valve failure. Check valve
operation. Repair or replace as necessary.
2d. Check for regenerating tower Purge Exhaust Valve failure examine valve and actuator for damage. Repair or replace
as necessary.
3. Check for air flow out of regenerating tower Depressurization Muffler indicating valve is not completely closed.
Repair or replace as necessary.
4a. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air filter is fully closed, ensure pilot air filter
cartridge is not clogged, ensure pilot air shut-off valve is
open.
4b. Examine repressurization valve (V11) for damage. Repair
or replace as necessary.
Temperature Under-Range
or
Temperature Over-Range
Alarm
31
SYMPTOM
Outlet Dew Point Alarm
Left Tower or Right Tower
POSSIBLE CAUSE(S)
CORRECTIVE ACTION
2. Check the inlet air line for liquids. Inspect prefilter and
drain valve. Clean, repair or replace automatic drain valve.
4. Desiccant dusting.
Heater Over-Temperature
Alarm
Heater Low-Temperature
Alarm
1b. Regenerating tower purge exhaust valve failed to open 1) Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air filter is fully closed, ensure pilot air filter
cartridge is not clogged, ensure pilot air shut-off valve is
open.
2) Check for purge pilot air solenoid valve failure. Check valve
operation. Repair or replace as necessary.
3) Check for regenerating tower Purge Exhaust Valve failure examine valve and actuator for damage. Repair or replace
as necessary.
1c. Purge exhaust piping obstructed - ensure piping is free of
obstructions.
1d. Regenerating tower purge check valve failed to open - examine valve internals. Repair or replace as necessary.
Heater High Inlet Temperature
(models 3200, 3600, & 4300
only)
32
2. Line failure
20
21
CUSTOMER PROVIDED
460VAC, 3 PHASE
(FOR FUSING AND WIRE
SIZING SEE TABLE 1)
L1
L2
L3
249 OHM
1/8W
72
OL1
MC2
OL2
MC3
OL3
L4
BLACK
402
405
2FU
L1
407
460VAC
H3 H2
1T 102
101A
X1 115VAC
N
N
+12VDC
PE
PE
20
+12VDC
DC COM
RTD1+
RTD1ANLG1-
GREEN
81
BROWN
+5VDC
DC COM
+ 4-20MA OUT
1
OPTION
RTD4
EXTERNALLY
LOCATED
ENERGY MGMT
SENSOR
RED
11
ORANGE
88
RPS
RPS
3CR1
20
32
33
1PS
34
34
35
2PS
IN2
IN3
38
L PURGE
50
L PURGE
R PURGE
R PURGE
L DRY
L DRY
R DRY
R DRY
102
102
102
A2
1TR1
108
18
MC
SOLENOID "F"
26
3PS
27
NOTE:
SET 1TR ON MODE "D".
(SIGNAL OFF-DELAY)
102
35
SET @ 45PSIG
36 OL-AUX
4PS
5PSIG
33
37
4CR
SOLENOID "G"
28
SET @ 45PSIG
21
SOLENOID "C"
5PSIG
32
36
HC
DC COM
2CR1
28
LPS
102
107
+12VDC
IN1
LPS
NO
15
26
LEFT CHAMBER
RTD1 RTD
89
RTD5-
114
RIGHT CHAMBER
RTD2 RTD
87
RTD5+
OL-AUX
104
YELLOW
20
HEATER OVERTEMPERATURE
RTD3 RTD
86
RTD4-
B1
101
101
+
5VDC
G
-
85
RTD4+
+
L1
105
OPTION
RTD3-
K TYPE
1TC
A1
84
RTD3+
+
1-5VDC OUT
RTD2+
RTD2-
102
101
GREEN
10
-V
1PSB
21
21
ANLG2-
+V
101
BLACK
249 OHM
1/8W
72
ANLG2+
21
21
20
EXTERNALLY LOCATED
DEWPOINT
3 TRANSMITTER
80
70
ANLG1+
21 BLACK
X2
+12VDC
20
21
H4
1.25 AMP
TB5
1HTR
406
L2
101
MOTOR
404
HC3
0.5 AMP
1M
403
HC2
L6
LOW TENSION
ENCLOSURE
401
HC1
L5
21
21
MC1
LEFT CHAMBER
PRESSURE SWITCH
29
5CR
SOLENOID "D"
21
21
21
21
21
RIGHT CHAMBER
PRESSURE SWITCH
37
1TS
39
OUT1
OUT2
NO
ALARM
CONTACTS NC
C
50 + 2CR - 51
51
52 + 3CR - 53
52
53
54
55
56
57
25
54
SOLENOID "B"
55
56
SOLENOID "A"
57
25
SOLENOID "E"
21
+12VDC
20
21
59 + 1CR - 21
HEAT ENABLE
59
20
USED ON MODELS
3200, 3600 & 4300
20
21
+12VDC
HIGH TENSION
ENCLOSURE
33
20
21
CUSTOMER PROVIDED
575VAC, 3 PHASE
(FOR FUSING AND WIRE
SIZING SEE TABLE 1)
L1
L2
L3
MC1
OL1
MC2
OL2
MC3
OL3
L4
401
402
405
HC2
L6
MOTOR
404
HC1
L5
1M
403
1HTR
406
HC3
249 OHM
1/8W
BLACK
72
21
21
LOW TENSION
ENCLOSURE
L
N
+12VDC
PE
PE
20
+12VDC
RTD1+
RTD1ANLG1+
ANLG1-
21 BLACK
GREEN
81
BROWN
70
BLACK
249 OHM
1/8W
575VAC
H3 H2
1T 102
101A
X1 115VAC
+5VDC
DC COM
+ 4-20MA OUT
1
OPTION
RED
11
ORANGE
RTD4
88
106
OL-AUX
104
YELLOW
RPS
RPS
34
34
35
2PS
38
3CR1
L PURGE
50
L PURGE
R PURGE
R PURGE
L DRY
L DRY
R DRY
R DRY
3PS
4PS
5PSIG
SET @ 45PSIG
35
SET @ 45PSIG
LEFT CHAMBER
PRESSURE SWITCH
RIGHT CHAMBER
PRESSURE SWITCH
37
OUT1
OUT2
NO
ALARM
CONTACTS NC
C
55
56
57
25
54
SOLENOID "B"
55
56
SOLENOID "A"
57
25
SOLENOID "E"
21
+12VDC
20
21
59 + 1CR - 21
HEAT ENABLE
59
20
USED ON MODELS
3200, 3600 & 4300
52 + 3CR - 53
53
20
21
+12VDC
NOTE:
SET 1TR ON MODE "D".
