Installation Manual
Installation Manual
INSTALLATION
INSTALLATION
INSTALLATION
1 INSTALLATION OF UNITS
1.1 Installation Positions
1.1.1 Installation Positions of Outdoor
Outdoor unit must be installed on a firm and solid support.
Outdoor unit shall be installed close to the indoor unit, hence to minimize the length and
bends of cooling pipe.
Avoid placing the outdoor unit under window or between two constructions, hence to prevent
normal operating noise from entering the room.
Air flow at inlet and outlet shall not be blocked.
Install at a well-ventilated place, so that the machine can absorb and discharge sufficient air.
Do not install at a place where flammable or explosive goods exist or a place subject to
severe dust, salty fog and polluted air.
1.1.2 Installation Positions of Indoor
Avoid direct sunshine.
Ensure the hanger rod, ceiling and building structure have sufficient strength to support the
weight of air conditioner unit.
Drainage pipe is easy to connect out.
Indoor and outdoor connection pipes are easy to go outdoors
Do not install at a place where flammable or explosive goods exist or flammable or explosive
gas might leak.
Do not install at a place subject to corrosive gas, severe dust, salty fog, smoke or heavy
moisture.
Air flow at inlet and outlet air is not blocked.
Note:
The water pressure gage is installed in returning water line in the indoor unit
Please adjust the hydraulics system pressure according to next item:
If the pressure is less than 0.5 bar, please recharge the water immediately;
when rechargingthe hydraulics system pressure should be not more than 2.5Bar.
1.1.3 Installation Positions of Water Tank
The insulated water tank should be installed and keep levelly within 5m and vertically within
3m from the Indoor unit. It can be installed in the room.
Standing water tank must be installed vertically with the bottom on the ground, never
suspended. Installation place must be firm enough and the water tank should be fixed on the
wall with bolts to avoid vibration, as shown in the following figure. Weight capacity of water
tank during installation should also be considered.
INSTALLATION
The minimum clearance from the water tank to combustible surface must be 500mm.
There should be water pipe, hot water joint and floor drain near the water tank in favor of
water replenishment, hot water supply and drainage of water tank.
Connection of inlet/outlet waterway: Connect the safety check valve attached with the unit
( points at insulated water tank) with the water inlet of water tank with PPR pipe according
to the following figure, sealing with unsintered tape. The other end of the safety check valve
should connect with tap water joint. Connect the hot water pipe and water outlet of water tank
with PPR pipe.
1.2 Matters Need Attention
The installation of unit must be in accordance with national and local safety codes.
Installation quality will directly affect the normal use of air conditioner unit. The user is
prohibited from installation by himself. Please contact your dealer after buying this machine.
Professional installation workers will provide installation and test services according to
installation manual.
Do not connect to power until all installation work is completed.
1.3 Dimension Data
1.3.1 Outdoor
GRS-CQ6.0Pd/Na-K(O),GRS-CQ8.0Pd/Na-k(O),GRS-CQ10Pd/Na-K(O)
GRS-CQ12Pd/Na-K(O),GRS-CQ14Pd/Na-K(O),GRS-CQ16Pd/Na-K(O)
GRS-CQ12Pd/Na-M(O),GRS-CQ14Pd/Na-M(O),GRS-CQ16Pd/Na-M(O)
INSTALLATION
1.3.2 Indoor
GRS-CQ6.0Pd/Na-K(I),GRS-CQ8.0Pd/Na-k(I),GRS-CQ10Pd/Na-K(I),
GRS-CQ12Pd/Na-K(I),GRS-CQ14Pd/Na-K(I),GRS-CQ16Pd/Na-K(I),
INSTALLATION
GRS-CQ12Pd/Na-M(I),GRS-CQ14Pd/Na-M(I),GRS-CQ16Pd/Na-M(I)
INSTALLATION
unit outline
Step3Attaching indoor unit to the wall make use of accessory expansion bolt
INSTALLATION
Expansion bolt
Install wall
C CAUTION!
While lifting the indoor unit, at least two persons should be joined. Weight of the
indoor unit is almost 52kg.
