ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 1
.Men Principal
Indice manual
Indice volumen
Indice norma
Index
SECTION 1 SCOPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3
1.4
1.5
Referenced Publications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
(Addition) Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
(Addition) Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
2
3
SECTION 2 MATERIALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 3 DESIGN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4
3.5
3.6
3.10
3.12
3.13
3.14
3.15
4.2
Bottom Plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shell Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shell Openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Roofs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
(Addition) Floating Roof Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
(Addition) Floating Roof Seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
(Additions) Floating Roof Supports and Drains . . . . . . . . . . . . . . . . . . . . .
(Addition) Design Additional Requirements . . . . . . . . . . . . . . . . . . . . . . . . .
Shop Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
5
5
7
7
9
9
10
11
SECTION 5 ERECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
5.2
5.3
Detail of Welding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inspection, Testing and Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
12
13
13
7.4
Qualification of Welders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 2
.Men Principal
Indice manual
Indice volumen
Indice norma
FOREWORD
This specification covers minimum requirements for materials, design,
fabrication, erection and testing of welded steel storage tanks for above ground
atmospheric liquid hydrocarbons and chemical storage. This specification does
not cover tanks for water storage.
This specification is intended to supplement API Standard 650, Tenth Edition,
November 1998. Paragraph numbers, figures and tables of this specification
correspond to those in API 650. Paragraph numbers not found in API 650 are new
paragraphs.
Paragraphs shall be highlighted as shown below to indicate the type of change
from the API Standard:
(Addition) New paragraph or supplemental requirements/clarifications to an
existing paragraph.
(Deleted) Paragraph deleted.
(Decision) A decision has been made as required.
(Substitution) Paragraph supersedes API in its entirety.
SECTION 1 SCOPE
1.1.3
1.1.9
(Substitution) The seismic design of tanks shall meet the requirements of PDVSA
FJ251, Seismic Design of Metallic Tanks.
1.3
Referenced Publications
1.3.1
1.3.2
1.3.3
1.3.4
1.4
(Addition) Drawings
The PDVSA representative shall supply data sheets and schematic drawings of
the basic design indicating tank capacity, properties of products to be stored,
ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 3
.Men Principal
Indice manual
Indice volumen
Indice norma
1.5
1.5.1
(Addition) Definitions
Low strength tank steels
Steels having a specified minimum yield strength equal or lower than 43,000 psi
and a specified maximum tensile strength equal to or lower than 85,000 psi.
1.5.2
1.5.3
Peaking
Deviation of shell contour from a true circle at vertical joints. It shall be determined
over a horizontal span of 900 mm, centered on the weld.
1.5.4
Banding
Deviation of the shell at horizontal joints from a vertical line. It shall be determined
over a vertical span of 900 mm centered on the weld.
1.5.5
Annular plates
Buttwelded bottom plates forming an annular ring upon which the shell is
installed.
1.5.6
1.5.7
1.5.7
ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 4
.Men Principal
Indice manual
Indice volumen
Indice norma
The production test coupons shall be taken from the bottom, middle and top
course longitudinal and circumferential weld seams. A test coupon shall be taken
from each heat number used in the tank construction. The test coupon shall be
welded as an extension to the end of the production weld. If it is not practical to
do it, the test plate will be made under the same production conditions as the
actual tank welds, using the same welding procedure, joint details, number of
passes, position, and consumables required for the actual tank joint. Inspector
refers to the PDVSA representative.
SECTION 2 MATERIALS
2.1.4
(Addition) Material specifications for annular plates shall be the same of the
corresponding first course.
2.1.5
2.1.6
SECTION 3 DESIGN
3.3.2
Corrosion Allowances
(Addition) Corrosion allowance shall be considered as specified in the PDVSA
data sheet, but never be less than 1.5 mm.
3.4
Bottom Plates
3.4.4
(Addition) PDVSAs sketch shall specify the following requirements for bottom
slope: None, Apex up or Apex Down.
3.5
3.5.6
(Addition) The annular bottom plate width shall be in accordance with Table 1 or
as calculated per 3.5.2 of API 650, whichever is greater.
TABLE 3.4A CATEGORY OF BOTTOM REQUIRED
Category
of Bottom
Specified
Predicted
Settlement (2)
Maximum at
shell
50 mm
ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 5
.Men Principal
150 mm
300 mm (3)
Indice manual
Indice volumen
Indice norma
NOTES:
a.
b.
c.
d.
e.
The annular plate width shall not be less than calculated according to API 650.
f.
3.6
Shell Design
3.6.1.3
(Addition) The specific gravity used for the design shall be 1,0. Use actual value
when the specific gravity of the fluid is greater than 1,0.
3.6.1.9
(Addition) The tank shell course thickness shall be designed according to the 1
foot method of API 650. Calculation of the thickness by the variable design point
method requires PDVSA approval.
3.6.1.10
(Addition) All vertical and horizontal shell joints shall be designed and specified
using complete penetration and fusion welding procedures.
