0% found this document useful (0 votes)
182 views

Prolec Trafos Dimension Sbtr-1208-1

The document discusses Prolec GE substation transformers, including their standard features, optional accessories, standard ratings and voltages. It provides details on transformer components, dimensions, weights and contact information.

Uploaded by

rober2222
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
182 views

Prolec Trafos Dimension Sbtr-1208-1

The document discusses Prolec GE substation transformers, including their standard features, optional accessories, standard ratings and voltages. It provides details on transformer components, dimensions, weights and contact information.

Uploaded by

rober2222
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Substation

Transformers
Optional Features & Accessories

Prolec GE offers a complete line of liquidfilled


distribution transformers that meet current applicable
ANSI / IEEE standards.
With high voltages up to 34.5kV and ratings up to 15 MVA
(ONAN), Prolec GE primary and secondary substation
transformers are used in a wide range of utility, commercial
and industrial applications. High-grade materials, combined
with state of the art technology in our design and
manufacturing systems, are key elements of a transformer
that will deliver years of high reliability service.
Prolec GE Primary and Secondary Substation
Transformers meet all of your industrial applications
for electric distribution.

Standard Features
Insulating mineral oil.
60 Hertz operation.
Externally operated de-energized tap changer with (2)
2.5% full capacity taps above and below nominal.
65C average winding rise.
Side-mounted bushings.
HV and LV flange connections.
Pressure-vacuum gauge.
Top filter press valve provision.
Liquid level gauge.
Liquid temperature gauge.
Pressure test valve.
ANSI grounding pad.
Drain / filter valve with sampling device.
Tank lifting lugs.
Corrosion resistant nameplate.
ANSI 61 paint finish, 5 mils thickness.
ANSI 70 paint finish, 5 mils thickness.
Hydran provision (above 7.5 MVA).

High-fire point fluid, such as silicone, hydrocarbon or


vegetable fluids. (up to 10 MVA)
55 C 55/65C average winding rise.
Forced air cooling
Forced air cooling with 2 stages (from 7.5 MVA and up
to 15 MVA)
Future fan wiring and control.
Removable radiators.
Pressure relief device.
Winding temperature device.
Sudden pressure relay with or without seal in.
Devices with alarm contacts.
Top filter press valve.
HV & LV air terminal compartments.
HV lightning arresters in ATC.
Current transformers.
Neutral grounding resistor.
Special impedances.
Low losses.
Special environment (i.e: classified areas).
Special / low sound level.
50 Hertz.
Seismic zone III and IV.
IBC/CBC certified product line up to 5 MVA
Retrofit to specific dimensions.
Non-standard loading conditions such as harmonic
loading or specified K-factor.
Stainless steel removable radiators.
Galvanized steel removable radiators.
Special paint for marine ambient.
Special paint thickness.
Special colors.
CSA compliance.
Other special features upon request.

Tests
Each transformer receives all standard commercial tests
in accordance with ANSI C57.12.90 (latest revision), with
test reports available by serial number of the transformer.
Routine tests include:
Resistance tests of all windings.
Ratio tests on the rated voltage and all tap connections.
Polarity and phase relation tests at rated voltage.
No load loss at rated voltage.
Exciting current at rated voltage.
Impedance and load losses.
Applied voltage test.
Induced voltage test.
Full wave impulse test.
ANSI is a registered trademark of American National
Standards Institute, Incorporated.
IEEE is a registered trademark of the Institute of Electrical
Electronics Engineers, Inc.

Pressure-relief device

Sudden-pressure relay
Lifting lugs

Fill plug
Vacuum
pressure gauge
Filter press
valve gauge

Winding
temperature gauge

Liquid-level gauge
Liquid
temperature gauge

Tap changer

Radiators
Nameplate

Drain valve

Control box

Overall Typical Dimensions for Reference

Standard Ratings (ONAN)

Oil Filled; 65C Rise; BIL 95 kV

Standard kVA Ratings

kVA

Height

Flange - Flange

Depth

Total Weight (Lb)

750
1000
1500
2000
2500
3000
3750
5000
7500
10000
12000
15000

90
90
95
95
95
100
105
105
120
130
130
130

50
60
60
65
65
70
70
75
80
80
85
130

60
70
75
75
80
90
90
95
110
135
135
155

6,400
7,300
9,500
11,400
13,100
15,800
18,200
22,000
29,000
32,800
38,200
70,000

kVA
750
1000
1500
2000
2500
3000
3750
5000
7500
10000
12000

High Fire Point Fluid; 65C; BIL 95 kV


Depth Total Weight (Lb)
Height
Flange - Flange
85
85
85
90
95
100
100
100
110
115
125

55
60
60
65
70
70
75
80
80
90
95

60
75
85
85
90
95
95
105
125
135
135

6,300
7,400
9,500
11,900
13,400
15,700
18,300
22,100
30,400
33,000
35,700

225
300
500
750
1000

1500
2000
2500
3750
5000

7500
10000
12000
15000

Standard Voltages (V)


Standard Primary Voltage Ratings
* 2400
4160
4800
6900

7200
12000
12470
13200

13800
23000
34500
Other

Standard Secondary Voltage Ratings


* 208Y
* 240
480
600

2400
4160Y
4800
12000

12470
13200
13800
Other

For kVAs not listed, contact factory. Dimensions and weights are
approximate and subject to change without notice and should not
be used for construction purposes.
For more information contact your local GE Sales Representative or visit our website at www.prolecge.com
Phone: Toll free 1 800-437-7653 (US & Canada) / +52 (81) 8030-2341 (Mexico) / Fax: +52 (81) 8030-2323 or 2325
SBTR-1208-1

You might also like