Lighting Circuits PDF
Lighting Circuits PDF
Lighting Circuits
Phase 2
Module No. 2.2
Unit No. 2.2.2
COURSE NOTES
SOLAS
Table of Contents
INTRODUCTION ................................................................................................................................................ 4
GRAPHICAL SYMBOLS ................................................................................................................................... 5
DEFINITIONS ...................................................................................................................................................... 8
SEQUENCE OF CONTROL ............................................................................................................................... 9
DOMESTIC INSTALLATION TYPES ........................................................................................................... 10
SURFACE MOUNTED INSTALLATION ...................................................................................................... 11
SWITCHES ......................................................................................................................................................... 12
LAMPHOLDERS ............................................................................................................................................... 17
BATTEN LAMPHOLDERS .............................................................................................................................. 18
CEILING ROSES ............................................................................................................................................... 20
SWITCHING CIRCUITS .................................................................................................................................. 23
THE INCANDESCENT LAMP ........................................................................................................................ 29
DOMESTIC LIGHTING CIRCUITS............................................................................................................... 36
TIMESWITCH CONTROLLED LIGHTING................................................................................................. 40
SMOKE ALARMS ............................................................................................................................................. 42
TESTING LIGHTING CIRCUITS................................................................................................................... 44
MINI-TRUNKING SYSTEMS .......................................................................................................................... 46
DRY LINING BOXES........................................................................................................................................ 55
UNIT RELATED ETCI RULES ....................................................................................................................... 59
SOLAS
Introduction
Welcome to this section of your course which is designed to enable you the learner, install
domestic lighting circuits.
Objectives
By the end of this unit you will be able to:
Reasons
Understanding this information will allow you read a drawing showing location of lighting
accessories, switches etc. in a domestic installation. You will be able to read a circuit drawing
showing lighting points controlled by 1 Way, Selective, 2 Way, and 2 Way and Intermediate
switching.
SOLAS
Graphical Symbols
Architectural
Distribution board
Intermediate Switch
Spotlight
SOLAS
Time Switch
SOLAS
Circuit
Fuse
Isolator
Fuse Isolator
Fuse Switch
Intermediate Switch
Conductors Crossing
( Not Connected )
Conductors Crossing
( Connected )
Earth
SOLAS
Definitions
Wiring System: An assembly made up of cables or busbars and the parts that secure, and if
necessary enclose, the cables or busbars.
DSO: The distribution system operator.
Main Supply Point ( origin of an installation ): The point at which the supply is connected to
an installation.
Nominal Voltage: A voltage by which an installation, or part of an installation, is designated.
Low Voltage: A nominal voltage exceeding 50 V AC or 120 V DC but not exceeding 1000 V
AC or 1500 V DC.
Extra Low Voltage: A nominal voltage not exceeding 50 V AC or 120 V DC between
conductors or between a conductor and earth.
Isolation ( isolating function ): Function intended to cut off the supply from all or a discrete
section of the installation by separating the installation or section from every source of
electrical energy for reasons of safety.
Isolating Switch: A mechanical switching device that, in the open position, complies with the
requirements specified for the isolating function.
Main Isolating Switch: A switching device provided at the main supply point for the purpose
of isolating an installation.
Switchgear: Equipment provided to be connected to an electrical circuit for the purpose of
carrying out one or more of the following functions: protection, control, isolation, switching.
Distribution Board: An assembly of protective devices, including two or more fuses or circuit
breakers, arranged for the distribution of electrical energy to final circuits or to other
distribution boards.
Circuit: Part of an electrical installation supplied from the same origin and protected against
overcurrents by a single protective device.
Current Using Equipment: Equipment intended to convert electrical energy into another form
of energy, for example light, heat or motive power.
Final Circuit: A circuit connected directly to current using equipment or to socket outlets.
Point ( in wiring ): A termination of the fixed wiring intended for the connection of currentusing equipment.
