Intruduction Final LV
Intruduction Final LV
QICC a Nexans Company is committed to deliver the highest standard wires and power cables to
the local market, GCC and for export.
In order to fit for the customer demand in the Middle East and for export, QICC a Nexans Company
produces a versatile product range covers most of our customer needs:
BUILDING SECTION:
Flexible wires and cables up to 16 mm2 to IEC 60227, EN 50525, BS 6004 & BS 6500.
Building wires (NYA) to IEC 60227, EN 50525 and BS 6004, from 1.5 mm2 and above.
Halogen Free Flame Retardant wire (HFFR/LSZH) to BS 7211 and EN 50525, with thermo
setting insulation which is alternative to wire type (NYA), where the application requires higher
standards of safety against the emission of smoke, fumes and toxic gases.
The wires coming mainly single core.
DESIGN CRITERIA
A power cable is an assembly of one or more electrical conductors, usually held together with an
overall sheath. The assembly is used for transmission of electrical power. Power cables may be
installed as permanent wiring within buildings, buried in the ground, run overhead, or exposed.
Flexible power cables are used for portable devices, mobile tools and machinery.
1. CONDUCTOR:
Is an object or type of material that permits the flow of electrical current in one or more directions.
Conductor materials are:
- Plain annealed or tin coated copper conductor (to BS EN 1977, ASTM B3, ASTM B49 &ASTM B 33)
- Aluminum (to ASTM B233)
The conductor structure is complying with the requirements of IEC 60228 class 2 stranded, non
compacted, compacted or compacted sector shaped conductors.
2. INSULATION:
The insulating materials used include:
2.1 Polyvinylchloride (PVC): (PVC/A 70 oC) complying with IEC 60502-1 requirements or Types (TI1
70 oC) & Heat Resistant PVC type TI-3 (90 oC to 105 oC) complying with BS EN 50363-3.
2.2 Halogen-Free, Flame Retardant compound (HFFR).
2.3 Cross-linked polyethylene (XLPE): complying with IEC 60502 and GP8 as per BS 7655-1.3
The insulation of building wires is covered by Ultra-violet (UV) resistant Masterbatch.
Colors to BS 5467
Brown or Blue
4. SCREEN DESIGNS:
The standard range of QICC Medium Voltage XLPE cables rated up to and including 33 kV
incorporates copper wire screens based on fault levels of either 3 kA or 10 kA for 1 second. If either
of the standard screen designs does not suit a particular installation, the screen constructions can be
tailored in size to meet the specific fault requirements of any operating system.
6. CABLE ASSEMBLY:
The Insulated cores are assembled together to form the laid up cable cores in case of multi core
cables.
Extruded suitable polymer compound or non-hygroscopic polypropylene filler is applied (when
required) between laid up cores to provide a circular shape to the cable.
7. JACKETINGS:
There are 3 different types of extruded sheaths:
7.1 Outer sheath
It provides protection of the cable from outside.
7.2 Inner sheath
It applies under a metallic protection and - optional - under a lead sheath.
7.3 Bedding
It separate the sheath applied between a lead sheath and a metallic protection (may also
consists of plastic tapes).
Polyvinylchloride (PVC) Type ST2 compounds as specified in IEC 60502-1, or its equivalent
PVC Type 9 to BS 7655-4.2.
Polyethylene (PE) compound fulfill and exceed the requirements of Type ST7 IEC 60502-1
for cables that require being abrasion resistant, protected against water ingress and strong
Environmental Stress Crack Resistant (ESCR).
Halogen Free Flame Retardant (HFFR) compounds complying with ST8 to IEC 60502-1
or Types LTS 1 & LTS 4 to BS 7655: section 6 for cables installed in intrinsically safe locations
and where the cables require being low smoke, low fume and low toxic gas emitting in case of
fire. Cables to this category are complying with the requirements of BS 6724.
All cables produced at QICC a Nexans Company with PVC or HFFR jackets are complying
with the flame retardant test to IEC 60332-1 and Ultra-violet (UV) resistant Masterbatch.
Whenever a requirement for more severe tests as IEC 60332-3 is needed, Oil resistant and
Hydrocarbon resistant for Oil and Gas projects.
8. ARMOUR:
There are 3 different types of armouring are listed below:
Galvanized round steel wire armour SWA:
(The wire diameter depends on the cable diameter under armour, min. diameter 0.9 mm).
Single or double layer of steel STA :
(The minimum thickness of a tape shall be 0.2 mm).
Aluminum or copper wire armour AWA / CWA:
(The wire diameter depends on the cable diameter under armour, min. diameter 0.9 mm).
9. JACKETING MARKETING:
Standard engraving outer Jacket Marking consisting of:
1.
2.
3.
4.
10. INSTALLATION
Low voltage cables with both PVC and XLPE insulation are suitable for indoor and outdoor
applications. The methods are based on IEC 60364-5-52 or BS 7671 IEE wiring regulation
seventeenth edition.
