Cathodic Protection System Using Ceramic Anodes
Cathodic Protection System Using Ceramic Anodes
CEMP-ET
Technical Letter
No. 1110-9-10
ETL 1110-9-10
5 January 1991
ETL 1110-9-10(FR)
CEMP-ET
Engineer Technical
Letter 1110-9-10(FR)
5 January 1991
Encl
RICHARD C. ARMSTRONG
Chief, Engineering Division
Directorate of Military Programs
ETL 1110-9-10(FR)
5 Jan 91
IMPRESSED CURRENT CATHODIC PROTECTION SYSTEMS
USING CERAMIC ANODES
TABLE OF CONTENTS
Page
SECTION 1
1-1
1-2
1-3
SECTION 2
. . . . . . . . . . . . . . . . . .
4
4
15
2-1
Purpose
2-2
2-3
2-4
2-5
2-6
. . . . .
70
2-7
78
104
113
116
2-8
2-9
2-10
SECTION 3: Tables
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
18
. . . . . . .
31
. . . . . . . . . . . . .
39
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
18
. . . . . . . . . .
58
117
128
ETL 1110-9-10(FR)
5 Jan 91
List of Figures
Page
2-1A
19
20
21
22
2-4
23
2-5
33
2-6
41
2-7
42
2-7A
43
2-8
44
2-8A
45
2-9A
48
2-9B
49
2-9C
50
2-10
Pole-Mounted Rectifier
57
2-11
60
68
69
2-1B
2-2
2-3
2-12
2-13
ETL 1110-9-10(FR)
5 Jan 91
2-14
76
77
80
2-16
81
2-17
86
2-18
87
2-19
89
2-20
90
2-14A
2-15
2-21
2-22
2-23
2-24
103
105
112
114
ETL 1110-9-10(FR)
5 Jan 91
CATHODIC PROTECTION DESIGN
1-1.
Introduction.
ETL 1110-9-10(FR)
5 Jan 91
a.
Collect data.
Design requirements should be established, and certain
assumptions will be made.
1)
History
Information from occupants in the area can indicate
the severity of corrosion problems. Data on failures
and failure rates of nearby structures can be invaluable and must be considered.
2)
Drawings
Drawings of the structure to be protected and the
area where it is or will be installed are needed to
provide the physical dimensions of the structure for
determining surface area to be protected, and
locations of other structures in the area that may
cause interference, of insulating devices, and of
power sources. Information on coatings should be
obtained.
3)
Tests
Current requirement test and potential survey test
results are needed for existing structures that will
be protected. Electrolyte (soil or water) resistivity tests and evaluation of conditions that could
support sulfate-reducing bacteria are needed for all
cathodic protection designs. This information will
indicate the size of the cathodic protection system
that will be required as well as the probability of
stray current problems. Soil resistivities contribute to both design calculations and location of the
anode groundbed.
4)
Life
The user must determine the required number of years
that the structure needs to be protected, or the
designer must assume a nominal life span. The structure will begin to deteriorate from corrosion at the
end of the cathodic protection system's design life
unless the system is rejuvenated.
ETL 1110-9-10(FR)
5 Jan 91
5)
Coatings
Cathodic protection complements the protective coating system. A good coating system substantially
reduces the amount of cathodic protection current
required. The coating efficiency has to be
assumed.
6)
Short circuits
All short circuits must be eliminated from both new
and existing structures for which a cathodic
protection system is being designed.
b.
c.
I = (A)(I')(l.0 - CE)
(eq 1-1)
ETL 1110-9-10(FR)
5 Jan 91
current requirement test has been performed, as a check
on assumptions made. Current density may be estimated
from information given in table 3-1.
d.
ETL 1110-9-10(FR)
5 Jan 91
ENVIRONMENT
LENGTH (ft)
Sea Water
Coke Breeze
Fresh Water
3
6
30
5
10
50
9
20
100
0.062 in.
ENVIRONMENT
0.125 in.
0.250 in.
LENGTH (ft)
Sea Water
Coke Breeze
Fresh Water
7
12
70
12
24
135
24
54
300
ETL 1110-9-10(FR)
5 Jan 91
e. Calculate number of anodes (N) or length of bare anode wire
(LB).
1)
2)
(eq l-2a)
(eq l-2b)
(eq 1-3)
ETL 1110-9-10(FR)
5 Jan 91
acceptable. As the required current increases, the total
resistance should be reduced. See table 3-10.
The total anode-to-electrolyte resistance (RN)
is
calculated in different ways according to the type of anode
installation. The anode-to-electrolyte resistance for a
single anode is given by RA.
For a single vertical anode:
RA =
(0.0052)
p
(L)
[ln (8L/d)-1]
(eq 1-4)
Where
RA is the anode-to-electrolyte resistance for a
single anode, p is the electrolyte resistivity in ohm-cm,
L is the length of the backfill column in feet, and d is
the diameter of the backfill column in feet.
It should be noted that the anode dimensions are the overall length and diameter including backfill, if the backfill
is coke breeze and is not significantly more than 2 ft
longer than the anode or not significantly more than 20 ft
longer than the anode column in a deep vertical groundbed
configuration.
For earth backfill, the backfill column
dimensions should be the dimensions of the manufacturer's
standard packaged anode can. Bare ceramic anodes shall not
be installed in ground without coke breeze backfill. Coke
breeze allows venting of gases and effectively reduces RA.
If vertical anode dimensions are assumed to be 6 in. in
diameter and 8 ft in length, the following empirical
relations may be used:
RA =
(eq 1-5)
p
398
If the anode dimensions are different, a different empirical relation may be used:
RA =
(eq 1-6)
p K
L
10
ETL 1110-9-10(FR)
5 Jan 91
Deep anode groundbed resistance graphs are available for
deep vertical ground beds. (See figure 2-9a through 2-9c
located in section 2-4.)