(SIGNAL OFF-DELAY)
102
21
4CR
SOLENOID "C"
SOLENOID "G"
50 + 2CR - 51
54
27
28
1TS
52
MC
SOLENOID "F"
37
51
108
18
26
33
36 OL-AUX
39
102
102
DC COM
2CR1
20
1PS
102
A2
5PSIG
33
IN3
1HC
+12VDC
32
IN2
107
NO
15
32
36
102
1TR1
114
28
LPS
B1
101
IN1
LPS
+
L1
105
26
LEFT CHAMBER
RTD1 RTD
89
RTD5-
105
MC-AUX
RIGHT CHAMBER
RTD2 RTD
87
RTD5+
104
1CR1
20
HEATER OVERTEMPERATURE
RTD3 RTD
86
RTD4-
K TYPE
1TC
101
+
5VDC
G
-
85
RTD4+
OPTION
RTD3-
21
102
A1
84
RTD3+
4CR1
101
+
1-5VDC OUT
RTD2+
RTD2-
X2
21
101
EXTERNALLY
LOCATED
ENERGY MGMT
SENSOR
GREEN
10
-V
H4
1.25 AMP
1PSB
21
21
ANLG2-
+V
101
EXTERNALLY LOCATED
DEWPOINT
3 TRANSMITTER
80
72
ANLG2+
20
20
21
DC COM
34
407
+12VDC
N
TB5
2FU
L1
101
0.5 AMP
L2
HIGH TENSION
ENCLOSURE
29
5CR
SOLENOID "D"
21
21
21
21
21
SUGGESTED
FUSING
WIRE SIZE
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
10 KW
2.5 HP
12 KW
4 HP
14 KW
4 HP
17 KW
4 HP
19 KW
5 HP
23 KW
7.5 HP
28 KW
10 HP
33 KW
10 HP
40 KW
10 HP
45 KW
15 HP
12.6
4.1
15.1
6.2
17.6
6.2
21.3
6.2
23.8
7.6
28.9
11
35.1
14
41.4
14
50.2
14
56.5
21
20 AMPS
7.5 AMPS
20 AMPS
10 AMPS
25 AMPS
10 AMPS
30 AMPS
10 AMPS
30 AMPS
12 AMPS
40 AMPS
17.5 AMPS
45 AMPS
20 AMPS
60 AMPS
20 AMPS
70 AMPS
20 AMPS
80 AMPS
30 AMPS
#12 AWG
#14 AWG
#12 AWG
#14 AWG
#12 AWG
#14 AWG
#10 AWG
#14 AWG
#10 AWG
#14 AWG
#8 AWG
#14 AWG
#8 AWG
#14 AWG
#6 AWG
#14 AWG
#4 AWG
#14 AWG
#4 AWG
#10 AWG
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
54 KW
5 HP
60 KW
7.5 HP
70 KW
7.5 HP
67.8
7.6
75.3
9.0
87.9
11
90 AMPS
12 AMPS
100 AMPS
12 AMPS
110 AMPS
17.5 AMPS
#2 AWG
#14 AWG
#2 AWG
#14 AWG
#2 AWG
#14 AWG
MODEL COMPONENT
500
600
750
900
1050
1300
1500
1800
2200
2600
3200
3600
4300
F.L.A.
@460VAC
RATING
F.L.A.
@575VAC
SUGGESTED
FUSING
WIRE SIZE
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
10 KW
2.5 HP
12 KW
4 HP
14 KW
4 HP
17 KW
4 HP
19 KW
5 HP
23 KW
7.5 HP
28 KW
10 HP
33 KW
10 HP
40 KW
10 HP
45 KW
15 HP
10.0
3.3
12.0
5.0
14.1
5.0
17.1
5.0
19.1
6.1
23.1
9.0
28.1
11.0
33.1
11.0
40.2
11.0
45.2
17.0
15 AMPS
6 AMPS
20 AMPS
9 AMPS
20 AMPS
9 AMPS
25 AMPS
9 AMPS
25 AMPS
9 AMPS
30 AMPS
15 AMPS
40 AMPS
17.5 AMPS
50 AMPS
17.5 AMPS
60 AMPS
17.5 AMPS
60 AMPS
25 AMPS
#12 AWG
#14 AWG
#12 AWG
#14 AWG
#12 AWG
#14 AWG
#12 AWG
#14 AWG
#12 AWG
#14 AWG
#8 AWG
#14 AWG
#8 AWG
#14 AWG
#8 AWG
#14 AWG
#6 AWG
#14 AWG
#6 AWG
#10 AWG
HEATER
MOTOR
HEATER
MOTOR
HEATER
MOTOR
54 KW
5 HP
60 KW
7.5 HP
70 KW
7.5 HP
54.2
6.1
60.2
6.1
70.3
9.0
70 AMPS
9 AMPS
80 AMPS
9 AMPS
90 AMPS
15 AMPS
#4 AWG
#14 AWG
#4 AWG
#14 AWG
#2 AWG
#14 AWG
MODEL COMPONENT
500
600
750
900
1050
1300
1500
1800
2200
2600
3200
3600
4300
35
10
13
14
DRY GAS
OUTLET
26
44A
27
V7
V11
44
V8
DPA
SOL 'E'
28
22
DEWPOINTER OPTION
3
25
V12
15
V13
19
M
20
V5
V6
SET AT
100 PSIG
24
23
6
12
1TC
SET @ 370F
LEFT
CHAMBER
RIGHT
CHAMBER
RTD 3
SET @ 650F
SET @
45 PSIG
1PS
SET @
45 PSIG
SET @
5 PSIG
SET @
5 PSIG
3PS
13
11
2PS
4PS
EXH.