Precautions on Installation of Indoor Unit
Indoor unit shall be vertically mounted on the wall of the room with expansion bolt.
Keep the Indoor unit away from heat sources such as heat sink and so on in the room as
much as possible.
Keep the indoor unit as close as possible to outdoor unit. Level distance between
connection pipes can not exceed 30m and vertical distance can not exceed 15m.
INSTALLATION
Water tank
Fix
with
bolts
Installed on the ground and
never suspended
The minimum clearance from the water tank to combustible surface must be 500mm.
There should be water pipe, hot water joint and floor drain near the water tank in favor of
water replenishment, hot water supply and drainage of water tank.
Connection of inlet/outlet waterway: Connect the safety check valve attached with the unit
( points at insulated water tank) with the water inlet of water tank with PPR pipe according
to the following figure, sealing with unsintered tape. The other end of the safety check valve
should connect with tap water joint. Connect the hot water pipe and water outlet of water tank
with PPR pipe.
Note:
For safe use of water, water outlet/inlet of water tank must connect with a certain length of
INSTALLATION
PPR pipe ,L 70R2cmR is inside radius of the pipe. Moreover, heat preservation should
be conducted and metal pipe can not be used. For the first use, water tank must be full of water
before the power is on.
Litre
SXVD200LCJ/A-K
SXVD200LCJ/A-M
200L
SXVD200LCJ2/A-K
SXVD200LCJ2/A-M
200L
SXVD300LCJ/A-K
SXVD300LCJ/A-M
300L
SXVD300LCJ2/A-K
SXVD300LCJ2/A-M
300L
coil
specification
coil
M
length
N
D(mm)
D1(mm)
H(mm)
A(mm)
B(mm)
C(mm)
E(mm)
F(mm)
I(mm)
J(mm)
K(mm)
INSTALLATION
SUS304 22X0.8
\
13m
10m
13m
\
18.5m
540
438
1595
272
10m
18.5m
620
528
1620
280
105
112
432
431
\
\
Outline
(DiameterH)
464
399
80
247.5
\
\
95
202.5
739
718
540X1595
620X1620
1620X625X630
1645X705X710
(mm)
Package
(W*D*H) (mm)
Net
kg
weight
Gross
kg
weight
68
71
82
87
77
80
92
97
INSTALLATION
Temp Sensor 1
Safety check
Filter
valve
Cool Water
Inlet
temp sensor 2
Tap water
Blow-off Outlet
Power cord of booster heater
Cut-off Valve
Joints Dimension
Description
Circulating water inlet/outlet of main unit
1/2Female BSP
3/4Female BSP
1/2Female BSP
Note:
Distance between main unit and insulated water tank should not exceed 5m levelly and
3m vertically. If higher, please contact with us. Water tank on lower and main unit on
higher side is recommended.
Prepare the materials according to the above joints dimension. If cut-off valve is installed
outside the room, PPR pipe is recommended to avoid freeze damage.
Waterway pipelines cant be installed until water heater unit is fixed. Do not let dust and
other sundries enter into pipeline system during installation of connection pipes.
After connection of all waterway pipelines, perform leakage test firstly. After that, perform
heat preservation of waterway system; meanwhile, pay more attention to valves and pipe
joints. Ensure enough thickness of insulated cotton. If necessary, install heating device
for pipeline to prevent the pipeline from freezing.
Hot water supplied from insulated water tank depends on pressure of water tap, so there
must be supply of tap water.
During using, the cut-off valve of cooling water inlet of water tank should be kept normally
on.
1.3.4 Electric Wiring
1.3.4.1 Wiring Principle
General principles
10
INSTALLATION
Wires, equipment and connectors supplied for use on the site must be in compliance
with provisions of regulations and engineering requirements.
Only electricians holding qualification are allowed to perform wire connection on the site.
Before connection work is started, the power supply must be shut off.
Installer shall be responsible for any damage due to incorrect connection of the external
circuit of the unit.
Caution --- MUST use copper wires.
Connection of power cable to the electric cabinet of the unit
Power cables should be laid out through cabling trough, conduit tube or cable channel.