For a single horizontal anode:
RA '
(0.0052) p
4L 2 % 4L (2h)2 % L 2
[1n
L
2 d h
%
(eq 1-7)
(2 h)2 % L 2
& 1]
L
2 h
&
L
p
441
(eq 1-8)
(0.0052) p
N L
+
2 L
Cc
ln (.656 N))
(eq 1-9)
ETL 1110-9-10(FR)
5 Jan 91
For optimum results, the length of the backfill column (L)
should be less than the anode spacing (Cc).
If multiple anodes are assumed to be 6 in. in diameter and
8 ft long, the following empirical expression may be used:
p FADJ
RN '
398
(eq 1-10)
RN '
RA
p PF
Cc
(eq 1-11)
RN '
p FADJ
441
(eq 1-12)
ETL 1110-9-10(FR)
5 Jan 91
RN '
(eq 1-13)
RN '
8DR
2 DR
0.0016 p
(1n
% 1n
)
DR
DA
H
(eq 1-14)
RW '
L W RMFT
100 ft
(eq 1-15)
RS
A
13
(eq 1-16)
ETL 1110-9-10(FR)
5 Jan 91
where RS is the coating resistance in ohm-square feet and
A is the total surface area. If the structure surface is
bare, negligible resistance is assumed (RC = 0).
g.
(eq 1-17)
(eq 1-18)
i.
ETL 1110-9-10(FR)
5 Jan 91
power. Prepare specifications to describe required features
of the system components.
1-3.
References.
The following documents describe corrosion fundamentals, traditional corrosion control techniques, and particular requirements of
U.S. Department of Defense agencies:
1.
2.
3.
4.
5.
6.
7.
8.
9.
Department of the Army, Economic Studies of Military Construction Design - Application, TM 5-802-1 (Headquarters,
Department of the Army, Washington D.C., 31 December 1988).
15
ETL 1110-9-10(FR)
5 Jan 91
10. Department of the Army, Electrical Design, Cathodic Protection,
TM 5-811-7 (Headquarters, Department of the Army, 22 April
1985).
11. Dwight, H.B.,
"Calculation of Resistance to Ground," AIEE
Transactions, vol. 55 (1939).
12. Electrical Engineering Cathodic Protection, Military Handbook
1004/10 (31 January 1990).
13. Fontana, Mars G., Corrosion Engineering, 3d ed. (McGraw Hill,
Inc., New York, 1986).
14. Hock, V., J. Givens, J. Suarez, and J. Rigsbee, "Structure,
Chemistry and Properties of Mixed Metal Oxide," Paper No.
230, Proceedings of the National Association of Corrosion
Engineers (1988).
15. Kumar, A., and M. Armstrong, "Cathodic Protection Designs Using
Ceramic Anodes," Materials Performance, vol. 27, No. 10
(Oct 1988), pp. 19-23.
16. Kumar, A., and M. Armstrong, "New Cathodic Protection Designs
Using Ceramic Anodes," Materials Performance, vol. 27, No.
10 (Oct 1988), pp. 19-23.
17. Kumar, A, and V. Hock, "Survey of Cathodic Protection Systems
Using Ceramic Coated Anodes," Paper No. 284, Proceedings of
the National Association of Corrosion Engineers (1989).
18. Morgan, John, Cathodic Protection, 2d ed., National Association
of Corrosion Engineers (Houston, 1987).
19. Myers, James R., Fundamentals and Forms of Corrosion (Air Force
Institute of Technology, October 1974).
20. Myers, J.R., and M.A. Aimone, Corrosion Control for Underground
Steel Pipelines: A Treatise on Cathodic Protection (July
1980).
21. NACE RP-02-72, "Recommended Practice - Direct Calculation of
Economic
Appraisals
of
Corrosion
Control
Measures"
(National Association of Corrosion Engineers, Houston,
1972).
22. NACE RP-0l-69,
"Recommended Practice - Control of External
Corrosion on Underground or
Submerged Metallic
Piping
Systems" (National Association of Corrosion Engineers,
Houston, 1969)
16
ETL 1110-9-10(FR)
5 Jan 91
23. NACE RP-02-85, "Recommended Practice - Control of External Corrosion on Metallic Buried, Partially Buried ,or Submerged
Liquid Storage Systems" (National Association of Corrosion
Engineers, Houston, 1985).
24. Paullin, Robert L., Pipeline Corrosion Protection: A Department
of Transportation Perspective (Materials Transportation
Bureau of the U.S. Department of Transportation, Washington
D.C., 1984).
25. Peabody, A.W., Control of Pipeline Corrosion (National Association of Corrosion Engineers, Houston, 1967).
26. Reding,
J.T., Performance of Mixed Metal Oxide Activated
Titanium
Anodes
(National
Association
of
Corrosion
Engineers, Houston, 1987).
27. Sunde, Earling D., Earth Conduction Effects in Transmission
Systems (D. VanNostrand Co., New York, 1949).
28. Treseder,
R.S.,
NACE Corrosion Engineer's Reference Book
(National Association of Corrosion Engineers, Houston,
1980).
29. Turner, Jane M., "Controlling Galvanic Corrosion in Soil With
Cathodic Protection," Gas Industries Magazine (Park Ridge,
IL, 1988).
30. Uhling, Herbert H., The Corrosion Handbook (John Wiley & Sons,
New York, 1948).
31. Uhling, Herbert H., and R. Winston Revie, Corrosion and
Corrosion Control: An Introduction to Corrosion Science and
Engineering, 3d ed. (John Wiley & Sons, New York, 1985).
32. West,
Lewis H.,
and Thomas F. Lewicki, Civil Engineering
Corrosion Control, Vol. 1: Corrosion Control - General;
Vol.
II:
Cathodic
Protection
Testing
Methods
and
Instruments; Vol. III: Cathodic Protection Design (Air
Force Civil Engineering Center, Tyndal Air Force Base, FL).
17
ETL 1110-9-10(FR)
5 Jan 91
EXAMPLES OF IMPRESSED CURRENT
CATHODIC PROTECTION DESIGN
2-1.
Purpose.