Luminaire: Apparatus that distributes, filters or transforms the light transmitted from one or
more lamps and includes all the parts necessary for supporting, fixing and protecting the lamps
and where necessary, circuit auxiliaries together with the means for connecting them to the
supply. It does not include the lamps themselves.
Main Earthing Terminal ( MET ) or Bar: A terminal or bar provided for the connection of
protective conductors, main equipotential bonding conductors and conductors for functional
earthing if any, to the means of earthing.
Live Part: A conductor or conductive part intended to be energised in normal use, including a
neutral conductor, but not a PEN conductor.
SOLAS
Sequence of Control
The electricity supply to a domestic installation begins at the meter cabinet which houses the
DSO service fuse, DSO meter and an isolator. This is the Main Supply Point.
The DSO supply cable is referred to as the service cable. The DSO service fuse and meter are
sealed to prevent any interference with this part of the installation. The Nominal Voltage of the
supply to domestic premises is 230 Volts. This is known as Low Voltage.
The control and distribution of the electricity supply to the installation is contained within one
enclosure. It is referred to as a Distribution Board. This unit has its own main switch fuse, or
a separate main switch and main fuse, or main MCB. This is followed by individual circuit
fuses or more commonly nowadays, Miniature Circuit Breakers ( MCBs ), to protect and
isolate each circuit. There will also be neutral and earth terminals provided. See Figure 1.
Isolator
To Final Circuits
Distribution Board
Figure 1.
The distribution board may also house other protective or control devices such as Residual
Current Devices ( RCDs ), bell transformers, time-switches and contactors.
Figure 2 represents the sequence of control for a very basic distribution board. Depending on
the installation requirements, a second or third RCD may be required and of course, more
MCBs, one for each circuit.
Distribution Board
Main Switch Fuse
SOLAS
10
SOLAS
Figure 3
Figure 4
11
SOLAS
Switches
The type of switch used in domestic installations is called a plate switch. Figure 5 illustrates a
1 gang 1 way plate switch. One gang refers to the fact that there is only one switch in the plate.
One-way indicates that it is a one-way switch, two-way and intermediate switches are also
available.
Figure 5
These switches are usually rated at 5 or 6 Amps, and intended for use on AC circuits only. They
are rocker type switches and the operating principle of a 1 way single pole switch is shown in
Figure 6.
Single pole means that there is only one contact. The contact must be used to break the phase
conductor. If the number of poles is not mentioned for a particular switch, then it is assumed to
be a single pole switch. Double pole switches are also available.
This type of switch has a centre-pivoted dolly. This dolly operates a contact, through a spring
loaded, ball and socket mechanism. When the rocker is pressed to the down position, the
contact closes and when pressed to the up position, the contact opens.
Terminal
Plate
Rocker Dolly
Up Position
Moving Contact
Contact Open
Terminal
On
Off
Figure 6.
12
SOLAS
Top
5A
250V
AC Only
Figure 7.
Figure 8 illustrates a 1 Gang 2 Way Single Pole switch, it has three terminals. The switch feed
is normally connected to the common terminal and the switch will then give an output on either
the L1 or L2 terminal. If there is more than one switch mounted on the plate, the wiring will be
more complicated. It is best to simply identify each switch as a separate item.
Common
Top
6A
250V
AC Only
L2
L1
Figure 8.
13
SOLAS
Figure 9 illustrates an intermediate switch, it has four terminals. This is a more complicated
switch and will be dealt with later on.
L1
Intermediate
6A
250V
AC Only
L2
Figure 9.
14
SOLAS
Figure 10.
Figure 11 illustrates a 2 Gang 2 Way Plate Switch. Two gang one way switches may not always
be available, in this event two gang two way plate switches are generally used. This also applies
to 3, 4 and 6 Gang switches.
Figure 11.
15
SOLAS
Figure 12.
Figure 13 illustrates a 4 Gang 2 Way Plate Switch; a double box is required for this switch.
A 6 Gang 2 Way Plate Switch is also available
Figure 13.