Power cables to be connected into the electric cabinet must be protected with rubber or
plastic to prevent scratch by edge of metal plate.
Power cables close to the electric cabinet of the unit must be fixed reliably to make the
power terminal in the cabinet free from an external force.
Power cable must be grounded reliably.
1.4 Installation Clearance Data
11
INSTALLATION
12
INSTALLATION
Note:
The water pump is three speed-adjustable(maximum/medium/minimum), In most case,
we strongly recommended to set speed as maximum;
If the noise of the pump is not acceptable, we recommended change the default speed to
medium speed, but to secure enough flow rate, do not set water speed as Min, it can
lead unexpected flow rate error EC;
(2). Water Volume and Expansion Vessel Pressure
Note:
13
INSTALLATION
Pg ( H /10 0.3) Bar H ---the difference between installing location of indoor unit and
the highest spot of water system.
Ensure that the volume of water system is lower than the maximum volume required in the
above figure. If it exceeds the range, the expansion vessel does not meet the installing
requirement.
Installation height difference
Water volume
280L
7 m
7 m
280L
1. Pre-set pressure needs to be
adjusted according to the above
formula.
2. Check if the water volume is
lower than the maximum water
volume. (with help of the above
figure)
Note
Installation height difference-the difference between installing location of indoor unit and
the highest spot of water systemif the indoor unit is located at the highest point of the
installationthe installation height difference is considered 0m
The minimum volume of the water system is 20 L.
Example 1The indoor unit is installed 5m below the outdoor unit and the total volume of the
water system is 100L.
Referring to the above figure, it is not necessary to adjust the pressure of the expansion
vessel.
Example 2 The indoor unit is installed on the highest spot of the water system and the total
14
INSTALLATION
ce
1 p1
1
1 p2
e --- The expansion factor of water (the difference between the expansion factor of the
original water temperature and that of highest water temperature.)
Water expansion factor in different temperature
Expansion factor e
Temperature
0
0.00013
4
0
10
0.00027
20
0.00177
30
0.00435
40
0.00782
45
0.0099
50
0.0121
55
0.0145
60
0.0171
65
0.0198
70
0.0227
75
0.0258
80
0.029
85
0.0324
90
0.0359
95
0.0396
100
0.0434
3. Filling of Refrigerant
Before shipped out from manufacturer, the outdoor unit has been filled with refrigerant.
15
INSTALLATION
Additional refrigerant may be filled when carrying out site connection of pipelines.
Check the liquid valve and the gas valve of the outdoor unit. The valves shall be completely
shut off.
Connect a vacuum pump to the liquid valve and the gas valve of the outdoor unit to remove
air from the inside of the indoor unit and the connecting pipe. Refer to the following figure:
Fig.22
After confirming that there is no leakage from the system, when the compressor is not in
operation charge additional R410A working fluid with specified amount to the unit through the
filling opening of the liquid pipe valve of the outdoor unit.
Be sure to charge the specified amount of refrigerant in liquid state to the liquid pipe
Since this refrigerant is a mixed refrigerant adding it in gas form may cause the
refrigerant composition to changepreventing normal operation.
Before chargingcheck whether the refrigerant cylinder is equipped with a siphon tube
or not
No siphon tube
16
INSTALLATION
17
model
GRS-CQ6.0Pd/Na-K
GRS-CQ8.0Pd/Na-K
GRS-CQ10Pd/Na-K
GRS-CQ12Pd/Na-K
GRS-CQ14Pd/Na-K
GRS-CQ16Pd/Na-K
GRS-CQ12Pd/Na-M
GRS-CQ14Pd/Na-M
GRS-CQ16Pd/Na-M
Pipe size
(Diameter:)
gas
Liquid
1/2"
1/4"
5/8"
3/8"
5/8"
3/8"
5/8"
3/8"
5/8"
3/8"
5/8"
3/8"
5/8"
3/8"
5/8"
3/8"
5/8"
3/8"
INSTALLATION
Length B
Standard
5.0m
7.5m
7.5m
7.5m
7.5m
7.5m
7.5m
7.5m
7.5m
Max.