2)
3)
4)
5)
6)
7)
(outside diameter
on
6.625
previous
ETL 1110-9-10(FR)
5 Jan 91
19
ETL 1110-9-10(FR)
5 Jan 91
20
ETL 1110-9-10(FR)
5 Jan 91
21
ETL 1110-9-10(FR)
5 Jan 91
22
ETL 1110-9-10(FR)
5 Jan 91
23
ETL 1110-9-10(FR)
5 Jan 91
8)
9)
2)
6 in.
Pipe length
6800 ft
Pipe surface
area per lin ft
External pipe
surface area
I'
CE
ETL 1110-9-10(FR)
5 Jan 91
I
I
IA
Where:
I
IA
2.8
1.2
2.8
2.4
p K
L
ETL 1110-9-10(FR)
5 Jan 91
5)
RA =
2000 x 0.0213
5
RA
8.53 ohms
Where:
RN =
RA
p PF
Cc
Groundbed-to-earth resistance.
RA
8.53 ohms
(Resistance of a single
anode-to-earth
from
the
previous
calculation)
PF
CC
20 ft
(Center-to-center spacing of
anodes [discussed below])
= 1.706 ohms
26
ETL 1110-9-10(FR)
5 Jan 91
This is the approximate resistance based on the law for
parallel circuits. (When equal resistance values are
joined together in a parallel circuit, the total resistance value of the circuit is approximately equal to a
single resistance value divided by the number of resistance values.)
To calculate the true anode resistance for five anodes,
we must perform the calculation from equation 1-11.
CC
RN
8.53
5
RN
1.706 + 0.268
RN
1.974 ohms
2000 x 0.00268
20
6 anodes
PF
RN
RN
8.53
+
20
2000 x 0.00252
1.67 ohms
6)
7)
ETL 1110-9-10(FR)
5 Jan 91
to be protected to assure uniform distribution of the
protective current to all structure components. The
higher the soil or water resistivity, the further away
the ground must be located. For this example, previous
experience has shown that the nearest anode should be
located a minimum of 100 ft from the structure to
assure good current distribution. Since there are no
other underground utilities in the area, the groundbed
may be installed either perpendicular or parallel to
the pipe (figures 2-IA and 2-lB).
8)
Determine the
equation 1-3:
total
circuit
resistance
(RT)
from
RT = RN + RW + RC
Where:
RN =
RW =
RC =
a)
1.67 ohms
c
RW '
Where:
LAVG =
1000 ft
=
=
=
LAVG/N
90/6
15 ft
LW
LW RMFT
28
ETL 1110-9-10(FR)
5 Jan 91
c)
RMFT
RW
15 ft x 2.58 ohms
1000 ft
RW
0.039 ohms
Rc '
Where:
d)
e)
RS
11,791
sq
ft
External
pipe surface area calculated in
step 1 of paragraph 2-2b.
RC
2500 ohm-sq ft
11,791 sq ft
RC
0.212 ohm
Calculate the
equation 1-3:
total
circuit
resistance
RT
RN + RW + RC
RT
RT
1.921 ohms
(RT)
from
ETL 1110-9-10(FR)
5 Jan 91
9)
c.
RT
1.92
ohms
resistance
calculation.
(Total
from
circuit
previous
120%
Rectifier
voltage
design safety factor.
capacity
VREC
VREC
6.45 V
Select rectifier.
Based on the design requirement of 2.8 amperes and 6.45
volts, specify a 10-V, 5-amp rectifier, which is the
nearest standard capacity available from commercial
cathodic protection rectifier manufacturers.
30
ETL 1110-9-10(FR)
5 Jan 91
2-3.
2)
3)
4)
5)
6)
7)
8)
9)
10)
circuit
resistance
b. Computations.
1)
ETL 1110-9-10(FR)
5 Jan 91
Area of each tank = 2 B (tank radius)2 + B (tank
diameter) (tank length)
32
ETL 1110-9-10(FR)
5 Jan 91
33
ETL 1110-9-10(FR)
5 Jan 91
Area of 3 tanks = 3 [2 x 3.14 x 42 +3.14 x 8 x 21.25]
= 1905 sq ft
Area per lin ft of 2-in. pipe = 0.621 sq ft/ft (from
table A-2)
Total pipe area = 750 ft x 0.621 sq ft/ft = 466 sq ft
Total area = 1905 sq ft + 466 sq ft = 2371 sq ft
2)
I' =
CE
I
IA
34
ETL 1110-9-10(FR)
5 Jan 91
Where:
I =
4)
IA =
8.2
1.0
per
p K
L
4500 ohm-cm (Soil resistivity
item 1 of paragraph 2-3a)
from
5
ft (60
length).
RA =
RA
5)
rating
in.)
(Effective
anode
4500 x 0.0234
5
=
21.06 ohms
35
ETL 1110-9-10(FR)
5 Jan 91
RN '
RA
N
Where:
RN =
p PF
Cc
Groundbed-to-earth resistance
RA
CC
PF
0.00212
(Paralleling
factor
from
table 3-5; assume 9 anodes; reasoning
is the same as in step 5, paragraph
2-2b)
RN
RN
21.06
9
4500 x 0.00212
10
3.29 ohms.
The numbers
Determine the
equation 1-3:
total
36
circuit
resistance
(RT)
from
ETL 1110-9-10(FR)
5 Jan 91
RT = RN + RW + RC
Where:
RN = Groundbed resistance (ohms)
RW = Header cable/wire resistance (ohms)
RC = Structure-to-earth resistance (ohms).
a)
RN = 2.26 ohms
b)
Where:
LW =
RMFT
RW =
RW =
c)
LW RMFT
1000 ft
Structure-to-earth resistance.
Since the tanks and piping are essentially bare and
are not electrically isolated, structure-to-earth
resistance may be considered negligible. Therefore
RC = 0.
