(Notes For Students) Power Engineering - 7 Distribution
(Notes For Students) Power Engineering - 7 Distribution
Introduction To Power
Engineering
1.3.3
1.3.4
1.3.4.1
1.3.4.2
1.3.4.3
1.3.4.4
1.3.5 Voltages............................................................................................................... 15
1.4
DIFFERENCES BETWEEN EUROPEAN AND NORTH AMERICAN SYSTEMS ..................................... 16
2
2.3.2
2.3.2.1
2.3.2.2
Figure 1: The vertical power system. Power is produced at a few large generators (only one is shown) and
moved over a transmission system consisting of dozens, even hundreds of regional power lines (only one path
is shown). Once brought to the local community, it is reduced in voltage and shipped to neighborhoods, and to
the individual consumer, on a distribution system (only one of thousands of lines and customers is shown).
Some utilities perform all the functions shown, others only a portion.
The subtransmission circuits extend from the bulk power source or sources to the
various distribution substations located in the load area. They may be radial circuits
connected to a bulk power source at only one end or loop and ring circuits connected to one
or more bulk power sources at both ends. The subtransmission circuits consist of
underground cable, aerial cable, or overhead open-wire conductors carried on poles, or
some combination of them.
Each distribution substation normally serves its own load area, which is a subdivision
of the area served by the distribution system. At the distribution substation the
subtransmission voltage is reduced for general distribution throughout the area. The
substation consists of one or more power-transformer banks together with the necessary
voltage regulating equipment, buses, and switchgear.
The area served by the distribution substation is also subdivided and each
subdivision is supplied by a distribution or primary feeder. The three-phase primary feeder
is usually run out from the low voltage bus of the substation to its load center where
it branches into threephase subfeeders and single-phase laterals. The primary feeders and
laterals may be either cable or openwire circuits, operated in most cases at 2400 or 4160
volts.
Distribution transformers are ordinarily connected to each primary feeder and its
subfeeders and laterals. These transformers serve to step down from the distribution
voltage to the utilization voltage. Each transformer or bank of transformers supplies a
consumer or group of consumers over its secondary circuit. Each consumer is connected to
the secondary circuit through his service leads and meter. The secondaries and service
connections may be either cable or open-wire circuits.
Briefly, the problem of distribution is to design, construct, operate, and maintain a
distribution system that will supply agequate electric service to the load area under
consideration, both now and in the future, at the lowest possible cost. Unfortunately, no
one type of distribution system can be applied economically in all load areas, because of
differences in load densities, existing distribution plant, topography, and other local
conditions.
In studying any load area, the entire distribution or delivery system from the bulk
power source-which may be one or more generating stations or power substations, to the
consumers should be considered as a unit. This includes subtransmission-distribution
substations, Primary feeders, distribution transformers, secondaries, and services. All of
these parts are interrelated and should be considered as a whole so that money saved in
one part of the distribution system will not be more than offset by a resulting increase
elsewhere in the system.
For different load areas, or even different parts of the same load area, the most
effective distribution system will often take different forms. Certain principles and features,
however, are common to almost all of these systems. The distribution system should
provide service with a minimum voltage variation and a minimum of interruption. Service
interruptions should be of short duration and affect a small number of consumers. The
overall system cost-including construction, operation, and maintenance of the systemshould be as low as possible consistent with the quality of service required in the load area.
The system should be flexible, to allow its being expanded in small increments, so as to meet
changing load conditions with a minimum amount of modification and expense. This
flexibility permits keeping the system capacity close to actual load requirements and thus
permits the most effective use of system investment. It also largely eliminates the need for
predicting the location and magnitudes of future loads. Therefore, long-range distribution
planning, which is at best based on scientific guesses, can be greatly reduced.
2.
Primary distribution, which carries the load at higher than utilization voltages
from the substation (or other source) to the point where the voltage is
stepped down to the value at which the energy is utilized by the consumer.
Primary distribution lines are medium-voltage circuits.