Below are the recommendations to be followed in order to get the optimal cable service:
1.
Unarmoured cables are not recommended for direct buried applications, except if the
quoted cables are designed and produced to pass direct burial test requirements (example, direct
burial tests described in UL 1277 and UL 1581).
2.
Armoured cables are not recommended for tray applications, as they are heavy in weight
and extra loads are exerted on the tray.
3.
A PVC jacket is a very stable material against a wide range of chemicals, while HDPE
jacketed cables can serve better in wet locations.
4.
A recommended minimum bending radius as per the technical data sheet of each group.
5.
HFFR cables are not recommended for direct buried applications, as the material is soft and
its mainly for building proposes.
10.1
Care should be taken to prevent damage to insulation or distortion of cable during installation.
The pulling force in Newtons should not exceed 0.036 times the circular mil area of the copper
cross-sectional area times the number of conductors in the cable when pulling on the conductors
utilizing pulling eyes and bolts. Pulling force for multi core cables when utilizing eyes or bolts should
not include drain or ground conductors in the copper cross-sectional area. When pulling with a
basket weave grip, maximum pulling tension (per grip) should not exceed 4.5kN, or the value
calculated for eyes or bolts, whichever is greater.
The sidewall pressure should not exceed a maximum of 7.3kN per meter of the inside radius of the
bend.
Cables should not be pulled in freezing conditions. If conditions are below 0C, consult the
manufacturer.
If it is necessary to pull in these conditions, cables should be stored at a temperature above 10C for
24 h prior to installation, if the cable has been previously stored in an area under 0C.
When installing low smoke cables, additional consideration should be given to handling and
lubrication due to their possible lower tear strength and higher coefficient of friction than other
marine cable.
For more guidance concerning this subject, refer to IEEE Std 576-2001
10.2
Single-conductor ac cables:
Closed magnetic circuits around single-conductor ac cable should be avoided, and no magnetic
material should be permitted between cables of different phases of a circuit.
1.
Single-conductor ac cables should not be located closer than 76mm from parallel magnetic
material.
2.
Single-conductor ac cable should be supported on insulators. Armor, if used, should be
grounded only at approximately the midpoint of the cable run.
3.
Where single-conductor ac cables penetrate the bulkhead, conductors of each phase of the
same circuit should pass through a common nonferrous bulkhead plate to prevent heating of the
bulkhead.
4.
Single-conductor cables in-groups should be arranged to minimize their inductive effect. This
may be accomplished by the transposition of cables in groups of three (one each phase) to give the
effect of triplexed cable. This transposition should be made at intervals of not over 15m and need not
be made in cable runs of less than 30m.
10.3
All cable should be continuous between terminations; however, splicing is permitted under certain
conditions. For cable provided with armor, the armor should be electrically continuous between
terminations and should be grounded at each end (multi conductor cables only); except that for final
sub circuits, the armor may be grounded at the supply end only.
10.4
Cable locations:
Cable installation should avoid spaces where excessive heat and gases may be encountered such as
galleys, boiler rooms and pump rooms, and spaces where cables may be exposed to damage such
as cargo spaces and exposed sides of deck houses. Cables should not be located in cargo tanks,
ballast tanks, fuel tanks, or water tanks except to supply equipment and instrumentation specifically
designed for such locations and whose functions require it to be installed on the tank. Such
equipment may include submerged cargo pumps and associated control devices, cargo monitoring,
and underwater navigation systems.
Unless unavoidable, cables should not be located behind or embedded in structural heat insulation.
Where cables are installed behind paneling, all connections should be readily accessible and the
location of concealed connection boxes should be indicated. Cables should preferably not be run
through refrigerated cargo spaces.
Cables should not be located below the faceplate of the vessel s main bottom structural members or
within .6m above any double bottom tank top.
10.5
Cable protection:
Cables should be adequately protected where exposed to mechanical damage. Cables should be
secured against chafing or displacement due to vibration. Cables in bunkers, and where particularly
liable to damage, such as locations in way of cargo ports, hatches, tank tops, and where passing
through decks, should be protected by removable metal coverings, angle irons, or other equivalent
means.
Where cables pass through insulation, they should be protected by a continuous pipe. For wiring
entering refrigerated compartments, the pipe should be of heat-insulating material (fiber or phenolic
tubing) joined to the bulkhead-stuffing tube, or a section of such material should be inserted between
the bulkhead-stuffing tube and the metallic pipe.
Where cables are installed in pipes, the space factor (ratio of the sum of the cross-sectional areas
corresponding to the external diameter of the cables to the internal cross-sectional areas of the pipe)
shall not be greater than 0.41, except for two cables, where the space factor shall not exceed 0.31,
Pipes shall be so arranged or designed to prevent the accumulation of internal condensation.