16
SOLAS
Lampholders
Figure 14 illustrates a standard Bayonet Cap ( BC ) lampholder. BC lampholders are normally
found in domestic installations. They are also available with a long shield. The shield, which is
screwed on, is also used to retain any lampshade, which may be fitted.
Figure 14.
Autom atic
Cord Grips
M oulde d
Cons truction
Te rm inals
Figure 15.
17
SOLAS
Batten Lampholders
There are a variety of batten type lampholders on the market. The following is a sample of
some of these.
Figure 16 illustrates a straight batten lampholder fitted with a short shield. This shield
provides protection against touching of the lamp cap. The batten lampholder has no backplate
and therefore cannot be mounted directly on a surface without the use of a suitable base or box.
Batten lampholders may have two or three terminals present.
Figure 16.
Figure 17 illustrates an angle batten lampholder fitted with a long shield. It is also available
with a short shield fitted. The long shield affords better protection against touching of the lamp.
They have limited use in a modern installation.
Figure 17.
18
SOLAS
Figure 18 illustrates a mounting block for use with batten lampholders where necessary.
Figure 18.
Figure 19 illustrates a straight batten lampholder with an integral backplate fitted. This type of
batten lampholder may have three or four terminals, and can be mounted directly on a surface.
Cable entry is via the backplate.
Figure 19.
IMPORTANT: Batten lampholders, without an integral backplate, may not be mounted
directly on a surface.
19
SOLAS
Ceiling Roses
There are basically two types of ceiling rose available, although there is a wide range of makes
and shapes. The two types are the Two-Plate Ceiling Rose, which has two terminals and the
Three-Plate Ceiling Rose, which has three terminals. Both were developed for use on different
wiring systems. Older types of ceiling roses were developed at a time when it was not necessary
to provide an earth at lighting points. It is now essential to provide an earth, and so an earth
terminal is now included on all ceiling roses. This in effect means that a Two-Plate Ceiling
Rose has a third terminal fitted, whilst a Three-Plate Ceiling Rose has four terminals.
Figure 20 illustrates one of the original types of Two-Plate Ceiling Rose. The earth terminal is
marked E and the two unmarked terminals are used for the neutral and the switch wire. There
must also be a cord grip provided similar to that in a lampholder.
Figure 20
Figure 21 illustrates a Three-Plate Ceiling Rose. The additional terminal, marked L, is for the
Phase or Live conductor, which is present in a lighting system wired using the Three-Plate
Ceiling Rose Method.
Figure 21.
20
SOLAS
Figure 22 illustrates a modern type Three-Plate Ceiling Rose which has been designed to
minimise installation time, and maximise safety of the installer and the end user. Each of the
four terminal blocks have three individual terminal screws. It caters for the connection of
twelve conductors.
Figure 22.
Figure 23 illustrates a lampholder connected to a ceiling rose. The complete unit is called a
pendant. The flex connecting the lampholder to the ceiling rose should be a minimum of
0.5mm2. Heat Resisting White Circular PVC type is recommended.
Pendants are available from certain manufacturers in a range of flex length. This allows
installations to be completed more efficiently.
Figure 23.
21
SOLAS
Figure 24 illustrates a plug-in type ceiling rose and safety lampholder, which can be easily
removed without leaving exposed conductors. The safety lampholder incorporates contacts,
which are automatically disconnected from the supply, when the lamp is removed.
Figure 24.
The table below set out the maximum weight, which can be supported by some common, flex
sizes.
Flex
0.5mm2
0.75mm2
1.0mm2
Max. Weight
2 kg
3 kg
5 kg
22
SOLAS
Switching Circuits
One-Way Switching Circuit
Figure 25 shows how a lamp is controlled by a simple one-way switch, providing on / off
control of the lamp. The phase conductor is connected to the one-way switch, terminal C,
through a suitably rated fuse or MCB, 6-10A. The neutral is connected directly to the lamp.
When the switch is closed the phase conductor is switched through to the lamp from terminal
L1 and the 230 V supply is placed across the terminals of the lamp and so the lamp is
illuminated.
