Guide To Low Voltage Busbar Trunking Systems-Beama
Guide To Low Voltage Busbar Trunking Systems-Beama
LOW VOLTAGE
BUSBAR TRUNKING
SYSTEMS
BEAMAInstallation Ltd
ABOUT BEAMAInstallation
BEAMAInstallation is an independent, incorporated association of manufacturers
of electrical installation equipment and cable management products, representing
95% of the industry.
Its roots go back to the early days of the electrotechnical industry.
During 1972 EIEMA was formed from the Electrical Installation Equipment
Department of BEAMA The British Electrotechnical and Allied Manufacturers
Association. April 2003 saw the creation of BEAMAInstallation Limited through the
merger between EIEMA (the Electrical Installation Equipment Manufacturers
Association) and BESA (the British Electrical Systems Association).
BEAMAInstallation has many members - from UK divisions of large multi-nationals
to small owner-managed niche market companies. The association is organised into
these product groups:
CONTENTS
About BEAMAInstallation
Preface
1
Distribution trunking
1.2
Feeder trunking
1.3
Tap-off units
1.4
Fire-stops
1.5
1.6
1.7
Neutral sizes/harmonics
1.8
1.9
1.10
Technical Specifications
2.1
2.1.1
2.1.2
Type testing
2.1.3
Application
2.2
Voltage drop
3.2
3.3
Making joints
3.4
3.5
3.6
Useful Definitions
2
3
10
13
16
PREFACE
designed and how they should be safely installed and used in service.
Principally, these requirements are detailed in BS EN 60439-2:2000 (IEC 604392:2000) and for a more thorough understanding this guide should be read in
conjunction with this standard.
The guide seeks to provide an understanding of the standard, accompanied by some
typical examples as foreseen for the general products available from
BEAMAInstallation member Companies.
Certain additional information has been included regarding:
Use
Application
Installation
Site testing
(IEC 60439-1:1999)
Low Voltage Switchgear and Controlgear Assemblies: Requirements for Type Tested
and Partially Type Tested Assemblies
BS 7671:2001
(IEC 60364)
(IEC 60529:1992)
European Directives
Busbar trunking systems come within the scope of 73/23/EEC Low Voltage
Directive, as amended by 93/68/EEC (CE Marking Directive), and UK Low Voltage
Electrical Equipment (Safety) Regulations 1994.
BS EN 13601:2002
Copper and copper alloys: copper rod, bar and wire for general electrical purposes
BS 1474:1987
Wrought aluminium and aluminium alloys for electrical purposes: bars and sections
USE AND
APPLICATION
1.0
Modern electrical installations are placing increasing demands on all products of the
electrical equipment manufacturer.
Products must have:
Energy efficiency
Power is taken from busbar trunking by the use of tap off units which connect at
defined positions along the busbar trunking, and allow power to be taken from the
system, usually via a suitable protective device.
Advantages over cable:
The contractor can achieve savings with respect to material i.e. cable trays and
multiple fixings and also labour costs associated with multiple runs of cable.
Reduced installation time since busbar trunking requires less fixings per metre run
than cable.
Greater mechanical strength over long runs with minimal fixings resulting in
shorter installation times.
Easier to install compared to multiples of large cables with all of the associated
handling problems.
Takes up less overall space, bends and offsets can be installed in a much smaller
area than the equivalent cable space.
Voltage drop and voltage dip in the majority of cases is lower than the equivalent
cable arrangement.
Medium power
busbar trunking
Switchboard
Small power
busbar trunking
Tap-off feeding
secondary
busbar distribution
Typical plug-in
tap off unit installed on
Busbar Trunking Unit
degree
of
enclosure
Plug-in units are arranged to be non-reversible to ensure that they can only be
connected to give the correct phase rotation.
Plug-in units are arranged to connect the protective circuit before the live
conductors during installation and disconnect the protective circuit after the live
conductors while being removed.
Where units are provided with a switch disconnector or circuit-breaker these are
capable of being locked in the OFF position.
Covers permitting access to live parts can only be removed by the use of a tool
and will have any internally exposed live parts shielded to a minimum of IP2X or
IPXXB in accordance with BS EN 60529.
1.4 FIRE-STOPS
Recommendations for the construction of fire-stops and barriers where trunking
penetrates walls and floors classified as fire barriers.
Internally the trunking may or may not require fire-stop measures according to the
construction; where they are required these will generally be factory-fitted by the
manufacturer and positioned according to a schematic drawing for the installation.