MANUFACTURING CHART
ELECTRICAL CHARACTERISTICS
STANDARDS RELATED TO POWER CABLES
1.
DOCUMENT NO.
DOCUMENT NAME
IEC 60038
IEC 60050-121
IEC 60060-1
IEC 60227-1
IEC 60227-2
IEC 60227-3
IEC 60227-4
IEC 60227-5
IEC 60227-6
IEC 60227-7
IEC 60229
IEC 60230
IEC 60270
IEC 60287-1-3
Electric Cables - Calculation of the Current Rating - Part 1-3: Current Rating
Equations (100% Load Factor) and Calculation of Losses - Current Sharing
between Parallel Single-Core Cables and Calculation of Circulating Current
Losses - First Edition
Electric cables Calculation of the current rating Part 2-1: Thermal
resistance Calculation of the thermal resistance CORRIGENDUM 1 Edition1.2
IEC 60287-2-1
IEC 60332-3-10
Tests on electric and optical fibre cables under fire conditions Part 3-10:
Test for vertical flame spread of vertically-mounted bunched wires or cables
Apparatus - Edition 1.1; Consolidated Reprint
IEC 60332-3-21
Tests on Electric Cables Under Fire Conditions - Part 3-21: Test for Vertical
Flame Spread of Vertically-Mounted Bunched Wires or Cables - Category A
F/RFirst Edition
IEC 60332-3-22
Tests on electric and optical fiber cables under fire conditions Part 3-22:
Test for vertical flame spread of vertically-mounted bunched wires or cables
Category A - Edition 1.1; Consolidated Reprint
IEC 60332-3-23
Tests on electric and optical fiber cables under fire conditions Part 3-23:
Test for vertical flame spread of vertically-mounted bunched wires or cables
Category B - Edition 1.1; Consolidated Reprint
IEC 60332-3-24
Tests on electric and optical fiber cables under fire conditions Part 3-24:
Test for vertical flame spread of vertically-mounted bunched wires or cables
Category C - Edition 1.1; Consolidated Reprint
IEC 60332-3-25
Tests on electric and optical fiber cables under fire conditions Part 3-25:
Test for vertical flame spread of vertically-mounted bunched wires or cables
Category D - Edition 1.1; Consolidated Reprint
IEC 60364-5-52
IEC 60446
IEC 60502-1
Power cables with extruded insulation and their accessories for rated voltages
from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) Part 1: Cables for
rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV) - Edition 2.1;
Consolidated Reprint
Power Cables with Extruded Insulation and Their Accessories for Rated
Voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2:
Cables for Rated Voltages from 6 kV (Um = 7,2 kV) and up to 30 kV (Um =
36 kV) - Edition 2
Calculation of the Lower and Upper Limits for the Average Outer Dimensions
of Cables with Circular Copper Conductors and of Rated Voltages up to and
Including 450/750 V - Edition 2; CENELEC EN 60719: 1993
IEC 60502-2
IEC 60719
IEC 60724
IEC 60826
IEC 60840
Power cables with extruded insulation and their accessories for rated voltages
above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV) Test methods and
requirements - Third Edition
IEC 60853-3
IEC 60865-1
IEC 60885-1
Electrical test methods for electric cables Part 1: Electrical tests for cables,
cords and wires for voltages up to and including 450/750 V - First Edition
IEC 60885-3
Electrical Test Methods for Electric Cables Part 3: Test Methods for Partial
Discharge Measurements on Lengths of Extruded Power Cable First Edition First Edition
IEC 60889
IEC 60986
IEC 61089
IEC 62067
Power cables with extruded insulation and their accessories for rated voltages
above 150 kV (Um = 170 kV) up to 500 kV (Um = 550 kV) Test
methods and requirements - Edition 1.1 * Consolidated Reprint
IEC TR 61597
IEC TS 61394
2.
DOCUMENT NAME
BS 5099
BS 5467
BS 6004
BS 6469-99.1
BS6724
BS 7211
BS 7655
BS 7655
Specification for Insulating and sheathing materials for cables. Section 1.2
General 90C application
BS 7655-0
BS 7655-1.3
BS 7655-4.2
Specification for Insulating and sheathing materials for cables - Part 4. PVC
sheathing compounds - Section 4.2: General application
BS 7835
BS 7846
BS 7870-4.10
BS 7870-4.11
BS 7870-4.20
BS 7889
BS 7970
Electric cables - metallic wire foil sheat constructions of power cables having
XLPE insulation for rated voltage from 66 kv (Um = 72.5 kv) to
132 kv (Um = 145 kv)
BS EN 10257-1:
Zinc or Zinc alloy coated non-alloy steel wire for armoring either power
cables or telecommunication cables
BS EN 50267-2-1
Common test methods for cables under fire conditions - Test on gases
evolved during combustion of materials from cables.