When the switch is opened the phase conductor is interrupted and the lamp is extinguished.
This occurs when the switch is in the up position.
Figure 25.
If more than one lamp is required, the extra lamp or lamps should be connected in parallel as
shown in Figure 26.
Figure 26.
23
SOLAS
Figure 27.
24
SOLAS
Figure 28
25
SOLAS
Figure 29
26
SOLAS
Figure 30.
The intermediate switch has four terminals. These terminals may be labelled in different ways,
few of which are of any benefit to the installer. To complicate matters, there are two distinct
types of intermediate switch. The more common type is shown in Figure 31. To consider how it
functions we will number the terminals as follows:
In the up position terminals 1 and 2 are connected to terminals 3 and 4 respectively.
In the down position terminals 1 and 2 are connected to terminals 4 and 3 respectively.
See Figure 32.
Figure 31
Figure 32
If we apply this information to the circuit above we can see that the lamp is off. By operating
the intermediate switch, the lamp can be switched on. The two two-way switches operate as
previously described. Other makes of intermediate switch may operate the opposite way round.
27
SOLAS
The other, less common type of intermediate switch operates as shown in Figure 33.
Up position
Down position
Figure 33
Figure 34
Again, if we apply the information regarding this type of intermediate switch, to the circuit
shown in Figure 34, we can see that the lamp is off. By operating the intermediate switch, the
lamp can be switched on. Alternate operating of the switches in any order will change the
lamp condition i.e. off to on or on to off
It is obvious from Figure 34, that an intermediate switch has four terminals. It is important to
remember that there are other types of switches, which have four terminals ( e.g. double pole
switches ). The word inter or intermediate should be clearly marked on the back of an
intermediate switch.
It is worth noting that a two-way switch or an intermediate switch can be used to complete the
function of a one-way switch in a circuit. Also, an intermediate switch can be used instead of a
two-way switch. This would only be done where the correct type of switch was not readily
available.
28
SOLAS
This very fine wire is wound in the form of a coil ( single coil filament ). This process is taken
a step further by coiling the coil ( coiled coil filament ), which improves the efficiency further,
especially for the smaller ranges of lamp ( below 150W ).
See Figure 35
Figure 35
29
SOLAS
Figure 36 illustrates the filament supported on a metal spider, which is held by a glass stem
and the whole arrangement is enclosed in a glass envelope, or bulb. The filament fuse is a
valuable feature as it avoids possible disruptive arcing and the blowing of circuit fuses when a
lamp fails.
Cap
Fuse
Lead - In Wires
Glass Stem
Spider for supporting
Filament
Figure 36.
1. Vacuum Lamp
To prevent oxidisation and premature failure of the lamp filament, all oxygen has to be
removed from the glass bulb. The filament is operated in a vacuum. The vacuum has the
disadvantage that the filament vaporises at a lower temperature. This allows tungsten to
condense on the internal surface of the bulb. The result is, blackening of the bulb and a
consequent reduction of efficiency. The highest temperature at which it is possible to operate
the filament is approximately 2100oC.
30
SOLAS
The light output covers the visible spectrum giving a warm white to yellow light with good
colour rendering. This means that the colours of articles viewed in the light of a GLS lamp are
faithfully reproduced. The life expectancy of a modern GLS lamp is about 1,000 hours.
The GLS lamp is unchallenged as the domestic light source. Despite the availability of more
efficient lamps there are more GLS lamps produced each year than any other type.
One factor which may have contributed to the popularity of the GLS lamp is that designers have
been able to modify the glass envelope to give a very pleasing decorative appearance as shown
in Figure 37.
Pear
Mushroom
Shaped
Candle
Twisted Candle
Figure 37.
31
SOLAS
Bulb Types
There are three main types of bulb:
Clear - a transparent bulb of clear glass, suitable for use in enclosed fittings where the bulb is
not visible. This is to reduce glare.
Pearl - acid treated on the inside, which causes diffusion of the light and reduces glare, suitable
for open-bottom type fittings.
