KEO Design Report
KEO Design Report
Specification
IA/12-13/D/003/ST
Pre Contract Professional Consultancy Design Services
for AI Rayyan Road & AI Bustan Street South (P007)
AL RAYYAN ROAD
Al Rayyan Road
Junctions R6 Road Tunnel
Control Sheet
Page i
Prepared by:
TABLE OF CONTENTS
1.0 INTRODUCTION ...................................................................................................................................... 1
1.1 Document Purpose and Scope.................................................................................................................. 1
1.2 Related Documents .................................................................................................................................. 1
1.3 Related Drawings ..................................................................................................................................... 1
1.4 Codes and standards applicable .............................................................................................................. 4
1.5 List of Abbreviations ................................................................................................................................. 5
2.0 ASHGHALS RELEVANT OBJEVTIVES ............................................................................................................ 9
3.0 ELECTROMAGNETIC COMPATIBILITY (EMC) ...................................................................................... 9
3.1 Normative references .......................................................................................................................... 9
4.0 PMCS OVERVIEW .................................................................................................................................. 10
4.1 Introduction............................................................................................................................................ 10
4.2 System Architecture ............................................................................................................................... 11
4.3 SCADA Servers ........................................................................................................................................ 11
4.4 Supervisory Control PLCs ....................................................................................................................... 12
4.5 Outstation PLCs ..................................................................................................................................... 12
4.6 Dual configuration ................................................................................................................................. 12
4.7 SCADA Graphical User Interface (Operator Interface) ........................................................................... 13
4.8 TMC/TSS ................................................................................................................................................. 14
4.9 Engineering Terminal ............................................................................................................................. 14
4.10 Control & Monitoring Software............................................................................................................ 15
4.11 Control Network ................................................................................................................................... 15
4.12 Instrumentation Interface .................................................................................................................... 15
4.13 Cable Types .......................................................................................................................................... 16
4.14 Equipment Accommodation ................................................................................................................. 16
4.15 Power Supply Redundancy ................................................................................................................... 16
4.16 Capacity Sizing ..................................................................................................................................... 16
5.0 GENERAL MONITORING AND CONTROL SCHEME ..................................................................................... 16
5.1 Data Acquisition ..................................................................................................................................... 16
5.2 Alarm Monitoring ................................................................................................................................... 17
5.3 Control and Data Flows .......................................................................................................................... 18
5.4 Control Modes ........................................................................................................................................ 18
5.5 Running Hours and Plant Metrics .......................................................................................................... 19
5.6 Signal Conditioning ................................................................................................................................ 19
6.0 TUNNEL LIGHTING SYSTEM CONTROL SCHEME ........................................................................................ 20
6.1 Control Scheme Overview ...................................................................................................................... 20
6.2 General Lighting Control Scheme ........................................................................................................... 20
6.3 Automatic Control Mode........................................................................................................................ 21
Page iii
Page iv
1.0 INTRODUCTION
1.1 Document Purpose and Scope
This document describes the outline design for the Tunnel Plant Monitoring and Control System
(PMCS) that forms part of the Tunnel construction works.
This document provides the following information:
Title
EXW-P007-0201-MC-KEO-RP-00209
EXW-P007-0201-MC-KEO-RP-00210
EXW-P007-0201-MC-KEO-RP-00211
EXW-P007-0201-MC-KEO-RP-00212
EXW-P007-0201-MC-KEO-RP-00213
EXW-P007-0201-MC-KEO-RP-00214
EXW-P007-0201-MC-KEO-RP-00215
EXW-P007-0201-MC-KEO-RP-00216
EXW-P007-0201-MC-KEO-RP-00217
Tunnel Panels
EXW-P007-0201-MC-KEO-RP-00218
EXW-P007-0201-MC-KEO-RP-00219
EXW-P007-0201-MC-KEO-RP-00220
EXW-P007-0201-MC-KEO-RP-00221
EXW-P007-0201-MC-KEO-RP-00222
EXW-P007-0201-MC-KEO-RP-00223
EXW-P007-0201-MC-KEO-RP-00224
Not used
EXW-P007-0201-MC-KEO-RP-00225
Title
RAYYAN ROAD KEY PLAN M&E LAYOUT (SHEET 1 OF 1)
RAYYAN ROAD FIRE SAFETY TYPICAL PLAN & SECTIONS (SHEET 1 OF 2)
RAYYAN ROAD FIRE SAFETY TYPICAL PLAN & SECTIONS (SHEET 2 OF 2)
RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES
LOCATION (SHEET 1 OF 8)
Page 1 of 36
Drawing No.