20m
30m
30m
30m
30m
30m
30m
30m
30m
Elevation A
Standard
0m
0m
0m
0m
0m
0m
0m
0m
0m
Max.
10m
15m
15m
15m
15m
15m
15m
15m
15m
Additional
refrigerant
20g/m
50g/m
50g/m
50g/m
50g/m
50g/m
50g/m
50g/m
50g/m
Note:
18
INSTALLATION
No additional charge of the refrigerant is need when the pipe length is less than 10 m (the
standard pipe length is 7.5m) , f the pipe length is longer than 10 m ,additional charge of the
refrigerant is needed according to the table.
Example: if 16kw model is installed at a distance of 25m, (25-10)*50=750g refrigerant should
be added;
Rated capacity is based on standard pipe length and maximum allowable length is base on
the product reliability in the operation.
Oil trap should be installed every 5-7 meters when the location of outdoor unit is higher than
indoor unit.
Wires, equipment and connectors supplied for use on the site must be in compliance
with provisions of regulations and engineering requirements.
Only electricians holding qualification are allowed to perform wire connection on the site.
Before connection work is started, the power supply must be shut off.
Installer shall be responsible for any damage due to incorrect connection of the external
circuit of the unit.
Power cables should be laid out through cabling trough, conduit tube or cable channel.
Power cables to be connected into the electric cabinet must be protected with rubber or
plastic to prevent scratch by edge of metal plate.
Power cables close to the electric cabinet of the unit must be fixed reliably to make the
power terminal in the cabinet free from an external force.
19
INSTALLATION
Silk Screen
Specification
AC-L
N
E1
L2-2
L1-1
L2-1
L1-2
U
V
W
DC_MOTOR1
4V 4V1
HEAT
VA-1
HPP
LPP
OVC-COMP
T-SENSOR2
TSENSOR3
CN66.CN67
CN65
FA
H-PRESS
(2). GRS-CQ12Pd/Na-K(O).GRS-CQ14Pd/Na-K(O).GRS-CQ16Pd/Na-K(O)
20
Silk Screen
AC-L
N
L1-1
INSTALLATION
L2-1
Specification
Live wire input of power supply, red
Neutral line input of power supplyPFC blue inductive wire blue
PFC brown inductive wire
PFC yellow inductive wire
L1-2
U-phase of compressor
V-phase of compressor
W-phase of compressor
DC_MOTOR1
DC_MOTOR2
4V1
HEAT
VA-1
HPP
LPP
T-SENSOR2
TSENSOR3
CN66.CN67
CN65
FA
H-PRESS
DC fan
1 pinstrong power supply3 pinfan GND4 pin+15V5 pincontrol
signal6 pinfeedback signal
DC fan
1 pinstrong power supply3 pinfan GND4 pin+15V5 pincontrol
signal6 pinfeedback signal
4-way valve
Electric heating tape
E-heater of chassis
High pressure switch
Low pressure switch
1, 2holepipe temperature3, 4holeenvironment5, 6holeexhaust
1 hole:+3.3V 2 hole: detection: suction temperature sensor
Communication cable 2 pin B3 pin A
Communication cable 1 pin earthed2 pin B3 pin A4 pin+12 power supply
It can not be used for communication between outdoor unit and indoor unit.