Secondary distribution, which includes that part of the system operating at
utilization voltages, up to the meter at the consumers premises.
(a)
(b)
(c)
Figure 3: Primary feeder schematic diagram showing trunk or main feeds and laterals or spurs.
This system is formed by tying together primary mains ordinarily found in radial
systems to form a mesh or grid. The grid is supplied by a number of power transformers
supplied in turn from subtransmission and transmission lines at higher voltages. A circuit
breaker between the transformer and grid, controlled by reverse-current and automatic
reclosing relays, protects the primary network from feeding fault current through the
transformer when faults occur on the supply subtransmission or transmission lines. Faults on
Dr Houssem Rafik El Hana Bouchekara
10
sections of the primaries constituting the grid are isolated by circuit breakers and fuses. See
Figure 8.
This type of system eliminates the conventional substation and long primary trunk
feeders, replacing them with a greater number of unit substations strategically placed
throughout the network. The additional sites necessary are often difficult to obtain.
Moreover, difficulty is experienced in maintaining proper operation of the voltage regulators
(where they exist) on the primary feeders when interconnected.
11
12
load among transformers; better normal voltage conditions resulting from such load
distribution; an ability to accommodate load increases by changing only one or some of the
transformers, or by installing a new transformer at some intermediate location without
disturbing the existing arrangement; the possibility that diversity between demands on
adjacent transformers will reduce the total transformer load; more capacity available for
inrush currents that may cause flicker; and more capacity as well to burn secondary faults
clear.
Some disadvantages associated with this type of system are as follows: should one
transformer fail, the additional loads imposed on adjacent units may cause them to fail, and
in turn their loads would cause still other transformers to fail (this is known as cascading);
the transformers banked must have very nearly the same impedance and other
characteristics, or the loads will not be distributed equitably among them; and sufficient
reserve capacity must be provided to carry emergency loads safely, obviating the savings
possible from the diversity of the demands on the several transformers.
Banked secondaries, while providing for failure of transformers, do not provide
against faults on the primary main or feeder. Further, a hazard on any transformer
disconnected for any reason may result from a back feed if the secondary energizes the
primary (which may have been considered safe).
13
up by a fuse so that, should the protector fail to operate, the fuse will blow and disconnect
the transformer from the secondary mains. See Figure 12.
The number of primary feeders supplying a network is very important. With only two
feeders, only one feeder may be out of service at a time, and there must be sufficient spare
transformer capacity available so as not to overload the units remaining in service; therefore
this type of network is sometimes referred to as a single-contingency network.
Most networks are supplied from three or more primary feeders, where the network
can operate with the loss of two feeders and the spare transformer capacity can be
proportionately less. These are referred to as second-contingency networks.
Secondary mains not only should be so designed that they provide for an equitable
division of load between transformers and for good voltage regulation with all transformers
in service, but they also must do so when some of the transformers are no longer in service
when their primary feeders are de-energized. They must also be able to divide fault current
properly among the transformers, and must provide for burning faults clear at any point
while interrupting service to a minimum number of consumers; this often limits the size of
Dr Houssem Rafik El Hana Bouchekara
14
secondary mains, usually to less than 500 cmil 103, so that when additional secondary
main capacity is required, two or more smaller size conductors have to be paralleled. In
some networks, where insufficient fault current might cause long sections of secondary
mains to be destroyed before the fault is burned clear, sections of secondary mains are
fused at each end.
Because these networks may represent very large loads, their size and capacity may
have to be limited to such values as can be successfully handled by the generating or other
power sources should they become entirely de-energized for any reason. When they are deenergized for any length of time, the inrush currents are very large, as diversity among
consumers may be lost, and this may be the limiting factor in restricting the size and
capacity of such networks.