Silica Coated - coated internally with a white silica compound and are usually mushroom
shaped. They produce glare free light.
GLS lamps are also available in a variety of colours to provide festive lighting.
A much smaller version of the GLS known as a pygmy lamp is used in such places as fridges
and ovens. These lamps are available in a range of colours and are often used to provide festive
lighting. They may also be used where space is restricted or as indicator lamps.
Cap Types
Incandescent or tungsten filament lamps are classified according to the type of cap, by which
they are connected to the supply. The two main types in use are the Bayonet Cap ( BC ) and the
Edison Screw ( ES )
Bayonet Cap ( BC )
This is the most commonly used type where the filament ends terminate in raised solder
contacts. These contacts connect to the corresponding pins in the lampholder and the lamp is
held in position by the two retaining pins as shown in Figure 38.
Solder Contact
Solder Contact
B22
Retaining
Pin
22 mm
Figure 38.
32
SOLAS
Solder Contact
B15
15 mm
Retaining
Pin
Figure 39
B9
Solder Contact
9mm
Retaining
Pin
Figure 40.
Edison Screw ( ES )
In this type of lamp the cap is threaded and screws into an Edison Screw lampholder. One side
of the filament is connected to a centre contact while the other side is connected to the brass
cap. The phase conductor is connected to a corresponding contact at the back of the lampholder
while the neutral is connected to the threaded part.
These lamps are manufactured in the same range as BC types and are frequently used for spot
lighting, infra red and reflector applications. See Figure 41.
E27
Thread
(Neutral)
Centre
Contact
(Phase)
Figure 41.
33
SOLAS
This is simply a larger version of the ES type ( both physically and electrically ). It is used for
higher wattage lamps than the ES type, mainly for street lighting. See Figure 42.
E40
Figure 42.
Small Edison Screw ( SES )
Used for lighting inside fridges / freezers and decorative lamps. See Figure 43.
E14
Figure 43.
Miniature Edison Screw ( MES )
Used in older cookers and clothes irons as an indicator lamp, usually 2.5, 6, or 12 Volts. Also
used in hand torches and bicycle lamps. See Figure 44.
E10
Figure 44.
Safety
Always ensure that the ES lampholder is correctly connected, otherwise a person removing or
replacing the lamp could receive a serious shock from the threaded part of the lamp or
lampholder.
34
SOLAS
Lamp Ratings
Lamps are rated according to their wattage.
BC Lamps are available in the following wattages:
15, 25, 40, 60, 75, 100, 150, 200 Watts.
ES Lamps are available in the same general range as BC but up to 300 Watts.
GES Lamps are available up to 1500 Watts.
Vibration
2.
Heat
3.
Ventilation
1. Vibration
When the filament, which is extremely fine, is at operating temperature any vibration or
mechanical shock can cause distortion of the coil and rapid burnout.
NEVER check a lamp to see if it has blown by vibrating it.
2. Heat
In normal service, the lamp dissipates heat. It is important that high temperatures are avoided,
in fittings wholly or partly made from plastics. The manufacturers maximum permitted lamp
wattage should not be exceeded. Most light fittings carry a label stating what this maximum
wattage is. All too frequently users increase the wattage of the lamp, as the fittings will
physically accept them. This practice should be avoided as it may be a fire hazard and also
shortens the life of the lamp.
3. Ventilation
Enclosed fittings must have adequate ventilation otherwise the life of the lamp will be
shortened.
35
SOLAS
Loop-in Method
The loop-in method is completed using 1.5mm2 PVC / PVC single core cables plus a Protective
Conductor ( PE ). Switch feeds and switch wires are wired with brown cable. Neutrals are wired
with blue cable. A protective conductor must be provided at all lighting points and at all switch
positions. These must be insulated with Green / Yellow sleeving. Switches are installed at a
standard height of 1.1 metres above the finished floor level ( FFL ).
Lamps are placed in the centre of room ceilings except when more than one lamp is to be fitted.