EN50525-2-31
Electric cables Low voltage energy cables of rated voltages up to and including 450/750 V
(U0/U) Part 2-31: Cables for general applications Single core non-sheathed cables with thermoplastic PVC insulation
EN50525-3-41
Electric cables Low voltage energy cables of rated voltages up to and including 450/750 V
(U0/U) Part 3-41: Cables with special fire performance Single core non-sheathed cables with halogen-free cross linked insulation
and low emission of smoke
BS EN 50363-3
Insulating, sheathing and covering materials for low voltage energy cables Part 3: PVC insulating compounds
BS EN 50363-4-1
Insulating, sheathing and covering materials for low voltage energy cables
BS EN 50363-5
Insulating, sheathing and covering materials for low voltage energy cables
BS EN 60230
BS EN 60332-1-2
BS EN 60332-2-2
Test on electric and optical fiber cables under fire conditions - Part 1-2: Test
for vertical flame propagation for a single small insulated wire or cable Procedure for diffusion flame
BS EN 60332-3-24
BS EN 60811-1-1
BS EN 60811-1-2
Common test methods for insulating and sheathing materials of electric and
optical cables
Insulating and sheathing materials of electric and optical cables - Common
Test methods
BS EN 60811-1-3
BS EN 60885-3
BS EN 61034-2
Measurement of smoke density of cables burning under defined condition Part 2: Test procedure and requirements.
BS EN 62230
BS EN ISO 14001
BS EN ISO 6892-1
BS EN ISO 9001
BS OSHAS 18001
SELECTION OF CABLES:
It is essential to consider the specific system and installation conditions to be able to select the right
cable.
The following criteria should be taken into account to choose the suitable cable.
1. Cable Laying:
Depending on the nature of the cable system (fixed or mobile) a rigid or flexible cable should be
selected. The appropriate protection of a cable will be determined taking into account the
mechanical stress and presence of chemical, oils or hydrocarbons.
3. Nature of Conductors
Copper or aluminum conductors can be used.
For equal current rating aluminum cross-section
= 1.28 copper cross-section
For equal ohmic resistance aluminum cross-section
= 1.65 copper cross-section
For copper, sector shaped conductors are available
On request from 70 mm2 and above
6. Load to be carried.
7. Frequency.
8. Magnitude and duration of possible overload Emergency current.
9. Magnitude and duration of short-circuit current for conductor and screen.
10.Length of line.
11.Voltage drop.
12.Chemical and physical properties of soil.
13.Min. and Max. ambient air temperatures and soil temperature.
14.Specification and requirements to be follow.
VOLTAGE:
The VOLTAGE Is the electric potential difference between two points, or the difference in electric
potential energy of a unit charge transported between two points, The standard rate voltage are
defined by three values Uo / U (Um), where :
Uo = rated rms power frequency voltage, core to screen or sheath.
U
Uo / U
(kV)
Um
(kV)
0.6/1 1.8/3 3.6/6 6/10 8.7/15 12/20 18/30 38/66 76/132 127/220
1.2
3.6
7.2 12
17.5
24
36
72.5
145
245
Cable design for 6/10, 12/20 and 18/30 kV is applicable for 6.35/11, 12.7/22 and 19/33 kV respectively.
Metal
Copper (annealed)
Copper (hard drawn)
Tin copper
Aluminum
Lead
Relative
Conductivity
100
97
95 - 97
61
8
Electrical Resistivity
at 20 C ohm. m
(10-8)
1.7241
1.777
1.741 - 1.814
2.8264
21.4
Temperature
Coefficient of
Resistance per C
0.00393
0.00393
0.00393
0.00403
0.0040
Unit
Copper
Aluminum
Lead
8890.00
2703.00
11340.00
17.00
1083.00
3.80
23.00
659.00
2.40
29.00
327.00
0.34
225.00
70-90
Physical Properties:
Property
Density at 20 C
kg / m
Per C x 10
C
W/cm C
Mn/m2
-6
4. INDUCTANCE
L : Inductance
Uo
U
d: Conductor diameter
2. RESISTANCE
mH/km
5. REACTANCE
Rt=R20x[l+20(t-20)]
/km
Rt : conductor DC resistance at t C
/km
X = 2 f L x 10-3
/km
/km
X: Reactance
/km
t : operating temperature
f : Frequency
Hz
L : Inductance
mH/km
6. IMPEDANCE
R2ac X 2
/km
Z=
RAC = Rt x[ 1+ ys + yp ]
X : Reactance
/km
/km
yp : proximity effect
7. INSULATION RESISTANCE
R=
3. CAPACITANCE
1000 * LN (D/d)
2*
F/km
C : Operating capacitance
F/km
mm
d : Conductor diameter
mm
R : Insulation resistance at 20 C
M.km
mm
mm
8.CHARGING CURRENT
I = Uo x 2 f x C x 10-6
I : Charging current
A/km
C : Capacitance to neutral
F/km
We recommend voltage drops not to exceed:
9. DIELECTRIC LOSSES
D = 2 f C Uo 2 tan 10-6
watt/km/phase
D : Dielectric losses
watt/km/phase
C : Capacitance to neutral
F/km
1. In DC
ISC(t) = ISC(1) / t
kA
kA
kA
u : Voltage drop
/km
X : Reactance
: Length
km
1.0
0.9
0.8
0.71
0.6
0.5
0.0
0.44
0.6
0.71
0.8
0.87
: 30 C
: 20C Depth
: 0.70 m
:2.5 K.m/W
For other installation conditions or any value of different air/ ground temperature, depth of laying,
different soil thermal resistivity the customer is divided to multiply the tabulated current rating by the
de-rating factor values as in tables 1 to 8.