1.3.5 VOLTAGES
For all types of service, primary voltages are becoming higher. Original feeder
primary voltages of about 1000 V have climbed to nominal 2400, 4160, 7620, 13,800,
23,000, and 46,000 V. Moreover, primary feeders that originally operated as single-phase
and two-phase circuits are all now essentially three-phase circuits; even those originally
operated as delta ungrounded circuits are now converted to wye systems, with their neutral
common to the secondary neutral conductor and grounded.
Secondary voltages have changed from nominal 110/220 V singlephase values to
those now operating at 120/240 V single-phase and 120/208 or 120/240 V for three-phase
circuits, the 120-V utilization being applied to lighting and small-motor loads while the 208and 240-V three-phase values are applied to larger-motor loads. More recently, secondary
systems have employed utilization voltage values of 277 and 480 V, with fluorescent lighting
operating single-phase at 277 V and larger motors operating at a three-phase 480 V. To
supply some lighting and small motors single-phase at 120 V, autotransformers of small
capacity are employed to step down the 277 V to 120 V.
Secondary voltages and connections will be explored further in discussing
transformers and transformer connections.
Note: Voltage levels are defined internationally, as follows:
Low voltage: up to 1000 V
Medium voltage: above 1000 V up to 36 kV
High voltage: above 36 kV
Supply standards variation between continents by two general standards have
emerged as the dominant ones:
In Europe
IEC governs supply standards
The frequency is 50 Hz and LV voltage is 230/400 V
In North America
15
1.4 DIFFERENCES
BETWEEN
EUROPEAN
AND
NORTH AMERICAN
SYSTEMS
Distribution systems around the world have evolved into different forms. The two
main designs are North American and European. This book deals mainly with North
American distribution practices; for more information on European systems. For both forms,
hardware is much the same: conductors, cables, insulators, arresters, regulators, and
transformers are very similar. Both systems are radial, and voltages and power carrying
capabilities are similar. The main differences are in layouts, configurations, and applications.
16
Figure 13 compares the two systems. Relative to North American designs, European
systems have larger transformers and more customers per transformer. Most European
transformers are three-phase and on the order of 300 to 1000 kVA, much larger than typical
North American 25- or 50-kVA single-phase units.
Secondary voltages have motivated many of the differences in distribution systems.
North America has standardized on a 120/240-V secondary system; on these, voltage drop
constrains how far utilities can run secondaries, typically no more than 250 ft. In European
designs, higher secondary voltages allow secondaries to stretch to almost 1 mi. European
secondaries are largely three-phase and most European countries have a standard
secondary voltage of 220, 230, or 240 V, twice the North American standard. With twice the
voltage, a circuit feeding the same load can reach four times the distance. And because
three-phase secondaries can reach over twice the length of a single-phase secondary,
overall, a European secondary can reach eight times the length of an American secondary
for a given load and voltage drop. Although it is rare, some European utilities supply rural
areas with single-phase taps made of two phases with single-phase transformers connected
phase to phase.
In the European design, secondaries are used much like primary laterals in the North
American design. In European designs, the primary is not tapped frequently, and primary-
17
level fuses are not used as much. European utilities also do not use reclosing as religiously as
North American utilities.
Some of the differences in designs center around the differences in loads and
infrastructure. In Europe, the roads and buildings were already in place when the electrical
system was developed, so the design had to fit in. Secondary is often attached to
buildings. In North America, many of the roads and electrical circuits were developed at the
same time. Also, in Europe houses are packed together more and are smaller than houses in
America.
Each type of system has its advantages. Some of the major difference between
systems are the following:
Cost The European system is generally more expensive than the North
American system, but there are so many variables that it is hard to compare
them on a one-to-one basis. For the types of loads and layouts in Europe,
the European system fits quite well. European primary equipment is
generally more expensive, especially for areas that can be served by singlephase circuits.
Flexibility The North American system has a more flexible primary design,
and the European system has a more flexible secondary design. For urban
systems, the European system can take advantage of the flexible secondary;
for example, transformers can be sited more conveniently. For rural systems
and areas where load is spread out, the North American primary system is
more flexible. The North American primary is slightly better suited for
picking up new load and for circuit upgrades and extensions.