There should be no more than ten lighting points per circuit. There should be at least two
lighting circuits per dwelling. This is to ensure that the entire house is not plunged into darkness
if one lighting circuit fails. Figure 45 shows how three lamps, individually controlled by oneway switches are connected to the supply.
Figure 45.
36
SOLAS
Figure 46.
37
SOLAS
Figure 47.
38
SOLAS
Figure 48.
Figure 49.
39
SOLAS
Figure 50.
Most timeswitches feature a built in switch. It may be labelled in different ways. It is
however a simple two way switch with an OFF position. It allows for the timeswitch load to
be permanently off, permanently on or timed. An indicator light is another useful feature as it
gives clear indication that the supply is on the load. It is connected across the outgoing supply
from the timeswitch.
N.B. Remember that any load supplied via a timeswitch may be powered up unexpectedly.
Typical Specifications
Voltage Rating
Current Rating
Switching Operations
Min. Switching Period
40
SOLAS
Analogue Timeswitch
Figure 52
Figure 51
Figure 53
41
SOLAS
Smoke Alarms
In the event of a fire, the presence of smoke in escape routes ( stairways and hallways ) is the
greatest problem in effecting a safe exit from a building. Smoke alarm units should be installed
in these areas. Almost half of domestic fires start in kitchens. Nearby exit routes must be
protected. Electrical appliances and wiring cause 15% of fires. The most common cause of
fatalities involves materials used by smokers. The use of electric blankets, particularly by the
elderly is another high risk situation. People with impaired mobility require more time to
escape. These areas must be protected.
Alarms will only work if sleeping occupants can hear them through a closed door. For people
with a severe hearing impairment, a visual alarm and under pillow vibrating disc is
recommended. These can be operated by a detector unit.
Smoke Alarm Systems are classified into six grades. The most elaborate system is a Grade A,
while the most basic system is a grade F.
A Grade F System consists of one or more battery operated alarm units. These are the least
reliable on account of the need for the battery to be checked periodically.
A Grade E System consists of one or more mains operated units. These are reliable only if there
is a very low risk of loss of mains supply.
A Grade D System consists of one or more mains operated units with battery back up supply.
These are the most reliable types as the battery maintains supply in the event of mains failure.
The system recommended in domestic premises is a Grade D.
There are three different types of detector.
1. Ionisation
2. Optical
3. Heat
An explanation of how they operate is beyond the scope of Phase 2.
The minimum requirement for most domestic installations is four detectors. One ionisation type
fitted upstairs on the landing and one optical type fitted downstairs in the hallway.
The optical type should be used on the same floor as the kitchen. It is much less likely to be
triggered by cooking operations than the ionisation type. A heat detector should be installed in
the kitchen. A smoke or heat detector should be installed in the main living room. A more
elaborate system may of course be installed.
Detectors should be installed in the centre of ceilings if possible. They should be at least 300
mm from any light fitting in the room. All units should be supplied directly from the same
lighting circuit MCB. This is for safety reasons, as all units are interconnected. The interconnect
wire should be treated as if it were a live conductor. Supplying the units from a lighting circuit
automatically provides monitoring of the mains supply to them.
Units should be interconnected so that if one is triggered, all other units will alarm. Observe
correct polarity of supply to all interconnected units. If polarity is wrong, damage will be done
through the interconnection.
42
SOLAS
Units should not be attached to their mounting plates until all building work is completed. This
is to avoid contamination by dust etc. Some manufacturers provide dust covers to overcome this
problem.
N.B. Disconnect units during Insulation Resistance testing as the high test voltage will cause
damage. This test is best done before the units are installed on their mounting bases.
Figure 54
Figure 55
43
SOLAS
A wander lead of known resistance is required to reach from the distribution board to each
switch and lamp position.
Connect the other lead to the switch feed terminal. See Figure 56.
A very low resistance value should be indicated, corresponding to the length and CSA of the
conductor involved. This resistance should be indicated, regardless of the switch position,
i.e. on or off.