Pipe electric expansion valve
1-4 pindriving impulse output5 pin+12V
Signal input of pressure sensor
1 pinGND2 pinsignal input3 pin+5V
(3). GRS-CQ12Pd/Na-M(O).GRS-CQ14Pd/Na-M(O).GRS-CQ16Pd/Na-M(O)
21
INSTALLATION
silk screen
L1
specification
L2
L3
N
U-phase of compressor
V-phase of compressor
W-phase of compressor
4V1
DC fan
1 pinstrong power supply3 pinfan GND4
pin+15V5 pincontrol signal6 pinfeedback signal
DC fan
1 pinstrong power supply3 pinfan GND4
pin+15V5 pincontrol signal6 pinfeedback signal
4-way valve
HEAT
VA-1
HPP
e-heater of chassis
high pressure switch
LPP
DC_MOTOR1
DC_MOTOR2
T-SENSOR2
4holeenvironment5,
TSENSOR3
CN66, CN67
CN65
FA
H-PRESS
22
INSTALLATION
GRS-CQ12Pd/Na-M(I).GRS-CQ14Pd/Na-M(I).GRS-CQ16Pd/Na-M(I)
HEAT2-L
RUN
HEAT1-L
PUMP2
AC_L N
HEAT3-L
PUMP1
2V1_OFF
ERR
2V1_ON
2V2_OFF
2V2_ON
3V1_OFF
3V1_ON
3V2_OFF
3V2_ON
LED1
LED2
LED3
CN30
T-SENSOR1
CN31
T-SENSOR2
T-SENSOR3
T-SENSOR4
T-SENSOR5
T-SENSOR6
TR-IN
TR-OUT1
Silk Screen
AC-L
N
PUMP1
PUMP2
RUN
HEAT3-L
HEAT1-L
HEAT2-L
ERR
2V1_OFF
2V1_ON
2V2_OFF
2V2_ON
3V1_OFF
3V1_ON
3V2_OFF
3V2_ON
T-SENSOR1
T-SENSOR2
T-SENSOR3
T-SENSOR4
T-SENSOR5
T-SENSOR6
DOOR-C
OVC-HEAT3
OVC-HEAT1
OVC-HEAT2
IN-SW
COM-MANUAL
COM-OUT
COM-BMS
TR-OUT1
TR-OUT2
TR-IN
CN30
CN31
TR-OUT2
COM-MANUAL
OVC-HEAT1
IN-SW
COM-OUT
OVC-HEAT2
COM-BMS
Location
X13
X14
X15
X16
X17
X18
X19
X5
X6
X7
X8
X9
X10
X11
X12
CN10
CN11
CN12
CN13
CN14
CN15
CN23
CN28
CN26
CN27
CN25
CN6
CN5
CN7
CN2
CN3
CN1
CN30
CN31
OVC-HEAT3
DOOR-C
Specification
live wire of power supply
Neutral wire of power supply
live wire of indoor water pump
live wire of solar water pump
running indicator
e-heater of water tank
e-heater of indoor unit 1
e-heater of indoor unit 2
error indicator
Electric magnetic 2-way valve1 is normally closed.
Electric magnetic 2-way valve1 is normally open.
Electric magnetic 2-way valve2 is normally closed.
Electric magnetic 2-way valve2 is normally open.
Electric magnetic 3-way valve1 is normally closed.
Electric magnetic 3-way valve1 is normally open.
Electric magnetic 3-way valve2 is normally closed.
Electric magnetic 3-way valve2 is normally open.
terminal of temperature sensor1
terminal of temperature sensor2
terminal of temperature sensor3
terminal of temperature sensor4
terminal of temperature sensor5
terminal of temperature sensor6
Door detection input
e-heater of water tank adhesion-proof protection detector
e-heater of indoor unit1 adhesion-proof protection detector
e-heater of indoor unit2 adhesion-proof protection detector
detection input of water flow switch
connect the wired controller
connect to outdoor unit
Building Management System (BMS)
transformer output 1
transformer output 2
220V in put of transformer
heavy-current interface of end controller
heavy-current interface of end controller
23
INSTALLATION
,GRS-CQ14Pd/Na-K(I),GRS-CQ16Pd/Na-K(I):
Indoor Unit
POWER
L
N
1
N(2)
2-way
valve1
XT1
2-way
valve2
Specification:
1 If there is gate control function,
pull out the leading wire 50 on
terminal boards between19 and 20
and then connect the
Gate-controller
XT2 20 19
3-way
valve1
3-way
valve2
XT2 20 19
AP
Running
indicating lamp
Error
indicating lamp
50
Gate-controller
PC
Long-distance
Monitor PC
Display
board
Indoor Unit
PE
POWER
XT1
XT3
2-way
valve1
2-way
valve2
3-way
valve1
PE
Specification:
1. If the gate control function is required,
pull out the leading wire 50 between
terminal 19 and 20 on the terminal block
and then install the gate-controller.