Safety The multigrounded neutral of the North American primary system
provides many safety benefits; protection can more reliably clear faults, and
the neutral acts as a physical barrier, as well as helping to prevent dangerous
touch voltages during faults. The European system has the advantage that
high-impedance faults are easier to detect.
Reliability Generally, North American designs result in fewer customer
interruptions. Some researchers simulated the performance of the two
designs for a hypothetical area and found that the average frequency of
interruptions was over 35% higher on the European system. Although
European systems have less primary, almost all of it is on the main feeder
backbone; loss of the main feeder results in an interruption for all customers
on the circuit. European systems need more switches and other gear to
maintain the same level of reliability.
Power quality Generally, European systems have fewer voltage sags and
momentary interruptions. On a European system, less primary exposure
should translate into fewer momentary interruptions compared to a North
American system that uses fuse saving. The three-wire European system
helps protect against sags from line-to-ground faults. A squirrel across a
bushing (from line to ground) causes a relatively high impedance fault path
that does not sag the voltage much compared to a bolted fault on a well-
18
Outside of Europe and North America, both systems are used, and usage typically
follows colonial patterns with European practices being more widely used. Some regions of
the world have mixed distribution systems, using bits of North American and bits of
European practices. The worst mixture is 120-V secondaries with European-style primaries;
the low-voltage secondary has limited reach along with the more expensive European
primary arrangement.
Higher secondary voltages have been explored (but not implemented) for North
American systems to gain flexibility. Higher secondary voltages allow extensive use of
secondary, which makes undergrounding easier and reduces costs. Westinghouse engineers
contended that both 240/480-V three-wire single-phase and 265/460-V four-wire
threephase secondaries provide cost advantages over a similar 120/240-V threewire
secondary (Lawrence and Griscom, 1956; Lokay and Zimmerman, 1956). Higher secondary
voltages do not force higher utilization voltages; a small transformer at each house converts
240 or 265 V to 120 V for lighting and standard outlet use (air conditioners and major
appliances can be served directly without the extra transformation). More recently,
Bergeron et al. (2000) outline a vision of a distribution system where primary-level
distribution voltage is stepped down to an extensive 600-V, three-phase secondary system.
At each house, an electronic transformer converts 600 V to 120/240 V.
2 LOAD CHARACTERISTICS
In the planning of an electrical distribution system, as in any other enterprise, it is
necessary to know three basic things:
1. The quantity of the product or service desired (per unit of time)
2. The quality of the product or service desired
3. The location of the market and the individual consumers
Logically, then, it would be well to begin with the basic building blocks, the individual
consumers, and then determine efficient means of supplying their wants, individually and
collectively.
Dr Houssem Rafik El Hana Bouchekara
19
2.1
DEFINITIONS
2. Maximum Demand
Example: the 15-minute maximum kW demand for the week was 150 kW
3. Average Demand
The average of the demands over a specified period (day, week, month, etc.)
4. Diversified Demand
Example: the 15-minute maximum diversified kW demand for the week was
500 kW
For a group of loads, the sum of the individual maximum demands without
any restriction that they occur at the same time
20
7. Demand Factor
8. Utilization Factor
9. Load Factor
2.2.1 DEMAND
In order to define the load, the demand curve is broken into equal time intervals. In
Figure 14 the selected time interval is 15 minutes. In each interval the average value of the
demand is determined. In Figure 14 the straight lines represent the average load in a time
interval. The shorter the time interval, the more accurate will be the value of the load. This
process is very similar to numerical integration. The average value of the load in an interval
is defined as the 15-minute kW demand.
The 24-hour 15-minute kW demand curve for a customer is shown in Figure 15. This
curve is developed from a spreadsheet that gives the 15-minute kW demand for a period of
24 hours.