Figure 56.
44
SOLAS
A very low resistance value should be indicated, only when the switch is in the on position.
Figure 57.
Note:
45
SOLAS
Mini-trunking Systems
There is a wide variety of types and sizes of plastic mini-trunking manufactured today.
One of the most common sizes of mini-trunking in use is 25mm wide and 16mm deep.
The following table illustrates the range of sizes available from one manufacturer.
Sizes are quoted in millimetres.
Sizes:
1 compartment
16 x 10
16 x 16
25 x 16
38 x 16
38 x 25
50 x 25
38 x 38
2 compartment
38 x 16
38 x 25
75 x 16
Figure 58.
46
SOLAS
There is a wide range of snap-on mini-trunking fittings available. These allow for changes in
trunking sizes and the direction of trunking runs.
Figure 59 illustrates a sample of the snap-on fittings available:-
Internal Bend
External Bend
Flat Bend
Coupler
Unequal Tee
Angle Tee
Figure 59.
Also available is a range of switch and socket boxes to suit the various trunking sizes.
Figure 60 shows a single switch box, which is 19mm deep and has knockouts to cater for 16 x
16mm or 25 x 16mm trunking entering the top or bottom. The box may be fitted either way up
to allow either size of trunking enter in the centre or towards the left or right hand corners. Note
the slotted fixing holes, which facilitate accurate alignment.
Figure 60.
47
SOLAS
Figure 61 shows a single socket box, which is 25mm deep. Other box sizes are available to
accept larger accessories or cables.
Figure 61.
Figure 62 illustrates the adaptors used to terminate the plastic trunking into the type of box
shown in Figures 60 and 61. This adaptor simply clicks into position on the box.
16 x16
25 x 16
Figure 62.
Figure 63 shows a double socket box, which is 32mm deep. This particular box allows for the
direct entry of 25 x 16mm trunking to the centre, top or bottom. Side entry versions of all these
boxes are also available.
Figure 63.
48
SOLAS
Figure 64 shows a ceiling rose adaptor. The adaptor allows for the entry of 16 x 16mm or 25 x
16mm trunking. It is designed to accept all popular makes of ceiling rose and batten
lampholder.
Figure 64.
Self-Fixing Mini-Trunking
To locate self-fixing mini-trunking, peel off the backing paper exposing 500mm of self
adhesive tape at a time. Line up the trunking accurately and press home. The self-adhesive tape
will bond to almost any dust-free surface. Surfaces must be smooth and flat. Uneven surface
contact will reduce the bonding performance of the self-adhesive tape. Surfaces must be clean
and dry. Installation of trunking in cold conditions may affect adhesion. Wood, plaster, plastics,
metals, brick, paintwork, paper and glass are suitable surfaces.
49
SOLAS
Fixing Mini-Trunking
The fixing technique used will vary depending on whether the joints are mitred or moulded
fittings are used.
Mitred Joints:
1. Plan the route of the main trunking run together with tees, drops to switches and socket
outlets etc. Mark the positions and fix all boxes.
2. The trunking must be accurately mitred for bends and tees etc. Cut the trunking body
and lid in the one operation. Where frequent temperature changes are likely, allow for
expansion of approximately 0.7mm per 10C per metre. Fix the body of the trunking
by drilling oversized holes and screwing through the base with roundhead screws. Do
not over tighten the fixing screws. The oversized holes allow for movement due to
expansion. It is recommended that for installations at low level, fixing centres should be
no greater than 375mm. For high level installations fixing centres should be no greater
than 600mm.
3. Cables are now installed. Clip on the lid, making sure that the lid and base joints are
staggered for better security. Ensure that the lid is clipped on properly throughout its
length.
Moulded Fittings:
1. Plan the route of the main trunking run together with tees, drops to switches and socket
outlets etc. Mark the positions and fix all boxes.