EXW-P007-0201-MC-KEODG-00107-002
EXW-P007-0201-MC-KEODG-00107-003
EXW-P007-0201-MC-KEODG-00107-004
EXW-P007-0201-MC-KEODG-00107-005
EXW-P007-0201-MC-KEODG-00107-006
EXW-P007-0201-MC-KEODG-00107-007
EXW-P007-0201-MC-KEODG-00107-008
EXW-P007-0201-MC-KEODG-00201-001
EXW-P007-0201-MC-KEODG-00201-002
EXW-P007-0201-MC-KEODG-00201-003
EXW-P007-0201-MC-KEODG-00201-004
EXW-P007-0201-MC-KEODG-00301-001
EXW-P007-0201-MC-KEODG-00301-002
EXW-P007-0201-MC-KEODG-00301-003
EXW-P007-0201-MC-KEODG-00301-004
EXW-P007-0201-MC-KEODG-00301-005
EXW-P007-0201-MC-KEODG-00301-006
EXW-P007-0201-MC-KEODG-00301-007
EXW-P007-0201-MC-KEODG-00302-001
EXW-P007-0201-MC-KEODG-00401-001
EXW-P007-0201-MC-KEODG-00401-002
EXW-P007-0201-MC-KEODG-00401-003
EXW-P007-0201-MC-KEODG-00401-004
EXW-P007-0201-MC-KEODG-00401-005
EXW-P007-0201-MC-KEODG-00401-006
Title
RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES
LOCATION (SHEET 2 OF 8)
RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES
LOCATION (SHEET 3 OF 8)
RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES
LOCATION (SHEET 4 OF 8)
RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES
LOCATION (SHEET 5 OF 8)
RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES
LOCATION (SHEET 6 OF 8)
RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES
SECTION (SHEET 7 OF 8)
RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 FIRE MAIN, HYDRANTS & VALVES
SECTION (SHEET 8 OF 8)
RAYYAN ROAD JUNCTION 6 TUNNEL TU1 ILLUMINATED EMERGENCY WAY
FINDING SIGN LOCATIONS (SHEET 1 OF 4)
RAYYAN ROAD JUNCTION 6 TUNNEL TU1 ILLUMINATED EMERGENCY WAY
FINDING SIGN LOCATIONS (SHEET 2 OF 4)
RAYYAN ROAD JUNCTION 6 TUNNEL TU1 ILLUMINATED EMERGENCY WAY
FINDING SIGN LOCATIONS (SHEET 3 OF 4)
RAYYAN ROAD JUNCTION 6 TUNNEL TU1 ILLUMINATED EMERGENCY WAY
FINDING SIGN LOCATIONS (SHEET 4 OF 4)
RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 EDP, EP, CCP & TULDB LOCATIONS
(SHEET 1 OF 7)
RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 EDP, EP, CCP & TULDB LOCATIONS
(SHEET 2 OF 7)
RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 EDP, EP, CCP & TULDB LOCATIONS
(SHEET 3 OF 7)
RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 EDP, EP, CCP & TULDB LOCATIONS
(SHEET 4 OF 7)
RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 EDP, EP, CCP & TULDB LOCATIONS
(SHEET 5 OF 7)
RAYYAN ROAD JUNCTION R6 TUNNEL- TYPICAL SINGLE EMERGENCY PANEL
ARRANGEMENT (WITHOUT HYDRANT) (SHEET 6 OF 7)
RAYYAN ROAD JUNCTION R6 TUNNEL- TYPICAL INDIVIDUAL LIGHTING
DISTRIBUTION PANEL (SHEET 7 OF 7)
RAYYAN ROAD JUNCTION R6 TUNNEL-TU1 EDP, EP &CCP GROUP
ARRANGEMENT (SHEET 1 OF 1)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 PA/VA SYSTEM LOCATIONS (SHEET 1
OF 6)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 PA/VA SYSTEM LOCATIONS (SHEET 2
OF 6)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 PA/VA SYSTEM LOCATIONS (SHEET 3
OF 6)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL PA/VA SYSTEM LOCATIONS (SHEET
4 OF 6)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL PA/VA SYSTEM LOCATIONS (SHEET
5 OF 6)
AL RAYYAN ROAD JUNCTION R6 ROAD TUNNEL PA/VA CONFIGURATION
(SHEET 6 OF 6)
Page 2 of 36
Drawing No.
EXW-P007-0201-MC-KEODG-00402-001
EXW-P007-0201-MC-KEODG-00501-001
EXW-P007-0201-MC-KEODG-00501-002
EXW-P007-0201-MC-KEODG-00501-003
EXW-P007-0201-MC-KEODG-00501-004
EXW-P007-0201-MC-KEODG-00601-001
EXW-P007-0201-MC-KEODG-00601-002
EXW-P007-0201-MC-KEODG-00601-003
EXW-P007-0201-MC-KEODG-00601-004
EXW-P007-0201-MC-KEODG-00701-001
EXW-P007-0201-MC-KEODG-00701-002
EXW-P007-0201-MC-KEODG-00701-003
EXW-P007-0201-MC-KEODG-00701-004
EXW-P007-0201-MC-KEODG-00702-001
EXW-P007-0201-MC-KEODG-00800-001
EXW-P007-0201-MC-KEODG-00801-001
EXW-P007-0201-MC-KEODG-00801-002
EXW-P007-0201-MC-KEODG-00801-003
EXW-P007-0201-MC-KEODG-00801-004
EXW-P007-0201-MC-KEODG-00801-005
EXW-P007-0201-MC-KEODG-00802-001
EXW-P007-0201-MC-KEODG-00802-002
EXW-P007-0201-MC-KEODG-00802-003
EXW-P007-0201-MC-KEODG-00802-004
EXW-P007-0201-MC-KEODG-00802-005
EXW-P007-0201-MC-KEO-
Title
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 PA/VA SCHEMATIC SHEET (SHEET 1
OF 1)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 GENERAL FIRE DETECTION &
WARNING (SHEET 1 OF 4)`
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 GENERAL FIRE DETECTION &
WARNING (SHEET 2 OF 4)`
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 GENERAL FIRE DETECTION &
WARNING (SHEET 3 OF 4)`
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 GENERAL FIRE DETECTION &
WARNING (SHEET 4 OF 4)`
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VENTILATION LAYOUT (SHEET 1 OF
4)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VENTILATION LAYOUT (SHEET 2 OF
4)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VENTILATION LAYOUT (SHEET 3 OF
4)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VENTILATION LAYOUT (SHEET 4 OF
4)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 LANE CONTROL SIGNS LOCATION
LAYOUT (SHEET 1 OF 4)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 LANE CONTROL SIGNS LOCATION
LAYOUT (SHEET 2 OF 4)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 LANE CONTROL SIGNS LOCATION
LAYOUT (SHEET 3 OF 4)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 LANE CONTROL SIGNS LOCATION
LAYOUT (SHEET 4 OF 4)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL PMCS/SCADA COMMUNICATION
NETWORK SHEET 1 OF 1
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 CCTV CAMERA SCHEMATIC (SHEET 1
OF 1)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 CCTV CAMERA LAYOUT (SHEET 1 OF
5)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL CCTV CAMERA SCHEMATIC (SHEET
2 OF 5)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL CCTV CAMERA SCHEMATIC (SHEET
3 OF 5)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL CCTV CAMERA SCHEMATIC (SHEET
4 OF 5)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL CCTV CAMERA SCHEMATIC (SHEET
5 OF 5)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VAID CAMERA LAYOUT (SHEET 1 OF
5)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL VAID SYSTEM SCHEMATIC (SHEET
2 OF 5)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL VAID CAMERA CONFIGURATION
(SHEET 3 OF 5)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VAID CAMERA LAYOUT (SHEET 4 OF
5)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VAID CAMERA CONFIGURATION
(SHEET 5 OF 5)
RAYYAN ROAD JUNCTION R6 TUNNEL TU1 VAID CAMERA SYSTEM SCHEMATIC
Page 3 of 36
Drawing No.