XT2 20 19
3-way
valve2
Running
indicating lamp
AP
PE
Error
indicating lamp
XT2 20 19
50
Communication line
OUTDOOR
UNIT AP1
PC
Display
board
Long-distance
Monitor PC
24
INSTALLATION
GRS-CQ12Pd/Na-K(O),GRS-CQ14Pd/Na-K(O),GRS-CQ16Pd/Na-K(O):
25
INSTALLATION
26
INSTALLATION
Thermostat1 Thermostat2
WP95A-R
PE
PE
(WP85A-R)
PE
Heater
PE
27
PE
Water tank
Water-tank
temp sensor1
Display
board
CN16
Main Baord
AP
Outdoor
Unit
CN5
Remote air
temp sensor
CN14
Thermostat
Long-distance
monitor PC
CN7
Thermostat
XT2
20 19
Gate-controller
Specification:
1 Running indicating lamp(HL1) and Error indicating lamp (HL2) are connected or not on the basis of the
clients'demand.
2 Client water pump AC contactor(KM4) is back-up Pump for the future , so it is not be connect;
3 Leakage SwitchLK is necessary for additional installation, Please reference to
page 10 4.3 Electrical Data
POWER
230V 50HZ
LK
XT1
L N 1 N(2)
3-way
valve2
Error
indicating lamp
PE
3-way
valve1
Inside Unit
Electric Box
2-way
valve2
Water-tank
temp sensor2
2-way
valve1
Running
indicating lamp
28
PE
LK
XT2
3-way
valve2
Water tank
PE
BKBN BU YEGN
29 30 31
PE
3-way
valve1
Inside Unit
Electric Box
2-way
valve2
Water-tank
temp sensor1
Display
board
CN16
Main Baord
AP
Outdoor
Unit
CN5
Remote air
temp sensor
CN14
Thermostat
Long-distance
monitor PC
CN7
Thermostat
XT2
20 19
Gate-controller
Specification:
1 Running indicating lamp(HL1) and Error indicating lamp (HL2) are connected or not on the basis of the
clients'demand.
2 Client water pump AC contactor(KM4) is back-up Pump for the future , so it is not be connect;
3 Leakage SwitchLK is necessary for additional installation, Please reference to
page 10 4.3 Electrical Data
POWER
380 415V-3Ph-50Hz
L1 L2 L3 N
L1 L2 L3 N
XT1
2-way
valve1
Error
indicating lamp
Water-tank
temp sensor2
Running
indicating lamp
29
INSTALLATION
Terminal board 3
21 22 23 24 25 26 27 28
Thermostat(1)
Thermostat(2)
Terminal Board 1
power supply for Water
tank electric heater
1
10
11
12
13
14
15
16
17
18
19
20
N(2)
Connection for
Indicating lihgt
Terminal Board 2
1
2 way value(1)
2 way value(2)
3 way value(1)
9 10
11 12 13 14 15 16 17 18 19 20
Connection for
Accident lihgt
30
INSTALLATION
Terminal Board 2
Connection for
Indicating lihgt
2 way value(1)
2 way value(2)
9 10
11 12 13 14 15 16 17 18 19 20
3 way value(1)
Connection for
Accident lihgt
Terminal Board 1
L1 L2 L3 N
Connecting external electric
power supply for Indoor Unit
Terminal board 3
21 22 23
24
25
Thermostat(1)
1.3.6
26 27
Thermostat(2)
28
29 30
31
31
INSTALLATION
Water Tank
CN15
CN14
CN13
CN12
CN11
CN10
10
11
12
13
14
15
16
17
18
19
20
Water -Tank
Temp Sensor1
N(2)
Water -Tank
Temp Sensor2
N
L
External Power Supply
(230V 50Hz AC)
32
INSTALLATION
Water Tank
CN15
CN14
CN13
CN12
CN11
CN10
10
11
12
13
14
15
16
17
18
19
20
Water -Tank
Temp Sensor1
L1
L2
L3
Water -Tank
Temp Sensor2
L3
L2
L1
water flow into under floor loop in cooling mode when fan coil unit is equipped for cooling
operation.