DERATING FACTORS
1. INSTALLATION CONDITIONS FOR CABLES IN AIR
Table 1: Rating factors for ambient air temperatures other than 30 C to be applied to the
current-carrying capacities for cables in the air:
Ambient
temperature
a C
Insulation
PVC
XLPE
and
EPR
Mineral a
PVC covered
or bare and
exposed to
touch 70 C
Bare not
exposed to
touch 105
C
10
1,22
1,15
1,26
1,14
15
1,17
1,12
1,20
1,11
20
1,12
1,08
1,14
1,07
25
1,06
1,04
1,07
1,04
30
1,00
1,00
1,00
1,00
35
0,94
0,96
0,93
0,96
40
0,87
0,91
0,85
0,92
45
0,79
0,87
0,78
0,88
50
0,71
0,82
0,67
0,84
55
0,61
0,76
0,57
0,80
60
0,50
0,71
0,45
0,75
65
0,65
0,70
70
0,58
0,65
75
0,50
0,60
80
0,41
0,54
85
0,47
90
0,40
95
0,32
For higher ambient temperatures, consult the manufacturer.
Ground
temperature
C
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
Insulation
PVC
1,10
1,05
1,00
0,95
0,89
0,84
0,77
0,71
0,63
0,55
0,45
Table 3: Rating factors for cables buried direct in the ground or in buried ducts for soil thermal
resistivities other than 2,5 Km/W to be applied to the current-carrying capacities for reference
method D:
0,5
1,2
8
1,8
averaged
8
0,7
1
1,2 1,1
0
1,6 81,5
2over the range
1,5
2
2,5
1,1 1,0
1
5
1,2 1,1
1
of
8 conductor
2 sizes and
3
0,9
6
0,9
types
0 of
installation included in Tables B.52.2 to B.52.5. The overall accuracy of correction factors is within 5 %.
NOTE 2 The correction factors are applicable to cables drawn into buried ducts; for cables laid direct in the
ground the correction f actors for thermal resistivities less than 2, 5 Km/W will be higher. W here more precise
values are required they may be calculated by methods given in the IEC 60287 series.
NOTE 3 The correction factors are applicable to ducts buried at depths of up to 0,8 m.
NOTE 4 It is assumed that the soil properties are uniform. No allowance had been made for the possibility y of
moisture migration which can lead t o a region of high thermal resistivity around t he cable. If partial drying out of
the soil is foreseen, the permissible current rating should be derived by the methods specified in the IEC 60287
series.
Item
Arrangement
(cables
touching)
Bunched in air,
on a surface,
embedded or
enclosed
1,00
0,80
0,70
0,65
0,60
0,57
0,54
0,52
0,50
Single layer on
wall, floor or
unperforated
cable tray
systems
1,00
Single layer
fixed directly
under a
wooden ceiling
0,95
0,81
0,72
0,68
0,66
0,64
0,63
0,62
0,61
Single layer on
a perforated
horizontal or
vertical cable
tray systems
1,00
0,88
0,82
0,77
0,75
0,73
0,73
0,72
0,72
Single layer on
cable ladder
systems or
cleats etc.,
1,00
12
16
20
0,45
0,41
0,38
To be
used with
currentcarrying
capacities,
reference
B.52.2
to B.52.13
Methods A
to F
0,85
0,79
0,75
0,73
0,72
0,72
0,71
0,70
B.52.2 to
B.52.7
No further
reduction factor for
more than nine
circuits or multicore
cables
Method C
B.52.8
to B.52.13
0,87
0,82
0,80
0,80
0,79
0,79
0,78
0,78
Methods E
and F
NOTE 1
NOTE 2
W here horizontal clearances between adjacent cables exceeds twice their overall diameter, no reduction factor need be applied.
NOTE 3
NOTE 4 If a system consists of both two- and three-core cables, the total number of cables is taken as the number of circuits, and the
corresponding f actor is applied to the tables for two loaded conductors for the two-core cables, and to the tables f or three loaded
conductors for the three-core cables.