21
The total energy consumed during the day is the summation of all of the 15-minute
interval consumptions. From the spreadsheet, the total energy consumed during the period
by Customer #1 is 58.96 kWh. The 15-minute average kW demand is computed by:
22
( 2)
23
24
25
26
A graph of the diversity factors is shown in Figure 21. Note in and Figure 21 that the
value of the diversity factor basically leveled out when the number of customers reached 70.
This is an important observation because it means, at least for the system from which these
diversity factors were determined, that the diversity factor will remain constant at 3.20 from
70 customers up. In other words, as viewed from the substation, the maximum diversified
demand of a feeder can be predicted by computing the total noncoincident maximum
demand of all of the customers served by the feeder and dividing by 3.2.
27
28
( 9)
This maximum diversified demand becomes the allocated load for the transformer.
Knowing the maximum demand for each customer is the first step in developing a
table of diversity factors as shown in Table 2. The next step is to perform a load survey
where the maximum diversified demand of groups of customers is metered. This will involve
selecting a series of locations where demand meters can be placed that will record the
maximum demand for groups of customers ranging from at least 2 to 70. At each meter
location the maximum demand of all downstream customers must also be known. With that
data, the diversity factor can be computed for the given number of downstream customers.
Example 1:
A single-phase lateral provides service to three distribution transformers as shown in
Figure 24. The energy in kWh consumed by each customer during a month is known. A load
survey has been conducted for customers in this class, and it has been found that the
customer 15-minute maximum kW demand is given by the equation:
The results of this calculation for the remainder of the customers is summarized
below by transformer.
29
30
31
Example 1 demonstrates that Kirchhoffs current law (KCL) is not obeyed when the
maximum diversified demands are used as the load flowing through the line segments and
through the transformers. For example, at node N1 the maximum diversified demand
flowing down the line segment N1-N2 is 92.8 kW, and the maximum diversified demand
flowing through transformer T1 is 30.3 kW. KCL would then predict that the maximum
diversified demand flowing down line segment N2-N3 would be the difference of these, or
62.5 kW. However, the calculations for the maximum diversified demand in that segment
was computed to be 72.6 kW. The explanation is that the maximum diversified demands for
the line segments and transformers dont necessarily occur at the same time. At the time
that line segment N2-N3 is experiencing its maximum diversified demand, line segment N1N2 and transformer T1 are not at their maximum values. All that can be said is that, at the
time segment N2-N3 is experiencing its maximum diversified demand, the difference
between the actual demand on line segment N1-N2 and the demand of transformer T1 will
be 72.6 kW. There will be an infinite amount of combinations of line flow down N1-N2 and
through transformer T1 that will produce the maximum diversified demand of 72.6 kW on
line N2-N3.
32
( 12)
The transformer demand will be either kW or kVA depending upon the metered
quantity.
When the kW or kVA is metered by phase, then the load can be allocated by phase
where it will be necessary to know the phasing of each distribution transformer. When the
maximum current per phase is metered, the load allocated to each distribution transformer
can be done by assuming nominal voltage at the substation and then computing the
resulting kVA. The load allocation will now follow the same procedure as outlined above. If
there is no metered information on the reactive power or power factor of the feeder, a
power factor will have to be assumed for each transformer load.
Modern substations will have microprocessor-based metering that will provide kW,
kvar, kVA, power factor, and current per phase. With this data, the reactive power can also
be allocated. Since the metered data at the substation will include losses, an iterative
process will have to be followed so that the allocated load plus losses will equal the metered
readings.
Example 2:
Assume that the metered maximum diversified kW demand for the system of
Example 1 is 92.9 kW. Allocate this load according to the kVA ratings of the three
transformers.
Solution:
Dr Houssem Rafik El Hana Bouchekara
33
Which method to use depends upon the purpose of the analysis. If the purpose is to
determine as closely as possible the maximum demand on a distribution transformer, then
either the diversity factor or the transformer load management method can be used.
Neither of these methods should be employed when the analysis of the total feeder is to be
performed. The problem is that using those methods will result in a much larger maximum
diversified demand at the substation than actually exists. When the total feeder is to be
analyzed, the only method that gives good results is that of allocating load based upon the
kVA ratings of the transformers.