General Information
Type
NO 2-wire
NC 2-wire
Power
Operating Mode
Supported
230V 50Hz
Yes
AC
Yes
230V 50Hz
Yes
AC
Yes
(1) : Normal Open type. When electric power is NOT supplied, the valve is open. (When electric power is
supplied, the valve is closed.)
(2) : Normal Closed type. When electric power is NOT supplied, the valve is closed. (When electric power is
33
INSTALLATION
OFF
ON
OFF
NC
NO
NC
2 way value 1
5
ON
NO
6
N
N
2 way value 2
Normal Open type should be connected to wire (NO) and wire (N)for valve closing in cooling mode.
Normal Closed type should be connected to wire (NC) and wire (N)for valve closing in cooling mod
(NO) : Line signal (for Normal Open type) from PCB to 2way valve
(NC) : Line signal (for Normal Closed type) from PCB to 2way valve
(N) : Neutral signal from PCB to 2way valve
General Information
Type
Power
SPDT
3-wire
Operating Mode
230V 50Hz AC
Supported
Yes
Yes
(1) : SPDT = Single Pole Double Throw. Three wires consist of Live1 (for selecting (for selecting Flow B), and
Neutral (for common).
(2) : Flow A means water flow from the indoor unit to under floor water circuit.
(3) : Flow B means water flow from the indoor unit to sanitary water tank.
How to Wire 3Way Valve
Follow below procedures Step 1 ~ Step 2.
Step 1. Uncover front cover of the indoor unit and open the control box.
Step 2. Find terminal block and connect wire as below.
34
INSTALLATION
7
OFF
8
ON
9 10
N
OFF
3 way value 1
11 12
ON
3 way value 2
3way valve should select water tank loop when electric power is supplied to wire (OFF) and wire (N).
3way valve should select under floor loop when electric power is supplied to wire (ON) and wire (N).
(OFF) : Line signal (Water tank heating) from PCB to 3way valve
(ON) : Line signal (Under floor heating) from PCB to 3way valve
(N) : Neutral signal from PCB to 3way valve
2.3.9 Gate-controller
If there is gate control function, pull out the leading wire 50 on terminal boardXT2
between19 and 20 and then connect the Gate-controller
Installation Guide follow as:
XT2
20 19
XT2 20 19
Gate-controller
50
Front side
Back side
35
INSTALLATION
1.5 Meters
NO
NO NO
Doors
Note:
Distance between the indoor unit and the remote air temperature senor should be less
than 15 meter due to length of the connection cable of remote air temperature sensor.
Height from floor is approximately 1.5 meter;
Remote air temperature sensor can not be located where the area may be hidden when
door is open;
Remote air temperature sensor can not be located where external thermal influence may
be applied;
Remote air temperature sensor should be installed where space heating is mainly
applied;
Installation Guide follow as:
CN15
PCB
Electric box
36
INSTALLATION
Thermostat:
22 23 24
21
XT3
Cool
Heat
L
(230V)
25 26 27
Cool
Heat
28
L
(24V)
Fig 1
XT3
22 23 24
21
Heat
L
(230V)
25 26 27
Heat
28
L
(24V)
Fig 2
(L) : Live signal from PCB to thermostat
(N): Neutral signal from PCB to thermostat
How to Wire Thermostat
Uncover the front cover of the indoor unit and open the control box
Identify the power specification of the thermostatif it is 230V find terminal block
XT3 as NO.2124; Otherwiseif it is 24Vfind terminal blockXT3 as NO.2528;
If it is Heating/Cooling thermostat please connect wire as Fig 1
If it is Heating only thermostat please connect wire as Fig 2
1)
NEVER USE 230V AC and 24V AC Thermostat at the same time, otherwise, it will cause
short-circuit and power cut-off by circuit breaker;
2)
3)
For other constrains, please refer to previous page where constrains about
4)
5)
Do not connect external electric loads, Wire (L) and (N) should be used only for
operation Electric type thermostat.
6)
Never connect external electric loads such as valves, fan coil units, etc. If connected, PCB of
the indoor unit can be seriously damaged
7)
Thermostat is generally used to control the product by air temperature. When thermostat is
connected to the product, the product operation is controlled by the thermostat.
37