3.6.1.11
ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 6
.Men Principal
3.7
Indice manual
Indice volumen
Indice norma
Shell Openings
3.7.1
General
3.7.1.9
(Addition) The minimum number of shell and roof manholes shall be as follows:
Nominal Tank
Diameter ( meters)
Up to 6 m
From 6 to 20 m
From 20 to 30 m
Greater than 30 m
Shell
1
2
2
3
Fixed
1
2
2
2
Roof
Floating
1
1
2
2
3.7.5
Shell Manholes
3.7.5.1
(Substitution) Shell manholes shall conform to Figures34A and 34B and Tables
33 through 35, except that the minimum size shall be equal or greater than 24
in. Other shapes are permitted by 3.7.1.8. Manhole reinforcing plates or each
segment of the plates if they are not made in once piece shall be provided with
a 6mm (1/4in.) diameter telltale hole (for detection of leakage through the
interior welds). Each hole shall be located on the horizontal position centerline and
shall be open to the atmosphere. All tanks shall have at least one manhole of 30
in.
3.7.8
3.7.8.12
(Addition) Flush type shell connections shall be provided with a flow guide box.
3.8.4
Roof Manholes
3.8.4.
(Addition) Manual Gauging and Sampling for Fixed Roof Tanks. A gauging hatch
shall be installed on a roof manhole cover, with a minimum diameter of 200 mm.
The gauging hatch shall have a heavy stayback cover and a seal with a corrosion
resistant seat, suitable for a pressure of 2 oz/sq. in, or the design pressure of the
tank, whichever is greater.
3.8.7
ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 7
.Men Principal
Indice manual
Indice volumen
Indice norma
S For tanks over 6 m in diameter a water sump is required. The end of the
drawoff pipe shall be 100 mm from the bottom of the sump.
3.9.4
3.9.6
3.9.6.4
When a curb angle is required at the top of the shell of floating roof tanks, the
horizontal leg shall extend outward (Figure 320, detail b, API 650).
3.10
Roofs
3.10.1
Definitions
3.10.1.b
3.10.2.3
(Substitution) Roof plates of supported cone roof shall not be attached to the
supporting members. For tanks to be operated at high temperatures, the rafter to
shell connection shall be designed to allow differential thermal expansion
between the shell and the roof rafters.
3.10.2.5.3 (Addition) A frangible joint at the roof to shell junction shall be provided for
supported cone and selfsupporting cone roof designs.
3.10.2.9
3.12
(Addition) The horizontal leg of the roofsupporting angle shall be turned inward.
If the shell top angle is buttwelded to the shell (API 650, Fig. F2 (d) or (i), a
double side weld is required.
3.12.1
The design of floating roof tanks with specified flush type nozzles shall permit the
outer pontoon to reach a point within 380 mm of the tank bottom, unless limited
by obstructions such as mixers, roof drains, etc.
3.12.2
Tank roof design for tanks larger than 18 m in diameter shall be as follows
a.
b.
ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 8
.Men Principal
Indice manual
Indice volumen
Indice norma
Roofs for tanks greater than 46 m in diameter shall be designed for elastic stability
against gross out of plane buckling and local buckling of the outer pontoon, due
to the radial load imposed by deflection of the center deck. This radial load shall
be determined from the 250 mm of rainfall loading condition as defined in API 650,
Appendix C.3.4. or punctured center deck loading condition, whichever governs.
For prevention of gross out of plane buckling, the following relations shall be
satisfied:
a.
b.
Or:
a.
b.
c.
3.12.4
The radial unsupported width of Partially Stiffened plates shall not exceed
3m.
The inner rim of Partially and Fully Stiffened pontoons shall have the following
minimum thickness:
ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 9
.Men Principal
Indice manual
TANK DIAMETER
60 to 75 m
75 to 90 m
3.12.5
3.12.6
3.13
Indice volumen
Indice norma
RIM THICKNESS
16 mm
19 mm
For tanks over 60 m in diameter the following calculations and tests are required
to substantiate the elastic stability of the roof pontoon design:
a.
Where the roof design has not been previously approved by PDVSA, the
vendor shall submit test data of a roof of similar diameter, to validate the
design.
b.
Where validation has not been made, the vendor shall conduct a proof test
on the largest tank to be supplied. The proof test shall be based on the most
critical design load condition. Calculations shall be submitted to PDVSA for
approval.
Tanks greater than 90 m in diameter shall have the following roof construction:
a.
b.
The top edge of the inner rim plates in the first two central compartments
shall be welded with continuous single fillet welds.
c.
3.13.1
Roof seals shall contact the liquid level at the shell for at least 90% of the
circumference of the tank. The maximum permissible gap between the primary
seal and the tank shell is 6 mm.
3.13.2
Toroidal type seals shall be equipped with a weather shield unless secondary
seals are specified. Liquid mounted toroidal seals are preferred.
3.13.3
Floating roofs with a flexible steel shoe type primary seal shall be equipped with
an abrasion resistant, weather and product proof, flexible seal in order to close
the space between the seating ring and the rim of the floating roof and shall be
designed to avoid any jam between the shell and the shoe when the roof is
moving.