Compact or sandwich-type trunking does not require internal fire-barriers, as
suitability as a fire-barrier is inherent in the design. However in all cases verification of
the performance of the trunking under fire conditions needs to be provided by the
manufacturer.
The following information is provided for guidance, and the method used
should be agreed with the trunking manufacturer. It is not the responsibility of
the trunking manufacturer to provide the specification or detail the rating or
construction of the fire-stop external to the trunking.
As a minimum a 50%
neutral current, or, in extreme cases, use parallel devices to meet the specification.
The extra heat produced in the neutral conductors within a busbar system leads to the
need for temperature de-rating factors to be applied to the standard designs of busbar
systems. Typical de-rating figures that may need to be applied as in the table below:
Rating factor
100% neutral
200% neutral
50%In
0.96
0.98
100%In
0.87
0.93
150%In
0.85
Offices
Hospitals
Electrical Generation
Apartments
Shopping Centres
Petrochemical Industries
Schools
Factories
Hotels
TECHNICAL
SPECIFICATIONS
2.0
2.1
10
between the busbars, which stress the supporting mechanical structure, including
vibrational forces on a.c. The only satisfactory way to verify the quoted ratings, is by
means of a type test to the British Standard.
2.1.2 TYPE TESTING
Busbar trunking systems are tested in accordance with BS EN 60439-2 to establish
one or more of the short-circuit withstand ratings defined above. In the case of
short-time rating the specified current is applied for the specified time. A separate
test may be required to establish the peak withstand current if the quoted value is
not obtained during the short-time test. In the case of a conditional rating with a
a
dc
specified SCPD, the test is conducted with the full prospective current value at the
En
it
un
f
f
po
Ta
trunking feeder unit and not less than 105% rated voltage, since the SCPD (fuse or
circuit-breaker) will be voltage dependent in terms of let through energy.
2.1.3 APPLICATION
It is necessary for the system designer to determine the prospective fault current at
every relevant point in the installation by calculation, measurement or based on
information provided, e.g. by the supply authority. The method for this is well
established, in general terms being the source voltage divided by the circuit
impedance to each point. The designer will then select protective devices at each
p
Ta
i
un
off
point where a circuit change occurs, e.g. between a feeder and a distribution run of a
lower current rating. The device selected must operate within the limits of the busbar
trunking short-circuit withstand. The time delay settings of any circuit-breaker must
be within the specified short time quoted for the prospective fault current. Any
SCPD used against a conditional short-circuit rating must have energy limitation not
exceeding that of the quoted SCPD. For preference the SCPD recommended by the
trunking manufacturer should be used.
2.2
p
Ta
ni
ff u
d
en
le it
b
Ca un
d
fee
VOLTAGE DROP
The requirements for voltage drop are given in BS 7671:Regulation 525-01-02. For
busbar trunking systems the method of calculating voltage drop is given in BS EN
60439-2 from which the following guidance notes have been prepared.
Voltage drop
Figures for voltage drop for busbar trunking systems are given in the
manufacturers literature.
Figures are expressed in volts or milli-volts per metre or 100 metres, allowing a
simple calculation for a given length of run.
Typical Busbar
Riser Application
Figures are usually given as line-to-line voltage drop for a 3 phase balanced load.
Figures take into account resistance of joints and temperature of conductors and
assume the system is fully loaded.
11
Standard data
BS EN 60439-2 requires the manufacturer to provide the following data for the
purposes of calculation, where necessary:
R20 the mean ohmic resistance of the system, unloaded, at 20C per metre per phase.
X
the mean ohmic resistance when loaded at rated current per metre per phase.
Application
In general the voltage drop figures provided by the manufacturer are used directly to
establish the total voltage drop on a given system; however this will give a pessimistic
result in the majority of cases.
Where a more precise calculation is required (e.g. for a very long run or where the
voltage level is more critical) advantage may be taken of the basic data to obtain a
more exact figure.
i) Resistance - the actual current is usually lower than the rated current and hence
the resistance of the conductors will be lower due to the reduced operating
temperature.
Rx = R20 [1+0.004 (Tc - 20)] ohms/metre and Tc is approximately Ta + Tr
where Rx is the actual conductor resistance.
Ta is the ambient temperature
Tr is the full load temperature rise in C (assume say 55C)
ii) Power factor - the load power factor will influence the voltage drop according
to the resistance and reactance of the busbar trunking itself.