DG-00803-001
EXW-P007-0201-MC-KEODG-00901-001
EXW-P007-0201-MC-KEODG-00902-001
EXW-P007-0201-MC-KEODG-00902-002
EXW-P007-0201-MC-KEODG-00903-001
EXW-P007-0201-MC-KEODG-00904-001
EXW-P007-0201-MC-KEODG-00904-002
EXW-P007-0201-MC-KEODG-00905-001
EXW-P007-0201-MC-KEODG-00906-001
EXW-P007-0201-MC-KEODG-00906-002
EXW-P007-0201-MC-KEODG-00906-003
EXW-P007-0201-MC-KEODG-00907-001
EXW-P007-0201-MC-KEODG-00908-001
EXW-P007-0201-MC-KEODG-00908-002
EXW-P007-0201-MC-KEODG-00908-003
EXW-P007-0201-MC-KEODG-00909-001
EXW-P007-0201-CD-KEODG-00212-005
EXW-P007-0201-CD-KEODG-00212-006
EXW-P007-0201-CD-KEODG-00208-001
Title
(SHEET 1 OF 1)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL ERT NETWORK (SHEET 1 OF 1)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL LHD DTS SCHEMATIC (SHEET 1 OF
2)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL LEAKY FEEDER (SHEET 2 OF 2)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL FIRE SAFETY SYSTEMS (SHEET 1 OF
1)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL LANE CONTROL SIGN SYSTEM
SCHEMATIC (SHEET 1 OF 2)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL DMS/LCS CONFIGURATION (SHEET
2 OF 2)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL IMPOUNDING SUMP VENTILATION
SCHEMATIC (SHEET 1 OF 1)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL SCP GA PANEL LAYOUT (SHEET 1
OF 3)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL SCP GA PANEL LAYOUT (SHEET 2
OF 3)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL SCP GA PANEL LAYOUT (SHEET 3
OF 3)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL TYPICAL SMOKE CONTROL
PANEL LAYOUT (SHEET 1 OF 1)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL - CROSS PASSAGE DOORS (SHEET 1
OF 3)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL - TYPICAL CROSS CONNECTION
DOORS (SHEET 2 OF 3)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL - DETAIL OF FIRE BRIGADE
CONNECTORS (SHEET 3 OF 3)
RAYYAN ROAD JUNCTION R6 ROAD TUNNEL - DETAIL OF FIRE BRIGADE
CONNECTORS (SHEET 3 OF 3)
Al RAYYAN ROAD JUNCTION R6 ROAD TUNNEL ATTENUATION TANK
SECTIONAL DETAIL (SHEET 5 OF 6)
Al RAYYAN ROAD JUNCTION R6 ROAD TUNNEL ATTENUATION TANK/PLANT
ROOM INSTALLATION SCHEMATIC (SHEET 6 OF 6)
Al RAYYAN ROAD UNDERPASS DRAINAGE CHANNEL DETAILS
Page 4 of 36
7.
8.
9.
10.
Meaning
Alternating Current
Air Changes
Anti-Friction Bearing Manufacturers Association
Analogue Input
Approval in Principle
American Iron and Steel Institute
Analogue Output
American Society for Testing and Materials
ATmosphres EXplosives or Explosive Atmospheres
British Standard
Break Glass
Charged Coupled Device
Closed Circuit Television
Compact Disc Recordable
Compact Disc
Construction Design and Management (Regulations)
Compact Disc Read Only Memory
Communications Equipment Room
Configuration Management
Certificate of Conformity
Carbon Monoxide
Control of Substances Hazardous to Health
Cross Passage Door
Distribution Board
Direct Current
Digital Input
Design Manual for Roads and Bridges
Distribution Panel
Digital Output
Direct-on-line
Dangerous Substances and Explosive Atmospheres Regulations UK (ATEX 137
implementation)
Distributed Temperature sensing
Duct Work (Specification)
European Commission
Emergency Distribution Point
Extra Low Voltage
Electromagnetic Compatibility
Electromagnetic Fields
Page 5 of 36
Abbreviation
EMI
EN
EP
EPDM
EPROM
2
E PROM
EEPROM
ERT
EX
FAP
FAT
FDS
FL
FO
FP
FRLS
FS
FSK
FSC
GSM
GUI
HA
HDLC
HEMP
HH
HMI
HVAC
HVCA
HV
Hz
IEC
I/O
IP
IP
IRT
ISO
ITS
LCP
LCS
LCS
LEL
LFS
LHD
LL
LPCB
LSOH
LV
M&E
MCB
Meaning
Electromagnetic Interference
European Standard
Emergency Point
Ethylene Propylene Diene Monomer
Erasable Programmable Read Only Memory
Electrically Erasable Programmable Read Only Memory
Electrically Erasable Programmable Read Only Memory
Emergency Roadside Telephone
Explosion Proof rated
Fire Alarm Panel
Factory Acceptance Tests
Functional Design Specification
Factory Link
Fibre Optic
Fire Protection
Fire Retardant Low Smoke
Fire Survivable
Frequency Shift Key
Forest Stewardship Council
Global System for Mobiles
Graphical User Interface
Highways Agency UK
High level Data Link Control
High Energy Magnetic Impulse
High-High
Human Machine Interface
Heating/Ventilation/Air-Conditioning
Heating and Ventilating Contractors Association UK
High Voltage
Hertz
International Electrotechnical Commission
Input/Output
Ingress Protection
Internet Protocol
Incident Response Team i.e. Emergency Services
International Standards Organisation
Intelligent Transportation Systems
Local Control Panel
Lane Control Signs
Lighting Control System
Lower Explosive Level
Low Fume and Smoke
Linear Heat Detection
Low-Low
Loss Prevention Certification Board
Low Smoke Zero Halogen
Low Voltage, Voltage below 1000 Vac and above 50 Vac.