37
ETL 1110-9-10(FR)
5 Jan 91
d)
Calculate total
equation 1-3:
circuit
resistance
(RT)
from
RT = RN + RW + RC
RT = 2.26 + 0.04 + 0 = 2.30 ohms
Since the design requirements call for a maximum
groundbed resistance of 2.5 ohms and RT = 2.30
ohms, the design using fourteen 2-in. by 60-in.
packaged ceramic anodes will work.
8)
VREC
= 22.6 V
c. Select rectifier.
Based on the design requirement of 22.6 V and 8.2 amp, a
rectifier can be chosen.
A 12-amp, 24-V unit is selected
because this is the nearest standard commercial size
available.
38
ETL 1110-9-10(FR)
5 Jan 91
2-4.
Four on-grade fuel oil storage tanks are to be constructed with the
configuration shown on figure 2-6. This design may be prohibited
if secondary containment uses a nonconductive membrane beneath the
tanks.
The membrane would not allow the cathodic protection
current to flow from the remotely located deep anode through the
nonconductive membrane to the tank bottoms.
If this situation
exists, a distributed anode design with the anodes located between
the membrane and the tank bottoms would have to be used.
All
piping will be above grade. To minimize the extent of underground
cable, it was decided to use a deep anode groundbed, located just
outside the spill containment dikes. (Note: Some county, state,
or federal agencies such as the EPA may have regulations that
affect the use of deep anode beds because they can provide a
conduit for the mixing of water between aquifer levels. In such
cases, regulations have sometimes required cementing of the annulus
between the deep anode bed casing and the augered hole to prevent
this water migration. The system designer should check with the
applicable agencies before committing to a deep anode design.
Figures 2-7, 2-7A, 2-8, and 2-8A illustrate a typical deep anode
groundbed using ceramic rod anodes. The tank bottoms will be bare.
All piping will be above ground. The tanks will be dielectrically
insulated from the structures. Field tests were made at the site
and the subsurface geology was determined to be suitable for a deep
anode groundbed (reference 25).
a. Design data.
1)
2)
3)
4)
5)
6)
7)
39
circuit
resistance
ETL 1110-9-10(FR)
5 Jan 91
8)
40
ETL 1110-9-10(FR)
5 Jan 91
41
ETL 1110-9-10(FR)
5 Jan 91
42
ETL 1110-9-10(FR)
5 Jan 91
43
ETL 1110-9-10(FR)
5 Jan 91
44
ETL 1110-9-10(FR)
5 Jan 91
45
ETL 1110-9-10(FR)
5 Jan 91
b. Computations.
1)
2)
3)
I'
CE
35 amp
I
IA
Where:
I = 35
amp
(Current
previous calculation)
requirement
from
35
6.6
46
ETL 1110-9-10(FR)
5 Jan 91
4)
36 ft
55 ft
20 ft
111 ft
Calculate
(RA).
the
ETL 1110-9-10(FR)
5 Jan 91
48
ETL 1110-9-10(FR)
5 Jan 91
49
50
ETL 1110-9-10(FR)
5 Jan 91
Where:
RA =
a)
RW
RC
from step
RA = 0.47 ohm
b)
Wire resistance
A deep anode groundbed is defined as one where the
top of the backfill column is at least 50 ft below
the surface of the earth. Actual depth will vary,
depending on subsurface geology and the distance
over which the current is expected to spread. In
this example, 65 ft was selected as the depth to
the top of the coke breeze column. The anodes can
be supplied through a single or dual feed. Dual
feed is preferred to reduce both the resistance of
the circuit and the chance of a failure due to a
cable break.
No. 4 AWG cable has been chosen.
Cable lengths
have been calculated based on the following
distances,
illustrated in the deep groundbed
example shown in figure 2-7.
51
ETL 1110-9-10(FR)
5 Jan 91
From grade to top of backfill column 65 ft
From top of backfill column to
top anode
10 ft
176 ft
10 ft
250 ft
91 ft
200 ft
291 ft
Calculate
top
equation 1-15:
RWT '
cable
resistance
(RWT)
from
LWT RMFT
1000 ft
Where:
LWT
200 ft (Cable
calculation)
RMFT
RWT
Calculate bottom
equation 1-15:
cable
52
length
from
previous
= 0.051 ohm
resistance
(RWB)
from
ETL 1110-9-10(FR)
5 Jan 91
Where:
LWB
291 ft (Cable
calculation)
RMFT
RWB
length
from
previous
= 0.074 ohm
1
RWT
1
RT/B
1
0.051
1
RT/B
1
RWB
+
1
0.074
LW R MFT
1000 ft
1
91 ft( x 0.254 ohm/ft
1
'
x
2
1000 ft
2
wire
resistance
must
also
be
53
ETL 1110-9-10(FR)
5 Jan 91
Therefore, one half the cable length is used in this
calculation. The calculation is also conservative since not
all the current flows through the complete intertank bond
circuit.
RNEG '
Where:
LW =
RMFT =
1000 ft
RNEG =
RNEG =
LW RMFT
295 x 0.254
1000
0.074
RW
0.116 ohm
Cable
insulation
is
also
important.
High
molecular
weight
polyethylene
insulation,
commonly used for cathodic protection work, tends to
blister, become brittle, and then crack in deep
groundbed use where chlorine gas generation can occur.
This has been most prevalent in open holes containing
brackish water, but may occur in coke breeze
backfilled holes also. Consequently, to minimize the
chances of cable failure, one of the two following
types of insulation, which show good resistance to
these oxidizing environments should be used:
Polyvinylidene fluoride (Kynar)1
____________________
1
54
ETL 1110-9-10(FR)
5 Jan 91
Copolymer of chlor-tri-fluorethylene and ethylene
(Halar)2
To
protect
the
insulation
itself
and
to
facilitate
handling,
cables
for
deep
anode
groundbeds also have an outer jacket of highmolecular weight polyethylene extruded over the
Kynar or Halar insulation.
c)
d)
= RN + RW + RC
RT
RT
= 0.586 ohm
(RT)
from
RT
120%
VREC =
VREC =
24.6 V
c. Select rectifier.