DRYING
(RTD4/HS1)
43
REGEN
3
1
42
16
29
18
SET @ 176F
SOL 'C'
RTD 1
SOL 'D'
SOL 'F'
54
RTD 2
SOL 'G'
21
19
5
17
V10
V9
EXH.
EXH.
V3
V4
V1
SOL 'A'
V2
SOL 'B'
WET GAS
INLET
NOTES
1. SYMBOLS ARE PER ANSI Y32.10 "GRAPHIC SYMBOLS FOR FLUID POWER DIAGRAMS."
2. AS SHOWN FLOW DIRECTION IS:
LEFT CHAMBER DRYING
RIGHT CHAMBER REGEN
PILOT GAS LINE
3. SOLENOID VALVES 'B', 'D', & 'G' ARE SHOWN ENERGIZED,
SOLENOID VALVES 'A', 'C', 'E', & 'F' ARE SHOWN DE-ENERGIZED.
INDICATES OPTION
4.
36
LEGEND
1.
INLET VALVE (V1 LEFT, V2 RIGHT)
2.
PURGE EXHAUST VALVE (V3 LEFT, V4 RIGHT)
3.
PURGE CHECK VALVE (V5 LEFT, V6 RIGHT)
4.
OUTLET CHECK VALVE (V7 LEFT, V8 RIGHT)
5.
DEPRESS VALVE (V9 LEFT, V10 RIGHT)
6.
PURGE HEATER WITH INSULATION
7.
HEATER TEMPERATURE THERMOCOUPLE
8.
HEATER OVERTEMPERATURE RTD
9.
CHAMBER RTD (LEFT & RIGHT)
10. RELIEF VALVE
11. CHAMBER PRESSURE GAUGES (LEFT & RIGHT)
12. CHAMBER PRESSURE SWITCH (LEFT & RIGHT)
13. SERVICE VALVE
14. PILOT AIR FILTER
15. PRESSURE REGULATOR & GAUGE
16. SOLENOID VALVE
17. MUFFLER
18. DESICCANT CHAMBER
19. DESICCANT RETAINING SCREEN (TOP & BOTTOM)
20. DESICCANT FILL PORT
21. DESICCANT DRAIN PORT
22. HOT PIPE INSULATION
23. PURGE PRESSURE GAUGE
24. PURGE BLOWER AND MOTOR
25. PURGE SUCTION FILTER SILENCER
26. REPRESS/SWEEP VALVE (V11)
27. REPRESS/SWEEP CHECK VALVE (V12 LEFT, V13 RIGHT)
28. REPRESS/SWEEP ORIFICE
29. CHAMBER BLOW-DOWN VALVE
DEWPOINTER OPTION
INSULATION OPTION
54.
CHAMBER INSULATION
176
V9
OPEN
CLOSED
SOLENOID
VALVE 'G'
N.C.
YES
NO
V10
OPEN
CLOSED
HEATER
YES
NO
ON
OFF
BLOWER
MOTOR
YES
NO
ON
OFF
55
LD
HO
N
ATIO
RIZ
N
SU
TIO
RES
ER A )
REP
EN
EG BLE
E R CTA
TAG SELE
DS
N
2N MPER
OW
(JU
LD
OO
RC
ATE
HE
CLOSED
OPEN
V11
YES
NO
G
ATIN
NO
YES
SOLENOID
VALVE 'F'
N.C.
TIO
IZA
OPEN
CLOSED
HE
V4
SOLENOID
VALVE 'E'
N.C.
UR
OPEN
CLOSED
176
ESS
V3
YES
NO
PR
DE
YES
NO
SOLENOID
VALVE 'D'
3 WAY
LD
HO
N
ATIO
RIZ
SU
ION
RES
RAT
REP
NE )
E
EG BLE
E R CTA
TAG SELE
DS
2N MPER
WN
DO
(JU
OL
CO
CLOSED
OPEN
V2
SOLENOID
VALVE 'C'
3 WAY
R
ATE
CLOSED
OPEN
ATIN
V1
YES
NO
HE
N
ATIO
RIZ
SSU
PRE
DE
NT
NE
PO
OM
SC S
CES TATU
S
NT
NE
PO
OM
SC
N
NE
YES
NO
SOLENOID
VALVE 'B'
3 WAY
HE
PR O
CES
PO
IZE
M
CO
ERG
AL
EN
RIC
CT
PRO
ELE
SOLENOID
VALVE 'A'
3 WAY
55
Sequence of Operation
(Models 500 through 600)
37
26
10
13
14
DRY GAS
OUTLET
44A
27
V7
V11
44
V8
DPA
SOL 'E'
28
22
DEWPOINTER OPTION
3
25
V12
15
V13
19
M
20
V5
V6
SET AT
100 PSIG
24
1TS
23
30
LEFT
CHAMBER
1PS
3PS
13
12
1TC
SET @ 370F
(225F)
11
RIGHT
CHAMBER
RTD 3
SET @ 650F
SET @
45 PSIG
SET @
45 PSIG
SET @
5 PSIG
SET @
5 PSIG
2PS
4PS
EXH.
DRYING
(RTD4/HS1)
43
REGEN
3
1
42
18
16
SET @ 176F
SOL 'C'
RTD 1
29
SOL 'D'
54
RTD 2
SOL 'G'
SOL 'F'
21
19
V10
V9
EXH.