Mechanical and Electrical
Miniature Circuit Breaker
Page 6 of 36
Abbreviation
MCC
MCCB
MCHW
MES
MET
MMFO
MTBF
MTTR
MUX
MV
NAMAS
N/B
NEMA
NER
NFPA
NO
NPSH
NR
NRV
NTCIP
ODVA
O&M
OPC
PA
PABX
PAVA
PC
PEFC
PIARC
PLC
PMCS
PN
PQP
PROM
PSU
PTZ
PVC
QA
QC
QCS
RAM
RH
RIO
RS232
RS422
RS485
RTD
RTU
SAT
Meaning
Motor Control Centre
Moulded Case Circuit Breaker
Manual of Contract Documents for Highway Work in the UK
Mechanical - Electrical - Systems
Metrological/Environmental/Traffic
Multi-Mode Fibre Optic
Mean Time Between Failure
Mean Time to Repair
Multiplexer
Medium Voltage, voltage above 1000 Vac but below HV
National Measurement Accreditation Services
Northbound
National Electrical Manufacturers Association
Neutral Earthing Resistor
National Fire Protection Association
Niitrogen Oxide
Net Positive Suction Head
Noise Reduction
Non-Return Valve
National Transportation Communications for ITS Protocol
Open DeviceNet Vendors Association
Operations and Maintenance
Open Process Control
Public Address
Private Automatic Branch Exchange
Public Address Voice Alarm
Personal Computer
Programme for the Endorsement of Forest Certification
The World Road Association
Programmable Logic Controller
Plant Monitoring and Control System
Pressure Normal
Project Quality Plan
Programmable Read Only Memory
Power Supply Unit
Pan, Tilt and Zoom
Polyvinyl Chloride
Quality Assurance
Quality Control
Qatar Construction Standards
Random Access Memory
Relative Humidity (as %)
Remote Input / Output
Recognised Standard 232
Recognised Standard 422
Recognised Standard 485
Resistance Temperature Detector
Remote Terminal Unit
Site Acceptance Tests
Page 7 of 36
Abbreviation
S/B
SCADA
SCP
SDS
SFA
SLV
SMFO
STP
TCP/IP
TDSCG
TERP
TFT
TM
TMC
TOA
TR
TSB
TSS
UL
UPS
USB
USSG
UK
UKAS
UTP
V
Vac
VAID
VCR
Vdc
VDU
VESDA
VID
VIS
VMS
VSD
VSD
WIS
XPLE
Meaning
Southbound
Supervisory Control and Data Acquisition
Smoke Control Panel
Software Design Specifications
Service Factor Amperes
Safety Low Voltage
Single Mode Fibre Optic
Sheilded Twisted Pair
Transmission Control Protocol/Internet Protocol
Tunnel Design and Safety Consultation Group
Tunnel Emergency Response Plan
Thin Film Transistor (Display Technology)
Tunnel Maintainer
Traffic Management Centre/Tunnel Management Centre
Tunnel Operating Authority
Technical Requirement
Tunnel Service Building
Tunnel Sub-System
Underwriters Laboratories
Uninterruptible Power supply
Universal Serial Bus
United States Standard Gage
United Kingdom
United Kingdom Accreditation Service
Unsheilded Twisted Pair
Volt(age)
Volts ac
Video Automatic Incident Detection
Video Cassette Recorder
Volts dc
Visual Display Unit
Very Early Smoke Detection Aspirator
Video Incident Detection
Visibility
Variable Message Sign
Video Smoke Detection
Variable Speed Detection
Water Industry Specifications UK
Cross-linked Polyethylene
Page 8 of 36
To meet the requirements of the UK HA DMRB BD78/99, the UK HA MCHW 5.7.2 and
Federal NFPA502 (IAN 020 Rev. A1) in respect to classification of tunnels and life safety
provisions.
Achieves environmental sustainability and whole life costs within the scheme budget
To provide a safe tunnel environment for road users, operators, maintenance staff, police
and the emergency services both during construction and in permanent conditions.
Reduces operational and maintenance risks
Meet The Road Tunnel Safety Regulations 2007 UK.
Safety of the work force and the road users
Deliver scheme as soon as possible
Page 9 of 36
Subject
Emission
Immunity
IEC 61000-6-4: Electromagnetic compatibility (EMC) - Part 6-4: Generic standards - Emission
standard for industrial environments
IEC 61000-6-2: Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity
for industrial environments
Power station and substation environment
IEC 61000-6-5: Electromagnetic compatibility (EMC) - Part 6-5: Generic standards - Immunity
for power station and substation environments
Indoor equipment
IEC 61000-6-6: Electromagnetic compatibility (EMC) - Part 6-6: Generic standards - HEMP
immunity for indoor equipment
Emission
Immunity
Immunity
HEMP
immunity
Supervisory Control and Data Acquisition (SCADA) servers, incorporating the Graphical User
Interface (GUI)
Central supervisory control Programmable Logic Controllers (PLCs)
Distributed outstation PLCs associated with plant requiring local control functions, such as
those at local control panels
The provision of layered hierarchical monitoring and control will provide the following benefits:
Page 10 of 36
Tunnel Subsystem
(TSS)
Dual Redundant
SCADA Servers
Manual Overrides and
Status Monitoring
Dual PLC
Processors
Dual PLC
Processors
Smoke Panel
Control Requests
and Plant Status
Control
and Status
Dual
Redundant
Dual
Redundant
Dual
Redundant
Control and
Status
Dual
Redundant
PMCS
NB Fan Starters,
Pollution Sensors
and VAID
NB Smoke
Control Panels
SB Smoke
Control Panels
SB Fan Starters,
Pollution Sensors
and VAID
The SCADA Servers will be configured as dual industrial-grade PCs operating in hot-standby mode.
Page 11 of 36
The supervisory control PLCs will be configured as dual industrial-grade PLCs operating in hotstandby mode.
4.5 Outstation PLCs
Outstation PLCs will be used where control functionality is required to be distributed within the
tunnel such as, for example, for the management of Smoke Control Panels (SCPs).
Outstation PLCs will be configured as dual industrial-grade PLCs operating in hot-standby mode.
4.6 Dual configuration
Master-standby arbitration and selection of the supervisory control PLCs will be achieved through
the use of external *with respect to the PLCs+ hardware watchdog timing circuitry. Such a hardwarebased approach will provide much greater determinism of mutual exclusion of mastery.
Upon system start-up one of the supervisory control PLC pair, arbitrarily selected, shall automatically
be configured as the master, assuming control of the PMCS.
