1.0 General
1. The Contractor shall design and install complete lightning protection systems for all the
buildings and structures in this Contract. The lightning protection system shall comprise air
termination, down conductors, bonding, testing joints, earth termination pits with electrodes
as specified conforming to IEC 62305 and BS 7430.
2. All earthing installation shall be carried out strictly in accordance with BS 7430:2011, the IEE
Wiring Regulations (IEC 60364 Part 5, Section 54) 17th Edition and requirements of EDC.
3. There shall be separate earthing systems for electrical installation and lightning protection
system and IT system but linked at specific points under the concept of equipotential
earthing.
1.1 Air Termination and Down Conductors
1. The roof conductor shall be copper / aluminium tape fixed in approved manner generally
along square symmetrical lines using air rod base / metal saddles along the roof.
2. The copper down conductors shall then be brought down to the testing clamps and then to
the earth termination pits by the most direct path possible.
1.2 Testing Joint and Clamp
1.
Each down conductor shall be provided with a testing joint in a position convenient to use
when testing. Testing clamp shall be tinned and of screw down pattern complete with bronze
fitting screws. All test clamps must be accessible. Down conductors below test clamps shall
be protected by PVC pipes recessed in structure.
1. All metallic service pipes and steel structure shall be bonded to the electric earth at strategic
locations on the ground floor to prevent dangerous voltage differential between earthing
paths and other metallic pipes/structure during fault conditions.