2. Where moulded fittings are used the need for accurate mitring is eliminated. The
trunking ends need only be cut to butt each other. Where frequent temperature changes
are likely, allow for expansion of approximately 0.7mm per 10C per metre. Fix the
body of the trunking by drilling oversized holes and screwing through the base with
roundhead screws. Do not over tighten the fixing screws. The oversized holes allow
for movement due to expansion. It is recommended that for installations at low level,
fixing centres should be no greater than 375mm. For high level installations fixing
centres should be no greater than 600mm.
3. Cables are now installed. Clip on the lid by sliding one end under the cover of the first
moulded fitting. Mark the lid about 6mm beyond the next fitting and cut. Spring the end
of the lid under next fitting and snap it into position along the main body of the
trunking. Repeat this procedure between fittings until installation is complete.
50
SOLAS
Mini-Trunking Fitting
Coupler
Cut the trunking to length as required. Allowing an appropriate gap for expansion, butt the ends
together, as shown in Figure 65.
Figure 65
Tee
Cut the trunking to length as required. Remove a section of the sidewall of the through
trunking. Allowing an appropriate gap for expansion, butt the tee trunking to the opening, as
shown in Figure 66.
Figure 66.
51
SOLAS
Flat Bend
Cut the trunking to length as required. Remove a section of sidewall. Allowing an appropriate
gap for expansion, butt the ends together, as shown in Figure 67. This method is only suitable
where a moulded fitting is to be used.
Figure 67.
Alternatively the ends of the trunking may be mitred as shown in Figure 68.
Figure 68.
52
SOLAS
Internal Bend
Cut the trunking to length as required. Remove a section of sidewall on one piece. Leave the
back of the trunking intact to complete the enclosure. Allowing an appropriate gap for
expansion, butt the ends together. See Figure 69.
Figure 69.
Alternatively the ends of the trunking may be mitred as shown in Figure 70.
Figure 70
53
SOLAS
Ceiling Tee
Cut the trunking to length as required. Remove a section of the lip of the through trunking.
Allowing an appropriate gap for expansion, butt the tee trunking to the opening, as shown in
Figure 71.
Alternatively, an offset tee may be used if the through trunking is run below ceiling height.
Figure 71.
Ceiling Rose Adaptor
Break out the appropriate knockout(s) in ceiling rose adaptor. Fix ceiling rose adaptor in
position. Cut the trunking to length as required and fix to ceiling.
A dummy run of trunking may be fixed to the opposite side of the ceiling rose adaptor in order
to achieve a visual balance. Running on through the ceiling rose adaptor will facilitate a second
light fitting, see Figure 72.
Figure 72.
54
SOLAS
Figure 73.
Figure 74 shows a twin dry lining box. It is also available in the three sizes mentioned above.
This box will accommodate double plate switches and twin sockets. A deeper version is
available for cooker switches and shaver sockets.
Figure 74.
55
SOLAS
Figure 75 shows a dual dry lining box. It will allow any two single accessories to be fitted side
by side. The box segregates the wiring to these accessories which is a requirement by the ETCI
Rules in certain circumstances.
Figure 75
A circular dry lining box is also available which may be used to fix ceiling roses, batten
lampholders, pull cord switches etc. It can be fixed to any board having a thickness between
10mm and 32mm. See Figure 76.
Figure 76
56
SOLAS
All dry lining boxes feature securing lugs which are used to retain the box in position.
See Figure 77.
Figure 77.
57
SOLAS
58
Figure 54
SOLAS
Distribution Boards
Switches
Luminaires
462
462.1
462.2
462.3
462.4
530
530.5, 530.5., 530.5.2, 530.5.3, 530.5.4, 530.5.6,
530.5.7, 530.5.8, 530.5.10, 530.5.11, 530.5.12
530.6
559
559.1
559.3
559.4, 559.4.1, 559.4.2
559.5, 559.5.1, 559.5.2
559.6, 559.6.1
559.6.2, 559.6.3, 559.6.3.1, 559.6.3.2
559.6, 559.6.4, 559.6.5
559.11
Annex 55A
1 ( Lighting Circuits only )
4, 4.1
59