____________________
2
55
ETL 1110-9-10(FR)
5 Jan 91
Based on the design requirement of 24.6 V and 35 amp, a
rectifier can be chosen.
A 30 V, 42 ampere unit is
commercially available and is selected. This rectifier can
be pole mounted as illustrated in figure 2-10.
d. Installation.
Figures 2-7 and 2-8 show this deep anode design.
56
ETL 1110-9-10(FR)
5 Jan 91
57
ETL 1110-9-10(FR)
5 Jan 91
2-5.
Experience
in
the
area
shows
the
subsurface
resistivity at a depth of 50 and 200 ft to be 2000 ohmcm.
2)
3)
4)
5)
6)
7)
8)
58
ETL 1110-9-10(FR)
5 Jan 91
9)
59
ETL 1110-9-10(FR)
5 Jan 91
60
ETL 1110-9-10(FR)
5 Jan 91
b. Computations.
1)
Length
1 1/4 in.
4 in.
6 in.
28,000 ft
1,200 ft
3,600 ft
Unit Area*
(sq ft/lin ft)
0.434
1.178
1.734
Total
3)
I' =
CE =
I
IA
40
amp
(Current requirement
previous calculation)
from
ETL 1110-9-10(FR)
5 Jan 91
N =
40
8
= 5 anodes
of
the
backfill
column
is
19.8 ft
65.0 ft
20.0 ft
104.8 ft
(use 105 ft)
5)
Calculate
(RA).
the
62
ETL 1110-9-10(FR)
5 Jan 91
RT = RA + RW + RC (Because the cathodic protection
system uses a single deep anode groundbed RA = RN)
Where:
RA =
a)
Backfill
(ohms).
column-to-earth
resistance
RW
RC
Backfill
step 5.
column-to-earth
resistance
(RA)
from
RA = 0.65 ohm
b)
RW '
LW RMFT
1000 ft
ETL 1110-9-10(FR)
5 Jan 91
EPR/HY50 cable has been chosen.
The cable
lengths have been calculated based on the
following distances, which are illustrated in the
deep groundbed examples shown in figures 2-12 and
2-13:
From grade to top of backfill column
From top of backfill column to top anode
From grade to bottom of backfill column
From bottom anode to bottom of backfill
column
From anode hole to rectifier 2 cables
at 10 ft
From top of anode assembly to bottom of
anode assembly
100 ft
10 ft
205 ft
10 ft
20 ft
85 ft
120 ft
205 ft
Calculate top
equation 1-15:
RWT '
cable
resistance
(RWT)
from
LWT RMFT
1000 ft
Where:
LWT
RMFT
RWT
120
ft
(Cable
length
previous calculation)
from
Calculate bottom
equation 1-15:
cable
resistance
(RWB)
from
Where:
LWB
205
ft
(Cable
length
previous calculation)
64
from
ETL 1110-9-10(FR)
5 Jan 91
RMFT
RWB
1
RWT
1
RT/B
1
0.014
1
RT/B
RT/B
1
RWB
+
1
0.024
L W RMFT
1000 ft
1
85 x 0.1183 ohm/ft
1
'
x
2
1000 ft
2
RNEG '
Where:
LW
LW RMFT
1000 ft
=
25 ft (Length of cable)
65
ETL 1110-9-10(FR)
5 Jan 91
RMFT =
RNEG =
25 x 0.254
1000
RNEG =
0.006 ohm
c)
RPOS
RW
+
=
RNEG
RW
=
0.020 ohm
0.009
0.005
d)
7)
(RC)
from
RT
RT
RT
= 0.670 ohm
Where:
I
RT
120%
Rectifier
voltage
safety factor
66
resistance
capacity
design
ETL 1110-9-10(FR)
5 Jan 91
VREC =
VREC =
32.2 V
c. Select rectifier.
Based on the design requirement of 32.2 V and 40 amp, a
rectifier can be chosen.
A 36-V, 50-amp unit is
commercially available and is selected.
d. Installation.
Figures 2-12 and 2-13 show how the deep anode groundbed
might look.
67
ETL 1110-9-10(FR)
5 Jan 91
68
ETL 1110-9-10(FR)
5 Jan 91
69
ETL 1110-9-10(FR)
5 Jan 91
2-6.
Design data.
1)
2)
3)
4)
5)
6)
7)
8)
9)
Computations.
70
ETL 1110-9-10(FR)
5 Jan 91
1)
IA =
I
IA
25
0.31
81 ft
25 ft 9 in.
3)
ETL 1110-9-10(FR)
5 Jan 91
But this diameter provides an anode length that is
still slightly less than that required for a 15-year
mode life.
Therefore, we will use a hoop diameter
that is 55 percent of the bowl diameter:
DE = 51.5 x 55% = 28.3 ft
4)
8 DR
2 DR
0.0016 p
(1n
% 1n
)
DR
DA
H
Where:
p =
DR =
DA =
H =
0.0016 (2000)
28.3
[ln
8 x 28.3
0.00521
+ ln
2 x 28.3
21
72
ETL 1110-9-10(FR)
5 Jan 91
5)
Anode-to-water resistance
Wire resistance
Tank-to-water resistance.
a)
b)
c)
RW
RW
Tank-to-water
resistance
circuit resistance.
(RC)
and
negative
ETL 1110-9-10(FR)
5 Jan 91
is negligible. The tank-to-water resistance is
also negligible because the coating is very
deteriorated.
d)
Calculate RT:
RT
RT
= 1.38 ohms
c.
(Total
from
circuit
previous
120%
VREC
VREC
= 41.4 V
Select rectifier.
Based on the design requirements of 41.4 V and 25 amp, a
commercially available 48-V, 28-amp unit is selected. To
prevent over- or under-protection as the water level
varies, automatic potential control is specified.
The
tank-to-water potential is maintained by the controller
through two permanent copper-copper sulfate reference
electrodes suspended beneath the anode wire circle. The
reference electrodes should have a life of at least 5
years.
The tank-to-water potential measured by the
controller should be free of IR drop error.