The master-standby state of the supervisory control PLCs will be used to derive and determine the
master-standby configuration of other dual configuration units throughout the PMCS, thus removing
the need for additional master-standby arbitration hardware in each instance of dual configurations
throughout the system.
External hardware-based watchdogging will be used to monitor the supervisory control PLCs for
failure, in which case mastery will be allocated the standby unit.
Software-based heartbeat watchdogging will be employed by the supervisory control PLCs to
monitor the health of other dual configuration units throughout the PMCS, and allocation of mastery
performed accordingly.
The dual configuration scheme will transparently implement the following dual configuration
functions:
Replication of the processing context to the standby, including programs and data
Detection of faults and switchover
Page 12 of 36
The Master SCADA GUI will be delivered by dual redundant servers and all SCADA GUIs will provide
the following features and functions:
The SCADA GUI will be presented on an Operator terminal featuring TFT-LCD monitor, keyboard, and
mouse/pointing device.
Page 13 of 36
4.8 TMC/TSS
The Tunnel Subsystem (TSS) is an segregation of a partition of the control and monitoring logical
software system deployed within the SCADA/PMCS application servers/PLCs at the TSB that
facilitates the control and monitoring of carriageway and tunnel infrastructure through the TMC
Traffic system, providing functions such as the following:
The TMC Traffic system acts as an integrated incident management tool that reacts to all relevant
situations by selecting the appropriate Tunnel Emergency Response Plan (TERP) from its database
and will display this to the Traffic Control Operator dealing with the tunnel incident for acceptance
and execution.
The TMC Tunnel System allows Traffic Control Operators to execute pre-defined response plans, as
well as allowing Operators to effect ad-hoc control actions in response to particular tunnel incidents
and situations.
4.9 Engineering Terminal
The PMCS will provide connectivity for an mobile engineering terminal for use by maintenance
personnel. The mobile engineering terminal may be connected to any suitable port on the PMCS
control network.
The engineering terminal will provide features and functions related to the commissioning and
maintenance of the system, including the following:
The engineering terminal will not normally be connected to the system, but will be capable of being
removed / inserted into the operational system.
The engineering terminal will consist of an industrial rough service Ultrabook with network interface
card hosting the engineering terminal software application.
Page 14 of 36
Ladder logic
Function block
Structured text
Instruction list
All Control and monitoring software will be developed in accordance with BS EN 61508 Safety
Integrity Level (SIL) 2 and a validation process shall be carried out confirming the criteria reached,
i.e. SIL2.
4.11 Control Network
The PMCS processing and I/O units will intercommunicate control and data via a dedicated dual
redundant Ethernet-based control network.
The PMCS control network will be formed of multi-mode fibre optic and copper segments, as
required.
The backbone of the PMCS control network linking central control units to outstation units will be
two fibre optic circuits, each arranged in a ring topology to form two independent A and B closedloop self-healing networks capable of continued operation in the event of a fibre-optic cable
disconnection or network switch failure.
The dual supervisory control PLCs will each be provided with dual connections to both the A and
B control networks, thereby providing resilience in the event of failure of one of the supervisory
control PLCs.
Each PMCS outstation processing and I/O unit will be provided with a single connection to one of the
A or B networks. At outstation locations where dual redundant processing and I/O units are
deployed, then each of these will be provide with a single connection to the A and B control
networks; one unit to the A control network and one unit to the B control network.
The dual SCADA Servers will each be provided with a single connection to the A or B control
networks; one to the A control network and one to the B control network.
The PMCS will use Ethernet-based Open Process Control (OPC) protocols for internal and external
communications.
4.12 Instrumentation Interface
The PMCS will provide connectivity to a range of instrumentation industry standards including the
following:
Doc. No. EXW-P007-0000-MC-KEO-RP-00209
Rev. D02
Page 15 of 36
Within the TSB within dedicated racks and remote positions (several locations)
Within 4 No. SCPs outside each portal (Dual configuration)
Within 8 No. EDPs within each bore (16 In total, single configuration interleaved)
In the midpoint sump plant room, (Dual Configuration)
Page 16 of 36
Data point transmission through the PMCS will be optimised with respect to update rates and data
push/pull configuration in order that:
The dual supervisory control PLCs will independently gather all data from local sources regardless of
master-standby status. This approach will provide validation that each main supervisory control PLC
has an active communication link with the outstation devices, and will maintain data currency
allowing hot-swap to the standby in the event of failure of the master unit.
5.2 Alarm Monitoring
The PMCS will monitor all controlled plant for alarm conditions, including PMCS-internal fault
conditions.
The following alarm conditions will be monitored, as follows:
Alarm indications generated as a result of detection of conditions external to the PMCS. The
nature and extent of such alarms will be determined during subsequent design stages, but
are likely to include sensing of out-of-band parameters, i.e. physical measurements outside
their expected range.
Alarm indications generated as a result of detection of conditions internal to the PMCS. The
nature and extent of such alarms will be determined at subsequent design stages, but are
likely to include sensing of failure of control system processors, and the like.
Active reporting by exception, whereby the plant and PMCS elements will signal alarm and
fault conditions detected
Polled monitoring by PMCS, whereby the active control elements of the control system will
intercommunicate periodically in order to determine the health, i.e. the correct operation,
of the control system itself.
Page 17 of 36
Alarm indications will be ranked by importance/severity and displayed via the SCADA Tunnel
Operator Terminal (GUI) such that conditions are displayed in different modes according to the
condition severity and the operating privileges of any user logged on to the system.
Alarm indications will be recorded in a historical database for subsequent analysis. Log entries will
provide the following information:
Automatic
Automatic control mode is the default control mode and is always active, although possibly overridden by a higher priority control mode. Automatic control mode demand is derived from plant
sensor levels and states, set-points, and control parameters. Automatic control mode demand will
Doc. No. EXW-P007-0000-MC-KEO-RP-00209
Rev. D02
Page 18 of 36
always be derived and presented to Operators, regardless of the actual control mode active, thereby
providing the operator with visibility of the automatically calculated demand.
Local plant control will be affected by direct operation of individual items of plant and/or their
associated autonomous control systems via plant-local control panels. The PMCS will continue to
monitor locally controlled plant and generate control demands wile local plant control is active; in
order that seamless transition of control may be achieved once local plant control is relinquished.
