INTRODUCTION
The TMG 740-3 burner control box is capable of controlling
and monitoring medium to high performance forced draught
and dual fuel oil/gas burners in single or two stage versions.
It can be used, as prefered, for multi-stage or modulating
operation with burners of any nominal rating as well as in
direct air heaters (as per DIN 4794).
Different model designations identify the control boxes
according to programme times for varying national standards,
or for special applications e.g. high-speed steam generators.
A special version is available for operation with ignition
spark monitoring in conformance with French national
regulations.
The TMG 740-3 is fully interchangeable with the earlier
versions -1 and -2.
TECHNICAL DATA
Supply voltage
AC frequency variations
deviations
Fuse rating
Power consumption
Max. current per
output terminal
Total
Sensitivity
Ionisation input
UV input
Min. sensor current
Ionisation/IR probe
UV tube
Air proving switch
Reset delay
Flame detector cable
Ionisation
CONSTRUCTIONAL FEATURES
The control box is enclosed in a protective, flame resistant,
transparent, plug-in type plastic housing, and includes:
- Synchronous motor with gearbox driving cam switch
- Cam switch with informative, coloured programme
indicator
- 16-way cam switch assembly controlling the programme
sequence
- 2 DC relays and 1 remanence relay on common yoke
- Plug-in printed circuit board with mains transformer, LED
display and electronic components
On the underside of the unit are robust plug terminals where
the air proving switch and monitoring of the ignition spark
can be programmed via two wire links which can be cut as
required. The flame detector selection switch is also situated
on the the underside of the unit.
50 m normal cable
100 m screened cable
UV tube
100 m normal cable
200 m screened cable
UV tube UVZ 780 blue
low sensitivity
UVZ 780 white
medium sensitivity
UVZ 780 red
high sensitivity
Weight incl. base
1100 g
Mounting attitude
any
Insulation standard
IP 44
Permissable ambient temp. -20 C to +60 C incl.
Classified acc. to EN 298 BTLLXN
Model No.
60
32
30
3
2
3
11
2
9
6
7
60
4
3
5
13.5
5
10
20
16
40
4
3
3
14
5
10
10
10
6
1
3
5
8
3
6
4
-
TECHNICAL FEATURES
1. Flame detection
The following types of flame detector can be used:
- Ionisation electrode, where the mains supply provides a
neutral earth connection. Suitable for gas burners (signal
current from flame cannot be influenced by interference
from ignition spark).
- UV sensor type UVZ 780 red, suitable for gas, oil and dual
fuel burners.
- Infra-red flicker detector type IRD 820 and 1020 for all
types of burner.
The flame signal amplifier is adjusted to the the type of
detector probe fitted by using the flame detector selection
switch on the underside of the unit. If the IRD flicker detector
is used, the selection switch must be adjusted to the "ION"
position.
Flame detection is only operational when the switch position
selected corresponds to the type of detector probe
connected.
By optimally matching the amplifier to the detector probe,
considerably longer signal transmission distances with less
sensitivity to interference can be achieved.
3. Safety
The design and programme sequence employed in the
control boxes in the TMG 740-3 series conform to the
presently applicable European standards and regulations.
The following features exceed the requirements of most
standards, and therefore ensure additional safety:
- After a normal shutdown, the stray light test is started
immediatly by the control box which directs an increased
voltage to the UV sensor. The very important extinguishing
function of the sensor can therefore be checked. If the fuel
valve does not close correctly, or a sensor or amplifier
malfunction occurs, shutdown and lockout take place
after approx. 20 sec., even if the controlling thermostat
is open.
- The contacts responsible for the release of fuel are checked
when the programme starts, to ensure that they have not
become welded together.
General:
- Can be mounted in any position, insulated as per IP 44
standard (unaffected by water spray). The control box and
detector probes should not however be subjected to
excessive vibration. With the UVZ 780 ultra-violet sensor,
care should be taken to ensure that a good electrical
contact to the burner exists via the metal flange.
- If an ionisation electrode is used, appropriate protective
measures are required in order to avoid contact with the
electrode while installation work is being carried out.
Trouble-free operation with this type of flame detection is
not possible if a voltage of over 25 volts is measured
between neutral and earth. In this case, provision must be
made for a separate isolating transformer.
- The maximum lengths for the detector probe cables,
depending on the type of cable installed, are listed in the
technical data and must be adhered to without fail. Laying
the cables parallel to mains cabling over long distances
should be avoided, and the use of multiple core cable is
also not permitted.
2. Burner Control
- Burners can be operated with or without post-purge.
This varies according to model (see technical data)
and is activated when the burner motor is connected to
terminal 19.
- Air damper operation is monitored to ensure the nominal
air volume during pre-purge and in the starting position
before fuel is released. If confirmation of the damper
positions "MIN" and "MAX" is not received, the control
box start sequence is interrupted.
- The air proving switch is checked for corrrect operation
before the start, and air pressure is monitored during prepurge as well as during normal operation. In normal use,
switch contacts with a rating of 6A/220V are sufficient.