EXH.
V3
17
2
V4
MODEL 750 ONLY
(SEE DETAIL 'A'
FOR 900-4300)
SOL 'A'
OPEN 5 TURNS
FROM FULL CLOSED 1A
& LOCK IN PLACE
V2
V1
SOL 'B'
WET GAS
INLET
NOTES
1. SYMBOLS ARE PER ANSI Y32.10 "GRAPHIC SYMBOLS FOR FLUID POWER DIAGRAMS."
2. AS SHOWN FLOW DIRECTION IS:
LEFT CHAMBER DRYING
RIGHT CHAMBER REGEN
PILOT GAS LINE
3. SOLENOID VALVES 'B', 'D', & 'G' ARE SHOWN ENERGIZED,
SOLENOID VALVES 'A', 'C', 'E', & 'F' ARE SHOWN DE-ENERGIZED.
4.
INDICATES OPTION
38
LEGEND
1.
INLET VALVE (V1 LEFT, V2 RIGHT)
1A. FLOW CONTROL VALVE
2.
PURGE EXHAUST VALVE (V3 LEFT, V4 RIGHT)
3.
PURGE CHECK VALVE (V5 LEFT, V6 RIGHT) (NO SPRING)
4.
OUTLET CHECK VALVE (V7 LEFT, V8 RIGHT)
5.
DEPRESS VALVE (V9 LEFT, V10 RIGHT)
6.
PURGE HEATER WITH INSULATION
7.
HEATER TEMPERATURE THERMOCOUPLE
8.
HEATER OVERTEMPERATURE RTD
9.
CHAMBER RTD (LEFT & RIGHT)
10. RELIEF VALVE
11. CHAMBER PRESSURE GAUGES (LEFT & RIGHT)
12. CHAMBER PRESSURE SWITCH (LEFT & RIGHT)
13. SERVICE VALVE
14. PILOT AIR FILTER
15. PRESSURE REGULATOR & GAUGE
16. SOLENOID VALVE
17. MUFFLER
18. DESICCANT CHAMBER
19. DESICCANT RETAINING SCREEN (TOP & BOTTOM)
20. DESICCANT FILL PORT
21. DESICCANT DRAIN PORT
22. HOT PIPE INSULATION
23. PURGE PRESSURE GAUGE
24. PURGE BLOWER AND MOTOR
25. PURGE SUCTION FILTER SILENCER
26. REPRESS/SWEEP VALVE (V11)
27. REPRESS/SWEEP CHECK VALVE (V12 LEFT, V13 RIGHT)
28. REPRESS/SWEEP ORIFICE
29. CHAMBER BLOW-DOWN VALVE
30. TEMPERATURE SWITCH (MODELS 3200 - 4300 ONLY)
SOL 'C'
SOL 'D'
4
2
V3
V4
DETAIL 'A' (MODELS 900-4300)
DEWPOINTER OPTION
INSULATION OPTION
54.
CHAMBER INSULATION
176
OPEN
CLOSED
HEATER
YES
NO
ON
OFF
BLOWER
MOTOR
YES
NO
ON
OFF
ER
V10
OW
OPEN
CLOSED
FP
V9
YES
NO
SO
YES
NO
SOLENOID
VALVE 'G'
N.C.
S
LO
SOLENOID
VALVE 'F'
N.C.
55
LD
HO
N
ATIO
RIZ
N
SU
TIO
RES
ERA )
REP
EN
EG BLE
E R CTA
TAG SELE
DS
N
2N MPER
OW
(JU
LD
OO
RC
ATE
CLOSED
OPEN
G
ATIN
V11
HE
OPEN
CLOSED
NO
YES
4
HE
V4
SOLENOID
VALVE 'E'
N.C.
N
ATIO
OPEN
CLOSED
YES
NO
RIZ
V3
SOLENOID
VALVE 'D'
3 WAY
SSU
YES
NO
PRE
SOLENOID
VALVE 'C'
3 WAY
176
DE
V2
CLOSED
OPEN
LD
HO
N
ATIO
RIZ
N
SU
TIO
RES
ERA )
REP
EN
EG BLE
E R CTA
TAG SELE
DS
N
2N MPER
OW
(JU
LD
OO
RC
ATE
CLOSED
OPEN
G
ATIN
V1
YES
NO
HE
N
ATIO
RIZ
SSU
PRE
DE
NT
NE
PO
OM
SC S
CES TATU
S
NT
NE
PO
OM
SC
NT
NE
PO
IZE
M
CO
YES
NO
SOLENOID
VALVE 'B'
3 WAY
HE
PRO
CES
AL
ERG
EN
RIC
CT
PRO
ELE
SOLENOID
VALVE 'A'
3 WAY
55
*
*
*
*
= FAILS IN POSITION
Sequence of Operation
(Model 750 through 4300)
39
8
42 43
9
6
25
24
REAR VIEW
26
23
LEFT CHAMBER
AIR
OUT
10
RIGHT CHAMBER
11
CONTROL
ENCLOSURE
11
HIGH TENSION
ENCLOSURE
14 15
44
AIR
IN
2
5
29
SIDE VIEW
FRONT VIEW
Phone: 724-745-1555
FAX: 724-745-6040
Email: [email protected]
Web: www.spx.com/hankison
40
500
MODEL
600
MAINTENANCE KITS
Year 2 Maintenance Kit
HBPMK2-04
HBPMK2-06
HBPMK3-04
HBPMK3-06
HBPMK4-04
HBPMK4-06
HBPMK5-04
HBPMK5-06
HBPDES-04
HBPDES-06
Desiccant Kit
*NOTE: For dryers shipped with optional pre-piped F0 or F3 Filter packages, add -A for year 2 - 5 kits. (Replacement Prefilter and Afterfilter elements are not included in Standard Kits.)
REPLACEMENT PARTS
ID#
SAFETY DRYER
STOCK
QTY.
