Day2 - Control Drawing Builder
Day2 - Control Drawing Builder
ENGINEERING COURSE
Day 2
Terminal Name
%Znnspcc
nn : Node Number.(1 - 10)
s : Slot Number.(1 - 8)
p : Port Number.(1 - 4)
Cc : Terminal Number.(1 - 64)
Service Comment
A character string consist of up to 40 characters can be entered.
Instrumentation & Automation Education Center (IAEC)
Yokogawa (Thailand) Ltd.
Label
As the name of the function blocks input/output terminal.
The entry format of user-defined labels is as follows:
%%Mnnnnnnnnnnnnn
M
: One uppercase letter
Nnnnnnnnnnnnn : up to 13 alphanumeric characters.
Terminal Name
%Znnspcc
nn : Node Number.(1 - 10)
s : Slot Number.(1 - 8)
p : Port Number.(1 - 4)
Cc : Terminal Number.(1 - 64)
Double Click
Drawing Comment
Grid Setting
For easy drawing, you can display the grid on the drawing panel. [Draw] [Grid Option].
Click
Click
Select Mode
Function Block
Wiring
Double Click
Edit Function
Block Detail
Click
Function Block
The object that represents the function block is called function block symbol.
Tag
Tag name
name
Terminal
Terminal name
name
Block
Block model
model
I/O
I/O connection
connection terminal
terminal
(Terminal
(Terminal area)
area)
PIO
PIO
AREAIN
AREAIN
AREAOUT
AREAOUT
An I/O data link block can connect to a process I/O or software I/O.
An external data link block connect to a function block defined in other control drawings
or a function block defined on other control stations.
Wiring
Wiring
This object represent the flow of data between function blocks or between
a function block and data link block.
Text
This object represents an arbitrary character string.
Text
Data Connection
-Data Reference
Data reference is a type of data connection in which data read from the
connection of the function block input terminal. The data value of the
connection destination is read as an input value of the function block in
data reference.
-Data Setting
Data setting is a type of data connection in which data written into the
connection destination from the function output terminal. The value of the
function block output data is sent to the connection destination.
Data reference
Data Setting
Data reference
Process Connection
connection with Process I/O
Is an I/O connection that connects the function block I/O terminal
to the process I/O such as analog I/O and contact I/O
10
Terminal Connection
The terminal connection specifies the I/O terminal of a function
as the connection destination of the function block I/O terminal.
The connection between I/O terminal of function are well applied
to the cascade loops where the upper stream block output depends
on the lower stream block status.
The terminal connection is mainly used in the following instances.
Connection Between Function Blocks
The output terminal (OUT) of the upstream function block and setting
input terminal (SET) or input terminal (IN) of the downstream function
block are connected under the cascade control.
Connection by Way of a Switch Block (SW-33, SW-91)
Terminal connection must always be used as the I/O connection method at
one the other of the I/O terminal (input side or output side) of the SW-33
or SW-91 block.
Terminal
Terminal connection
connection
11
The regulatory control blocks are the function block perform control
computation processing mainly on the analog input as input signals.
The calculated results are used for process monitor and process control.
12
13
1.Input Processing
Receives a signal from the input terminal and output a process variable (PV).
2.Control Computation Processing
Performs control computation processing by reading the PV and output a manipulated variable (MV)
3.Output Processing
Reads the MV and output the result of control computation processing to the output terminal as an output
signal.
4.Alarm Processing
Detects an abnormality in the PV or MV and notifies the operation and monitoring function.
Instrumentation & Automation Education Center (IAEC)
Yokogawa (Thailand) Ltd.
14
15
16
EXAMPLE
17
EXAMPLE
EXAMPLE
18
Note..
19