74
ETL 1110-9-10(FR)
5 Jan 91
d.
Installation.
Figure 2-14 shows a typical installation while figure 2-14A
provides a typical detail for a pressure entrance fitting
for underwater power and reference cell wire penetrations.
75
ETL 1110-9-10(FR)
5 Jan 91
76
ETL 1110-9-10(FR)
5 Jan 91
77
ETL 1110-9-10(FR)
5 Jan 91
2-7.
This impressed current design is for a tank (figure 2-15) that has
not been built; thus, it is not possible to measure current
requirements and other factors. Calculated estimates are used.
a.
Design data.
1)
2)
3)
4)
5)
6)
Segmented rod anodes will be used; 4-ft long by 0.138in. diameter. Note: Segmented rods have an advantage
in that they can be field assembled using factory-made
connections.
On the other hand, continuous wire
(.0625-in. diameter) is also available in long lengths
(typically 500 ft).
These can be fabricated with
factory-made wire connections but their overall length
must be specified. Continuous wire will almost always
be less expensive.
7)
8)
9)
78
Area
ETL 1110-9-10(FR)
5 Jan 91
b.
Computations.
1)
79
ETL 1110-9-10(FR)
5 Jan 91
80
ETL 1110-9-10(FR)
5 Jan 91
81
ETL 1110-9-10(FR)
5 Jan 91
A = AT + AC + AB
(eq 2-1)
Where:
AT = Wetted area of the top section
AC = Area of the center section
AB = Area of the bottom section.
a)
(eq 2-2)
Where:
r
h
b)
=
=
28 ft (Tank radius)
10 ft (Water height)
AT =
2 x 3.1416 x 28 ft x 10 ft
1759 sq ft (approximate).
c)
=
=
28 ft (Tank radius
11 ft (Water height)
AC =
2 x 3.1416 x 28 ft x 11 ft
1935 sq ft
(eq 2-2)
2 A r h2 % r2
Where:
r = 28 ft (Tank radius)
h = 14 ft (Water height)
AB '
82
(eq 2-3)
ETL 1110-9-10(FR)
5 Jan 91
d)
Calculate (A):
A
A
2)
=
=
(eq 2-2)
Where:
3)
rR =
hR =
AR =
AR =
1806 sq ft
Find the maximum design current for the tank bowl (IT)
using equation 1-1:
IT = (A) (I) (1.0 - CE)
Where:
A =
I =
CE =
IT =
IT =
4)
current
for
the
riser
83
ETL 1110-9-10(FR)
5 Jan 91
5)
I' =
CE =
IR =
IR =
19
amp
(Current
determined in step 3)
IA =
6)
I
IA
requirement
I
IA
14.5
amp
(Current
determined in step 4)
requirement
ETL 1110-9-10(FR)
5 Jan 91
7)
14.5
1
14.5; use 15 rod segments (4 ft.
long)
D x N
2 (A % N)
Where:
D =
N
AR =
AR =
AR =
(eq 2-4)
85
ETL 1110-9-10(FR)
5 Jan 91
86
ETL 1110-9-10(FR)
5 Jan 91
87
ETL 1110-9-10(FR)
5 Jan 91
8)
CC =
CC =
b)
9)
2 A AR
N
(eq 2-5)
88
ETL 1110-9-10(FR)
5 Jan 91
89
ETL 1110-9-10(FR)
5 Jan 91
90
ETL 1110-9-10(FR)
5 Jan 91
RN '
Where:
p =
D
AR =
DE =
0.275 (Equivalent
from figure 2-17)
LB =
RN =
RN =
1.33 ohms.
diameter
factor
b)
ETL 1110-9-10(FR)
5 Jan 91
be seen that stub anodes are required for this
design. For a two-ring anode design (main and
one-stub anode ring), which is usually sufficient
for tanks up to 1 million gal storage capacity,
the 4-ft long stub anodes are located on a radius
one-fourth of the bowl radius, or 7 ft (28 ft x
0.25 = 7 ft). Typically, there will be about one
half as many stub anodes (two ring design) as
there are main anodes so we will plan for five 4ft long stub anodes on a 7-ft radius.
The
outside radius of the area to be protected by the
stub anodes is approximately 13 ft and the inside
radius is 2.5 ft (riser radius). The stub anodes
are thus located on an 7-ft radius to place them
in the center of the area to be protected. (Note:
For smaller diameter tanks, stub anodes may not
be required.)
c)
Where:
r1 =
r2 =
(eq 2-6)
28 ft (tank radius) - 6 ft - 9 ft = 13 ft
ASB =
ASB =
3.1416 x 162.75
ASB =
ETL 1110-9-10(FR)
5 Jan 91
(2)
(4)
The current
therefore;
19.0
d)
for
the
main
anodes
is,
N5 =
NS =
Check
I
IA
93
ETL 1110-9-10(FR)
5 Jan 91
Where:
p =
D
AR =
DE =
0.07 (Equivalent
from figure 2-17)
LB =
RN =
RN =
21.03 ohms.
diameter
factor
(eq 2-7)
94
ETL 1110-9-10(FR)
5 Jan 91
d = 0.0115 ft
L/d =
4
0.0115
= 348
Anode-to-water resistance.
Header cable/wire resistance.
Tank-to-water resistances.
RW
= 0.13 ohm
LW RMFT
1000 ft
RMFT
RW
95
= 0.13 ohm
ETL 1110-9-10(FR)
5 Jan 91
RC
b)
c)
b)
c)
115
7.75
= 14.8 or 15 anodes
96
ETL 1110-9-10(FR)
5 Jan 91
The number of anodes required for current
distribution equals the number needed for the
current requirement. To allow for a factor of
safety, use twenty anodes.
d)
33.5
19
= 1.76 ft or 1 ft 9 in.
= 28.4 anodes
97
ETL 1110-9-10(FR)
5 Jan 91
Weight is not a factor in supporting the string.