DESCRIPTION
1
Inlet Valve Assembly (V1 & V2)
*
Solenoid Valve (Sol A, B)
2
Purge Exhaust Valve Assembly (V3 & V4)
*
Solenoid Valve (Sol C, D)
3
Purge Check Valve (V5 & V6)
4
Outlet Check Valve (V7 & V8)
5
Depress Valve (V9, V10)
*
Depress Solenoid Valve (Sol F, G)
6
Purge Heater
7
Heater Temperature Thermocouple (1TC)
8
Heater Overtemperature RTD (RTD3)
9
Chamber RTD (RTD1, RTD2)
10
Pressure Relief Valve
11
Chamber Pressure Gauge
12
Chamber Pressure Switch (1PS, 2PS)
*
Chamber Depressurization Pressure Switch (3PS, 4PS)
14
Pilot Air Filter Element
15
Pilot Air Pressure Regulator
17
Depress Muffler
*
Depress Muffler Replacement Core
23
Purge Pressure Gauge
24
Blower (460V)
*
Blower Hose
25
Silencer Assembly
*
Blower Inlet Silencer Element
26
Repress/Sweep Valve (V11)
*
Repress/Sweep Solenoid Valve (Sol E)
27
Repress/Sweep Check Valve (V12 & V13)
29
Chamber Blowdown Valve
42
Energy Management Pilot Operated Valve
43
Energy Management Sensor (RTD4/HS1)
*
Energy Management Vent Needle Valve
44
Dew-point Sensor - Ceramic
*
Dryer Controller
*
Heater Contactor
*
Blower Motor Contactor
*
Relay, Overload, 3Pole, 600V Max, 3.2-16Amp
*
Relay, SPDT 12VDC Coil, 120VAC, 10A (1CR, 2CR, 3CR, 4CR, 5CR)
*
Fuse 1.25A 600V (3FU)
*
Fuse .5A 600V (1FU, 2FU)
*
Temperature Controller
*
Timer, SPDT, 0.1S-120HR
Desiccant Evaluation Kit
Pre-Filter Assembly
Auto-Drain
Afterfilter Assembly
3151877
3203652
3152701
3203652
3160401
3160401
4010085
3203652
3152742
3153971
3153224
3153224
7400684
4011096
3149016
3152525
3158592
3154237
3133635
3075949
3158833
3157894
3251999
3152461
1270769
4010085
3203652
3151005
4009894
1274209
3144864
3158747
3154859
7417845
3153829
3158056
3158551
3154359
1240671
1241118
7416897
3203083
3150628
HF5-44-20-DG
3152270
HTA600
3151877
3203652
3152701
3203652
3160401
3160401
4010085
3203652
3152741
3153971
3153224
3153224
7400684
4011096
3149016
3152525
3158592
3154237
3133635
3075949
3158833
3158197
3242540
3152461
1270769
4010085
3203652
3151005
4009894
1274209
3144864
3158747
3154859
7417845
3153829
3158056
3158551
3154359
1240671
1241118
7416897
3203083
3150628
HF5-44-20-DG
3152270
HTA600
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
1
1
1
2
1
2
2
2
1
1
2
2
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
5
1
2
1
1
NOTES:
1. Parts and Maintenance Kits are for standard builds only. Please contact the factory with your dryer serial number for assistance on identifying spare parts and maintenance kits for your specific unit.
2. All quantities for one dryer.
3. ID# correspond to P&ID legend (* Not pictured in diagrams.)
Phone: 724-745-1555
FAX: 724-745-6040
Email: [email protected]
Web: www.spx.com/hankison
41
42 43
8
MODEL 750
25
1 1A
24
REAR VIEW
10
26
23
AIR
OUT
LEFT CHAMBER
RIGHT CHAMBER
11
CONTROL
ENCLOSURE
HIGH TENSION
ENCLOSURE
11
14 15
44
AIR
IN
29
SIDE VIEW
FRONT VIEW
Phone: 724-745-1555
FAX: 724-745-6040
Email: [email protected]
Web: www.spx.com/hankison
42
750
900
1050
MODEL
1300
1500
1800
MAINTENANCE KITS
Year 2 Maintenance Kit
HBPMK2-08
HBPMK2-10
HBPMK2-12
HBPMK2-14
HBPMK2-16
HBPMK2-18
HBPMK3-08
HBPMK3-10
HBPMK3-12
HBPMK3-14
HBPMK3-16
HBPMK3-18
HBPMK4-08
HBPMK4-10
HBPMK4-12
HBPMK4-14
HBPMK4-16
HBPMK4-18
HBPMK5-08
HBPMK5-10
HBPMK5-12
HBPMK5-14
HBPMK5-16
HBPMK5-18
HBPDES-08
HBPDES-10
HBPDES-12
HBPDES-14
HBPDES-16
HBPDES-18
Desiccant Kit
*NOTE: For dryers shipped with optional pre-piped F0 or F3 Filter packages, add -A for year 2 - 5 kits. (Replacement Prefilter and Afterfilter elements are not included in Standard Kits.)
REPLACEMENT PARTS
ID#
SAFETY DRYER
STOCK
QTY.