The voltage drop line-to-line (v) is calculated as follows:
v = 3 I (R x cos + X sin ) volts/metre
where I is the load current and Rx is the actual conductor resistance (/m)
X is the conductor reactance (/m)
cos is the load power factor
sin = sin (cos-1 )
iii) Distributed load - where the load is tapped off the busbar trunking along its
length this may also be taken into account by calculating the voltage drop for each
section.
As a rule of thumb the full load voltage drop may be divided by 2 to give the
approximate voltage drop at the end of a system with distributed load.
iv) Frequency - the manufacturers data will generally give reactance (X) at 50Hz for
mains supply in the UK. At any other frequency the reactance should be re-calculated.
Xf = XF/50
where Xf is the reactance at frequency f in Hz
12
INSTALLATION
& SITE TESTING
3.0
3.1
All components should be checked for mechanical damage and insulation resistance
before installation.
3.3
MAKING JOINTS
As the electrical joints may be carrying high currents, the contact surfaces must be
clean and particular care taken with alignment while the connections are made - best
practice must be employed when making electrical connections.
carrying capacity is very dependent on contact pressure the torque settings specified
by the manufacturer must be used.
3.4
The correct time to make the Initial Verification/Inspection to BS 7671, and any
additional requirements from manufacturers instructions, is during installation and
not as a preliminary to commissioning.
To check that the installation has been made correctly, and to provide records for
comparison during maintenance, the following should be considered:
(a) INSULATION RESISTANCE BS 7671 requires the insulation resistance of a
complete system to be checked, and sets minimum values. The measured value
not only depends on the quality of the insulation and length of the busbar system,
but can also be affected by for example, ingress of moisture.
(b) DIELECTRIC (FLASH) This test is made in the factory using voltage specified in
the busbar Standard BS EN 60439-2. It is not advisable to repeat on an installed
busbar trunking due to the safety hazards from high voltages and currents (2500V
50Hz at 3000mA is typical).
13
First and foremost within the UK, the requirements of The Electricity At Work
Regulations 1989, must be complied with; Regulation 14 is particularly pertinent and
requires:
No person shall be engaged in any work activity on or so near any live
conductor (other than one suitably covered with insulating material so as to
prevent danger) that danger may arise unless: a) it is unreasonable in all the circumstances for it to be dead; and
b) it is reasonable in all the circumstances for him to be at work on or near it
while it is live; and
c) suitable precautions (including where necessary the provision of suitable
protective equipment) are taken to prevent injury.
Regulation 4(4) in particular also applies to the provision and use of protective
equipment. Effectively this means that, where live working is being contemplated, a
risk assessment and judgement must be made for every situation by the Duty
Holder*. This must take account of all relevant factors, some of which include:
14
Manufacturers cannot give all-embracing assurances for safe working with the system
live. This can only be determined on a case by case basis depending on the work to
be done.
*Duty Holder: The term used within the Electricity At Work Regulations 1989 to refer to
the person appointed to be responsible for the electrical equipment, systems and conductors
and any work or activities being carried out on or near electrical equipment. The Duty
Holder must be competent and may be the employer, an employee, or a self-employed
person.
15
4.0
USEFUL DEFINITIONS
16
BUSDUCT
MANUFACTURERS
Eaton Cutler Hammer
Reddings Lane, Tyseley
Birmingham, West Midlands
B11 3EZ United Kingdom
T +44 (0) 121 685 2100
F +44 (0) 121 706 2012
E [email protected]
W www.cutler-hammer.eaton.com/global/UK
Eaton MEM
Reddings Lane, Tyseley
Birmingham, West Midlands
B11 3EZ United Kingdom
T +44 (0) 121 685 2100
F +44 (0) 121 706 2012
E [email protected]
W www.memonline.com
Merlin Gerin LV Equipment
Stafford Park 5, Telford
Shropshire TF3 3BL
United Kingdom
T +44 (0) 1952 290 029
F +44 (0) 1952 290 534
W www.schneider.co.uk
GUIDE TO
LOW VOLTAGE
BUSBAR TRUNKING
SYSTEMS
An BEAMAInstallation Publication
Issue No2
BEAMAInstallation Ltd
Westminster Tower
3 Albert Embankment
London SE1 7SL
Telephone: 020 7793 3013
Fax: 020 7793 3003
Email: [email protected]
Website: www.beamainstallation.org.uk
Other publications from BEAMAInstallation:
Guide to the IP Codes for Enclosures
Guide to Switch & Fusegear Devices
Guide to Fuse Link Applications
Guide to Circuit Breaker Standards
Guide to Forms of Separation
Guide to Type Tested Assemblies and Partially Type Tested Assemblies
RCD Handbook