15) Calculate the anode-to-water resistance of a single
anode rod (RA), using equation 2-8:
RA '
0.0052 p 1n(D/DA)
LB
Where:
p =
(eq 2-8)
D =
DA =
LB =
112 ft
(Length of anode rod from
previous discussion)
RA =
RA =
Anode-to-water
resistance
single anode rod.
RW =
Wire resistance.
RC =
Tank-to-water resistance.
of
a)
b)
98
ETL 1110-9-10(FR)
5 Jan 91
RW '
Where:
LW =
RMFT =
RW =
LW RMFT
1000 ft
240 ft (After reviewing figure 2-20,
it is estimated that 240 ft of wire
will be required to
connect
the
rectifier to the riser anode string)
0.640 ohm (Wire resistance per 1000
lin ft of No. 8 AWG HMWPE insulated
wire)
240 ft x 0.640 ohm
1000 ft
= 0.15 ohm
= 0.74 ohm
= 0.048 ohm
ETL 1110-9-10(FR)
5 Jan 91
Thus, the copper cored anode longitudinal
resistance
is less than
10 percent of the
anode-to-water resistance (0.048 ohm/1.13 ohm 0.043 = 4.3 percent) making this an acceptable
riser anode design.
c)
Tank-to-water
resistance (RC)
circuit resistance = 0.0 ohm.
and
negative
d)
Current requirement.
Total circuit resistance.
Main Anodes:
I = 17.7 amp (from step 11c).
RT = 1.46 ohms (from step 13b).
E = 17.7
x 1.46 = 25.8 V
Stub Anodes:
I =
RT =
100
ETL 1110-9-10(FR)
5 Jan 91
b)
Main anodes
Stub anodes
Riser anodes
Total current
requirement
c)
Current Resistance
(ohm)
17.7
1.3
14.5
current
Voltage Required
(V)
1.46
21.16
1.28
25.8
27.5
18.6
33.5
c.
Select rectifier
1)
Rectifier capacity.
A commercially available rectifier having a rated
output of 40 V, 42 amp is selected.
Because of the different circuit resistances, separate
control of each circuit is required.
This is best
handled by a rectifier having three separate output
circuits.
2)
ETL 1110-9-10(FR)
5 Jan 91
rectifier for a fraction of a second, during which
time the tank-to-water potential is measured.
The
measurement is then compared with a preset standard
and the output adjusted accordingly.
d.
Installation details.
Figures 2-19, 2-20, and 2-21 show typical details.
e.
102
ETL 1110-9-10(FR)
5 Jan 91
103
ETL 1110-9-10(FR)
5 Jan 91
2-8.
Design data.
1)
2)
3)
4)
5)
6)
7)
8)
9)
Computations.
1)
104
ETL 1110-9-10(FR)
5 Jan 91
105
ETL 1110-9-10(FR)
5 Jan 91
Where:
r =
2)
23 ft (Tank radius
paragraph 2-8a)
from
item
of
h =
A =
2 it x 23 x 20 + it x 232
A =
2890 + 1662
A =
4552 sq ft
4552 sq ft
(Area of tank to be
protected from previous calculation)
I' =
density
CE =
Current required:
I =
I =
I
IA
12
amp
(Current
requirement
previous calculation)
106
from
ETL 1110-9-10(FR)
5 Jan 91
IA =
Based on
selecting a wire anode of
0.0625-in.
diameter, the minimum wire length and hoop diameter
can be calculated:
For 0.0625 in. LB
4)
12 amp
0.31 amp/ft
38.7 ft
(Length of
Wire for
15-Year Life)
12 ft 4 in
(Minimum
Diameter of
Wire Circle)
5)
8 DR
2 DR
0.0016 p
(1n
% 1n
DR
DA
H
Where:
p =
DR =
DA =
Assume
0.0052
ft
(0.0625
in)
(Diameter of anode wire from step 3
of paragraph 2-8b)
107
ETL 1110-9-10(FR)
5 Jan 91
H =
20 ft x 40% = 8 ft
Anode depth below water surface (H):
H = 20 ft - 8 ft = 12 ft
Calculate RA:
RA
RA
RA
RA
= 1.42 ohm
= I x RA
= 12 x 1.42 = 17.2 V
ETL 1110-9-10(FR)
5 Jan 91
a)
b)
RW '
Where:
LW =
RMFT =
1000 ft
The positive wire from the rectifier
to the first splice is 15 ft long.
The power feed then continues on
around the hoop to the opposite
side. The length of this run is
about 43.2 ft but since only half
the current is passing through this
portion, its effective length is
43.2/2 = 21.6 ft.
1.02 ohms (From table 3-6, based on
selecting No. 10 AWG cables)
RW =
RW =
c)
d)
Calculate RT:
RT = 1.42 + 0.037 + 0.00
RT = 1.457 ohms; use 1.5 ohms
This is well below the design requirement.
7)
ETL 1110-9-10(FR)
5 Jan 91
VREC = (I) (RT) (120%)
Where:
I
=
c.
RT
120%
VREC
VREC
21.6 V
Select rectifier.
Based on the design requirements of 21.6 V and 12 amp, a
commercially available 24-V 16-amp unit is selected.
d.
e.
Installation details.
Figures 2-22 and 2-23 show typical details.
f.
ETL 1110-9-10(FR)
5 Jan 91
The wire circle, or loop anode is supported from the sides
of the tank by polyester rope as shown in figure 2-22. The
number of supports varies with the tank diameter as
recommended in table 3-8.
111
ETL 1110-9-10(FR)
5 Jan 91
112
ETL 1110-9-10(FR)
5 Jan 91
2-9.
Where:
RA
p
L
d
h
=
=
=
=
=
RN '
RA
N
p PF
CC
113
ETL 1110-9-10(FR)
5 Jan 91
114
ETL 1110-9-10(FR)
5 Jan 91
Where:
RN =
RA
Resistance-to-electrolyte of a single
horizontal anode
Number of anodes
PF
CC
115
ETL 1110-9-10(FR)
5 Jan 91
2-10.