DESCRIPTION
1
Inlet Valve Assembly (V1 & V2)
*
Solenoid Valve (Sol A, B)
1A
Inlet Pilot Operated Valve
2
Purge Exhaust Valve Assembly (V3 & V4)
*
Solenoid Valve (Sol C, D)
3
Purge Check Valve (V5 & V6)
4
Outlet Check Valve (V7 & V8)
5
Depress Valve (V9, V10)
*
Depress Solenoid Valve (Sol "F", "G")
6
Purge Heater
7
Heater Temperature Thermocouple (1TC)
8
Heater Overtemperature RTD (RTD3)
9
Chamber RTD (RTD1, RTD2)
10
Pressure Relief Valve
11
Chamber Pressure Gauge
12
Chamber Pressure Switch (1PS, 2PS)
*
Chamber Depressurization Pressure Switch (3PS, 4PS)
14
Pilot Air Filter Element
15
Pilot Air Pressure Regulator
17
Depress Muffler
*
Depress Muffler Replacement Core
23
Purge Pressure Gauge
24
Blower (460V)
*
Blower Hose
25
Purge Suction Filter Silencer Assembly
*
Blower Inlet Silencer Element
26
Repress/Sweep Valve (V11)
*
Repress/Sweep Solenoid Valve (Sol E)
27
Repress/Sweep Check Valve (V12 & V13)
29
Chamber Blowdown Valve
42
Energy Management Pilot Operated Valve
43
Energy Management Sensor (RTD4/HS1)
*
Energy Management Vent Needle Valve
44
Dew-point Sensor - Ceramic
*
Dryer Controller
*
Heater Contactor
*
Blower Motor Contactor
*
Relay, Overload, 3Pole, 600V Max, 3.2-16Amp
*
Relay, Overload, 3Pole, 600V Max, 5.4-27Amp
*
Relay, SPDT 12VDC Coil, 120VAC, 10A (1CR, 2CR, 3CR, 4CR, 5CR)
*
Fuse 1.25A 600V (3FU)
*
Fuse .5A 600V (1FU, 2FU)
*
Temperature Controller
*
Timer, SPDT, 0.1S-120HR
Desiccant Evaluation Kit
Pre-Filter Assembly
Auto-Drain
Afterfilter Assembly
3152393
3203652
3155189
3152701
3203652
7405310
3160059
4010085
3203652
1200773
3153971
3153224
3153224
7400684
4011096
3149016
3152525
3158592
3154237
3133635
3075949
3158833
3158197
3242540
3152728
1270769
7010085
3203652
3151005
4009894
1274209
3144864
3158747
3154859
7417845
3153829
3158056
3158551
N/A
3154359
1240671
1241118
7416897
3203083
3150628
HF5-48-20-DG
3152270
HTA1200
3152393
3203652
3155189
3152394
4009880
7405310
3160059
4010085
3203652
3152734
3153971
3153224
3153224
7400684
4011096
3149016
3152525
3158592
3154237
3133635
3075949
3158833
3158197
3242540
3152728
1270769
4010085
3203652
3151005
4009894
1274209
3144864
3158747
3154859
7417845
3153829
3158056
3158551
N/A
3154359
1240671
1241118
7416897
3203083
3150628
HF5-54-24-G
6000003
HTA1200
3152393
3203652
3155189
3152394
4009880
7405310
3160059
4010085
3203652
3152735
3153971
3153224
3153224
7400684
4011096
3149016
3152525
3158592
3154237
3071392
3107791
3158833
3158198
3242540
3152728
1270769
4010085
3203652
3151005
4009894
1274209
3144864
3158747
3154859
7417845
3153829
3158056
3158551
N/A
3154359
1240671
1241118
7416897
3203083
3150628
HF5-56-24-G
6000003
HTA1200
3152393
3203652
3155189
3152394
4009880
7405310
3160059
4010085
3203652
1171782
3153971
3153224
3153224
7400684
4011096
3149016
3152525
3158592
3154237
3071392
3107791
3158833
3158199
3251998
3152729
3153683
4010085
3203652
3151005
4009894
1274209
3144864
3158747
3154859
7417845
3147965
3158653
3158551
N/A
3154359
1240671
1241118
7416897
3203083
3150628
HF5-60-24-G
6000003
HTA1800
3152393
3203652
3155189
3152394
4009880
7405310
3160059
4010086
3203652
3152736
3153971
3153224
3153224
3100938
4011096
3149016
3152525
3158592
3154237
3071392
3107791
3158833
3158200
3242539
3152729
3153683
4010085
3203652
3151005
4009900
1274209
3144864
3158747
3154859
7417845
3147965
3147640
N/A
3158481
3154359
1240671
1241118
7416897
3203083
3150628
HF5-60-24-G
6000003
HTA1800
3152393
3203652
3155189
3152394
4009880
7405310
3160059
4010086
3203652
3152738
3153971
3153224
3153224
3100938
4011096
3149016
3152525
3158592
3154237
3071392
3107791
3158833
3158200
3242539
3158021
3159138
4010085
3203652
3151005
4009900
1274209
3144864
3158747
3154859
7417845
3151845
3147640
N/A
3158481
3154359
1240671
1241118
7416897
3203083
3150628
HF5-60-24-G
6000003
HTA1800
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
1
1
1
2
1
2
2
2
1
1
2
2
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
5
1
2
2
1
NOTES:
1. Parts and Maintenance Kits are for standard builds only. Please contact the factory with your dryer serial number for assistance on identifying spare parts and maintenance kits for your specific unit.
2. All quantities for one dryer.
3. ID# correspond to P&ID legend (* Not pictured in diagrams.)
4. N/A - Not Applicable to this Model Size
Phone: 724-745-1555
FAX: 724-745-6040
Email: [email protected]
Web: www.spx.com/hankison
43
7
3
42 43
?
9
6
25
1 1A
24
REAR VIEW
10
AIR
OUT
26
23
LEFT CHAMBER
RIGHT CHAMBER
11
CONTROL
ENCLOSURE
11
HIGH TENSION
ENCLOSURE
14 15
44
AIR
IN
29
FRONT VIEW
SIDE VIEW
(RIGHT CHAMBER REMOVED FOR CLARITY)
Phone: 724-745-1555
FAX: 724-745-6040
Email: [email protected]
Web: www.spx.com/hankison
44
2200
MODEL
2600
MAINTENANCE KITS
Year 2 Maintenance Kit
HBPMK2-20
HBPMK2-22
HBPMK3-20
HBPMK3-22
HBPMK4-20
HBPMK4-22
HBPMK5-20
HBPMK5-22
HBPDES-20
HBPDES-22
Desiccant Kit
*NOTE: For dryers shipped with optional pre-piped F0 or F3 Filter packages, add -A for year 2 - 5 kits. (Replacement Prefilter and Afterfilter elements are not included in Standard Kits.)