Additional switch contacts which are to be monitored can
be connected between terminal 18 and the air proving
switch working contact. In this case, jumper II on the
underside of the control box should be cut.
2
TMG 740-3
At the base:
- 3 earth terminals, with an additional tag for the burner
earth.
- 3 neutral terminals, with a fixed internal through connection
to the neutral input, terminal 8.
- 2 separate slide-in plates and 4 fixed, threaded knockouts
(PG 11 thread) as well as a wiring opening from below, to
facilitate wiring of the base.
- A keyed fit ensures that the wrong control box type cannot
be fitted to the base. The corresponding control box
designation is shown in lettering on the base.
WIRING DIAGRAMS
IRD CONNECTION
IRD
1020
blue
Kl. 8
black
Kl. 1
brown
Kl. 20
Ph 220/240V ~
max. 10A rapid
6A slow
GW
RT
HS
ST
19
20
GLT
1
21
13
max. LK
14
15
16
17
18
12
10
11
max. min.
IS
M1
PV
IRD
Z
V1
LW
SA
R
UV
SV
V2
HS
ST
GW
RT
GLT
M
M1
Z
IRD
UV
Mains switch
Limit thermostat
Gas Pressure proving switch
Control thermostat
High/low operation thermostat
Burner motor
Burner motor for post-purge
Ignition transformer
Infra-red flicker detector
UV-cell
IS
PV
SV
V1
V2
LK
LW
R
SA
Programdisplay
blue
Start
blue
orange
yellow
Sz SV
Sz PV
red
Sz V1
green
Betrieb
black
TMG 740-3
19
20
21
13
14
15
required Input
16
17
18
Output
12
10
Terminal No.
2. Routine Checks
1. Important
Fault finding
Fault finding is considerably simplfied by making use of
the coloured programme indicator. Irregularities during
commissioning, normal operation or a normal shutdown
pause can be localised via the programme indicator disc.
If a malfunction occurs, it is useful to note the exact position
of the indicator before operating the control switch or reset
button.
The following list is designed to assist with fault finding.
COLOUR
WHERE
WHAT
REASON
BLUE
beginning
doesnt start
line
end
anywhere
continuous ventilation
lockout
continuous ventilation
lockout
YELLOW
end
lockout
RED
end
lockout
GREEN
end
lockout
BLACK
end
lockout
- stray light due to burning on, UVZ sensor tube reached end
of life and activates shutoff, defect in flame detector circuit
TMG 740-3
A test baseplate is available for checking the burner control box functions (model designation UP 7520, item no. 18601)
BURNER 1- OR 2-STAGE
Ph 220/240V ~
max. 10A rapid
6A slow
GW
RT
HS
ST
19
20
GLT
1
21
13
14
15
16
17
18
12
10
11
IS
M1
V1
IRD
SA
R
LW
UV
V2
GW
RT
HS
ST
19
20
GLT
1
21
13
14
15
16
17
18
12
10
11
M1
IRD
Z
LW
V1
UV
SA
R
V2
SV
2 NOZZLE BURNER
Ph 220/240V ~
max. 10A rapid
6A slow
GW
RT
HS
ST
19
20
GLT
1
21
13
14
15
16
17
18
12
10
11
TMG 740-3
M1
PV
IRD
Z
LW
V1
SA
R
UV
V2
SCHEMATIC DIAGRAMM
10A
ts 1
PH
ST
GAS
AIR
HS
ts 3
20
RT
10
17
18
16
ts 2
rm1
II
B
C
13
rs1
D
G1
NTC1 -
14
RM
+ C2
RF
rm2
3
18 2
1 5
7 8
15
R5
B
rf3
16
9
R2
R1
R6
rs2
rf1
rm3
O
12
D1
Q
K
rf2
R3
bl
R4
Sy
O
SA
R
IS
7
SA
11
21
max.
1
UV
RS
14
19
15
12
13
GL
M
SV
V1
PV
M BM
M BM
gn
sw
120
95
or gb rot
3
LM
R
V2
blau
17
max.
11
min.
10
r t
C1
PG 11
138
42
22
26
30.5
25
102
102
80
M4 earth tag
96
75
30
8
4
51
80
102
28
51
r 40
22
36
48
M4
underside cable entry
10
ORDERING INFORMATION
ITEM
DESIGNATION
Burner control box
Type TMG 740-3 Mod. 32-32
Socket
Socket TMG
Insert plate
PG-plate
optional
Cable entry plate
Flame detector
UVZ 780 white
or
UVZ 780 blue
or
UVZ 780 red
Flame detector
IRD 820
Flame detector
IRD 1020 end-on viewing
Flame detector
IRD 1020 side-on left
Flame detector
IRD 1020 side-on right
IRD mounting flange
IRD Holder M93
Flame detector cable
3-wire, 0.6 m
The above ordering information refers to the standard version.
Special versions are also included in our product range.