NOTE 5 If a group consists of n single-core cables it m ay either be considered as n/2 circuits of two loaded conductors or n/ 3 circuits of
three loaded conductors.
Number of
circuits
Table 5: Rating factors for more than one circuit, cables laid directly in the ground Single-core or
multi-core cables:
Cable to cable clearancea
Nil
(cables
touching)
One
cable
diameter
0,125 m
0,25 m
0,5 m
0,75
0,80
0,85
0,90
0,90
0,65
0,70
0,75
0,80
0,85
0,60
0,60
0,70
0,75
0,80
0,55
0,55
0,65
0,70
0,80
0,50
0,55
0,60
0,70
0,80
0,45
0,51
0,59
0,67
0,76
0,43
0,48
0,57
0,65
0,75
0,41
0,46
0,55
0,63
0,74
12
0,36
0,42
0,51
0,59
0,71
16
0,32
0,38
0,47
0,56
0,38
20
0,29
0,35
0,44
0,53
0,66
a Multi-core cables
a Single-core cables
NOTE 1 Values given apply to an installation depth of 0,7 m and a soil thermal
resistivity of 2,5 Km /W . They are average values for the range of cable sizes and
types quoted for Tables B.52.2 to B.52.5. The process of averaging, together with
rounding off, can result in some cases in errors up to 10 %. (W here m ore precise
values are required they may be calculated by methods given in IEC 60287 -2-1.)
NOTE 2 In case of a thermal resistivity lower than 2, 5 Km /W the corrections factors
can, in general, be increased and can be calculated by the methods given in IEC
60287-2-1.
NOTE 3 If a circuit consists of m parallel conductors per phase, then for
determining the reduction factor, this circuit should be considered as m circuits.
Table 6: Rating factors for more than one circuit, cables laid in ducts in the ground:
A) Multi-core cables in single-w a y ducts
Number
of cables
0,25 m
0,5 m
1,0 m
2
3
0,85
0,75
0,90
0,85
0,95
0,90
0,95
0,95
0,70
0,80
0,85
0,90
0,65
0,80
0,85
0,90
0,60
0,80
0,80
0,90
0,57
0,76
0,80
0,88
0,54
0,74
0,78
0,88
0,52
0,73
0,77
0,87
10
0,49
0,72
0,76
0,86
11
0,47
0,70
0,75
0,86
12
0,45
0,69
0,74
0,85
13
0,44
0,68
0,73
0,85
14
0,42
0,68
0,72
0,84
15
0,41
0,67
0,72
0,84
16
0,39
0,66
0,71
0,83
17
0,38
0,65
0,70
0,83
18
0,37
0,65
0,70
0,83
19
0,35
0,64
0,69
0,82
20
0,34
0,63
0,68
0,82
B)
Number of
single- core
circuits of
two or three
cables
Nil
(ducts
touching)
0,25 m
0,5 m
1,0 m
2
3
0,80
0,70
0,90
0,80
0,90
0,85
0,95
0,90
0,65
0,75
0,80
0,90
0,60
0,70
0,80
0,90
0,60
0,70
0,80
0,90
0,53
0,66
0,76
0,87
0,50
0,63
0,74
0,87
0,47
0,61
0,73
0,86
10
0,45
0,59
0,72
0,85
11
0,43
0,57
0,70
0,85
12
0,41
0,56
0,69
0,84
13
0,39
0,54
0,68
0,84
14
0,37
0,53
0,68
0,83
15
0,35
0,52
0,67
0,83
16
0,34
0,51
0,66
0,83
17
0,33
0,50
0,65
0,82
18
0,31
0,49
0,65
0,82
19
0,30
0,48
0,64
0,82
20
0,29
0,47
0,63
0,81
b Single-core cables
NOTE 1 Values given apply t o an installation depth of 0,7 m and a soil t herm al
resistivity of 2,5 Km/W . They are average values for the range of cable sizes and
types quoted for Tables B.52.2 to B.52.5. The process of averaging, together
with rounding off, can result in some cases in errors up to 10 %. W here m
ore precise values are required they may be calculated by methods given in the IEC
60287series.
NOTE 2 In case of a thermal resistivity lower than 2, 5 Km/W the corrections factors
can, in general, be increased and can be calculated by the methods given in IEC
60287-2-1.