REPLACEMENT PARTS
ID#
SAFETY DRYER
STOCK
QTY.
DESCRIPTION
1
Inlet Valve Assembly (V1 & V2)
*
Solenoid Valve (Sol A, B)
1A
Inlet Pilot Operated Valve
2
Purge Exhaust Valve Assembly (V3 & V4)
*
Solenoid Valve (Sol C, D)
3
Purge Check Valve (V5 & V6)
4
Outlet Check Valve (V7 & V8)
5
Depress Valve (V9, V10)
*
Depress Solenoid Valve (Sol "F", "G")
6
Purge Heater
7
Heater Temperature Thermocouple (1TC)
8
Heater Overtemperature RTD (RTD3)
9
Chamber RTD (RTD1, RTD2)
10
Pressure Relief Valve
11
Chamber Pressure Gauge
12
Chamber Pressure Switch (1PS, 2PS)
*
Chamber Depressurization Pressure Switch (3PS, 4PS)
14
Pilot Air Filter Element
15
Pilot Air Pressure Regulator
17
Depress Muffler
*
Depress Muffler Replacement Core
23
Purge Pressure Gauge
24
Blower (460V)
*
Blower Hose
25
Purge Suction Filter Silencer Assembly
*
Blower Inlet Silencer Element
26
Repress/Sweep Valve (V11)
*
Repress/Sweep Solenoid Valve (Sol E)
27
Repress/Sweep Check Valve (V12 & V13)
29
Chamber Blowdown Valve
42
Energy Management Pilot Operated Valve
43
Energy Management Sensor (RTD4/HS1)
*
Energy Management Vent Needle Valve
44
Dew-point Sensor - Ceramic
*
Dryer Controller
*
Heater Contactor
*
Blower Motor Contactor
*
Relay, Overload, 3Pole, 600V Max, 5.4-27Amp
*
Relay, SPDT 12VDC Coil, 120VAC, 10A (1CR, 2CR, 3CR, 4CR, 5CR)
*
Fuse 1.25A 600V (3FU)
*
Fuse .5A 600V (1FU, 2FU)
*
Temperature Controller
*
Timer, SPDT, 0.1S-120HR
Desiccant Evaluation Kit
Pre-Filter Assembly
Auto-Drain
Afterfilter Assembly
3152117
3203652
3155189
3152394
4009880
3160063
3160060
4010086
3154249
1217919
3153971
3153224
3153224
3100938
4011096
3149016
3152525
3158592
3154237
3204478
3126761
3158833
3158200
3242539
3158021
3159138
4010086
3154249
3152094
4009900
1274209
3144864
3158747
3154859
7417845
3158650
3149521
3158481
3154359
1240671
1241118
7416897
3203083
3150628
HF5-64-4F-G
6000003
HTA2400
3152117
3203652
3155189
3152394
4009880
3160063
3160060
4010086
3154249
1205010
3153971
3153224
3153224
3100938
4011096
3149016
3152525
3158592
3154237
3204478
3126761
3158833
3158201
3242539
3158021
3159138
4010086
3154249
3152094
4009900
1274209
3144864
3158747
3154859
7417845
3158650
3149521
3158481
3154359
1240671
1241118
7416897
3203083
3150628
HF5-68-4F-G
6000003
HTA3000
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
1
1
1
2
1
2
2
2
1
1
2
2
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
5
1
2
1
1
NOTES:
1. Parts and Maintenance Kits are for standard builds only. Please contact the factory with your dryer serial number for assistance on identifying spare parts and maintenance kits for your specific unit.
2. All quantities for one dryer.
3. ID# correspond to P&ID legend (* Not pictured in diagrams.)
Phone: 724-745-1555
FAX: 724-745-6040
Email: [email protected]
Web: www.spx.com/hankison
45
26
42 43
25
1 1A
24
REAR VIEW
10
AIR
OUT
23
RIGHT CHAMBER
LEFT CHAMBER
11
30
CONTROL
ENCLOSURE
11
HIGH
TENSION
ENCLOSURE
14 15
AIR
IN
44
2
5
29
FRONT VIEW
SIDE VIEW
(RIGHT CHAMBER REMOVED FOR CLARITY)
Phone: 724-745-1555
FAX: 724-745-6040
Email: [email protected]
Web: www.spx.com/hankison
46
3200
MODEL
3600
4300
MAINTENANCE KITS
Year 2 Maintenance Kit
HBPMK2-24
HBPMK2-26
HBPMK2-28
HBPMK3-24
HBPMK3-26
HBPMK3-28
HBPMK4-24
HBPMK4-26
HBPMK4-28
HBPMK5-24
HBPMK5-26
HBPMK5-28
HBPDES-24
HBPDES-26
HBPDES-28
Desiccant Kit
*NOTE: For dryers shipped with optional pre-piped F0 or F3 Filter packages, add -A for year 2 - 5 kits. (Replacement Prefilter and Afterfilter elements are not included in Standard Kits.)
REPLACEMENT PARTS
ID#
SAFETY DRYER
STOCK
QTY.