34
In order to avoid an iterative solution, the voltage at the source is assumed and the
voltage drops calculated from that point to the last transformer.
Example 3 demonstrates how the method of load allocation using diversity factors is
applied. The same system and allocated loads from Example 1 are used.
Example 3:
For the system of Example 2.1, assume the voltage at N1 is 2400 volts and compute
the secondary voltages on the three transformers using the diversity factors. The system of
Example 2.1, including segment distances, is shown in Figure 2.12.
Assume that the power factor of the loads is 0.9 lagging.
The impedance of the lines are: z = 0.3 + j0.6 /mile
The ratings of the transformers are
Solution:
From Example 1 the maximum diversified kW demands were computed. Using the
0.9 lagging power factor, the maximum diversified kW and kVA demands for the line
segments and transformers are
35
36
37
38
39
Example 5:
Shown below are the 15-minute kW demands for four customers between the hours
of 17:00 and 21:00. A 25-kVA single-phase transformer serves the four customers.
40
The following table gives the time interval and kVA demand of the four customer
demands during the peak load period of the year. Assume a power factor of 0.9 lagging.
The 15-minute kW demands for the 12 customers between the hours of 5:00 p.m.
and 9:00 p.m. are given in the tables that follow. Assume a load power factor of 0.95 lagging.
The impedance of the lines are z = 0.306 + j0.6272 /mile. The voltage at node N1 is 2500 V.
Transformer ratings:
41
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
42
Example 8:
A single-phase lateral serves four transformers as shown in Figure 28.
Example 9:
Assume that each customers maximum demand is 15.5 kW +j7.5 kvar. The
impedance of the single-phase lateral is z=0.4421+j0.3213/1000 ft. The four transformers
are rated as:
T1 and T2: 37.5 kVA, 2400-240 V,
Z=0.01+j0.03 per-unit
T3 and T4: 50 kVA, 2400-240 V,
Z=0.015+j0.035 per-unit
Use the diversity factors found in Table 2 and determine:
(1) The 15-minute maximum diversified kW and kvar demands on each
transformer.
(2) The 15-minute maximum diversified kW and kvar demands for each line
section.
(3) If the voltage at node 1 is 2600 V, determine the voltage at nodes 2,3,4,5,6,7,8,
and 9. In calculating the voltages, take into account diversity using the answers
from (1) and (2) above.
(4) Use the 15-minute maximum diversified demands at the lateral tap (Section 12) from Part (2) above. Divide these maximum demands by 18 (number of
customers) and assign that as the instantaneous load for each customer. Now
calculate the voltages at all of the nodes listed in Part (3) using the
instantaneous loads.
(5) Repeat Part (4) above, but assume the loads are constant current. To do this,
take the current flowing from node 1 to node 2 from Part (4) above, divide by
18 (number of customers), and assign that as the instantaneous constant
current load for each customer. Again, calculate all of the voltages.
(6) Take the maximum diversified demand from node 1 to node 2 and allocate that
to each of the four transformers based upon their kVA ratings. To do this, take
the maximum diversified demand and divide by 175 (total kVA of the four
transformers). Now multiply each transformer kVA rating by that number to
43
give how much of the total diversified demand is being served by each
transformer. Again, calculate all of the voltages.
(7) Compute the percent differences in the voltages for Parts (4), (5), and (6) at
each of the nodes using the Part (3) answer as the base.
Example 10:
Given a 120-volt 15-ampere branch circuit supplies a load which consists of four
lamps. Each lamp draws 3 amperes of current from the source. The lamps are located at 10foot intervals from the power distribution panel. The resistance of 1000 feet of No. 14
copper wire is 2.57 ohms.
Find the voltage across lamp No 4.
Figure 29: Circuit for calculating the voltage drop in a branch circuit.
Solution:
a. The resistance of 1000 feet of No. 14 copper wire is 2.57 ohms.
