The ACM4 is a power controller that converts one 12-24V AC or DC input into four independently controlled and fuse protected outputs. It has four access control system trigger inputs that can activate the outputs. The outputs can operate in fail-safe or fail-secure mode and can provide power or dry contacts. The unit has a fire alarm disconnect feature for each output and an auxiliary FACP output. It is powered by a single power source for both operation and devices or two separate sources.

Uploaded by

Sanrasni
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
90 views

Acm4 Multi-Output Access Power Controllers: Rev. DSACM4 - 11122014

The ACM4 is a power controller that converts one 12-24V AC or DC input into four independently controlled and fuse protected outputs. It has four access control system trigger inputs that can activate the outputs. The outputs can operate in fail-safe or fail-secure mode and can provide power or dry contacts. The unit has a fire alarm disconnect feature for each output and an auxiliary FACP output. It is powered by a single power source for both operation and devices or two separate sources.

Uploaded by

Sanrasni
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

ACM4

Multi-Output Access Power Controllers


Rev. DSACM4_11122014

Overview

ACM4

Input:

ACM4 converts one (1) 12 to 24 volt AC or DC input into four (4) independently
controlled fuse protected outputs. These power outputs can be converted to dry
form C contacts. Outputs are activated by an open collector sink or normally
open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. The ACM4 will route power to a variety of access
control hardware devices including Mag Locks, Electric Strikes, Magnetic Door
Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes.
Units are designed to be powered by one common power source which will provide power for both the board operation and locking devices, or two (2) totally
independent power sources, one (1) providing power for board operation and
the other for lock / accessory power. The FACP Interface enables Emergency
Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices.
The fire alarm disconnect feature is individually selectable for any or all of the
four (4) outputs.

Specifications
Features:

12 to 24 volt AC or DC operation
(setting not required), 0.4 amp @ 12volt,
0.2 amp @ 24 volt current consumption with all
relays energized.
Power supply input options:
a) One (1) common power input
(board and lock power).
b) Two (2) isolated power inputs (one (1) for
board power and one (1) for lock/accessory power).
Four (4) Access Control System trigger inputs:
a) Four (4) normally open (NO) inputs.
b) Four (4) open collector sink inputs.
c) Any combination of the above.

Output:
Four (4) independently controlled outputs:
a) Four (4) Fail-Safe and/or Fail-Secure
power outputs.
b) Four (4) dry form C 5 amp rated relay outputs
c) Any combination of the above
Four (4) auxiliary power outputs (unswitched).
Output ratings:
- Fuses are rated 3 amp each.
- Main fuse is rated at 10 amp.
Note: Total output current is determined by the
power supply, not to exceed a maximum
of 10 amp total.

Fire Alarm disconnect (latching or non-latching) is


individually selectable for any or all of the
four (4) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry
contact input.
b) Polarity reversal input from FACP signaling circuit.
FACP output relay (form C contact rated @ 1 amp
28VDC not evaluated by UL).
Removable terminal blocks facilitate ease
of installation.

Visual Indicators:
Red LEDs indicate outputs are triggered
(relays energized).
Green LED indicates FACP disconnect is triggered.

Electrical:
Operating temperature: 0 C to 49 C ambient.
BTU/Hr.:
- 12VDC or 12VAC: 1.22 BTU/Hr.
- 24VDC or 24VAC: 2.46 BTU/Hr.

Mechanical:
Board Dimensions (L x W x H approx.):
5.175 x 3.36 x 1.25
(131.4mm x 85.3mm x 31.75mm)
Product weight (approx.): 0.35 lbs. (0.16 kg).
Shipping weight (approx.): 0.45 lbs. (0.2 kg).

Agency Approvals
UL Listed Sub-Assembly for Access Control System Units (UL 294) and
Signal Equipment Evaluated to CSA Standard C22.2 No.205-M1983.

Board Dimensions (L x W x H approximate):


5.175 x 3.36 x 1.25 (131.4mm x 85.3mm x 31.75mm)

Mounting Diagram
0.156" (3.96mm)

0.33" (8.4mm)

0.13"
(3.3mm)

4.9"
(124.46mm)

2.4"
(60.96mm)

ACM4

5.175"
131.4mm

Altronix Corp. - 140 58th Street, Brooklyn, NY 11220 718-567-8181 888-258-7669 altronix.com

3.36"
(85.3mm)