Additional control modes specific to particular tunnel systems will be provides, as required, and
these are described herein within the sections detailing the control schemes for specific tunnel
systems.
5.5 Running Hours and Plant Metrics
The PMCS will acquire/derive and store data relating to the running time of plant, as well as other
metrics required to assist the effective and efficient plant maintenance. Data to be a
acquired/derived and stored includes the following:
The PMCS will provide the ability to reset metrics for individual items of plant.
5.6 Signal Conditioning
The PMCS will implement a scheme of signal conditioning and scaling that ensures that data is
transmitted, stored, and manipulated in a uniform and consistent manner.
Page 19 of 36
Where required, digital inputs will be conditioned by pulse stretching in order that fast switching
signals are detected correctly
Where required, digital inputs will be conditioned by de-bouncing in order that switch selections and
the like are read correctly.
Automatic
Manual Operator Override from TMC/TSS
Manual Operator Override from TOA/SCADA GUI
Manual Operator Override from SCP
Manual Operator Override from Lighting Control Panel (LCP)
Automatic control mode is the default control mode, and is always active, although possibly overridden by a higher priority control mode
The manual operator override control modes provide an Incident Control sub-mode that allows
lighting level change demands to be actioned with reduced rate-of-change constraints, thus allowing
more rapid changes in lighting levels to be achieved.
Lighting control will be achieved via an autonomous Lighting Control System (LCS). A LCS will be
provided for each tunnel bore. Each LCS will be provided with a local LCP. The PMCS will interface
with the LCS, generating demands for lighting levels and monitoring LCS and lighting system status.
The Manual Operator Override from LCP, also known as Ancillary Local Manual Control, control
mode will be provided by the LCS
6.2 General Lighting Control Scheme
The LCS will control the tunnel lighting automatically based upon photometer sensor readings.
Two external photometers will be provided at the stopping distance from each tunnel bore entrance
portal, and the average reading of these will be used by the LCS to calculate a lighting level demand
for each tunnel bore.
The LCS will support seven stages of lighting, with stage 1 providing the lowest level of illumination
and stage 7 providing the highest level of illumination, this representing 100% of total possible
Doc. No. EXW-P007-0000-MC-KEO-RP-00209
Rev. D02
Page 20 of 36
lighting system output. The LCS will convert photometer sensor readings into a demand for lighting
for stages 1 through to 7.
The LCS will integrate photometer sensor readings in order to filter fast rate of change
environmental effects upon the sensors, thus avoiding rapid and spurious lighting level changes.
The LCS will sequence through lighting stages with a set-point limit period between stage transitions
in order that gradual changes in lighting levels are achieved, with an associated reduction in peak
inrush currents. An Incident Control Mode will be provided by the LCS in which the limit period
between stage transitions is reduced so that more rapid changes in lighting level may be made.
The LCS will detect lamp failures and switch in additional units to compensate and maintain lighting
levels.
Threshold zone luminance will track the L20 luminance measured by the external photometers. The
threshold zone luminance will maintain 7% of the L20 value.
Transition zone luminance will track the threshold zone luminance and will vary along the length of
the zone following the reduction curve defined in BS5489-2.
Exit zone luminance will be as defined in BS5489-2.
Emergency lighting levels will be in accordance with BS5489-2 and BS EN 1838:1999, taken to be the
greater of the required level for stage 2 lighting or 15lux.
Lighting stages 1 through to 4 will be backed up by Emergency Standby Generator, with UPS support
for stage 1 and 2 lighting to cover the period of generator start-up. Failure of the Emergency Standby
Generator to provide a supply within 5 minutes of a demand will result in reversion to emergency
lighting levels, which will be maintained for at least 2 hours via the UPS.
6.3 Automatic Control Mode
In Automatic control mode the LCS will autonomously control the lighting levels within each tunnel
bore based upon external photometer sensor readings.
The automatically calculated lighting stage demand, and the currently active lighting stage for each
tunnel bore will be monitored by the PMCS, and this will be displayed on the SCADA GUI and
recorded by the SCADA Servers. This will give the Operator visibility of how the lighting control will
change when higher priority control modes are de-activated and lower priority control modes
become active.
6.4 Manual Operator Override from TMC Control Mode
The PMCS will accept Manual Operator Override from TMC control mode demands for each tunnel
bore. These demands will be for lighting stage 7 only.
The Manual Operator Override from TMC control mode will remain active until the PMCS receives a
control mode reset command from the TMC.
Doc. No. EXW-P007-0000-MC-KEO-RP-00209
Rev. D02
Page 21 of 36
The SCADA GUI will provide a password-protected manual operator override control mode reset
function in case it is not possible for the TMC operator to issue a reset command due to TMC
communications link failures, and the like. The use of this function will be recorded by the SCADA
Servers for auditing purposes.
6.5 Manual Operator Override from SCADA GUI Control Mode
The PMCS will accept Manual Operator Override from SCADA GUI control mode demands for each
tunnel bore. These demands will be for lighting stages 1 through 7.
The PMCS will request the LCS to activate the lighting stage demanded by the operator. The LCS will
arbitrate the PMCS lighting stage demand, only selecting for activation demanded lighting stages
greater than the lighting stage demand calculated automatically by the LCS. Lighting stage demands
rejected by the LCS will be displayed by the SCADA GUI and recorded by the SCADA Servers.
The PMCS will provide an Incident Control Mode that will allow the PMCS to request the LCS to
activate the demanded lighting stage with reduced transition times between lighting stages in order
to allow more rapid variations in lighting levels to be achieved.
The Manual Operator Override from SCADA GUI control mode will remain active until the PMCS
receives a control mode reset command from the SCADA GUI.
6.6 Manual Operator Override from SCP Control Mode
The PMCS will accept Manual Operator Override from SCP control mode demands from for each
tunnel bore. These demands will be for lighting stages 1 through 7.
Four smoke control panels will be provided, situated at the portals, one per entrance and exit to
each tunnel bore.
Lighting control via the SCPs will be arbitrated on a first-come, first-served basis such that once an
SCP has been granted control for a tunnel bore the other SCPs will be locked out from control of
that tunnel bore for the duration of the control selection being active.
SCPs will provide the following lighting-related controls and indicators for each tunnel bore:
The PMCS will request the LCS to activate the lighting stage demanded by the Operator at the SCP.