Therefore, the resistance of 20 feet of wire is:
44
Notice that the voltage across lamp No. 4 is substantially reduced from the 120-volt
source value due to the voltage drop of the conductors. Also, notice that the resistances
used to calculate the voltage drops represented both wires (hot and neutral) of the branch
circuit. Ordinarily, 120-volt branch circuits do not extend more than 100 feet (30.48 meters)
from the power distribution panel. The preferred distance is 75 feet (22.86 meters). The
voltage drop in branch-circuit conductors can be reduced by making the circuit shorter in
length or by using larger conductors.
In residential electrical wiring design, the voltage drop in many branch circuits is
difficult to calculate since the lighting and portable appliance receptacles are placed on the
same branch circuits. Since portable appliances and plug-in lights are not used all of the
time, the voltage drop will vary according to the number of lights and appliances in use. This
problem is usually not encountered in an industrial or commercial wiring design for lights,
since the lighting units are usually larger and are permanently installed on the branch
circuits.
Example 11:
Given a single-phase 240-volt load in a factory is rated at 85 kilowatts. The feeders
(two hot lines) will be 260-foot lengths of RHW copper conductor. The maximum conductor
voltage drop allowed is 2%.
Find the feeder conductor size required.
45
Solution:
Determine the feeder conductor size. The next larger size conductor is 400 MCM.
The 400 MCM RHW copper conductor will carry 335 amperes. This is less than the required
354.2 amperes, so use the next larger size, which is a 500 MCM conductor.
Example 12:
Given a 480-volt three-phase three-wire (delta) feeder circuit supplies a 45-kilowatt
balanced load to a commercial building. The load operates at a 0.75 power factor. The
feeder circuit (three hot lines) will be a 300-foot length of RH copper conductor. The
maximum voltage drop is 1%.
Find the feeder size required (based on the voltage drop of the circuit).
Solution:
46
Determine the feeder conductor size. The closest and next larger conductor size is
No. 1 AWG. The No. 1 AWG RH copper conductor will carry 130 amperes, much more than
the required 72.25 amperes. Therefore, use No. 1 AWG RH copper conductors for the feeder
circuit.
Example 13: The single-phase distributor
A two-core, single-phase distributor, ABCD, is 640 m long, is fed at end A only, and
supplies loads at B, C, and D. the distance from A to B is 274.3 m, that from B to C is 274.3 m,
and that from C to D is 91.4 m. the distributor has a resistance of 0.2 and an inductive
reactance of 0.075 , each per 914.4 m of single core. Calculate the voltage required at A so
that the voltage at D shall be 220 V when the loads are as follows:
60 A at 0.8 PF. lagging, at B;
50 A at 0.9 PF. lagging, at C;
30 A at unity PF., at D.
The distributor is represented by a single-line diagram in figure 1.5.
Example 14: Distributor fed from both ends
47
Calculate the current distribution and the voltage at points B and C when the
distributor in example 1.3 is fed at both ends at 250 V, the load being unaltered.
In figure 1.6, the current fed in from end A is assumed to be
the other sections have been obtained using Kirchhoffs first law.
Solution:
Hence the current distribution is as in figure 1.7.
Obviously, these currents are alternating, but the arrows are useful in that they
indicate the direction of energy flow. Also they show that B is the point of minimum
potential.
Example 15:
Calculate the current distribution when the distributor in example 1.4 is fed at end A
at 250 V and at end B at 245 V, the load being unaltered.
Example 16: Distribution networks
Calculate the current distribution when the two-core ring main represented by the
single-line diagram, figure 1.10, is fed at point A.
Solution:
The solution is the same as that for a distributor fed from both ends at the same potential.
See example 1-4.
Hence the current distribution is as shown in figure 1.11.
Example 17:
Calculate the current distribution when the two-core ring main represented by the
single-line diagram, figure 1.12, is fed at point A at 250 V. hence calculate the voltage at
each load point.
48