NOTE 3 If a circuit consists of n parallel conductors per phase, then for determining
the reduction factor this circuit shall be considered as n circuits
Table 7: Rating factors for group of more than one multi-core cable to be applied to reference
current-carrying capacities for multi-core cables in free air:
Perforat
ed cable
tray
systems
31
Spaced
(not e 3)
Numb
er of
trays
or
ladder
s
1,00
0,88
0,82
0,79
0,76
0,73
1,00
0,87
0,80
0,77
0,73
0,68
1,00
0,86
0,79
0,76
0,71
0,66
1,00
0,84
0,77
0,73
0,68
0,64
1,00
1,00
0,98
0,95
0,91
1,00
0,99
0,96
0,92
0,87
1,00
0,98
0,95
0,91
0,85
1,00
0,88
0,82
0,78
0,73
0,72
1,00
0,88
0,81
0,76
0,71
0,70
1,00
0,91
0,89
0,88
0,87
1,00
0,91
0,88
0,87
0,85
0,97
0,84
0,78
0,75
0,71
0,68
0,97
0,83
0,76
0,72
0,68
0,63
0,97
0,82
0,75
0,71
0,66
0,61
0,97
0,81
0,73
0,69
0,63
0,58
1,00
0,87
0,82
0,80
0,79
0,78
1,00
0,86
0,80
0,78
0,76
0,73
1,00
0,85
0,79
0,76
0,73
0,70
1,00
0,84
0,77
0,73
0,68
0,64
Touching
Vertical
perforated
cable tray
systems
31
(not e
4)
Spaced
Touching
Un
perforat ed
cable tray
systems
31
Touching
Cable
ladder
systems,
cleats, etc.
(not e
3)
32
33
34
Spaced
1
1,00
1,00
1,00
1,00
1,00
1,00
0,99
0,98
0,97
0,96
1,00
0,98
0,97
0,96
0,93
NOTE 1 Values given are averages for the cable types and range of conductor sizes considered in Tables A.52.8 to
A.52.13. The spread of values is generally less than 5 %.
NOTE 2 Factors apply to single layer groups of cables as shown above and do not apply when cables are installed in
more than one layer touching each other. Values for such installations may be significantly lower and has to be
determined by an appropriate method.
NOTE 3 Values are given for vertical spacing between cable t rays of 300 mm and at least 20 mm between cable
trays and wall. For closer spacing the factors should be reduced.
NOTE 4 Values are given for horizontal spacing between cable t rays of 225 mm with cable trays mounted back t o
back. For closer spacing the factors should be reduced.
Table 8: Rating factors for groups of one or more circuits of single-core cables to be applied to
reference current-carrying capacity for one circuit of single- core cables in free air
Number
of trays
or
ladders
0,98
0,91
0,87
0,96
0,87
0,81
0,95
0,85
0,78
0,96
0,86
0,95
0,84
Use as a
multiplier
to currentcarr yi ng
capacit y
for
Touching
Perforat
ed cable
tray
systems
31
(not e 3)
Vertical
perforat
ed cable
tray
systems
31
Touching
(not e
Cable
4)
ladder
systems,
32
1,00
0,97
0,96
cleats, etc.
33
0,98
0,93
0,89
(not e 3)
34
0,97
0,90
0,86
Three cables
in
horizontal
formation
Three cables
in vertical
formation
Touching
Touching
Three cables
in
horizontal
Perforat
ed cable
tray
systems
1,00
0,98
0,96
0,97
0,93
0,89
0,96
0,92
0,86
1,00
0,91
0,89
1,00
0,90
0,86
32
1,00
1,00
1,00
33
0,97
0,95
0,93
34
0,96
0,94
0,90
31
(not e 3)
Vertical
perforat
ed cable
tray
systems
(not e
Cable
4)
ladder
systems,
cleats, etc.
(not e 3)
Spaced
31
Three cables
in trefoil
formation
NOTE 1 Values given are averages f or t he c able types and range of conductor sizes considered in Table B. 52.8
to B.52.13. The spread of values is generally less than 5 %.
NOTE 2
Factors are given for single layers of cables (or trefoil groups) as shown in the table and do not apply
when cables are installed in more than one layer touching each other. Values f or such installations may be
significantly lower and should be determined by an appropriate method.
NOTE 3 Values are given for vertical spacing between cable trays of 300 mm and at least 20 mm between cable
trays and wall. For closer spacing the factors should be reduced.
NOTE 4 Values are given for horizontal spacing between cable trays of 225 mm with cable trays mounted back
to back. For closer spacing the factors should be reduced.
NOTE 5
For circuits having more than one cable in parallel per phase, each three phase set of conductors
should be considered as a circuit for the purpose of this table.
NOTE 6 If a circuit consists of m parallel conductors per phase, then for determining the reduction factor this circuit
should be considered as m circuits.
