Motor Protection Principles
Motor Protection Principles
Craig Wester
GE Multilin
[email protected]
IEEE STUDY
FAILURE CONTRIBUTOR
Persistent Overload
Normal Deterioration
EPRI STUDY
%
4.20%
FAILED COMPONENT
Stator Ground Insulation
AVERAGE
%
23.00
4.00
3.00
Core
1.00
Cage
5.00
36.00%
High Vibration
16.00
Poor Lubrication
8.00
5.00
Rotor Shaft
2.00
Rotor Core
1.00
33%
Mechanical Related Failures
31%
2
30.70%
32.00%
3
5.8
Bearing Seals
Oil Leakege
6.00
3.00
Abnormal Voltage
1.5
Frame
1.00
Abnormal Frequency
0.6
Wedges
1.00
Abrasive Chemicals
4.2
3.9
19.7
Other Components
21.00
38.70%
Environmental, Maintanence&
Other reasons Related
Failures
36%
32.00%
temperature
165
C causes of
motor
insulation, stator
lifetime to decrease
to
For50%
F class
110
100
90
80
A-CLASS (105 C)
60
50
F-CLASS (155 C)
H-CLASS (180 C)
40
30
Thermal Overload
10
0
Process Caused (Excessive
load)
0
50
100
150
200
250
300
Phase Fault
Ground Fault
Abnormal Operating Conditions
Over & Under Voltage, Under frequency, Voltage and Current Unbalance, Load Loss,
Jamming, Jogging
Motor Starting:
Previous state is Stopped & Current > 0 threshold. Motor current must
increase to the level higher than overload pickup within seconds.
Motor Running:
Previous state is Starting or Overloading & Current drops below overload
pickup level.
Motor Overloading:
Previous state is Running & Current raises above overload pickup level.
Thermal Capacity Used (TCU) begins to accumulate during overload.
Thermal
Limit
Curves:
A
C
B
D
A. Cold
Running
Overload
B. Hot
Running
Overload
C. Cold
Locked
Rotor Curve
1.0
1.1
1.15
1.25
10
Overload Curve
Set the overload curve below cold thermal limit and above hot thermal limit If only
hot curve is provided by mfgr, then must set at or below hot thermal limit
11
NEMA standard temperature rises for motors up to 1500HP and Service Factors
1 and 1.15 respectively.
AMBIENT
CLASS A
CLASS B
CLASS F
CLASS H
When motor is running below overload pickup, the TCU will rise or fall to value
based on average current and HCR. HCR is used to calculate level of TCU by
relay, at which motor will settle for current below overload pickup.
12
HCR=
LRTHOT
LRTCOLD
=> 0.86
LRTcold = 8sec
LRThot = 6sec
LRC = 5.4FLA
13
14
Overload Curve
Selection
A custom
overload curve
will allow the user
to tailor the
relays thermal
damage curve to
the motor such
that a successful
start can occur
without
compromising
protection while
at the same time
utilizing the
motor to its full
potential during
the running
condition.
15
16
Main causes
of current unbalance
Blown fuses
Loose connections
Positive Sequence
17
Negative Sequence
IEQ= (Im2X1+KX(I2/I1))
Im - real motor current; K - unbalance bias factor; I1 & I2 - positive and negative
sequence components of motor current.
18
K factor reflects the degree of extra heating caused by the negative sequence
component of the motor current.
IEEE guidelines for typical and conservative estimates of K.
K =175
ILRC2
TYPICAL
K =230
ILRC2
CONSERVATIVE
19
20
Thermal Model
Overvoltage Protection
The overall result of an overvoltage condition is a decrease in load current and poor
power factor.
21
Although old motors had robust design, new motors are designed close to
saturation point for better utilization of core materials and increasing the V/Hz
ratio cause saturation of air gap flux leading to motor heating.
The overvoltage element should be set to 110% of the motors nameplate unless
otherwise started in the data sheets.
Undervoltage Protection
The overall result of an undervoltage condition is an increase in current and motor
heating and a reduction in overall motor performance.
The undervoltage protection element can be thought of as backup protection for the
thermal overload element. In some cases, if an undervoltage condition exists it may
be desirable to trip the motor faster than thermal overload element.
The under voltage trip should be set to 80-90% of nameplate unless otherwise stated
on the motor data sheets.
Motors that are connected to the same source/bus may experience a temporary under
voltage, when one of motors starts. To override this temporary voltage sags, a time
delay set point should be set greater than the motor starting time.
Unbalance Protection
Indication of unbalance negative sequence current / voltage
Unbalance causes motor stress and temperature rise
Current unbalance in a motor is result of unequal line voltages
Unbalanced supply, blown fuse, single-phasing
22
Mo connection
tor
Rel
ay
23
To limit the level of the ground fault current connect an impedance between the supplies
neutral and ground. This impedance can be in the form of a resistor or grounding
transformer sized to ensure maximum ground fault current is limited
24
25
26
Differential Protection
Differential protection may be considered the first line of protection for internal phase-tophase or phase-to-ground faults. In the event of such faults, the quick response of the
differential element may limit the damage that may have otherwise occurred to the
motor.
27
Differential Protection
Summation method with six CTs:
If six CTs are used in a summing configuration, during motor starting, the values from the
two CTs on each phase may not be equal as the
CTs are not perfectly identical and asymmetrical
currents may cause the CTs on each phase to have
different outputs.
To prevent nuisance tripping in this configuration,
the differential level may have to be set less
sensitive, or the differential time delay may have
to be extended to ride through the problem period
during motor starting.
The running differential delay can then be fine
tuned to an application such that it responds very
fast and is sensitive to low differential current
levels.
28
Differential Protection
between CTs during external faults. CT unbalances arise as a result of CT accuracy errors
or CT saturation.
Characteristic allows for very sensitive settings when the fault current is low and less
sensitive settings when the fault current is high and CT performance may produce
incorrect operating signals.
29
30
Start Inhibit
This function will limit starts when the motor is already hot.
Starts/Hour
31
Acceleration Trip
Set higher than the maximum starting time to avoid nuisance tripping when the voltage is
lower or for varying loads during acceleration.
Conclusions
Induction & synchronous motors are valuable assets to todays industrial facilities.
The temperature rise of motor dictates its life
When applied, thermal protection can prevent loss of motor life
Additional protection elements such as overvoltage, undervoltage, unbalance, ground fault,
differential, short circuit and stator RTD supplement the thermal model protection and provide
complete motor protection.
Harsh conformal coating of motor protection relays should be considered to avoid the
environmental effects of harsh gaseous sulphides (H2S, etc.)
32