3.13.4
3.13.5
The design of primary seals, secondary seals and weather shields shall permit
installation and removal from the top of the roof.
3.14
3.14.1
ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 10
.Men Principal
Indice manual
Indice volumen
Indice norma
3.14.2
The clearance between the support and the roof support sleeve shall be 3 mm
nominally at all points.
3.14.3
The lower position shall permit the roof to reach 75 mm below the specified
lowest operating position, without interference with any internal accessory
or roof seal mechanism.
b.
The upper position shall provide a clearance of 2 meters between the roof
and the tank bottom, for cleaning purposes.
3.14.4
Bearing plates shall be centered under each support, welded to the shell bottom
by a 5mm continuous fillet weld. Plate dimension shall be 24 in square by 3/8 in
thick.
3.14.5
The length of the leg support sleeves shall be such that any opening will be above
the liquid level when the deck is deflected by the 250mm rainfall or by a
punctured center deck loading condition. The height of the support sleeves for a
single deck pontoon roof shall never be less than the tank diameter divided by 60.
3.14.6
Emergency drains shall not be provided when the pontoon area is less than 50%
of the roof area. Only for double deck type roofs may credit is taken in the roof
design when emergency drains are furnished.
3.15
3.15.1
3.15.2
3.15.3
Roof Vents
For fixed roof tanks, design and installation of normal and emergency vents
(including vacuum vents), shall be as specified in API STD 2000.
Floating roof tanks shall be equipped with a bleeder vent, designed to open
automatically when the roof lowers to a level of 75 mm.
When flexible, steel shoe type seals are employed and the shoes extend into the
liquid more than 100 mm, the roof shall be equipped with a vent or vents between
the roof rim and the seal shoe. These vents shall release excess air or
noncondensable vapors entering the tank through the filling line.
ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 11
.Men Principal
3.15.4
Indice manual
Indice volumen
Indice norma
3.15.5
Fill Nozzles
Fill nozzles shall be sized to meet fluid velocity requirements according to API RP
2003.
3.15.6
3.15.7
3.15.8
a.
b.
Fill and discharge nozzles shall be API Low Type unless otherwise specified.
c.
Shell nozzle 50 mm and larger for internal pipe tank connections shall extend
into the tank as per API 650.
d.
3.15.9
3.15.9.1
3.15.9.2
For fixed roof tanks handrails shall be installed along the edge of the roof,
extending at least 4500 mm beyond the platform in each direction.
3.15.9.3
ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 12
.Men Principal
Indice manual
Indice volumen
Indice norma
walkways and platforms posts will be installed on the base plates on all sides
except at the access.
3.15.9.4
Dome roof tanks shall require walkways from the edge to the center of the roof
for maintenance of accessories. These walkways will have handrails on both
sides and around working platforms. A swinging door shall be installed at access.
SECTION 5 ERECTION
5.2
5.2.5
Detail of Welding
Roofs
(Addition) Cone and dome roofs shall not have depressions that will allow
accumulation of water.
5.3
5.3.1
General
5.3.1.5
5.3.4
All bottom plate joints shall be vacuum tested using soapsuds solution at
10 psig.
b.
c.
ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 13
.Men Principal
5.3.6
Indice manual
Indice volumen
Indice norma
h.
TANK PORTION
Top course
Below Top Course
Top Third
Middle Third
Bottom Third
FILLING RATE
mm/hr
300
450
225
300
450
(Addition) The PDVSA inspector shall take note of water levels in the tanks.
The hydrotest shall be maintained for at least 24 hours.
6.1.6.1
b.
c.
Qualification of Welders
(Addition) For the fillet welded bottom plates, a minimum of two welding passes
are required. The geometry and qualification procedures are as follows:
ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 14
.Men Principal
Indice manual
Indice volumen
Indice norma
a.
b.
c.
75 x 400mm tensile test strips shall be cut of this weld. The minimum
breaking strength of the strips shall be at least 70% or 80% of the specified
or guaranteed minimum tensile strength of the nonwelded plate for a 70%
or 80 % joint efficiency, respectively. Weld failure shall be at least 95% of the
shear fracture.
d.
From a separate test plate consisting of 300 mm of the first pass of the
bottom plate fillet weld, three cross sections of the weld shall be taken to
show the penetration into the base material. The minimum penetration at the
heel to be mm, as shown in the above sketch, and complete fusion shall
exist throughout each cross section.
ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 15
.Men Principal
Indice manual
Indice volumen
Indice norma
b.
Number of
Diameter Axes
4
6
8
10
ENGINEERING SPECIFICATION
PDVSA
PDVSA F201
REVISION
FECHA
DEC.00
Pgina 16
.Men Principal
Indice manual
Indice volumen
Indice norma
Lnea diametral
Punto de
medicin
en placa
anular
3m
Placa del fondo
3m
Placa anular
Punto de medicin
en placa anular
Punto de
medicin
en la pared