The LCS will arbitrate the PMCS lighting stage demand, only selecting for activation demanded
lighting stages greater than the lighting stage demand calculated automatically by the LCS. Lighting
stage demands rejected by the LCS will be displayed by the SCADA GUI and recorded by the SCADA
Servers.
Doc. No. EXW-P007-0000-MC-KEO-RP-00209
Rev. D02
Page 22 of 36
The PMCS will provide an Incident Control Mode that will allow the PMCS to request the LCS to
activate the demanded lighting stage with reduced transition times between lighting stages in order
to allow more rapid variations in lighting levels to be achieved.
The Manual Operator Override from SCP control mode will remain active until the PMCS receives a
relinquish control command from the SCP.
6.7 Manual Operator Override from LCP Control Mode
The Manual Operator Override from LCP control mode will be provided by the LCS.
A local control panel will be provided, adjacent to the LCS at the TSB.
The Manual Operator Override from LCP control mode will remain active until relinquished at the
LCP.
6.8 Lamp Status Monitoring
The TPM&CS will continuously monitor the LCS for the status of the tunnel lamps, segmented into
tunnel zones. The following information will be displayed on the SCADA GUI and recorded by the
SCADA Servers for each tunnel zone:
The PMCS will continuously monitor EP and EDP limit switch status this information will be displayed
on the SCADA GUI and recorded by the SCADA Servers.
Page 23 of 36
Slow vehicle
Stopped vehicle
Vehicle in wrong direction
Smoke detected
Object in carriageway (size to be determined)
Pedestrian/animal in carriageway
VAID detection events will be displayed on the SCADA GUI and recorded by the SCADA Servers.
The VAID systems for each tunnel bore will autonomously monitor and detect camera faults and will
signal these to the PMCS. VAID system camera faults will be displayed on the SCADA GUI and
recorded by the SCADA Servers.
The VAID smoke detection events for both tunnel bores will be displayed at each SCP.
The PMCS will allow the Operator to configure the VAID system for contra-flow working via the
SCADA GUI. The use of this function will be recorded by the SCADA Servers.
7.3 Smoke Control Panels
Four smoke control panels will be provided, situated at the portals, one per entrance and exit to
each tunnel bore.
SCPs will provide the following control-related controls and indicators for each tunnel bore:
SCPs will provide a limit switch to sense the panel door open/close position. The PMCS will
continuously monitor the limit switches for status and this information will be displayed on the
SCADA GUI and recorded by the SCADA Servers.
Page 24 of 36
Page 25 of 36
Bus status
ACB status
Description
TSB VCB 'A' Incomer Status
TSB VCB 'B' Incomer Status
Format
+24vdc
+24vdc
DIG
DIG
I
I
Failed/Normal
Failed/Normal
+24vdc
+24vdc
DIG
Failed/Normal
+24vdc
DIG
DIG
I
I
Failed/Normal
Failed/Normal
+24vdc
+24vdc
Page 26 of 36
continues with full functionality. The transformers will be located within separate enclosures at the
TSB. Low maintenance transformers will be utilised.
Each transformer will be fitted with at least two temperature-sensing devices fitted within pockets in
each phase winding to provide Over Temperature protection. The transformers will have Restricted
Earth Fault protection, as well as conventional Overcurrent, and Earth fault protection.
An estimate of the required loads based on the equipment being provided at part of the tunnel and
underpass design (excluding ITS loads) indicates the following capacities for the new equipment:
Transformer A
Transformer B
Transformer C
Transformer D
Description
Tx1 'A' Operating Temp
Tx1 'A' Operating Temperature
Tx1 'A' Primary Feeder Brkr Control
Tx1 'A' Primary feeder Brkr Control
Tx1 'A' Primary Feeder Brkr Posn
Tx1 'A' Primary Feeder Brkr Posn
Tx1 'A' Primary feeder Brkr Posn
Tx1 'A' Primary feeder Brkr Posn
Tx1 'A' Primary Feeder Brkr Service
Tx1 'A' Primary feeder Brkr Service
Tx1 'A' Primary Feeder Brkr Status
Tx 1'A' Primary feeder Brkr Status
Tx1 'A' Secondary Power Status
Tx1 'A' Secondary Power Status
Type
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
Direction
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Sense/Units
Normal/High
Normal/High
Normal/LocalO/R
Normal/LocalO/R
/Open
/Closed
-/Open
-/Closed
Avail/OutServ
Avail/OutServ
Normal/Tripped
Normal/Tripped
Failed/Normal
Failed/Normal
Format
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
I
I
I
I
I
I
I
I
I
I
Normal/High
Normal/High
Normal/LocalO/R
Normal/LocalO/R
/Open
/Closed
-/Open
-/Closed
Avail/OutServ
Avail/OutServ
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
Page 27 of 36
DIG
DIG
DIG
DIG
I
I
I
I
Normal/Tripped
Normal/Tripped
Failed/Normal
Failed/Normal
+24vdc
+24vdc
+24vdc
+24vdc
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Normal/High
Normal/High
Normal/LocalO/R
Normal/LocalO/R
/Open
/Closed
-/Open
-/Closed
Avail/OutServ
Avail/OutServ
Normal/Tripped
Normal/Tripped
Failed/Normal
Failed/Normal
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
DIG
DIG
DIG
I
I
I
+24vdc
+24vdc
+24vdc
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
I
I
I
I
I
I
I
I
I
I
Normal/High
Normal/High
Normal/Local
O/R
Normal/Local
O/R
/Open
/Closed
-/Open
-/Closed
Avail/OutServ
Avail/OutServ