DESCRIPTION
1
Inlet Valve Assembly (V1 & V2)
*
Solenoid Valve (Sol A, B)
1A
Inlet Pilot Operated Valve
2
Purge Exhaust Valve Assembly (V3 & V4)
*
Solenoid Valve (Sol C, D)
3
Purge Check Valve (V5 & V6)
4
Outlet Check Valve (V7 & V8)
5
Depress Valve (V9, V10)
*
Depress Solenoid Valve (Sol "F", "G")
6
Purge Heater
7
Heater Temperature Thermocouple (1TC)
8
Heater Overtemperature RTD (RTD3)
9
Chamber RTD (RTD1, RTD2)
10
Pressure Relief Valve
Chamber Pressure Gauge
11
12
Chamber Pressure Switch (1PS, 2PS)
*
Chamber Depressurization Pressure Switch (3PS, 4PS)
14
Pilot Air Filter Element
15
Pilot Air Pressure Regulator
17
Depress Muffler
*
Depress Muffler Replacement Core
23
Purge Pressure Gauge
24
Blower (460V)
*
Purge Blower Throttling Valve
*
Expansion Joint
25
Purge Suction Filter Silencer Assembly
*
Blower Inlet Silencer Element
26
Repress/Sweep Valve (V11)
*
Repress/Sweep Solenoid Valve (Sol E)
27
Repress/Sweep Check Valve (V12 & V13)
29
Chamber Blowdown Valve
30
Heater High Inlet Temperature Switch (1TS)
42
Energy Management Pilot Operated Valve
43
Energy Management Sensor (RTD4/HS1)
*
Energy Management Vent Needle Valve
Dew-point Sensor - Ceramic
44
*
Dryer Controller
*
Heater Contactor
*
Blower Motor Contactor
*
Relay, Overload, 3Pole, 600V Max, 3.2-16Amp
*
Relay, SPDT 12VDC Coil, 120VAC, 10A (1CR, 2CR, 3CR, 4CR, 5CR)
*
Fuse 1.25A 600V (3FU)
*
Fuse .5A 600V (1FU, 2FU)
*
Timer, SPDT, 0.1S-120HR
*
Temperature Controller
Desiccant Evaluation Kit
Pre-Filter Assembly
Auto-Drain
Afterfilter Assembly
3152117
3203652
3155189
3152093
4009880
3160064
3160061
4010086
3203652
1181451
3153971
3153224
3153224
3100938
4011096
3149016
3152525
3158592
3154237
3130773
3121200
3158833
3158474
1170918
1206327
3032795
3504482
4010086
3203652
3152094
4009900
3159879
1274209
3144864
3158747
3154859
7417845
3158326
3158653
3158551
3154359
1240671
1241118
3203083
7416897
3150628
HF5-72-6F-G
6000003
HTA4800
3152798
3203652
3155189
3152093
4009880
3160064
3160061
4010086
3203652
1185499
3153971
3153224
3153224
3100938
4011096
3149016
3152525
3158592
3154237
3130773
3121200
3158833
3158475
1170918
1206327
3032795
3504482
4010087
3203652
3152095
4009900
3159879
1274209
3144864
3158747
3154859
7417845
3158326
3158653
3158551
3154359
1240671
1241118
3203083
7416897
3150628
HF5-72-6F-G
6000003
HTA4800
3152798
3203652
3155189
3152093
4009880
3160064
3160061
4010087
3158444
1276268
3153971
3153224
3153224
3119442
4011096
3149016
3152525
3158592
3154237
3130773
3121200
3158833
3158475
1170918
1206327
3032795
3504482
4010087
3158444
3152095
4009900
3159879
1274209
3144864
3158747
3154859
7417845
3158326
3158653
3158551
3154359
1240671
1241118
3203083
7416897
3150628
HF5-72-6F-G
6000003
HTA4800
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
1
1
1
2
1
2
2
2
1
1
2
2
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
5
1
2
1
1
NOTES:
1. Parts and Maintenance Kits are for standard builds only. Please contact the factory with your dryer serial number for assistance on identifying spare parts and maintenance kits for your specific unit.
2. All quantities for one dryer.
3. ID# correspond to P&ID legend (* Not pictured in diagrams.)
Phone: 724-745-1555
FAX: 724-745-6040
Email: [email protected]
Web: www.spx.com/hankison
47
WARRANTY
The manufacturer warrants the product manufactured by it, when properly installed, operated, applied, and maintained in accordance
with the procedures and recommendations outlined in the manufacturers instruction manuals, to be free from defects in material or
workmanship for a period of one (1) year from the date of shipment from the manufacturer or the manufacturers authorized distributor,
or eighteen months from the date of shipment from the factory, whichever occurs first, provided such defect is discovered and brought to
the manufacturers attention the aforesaid warranty period. The manufacturer will repair or replace any product or part determined to be
defective by the manufacturer within the warranty period, provided such defect occurred in normal service and not as the result of misuse,
abuse, neglect, or accident.
The warranty covers parts and labor for the warranty period. Repair or replacement shall be made at the factory or the installation site,
at the sole option of the manufacturer. The manufacturer must first authorize any service performed on the product by anyone other than
the manufacturer. Normal maintenance items requiring routine replacement are not warranted. Unauthorized service voids the warranty
and any resulting charge or subsequent claim will not be paid.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, WRITTEN, ORAL, OR STATUTORY,
AND IS EXPRESSED IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS
FOR A PARTICULAR PURPOSE. THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAMAGE BY REASON OF STRICT
LIABILITY IN TORT OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN, MANUFACTURE, OR INSPECTION OF
THE EQUIPMENT OR ITS FAILURE TO DISCOVER, REPORT, REPAIR, OR MODIFY LATENT DEFECTS INHERENT THEREIN. THE
MANUFACTURER, HIS REPRESENTATIVE OR DISTRIBUTOR SHALL NOT BE LIABLE FOR LOSS OF USE OF THE PRODUCT OR
OTHER INCIDENTAL OR CONSEQUENTIAL COSTS, EXPENSES, OR DAMAGES INCURRED BY THE BUYER, WHETHER ARISING
FROM BREACH OF WARRANTY, NEGLIGENCE OR STRICT LIABILITY IN TORT.
The manufacturer does not warranty any product, part, material, component, or accessory manufactured by others and sold or supplied
in connection with the sale of the manufacturers products.
HBP SERIES
Blower Purge Desiccant
Compressed Air Dryer
SPX
Revision: I