Ik (0.155/ t) * S
Figure 2
Ik (0.1038/ t) * S
Figure 3
Ik (0.075/ t) * S
Figure 4
Ik (0.068/ t) * S
Figure 5
Ik (0.143/ t) * S
Figure 6
Ik (0.0937/ t) * S
I
k
S
Item
Temp. C
PVC insulation
Sheathing
XLPE insulation
250
PVC sheathing
200
LDPE sheathing
150
HDPE sheathing
180
PVC (based on 70C type TI-1 or 90C type TI-3) cables copper and aluminum
conductor:
Short Circuit Ratings for 1 second in k Amp
Conductor
Size
Copper Conductor
Aluminum Conductor
10
1.2
0.86
16
1.8
1.1
25
2.85
1.8
35
3.55
2.55
50
3.4
70
6.9
4.9
95
10.9
6.8
120
11.8
8.5
150
15.3
11
185
18.7
13
240
23.6
16.5
300
30.1
22.5
400
41.2
29.5
500
51.5
36
630
64.9
45.5
800
82.4
62
1000
103
78
Aluminum Conductor
10
1.43
0.94
16
2.29
1.5
25
3.58
2.35
35
3.29
50
7.15
4.7
70
10.01
6.58
95
13.59
8.93
120
17.16
11.28
150
21.45
14.1
185
26.46
17.39
240
34.32
22.56
300
42.9
28.2
400
57.2
37.6
500
71.5
46.09
630
90.09
59.22
800
114.4
75.2
1000
143
94
Graph 1 : PVC (90 C type) insulated cables short circuit (Copper Conductor):
Graph 2 : PVC (90 C type) insulated cables short circuit (Aluminum Conductor):
Graph 3 : XLPE (90 C type) insulated cables short circuit (Copper Conductor):
Graph 4 : XLPE (90 C type) insulated cables short circuit (Aluminum Conductor)
INSTALLATION RECOMMENDATIONS
Instructions for transport, handling, storage of drums and laying of the cables.
The cables, whether they are armoured or unarmoured, are manufactured with high quality materials
allowing long storage, handling, transport and unreeling subject to the following recommendations.
Before acceptance of a shipment, all reels must be inspected. Any sign of damage should be noticed
to the carrier (broken flanges, damaged wrapping or or lagging, interlocked flanges, broken reels)
I.
The wooden drums must be always carried vertically. They must be fixed and properly chocked with
care on the vehicle, on the wagon and on the ship, in order to avoid any exterior damages.
Correct
Incorrect
The unloading and the different handling will be done carefully with lifting
equipments.
In case of handling with a crane, an axle is used in crossing the drum centre, lifted from both ends by
two slings. It must have length equal, at least, to the width of the drum. It prevents the lifting cable or
chain from pressing against the reel flanges.
Correct
Incorrect
In case of handling with a forklift truck, the drum is laid vertically with care on the forks.
Correct
Incorrect
II.
Rolling directions
When a reel is rolled from one point to another, it must be rolled only in the direction shown by
arrows as printed on the reel.
Correct
III.
Incorrect
Storage
Cables can be stored, with site temperature limits: -15 + 60 degrees celcius. For Outdoor location the
maximum relative humidity is 90% at all temperatures. The cables drums must be appropriately
wedged, transported and stored in a vertical position (never laid on flange) on a flat, dry and solid
ground that is not liable to settlement.
They must be protected to avoid any mechanical risk and exterior shocks.
The original wooden lags have to be kept until the cable unreeling to ensure a good protection of the
cable. The both ends of the cable (inner & outer ends) have to be watertight in order to avoid
penetration of water or humidity inside the cable. Thermo retractable polyethylene caps must be fixed
on both ends.
IV.
Lifting, loading & unloading of cable drums should be performed using slings fitted to shafts inserted
through the cable drum hubs. Spreader bars shall be used where required to avoid pressure on the
drum flanges.
If Forklifts are used, both cable drum flanges must sit on the forks of the fork lift
Cable drums may only be moved short distances by Drum rolling and drums must always be rolled
in the direction as indicated on the drum flanges.
V.
Ultraviolet Protection
Cable drums with cable that is not UV resistant shall at times be covered to protect the cable from
UV damage.
VI.
Laying temperature:
Installation shall be postponed if the temperature is lower than- 5 degrees celcius. Below this temp.
cables shall be stored in a room where temp. is higher than 10 degrees celcius at least 24hours
before unreeling. Cables shall be unreeled as soon as they are removed from the room and the usual
bending radius should be increased as possible.
Pulling strength:
The pulling strengths applied directly to the copper or aluminum cores of the cables should not
exceed:
- 5daN/mm2 of cross section for copper conductors
-3daN/mm2 of cross section for aluminum conductors.
The pulling must be regular without shock and continuously checked by a dynamometer (esp. in case
of using a winch).
Bending radius:
During the unreeling, the bending radius shall be, at least, twice the static bending radius (as
specified in our technical data sheets).
Cables Unreeling:
The drum shall be settled on jacks by using a spindle through the central hole of the drum.
The unreeling speed shall be monitored at any moment.
The cables must be reeled only in the opposite direction indicated by the arrow printed on the
flange of the drum (do not unreel the cable in the same direction of the arrow).
Correct
Incorrect
Cable Wind direction and end mark shall be indicated on both the flanges. While unreeling, the
cables shall not be twisted, waved or buckled.