Normal/Tripped
Normal/Tripped
Failed/Normal
Failed/Normal
Type
DIG
Direction
I
Format
+24vdc
DIG
Sense/Units
DeEngsd/Engisdd
Normal/Low
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
Page 28 of 36
DIG
DIG
I
I
+24vdc
+24vdc
I
I
I
I
I
I
I
I
I
I
Normal/Low
DeEngsd/Engisdd
Normal/Low
Normal/Low
Normal/Fault
Normal/Fault
Normal/Failed
Normal/Failed
Normal/Low
Normal/Low
Normal/Fault
Normal/Fault
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
I
I
I
I
Normal/LocalO/R
-/Open
-/Closed
Avail/OutServ
+24vdc
+24vdc
+24vdc
+24vdc
DIG
DIG
ANA
ANA
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
I
I
I
I
I
I
I
I
I
I
I
I
Normal/LocalO/R
Normal/LocalO/R
kWh
kWh
-/Open
-/Closed
-/Open
-/Closed
Avail/OutServ
Avail/OutServ
Normal/Tripped
Normal/Tripped
+24vdc
+24vdc
4-20mA
4-20mA
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
DIG
DIG
ANA
ANA
DIG
DIG
DIG
DIG
DIG
I
I
I
I
I
I
I
I
I
Normal/LocalO/R
Normal/LocalO/R
kWh
kWh
-/Open
-/Closed
-/Open
-/Closed
Avail/OutServ
+24vdc
+24vdc
4-20mA
4-20mA
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
Page 29 of 36
DIG
DIG
DIG
I
I
I
Avail/OutServ
Normal/Tripped
Normal/Tripped
+24vdc
+24vdc
+24vdc
DIG
DIG
I
I
Failed/Normal
Failed/Normal
+24vdc
+24vdc
DIG
ANA
ANA
ANA
ANA
ANA
ANA
ANA
I
I
I
I
I
I
I
I
kWh
kWh
kWh
kWh
kWh
kWh
kWh
+24vdc
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
DIG
ANA
ANA
ANA
ANA
ANA
ANA
ANA
I
I
I
I
I
I
I
I
kWh
kWh
kWh
kWh
kWh
kWh
kWh
- +24vdc
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
4-20mA
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
I
I
I
I
I
I
I
I
I
I
I
I
I
Off/On
On/Off
Off/On
On/Off
Off/On
On/Off
Off/On
On/Off
Off/On
On/Off
Off/On
On/Off
Normal/Fault
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
DIG
DIG
I
I
Off/On
On/Off
+24vdc
+24vdc
Page 30 of 36
Off/On
On/Off
Off/On
On/Off
Off/On
On/Off
Off/On
On/Off
Off/On
On/Off
Normal/Fault
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
Sense/Units
Open/Closed
Normal/Failed
Normal/Low
Auto/Manual
Normal/Alarm
Normal/Low
Normal/High
Normal/Failed
Normal/Failed
Normal/High
Healthy/Tripped
Failed/Normal
Normal/Dump
Normal/Fill
Format
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
Relay
Relay
Open/Closed
Normal/Failed
Normal/Low
Auto/Manual
Normal/Alarm
Normal/Low
Normal/High
Normal/Failed
Normal/Failed
Normal/High
Healthy/Tripped
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Page 31 of 36
DIG
DIG
DIG
I
O
O
Failed/Normal
Normal/Dump
Normal/Fill
+24vdc
Relay
Relay
Type
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
Direction
I
I
I
I
I
I
I
I
I
I
I
I
Sense/Units
Normal/Low
Normal/Low
Normal/Fault
Normal/Fault
Normal/Fault
Normal/Fault
Normal/Failed
Normal/Failed
Normal/Fault
Normal/Fault
Normal/Bypassed
Normal/Bypassed
Format
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
I
I
I
I
I
I
I
I
I
I
I
I
Normal/Low
Normal/Low
Normal/Fault
Normal/Fault
Normal/Fault
Normal/Fault
Normal/Failed
Normal/Failed
Normal/Fault
Normal/Fault
Normal/Bypassed
Normal/Bypassed
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
I
I
I
I
I
I
I
I
I
Normal/LocalO/R
Normal/LocalO/R
-/Open
-/Closed
-/Open
-/Closed
Avail/OutServ
Avail/OutServ
Normal/Tripped
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
Page 32 of 36
DIG
Normal/Tripped
+24vdc
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
DIG
I
I
I
I
I
I
I
I
I
I
Normal/LocalO/R
Normal/LocalO/R
-/Open
-/Closed
-/Open
-/Closed
Avail/OutServ
Avail/OutServ
Normal/Tripped
Normal/Tripped
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
DIG
DIG
DIG
DIG
DIG
ANA
I
I
I
I
I
I
Normal/LocalO/R
-/Open
-/Closed
Avail/OutServ
Normal/Tripped
kWh
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
4-20mA
DIG
DIG
DIG
DIG
DIG
ANA
I
I
I
I
I
I
Normal/LocalO/R
-/Open
-/Closed
Avail/OutServ
Normal/Tripped
kWh
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
4-20mA
DIG
DIG
DIG
DIG
DIG
ANA
I
I
I
I
I
I
Normal/LocalO/R
-/Open
-/Closed
Avail/OutServ
Normal/Tripped
kWh
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
4-20mA
DIG
DIG
DIG
DIG
DIG
ANA
I
I
I
I
I
I
Normal/LocalO/R
-/Open
-/Closed
Avail/OutServ
Normal/Tripped
kWh
+24vdc
+24vdc
+24vdc
+24vdc
+24vdc
4-20mA
Page 33 of 36
11.0 Interfaces
11.1 TMC Interface
The interface with the TMC is defined in the document Tunnel TMC/TSS SCADA/PMCS Control
Interface (document reference EXW-P007-0201-MC-KEO-RP-00210).
11.2 Physical Locations of PMCS Plant Interfaces
The PMCS will provide plant interfaces, i.e. PLCs or RIO units, at following locations:
Plant signals from plant marshalled at EPs will be cabling to the nearest [via containment route]
adjacent point-of-presence of a PMCS PLC/RIO unit. This will be an adjacent EDP or one of the
Ventilation Building switch rooms.
11.3 Plant Interfaces
The PMCS will interface to plant at the following locations:
Plant
Location
MV/LV panels
TSB
UPSs
TSB
TSB
Page 34 of 36
photocells
TSB
TSB
TSB
TSB
TSB
TSB
TSB
TSB
SCP 1 and 2
EDPs 1 to 8
TSB
Sump plant room
The W/B bore network switches will be provided at the following locations:
SCP 3 and 4
EDP 1 to 8
Page 35 of 36
TSB
The provision of switches at each location, other than EDPs, will be dual redundant so that access to
the network at each location can be maintained in the event of a switch failing.
Network switches will provide the following configurable services as a minimum:
Page 36 of 36