116
ETL 1110-9-10(FR)
5 Jan 91
SECTION 3
TABLES
Table 3-1. Range of current density requirements for cathodic
protection of uncoated steel.
Environment
Neutral soil
Wellaerated neutral soil
Wet soil
Highly acidic soil
Soil-supporting active sulfatereducing bacteria
Heated soil
Stationary freshwater
Moving freshwater
Moving freshwater containing
dissolved oxygen
Seawater (depending on velocity,
temperature & oxygen content
Current density
APM 88-9a
0.4
2
1
3
to 1.5
to 3
to 6
to 15
to 1.5
to 3
to 6
to 15
6
to 42
3
to 25
1
to 6
----- ------
Up to 42
5 to 25
Up to 5
--------
to 15
5 to 15
to 10
5 to 25
0.5
1.5
1
3
to 1.5
to 3
to 3
to 15
---------3 or more
1.5 to 3
3
to 8
----------
to 50
Corrosion Control, Air Force Manual (AFM) 889 (Headquarters, U.S. Air Force,
August, 1962), ch. 4, p. 203.
b
J.S. Gerrard, Practical Applications of Cathodic Protection, Corrosion,
(Newnes-Butterworths, London, 1976), vol. 2, p 11:65. Used with permission.
c
Data based on the experience of other Professional Cathodic Protection
engineers.
117
ETL 1110-9-10(FR)
5 Jan 91
Table 32. Typical Surface Area Per Linear Foot of Common Size
Pipe.
Nominal Pipe Size
3/4
1
1 1/4
1
2
2
3
3
4
5
6
8
10
12
14
16
18
20
22
24
0.840
1.050
1.315
1.660
1.900
2.375
2.875
3.500
4.000
4.500
5.563
6.625
8.625
10.750
12.750
14.000
16.000
18.000
20.000
22.000
24.000
Sq Ft/Lin Ft
0.220
0.275
0.344
0.434
0.497
0.621
0.752
0.916
1.047
1.178
1.456
1.734
2.258
2.814
3.338
3.665
4.189
4.712
5.236
5.760
6.283
___________
NOTE: Data on anodes shapes and sizes as well as recommended operating limits
were obtained from the following manufacturers:
APSMaterials Inc.
153 Walbrook
Dayton, OH 45405
(513) 2786547
FAX: (513) 2784352
118
2"
3"
3"
3"
60"
60"
60"
96"
119
3" x 96"
3" x 96"
3" x 120"
3" x 120"
1/8" x 6'
1/4" x 6'
1/8" x 8'
1/4" x 8'
lbs.
lbs.
lbs.
lbs.
44 lbs.
44 lbs.
35 lbs.
35 lbs.
22 lbs.
23 lbs
24 lbs
12
22
22
35
6 lbs.
14 lbs.
26 lbs.
Weight
5.4
11.0
4.0
8.2
7.5
10.0
15.0
2.7
2.7
5.5
4.0
1.3
1.5
1.5
amps
amps
amps
amps
amps
amps
amps
amps
amps
amps
amps
amps
amps
amps
10-Year
Design Life
HDC*
_________
*Heavy Duty Coating Tubular Anodes (in Coke Breeze)
**Standard Coating Tubular Anodes (in Coke Breeze)
3"
3"
3"
x 60"
x 60"
x 60"
x
x
x
x
3/8" x 4'
" x 4'
3/4" x 4'
4'
4'
4'
6'
1/8"
1/8"
1/4"
1/8"
x
x
x
x
2"
2"
3"
1/8" x 2'
1/16" x 5'
1/16" x 5'
x 30"
x 72"
x 72"
Package
Size
Anode Element
Dimension
amps
amps
amps
amps
4.4 amps
8.8 amps
3.3 amps
6.6 amps
6.0 amps
8.0 amps
12.0 amps
2.2
2.2
4.4
3.3
1.10 amps
1.25 amps
1.25 amps
amps
amps
amps
amps
2.4 amps
4.8 amps
1.8 amps
3.6 amps
3.6 amps
4.8 amps
7.2 amps
1.2
1.2
2.4
1.8
0.6 amps
0.7 amps
0.7 amps
15-Year
Design Life
HDC*
SC**
amps
amps
amps
amps
3.6 amps
7.0 amps
2.7 amps
5.3 amps
5.1 amps
6.8 amps
10.0 amps
1.8
1.8
3.5
2.7
0.9 amps
1.0 amps
1.0 amps
amps
amps
amps
amps
2.0 amps
4.0 amps
1.5 amps
3.0 amps
3.0 amps
4.0 amps
6.0 amps
1.0
1.0
2.0
1.5
0.5 amps
0.6 amps
0.6 amps
20-Year
Design Life
HDC*
SC**
ETL 1110-9-10(FR)
5 Jan 91
ETL 1110-9-10(FR)
5 Jan 91
Table 3-3. (Cont*d)
Anode Element
Dimension
1" x 9.8"
1" x 19.7"
1" x 39.4"
0.63" x 9.8"
0.63" x 19.7"
0.63" x 39.4
2.00
4.00
8.00
1.25
2.50
5.00
120
amp
amp
amp
amp
amp
amp
ETL 1110-9-10(FR)
5 Jan 91
Table 33 (Cont*d). Fresh and Seawater Usage
Wire and Rod Anodes (Bare)
Life
(years)
Fresh Water
Brackish Water
Seawater
Maximum Current/1-ft Length for 20-Year Design Life of .0625 in. Dia. Wire
10
15
20
0.39
0.31
0.26
0.51
0.44
0.39
0.85
0.74
0.67
Maximum Current/1-ft Length for 20Year Design Life of .125 in. Dia. Rod or
Wire
10
15
20
0.79
0.62
0.52
1.02
0.88
0.79
1.70
1.47
1.33
Maximum Current/1-ft Length for 20Year Design Life of .25 in. Dia. Rod
10
15
20
1.58
1.24
1.04
2.04
1.76
1.58
3.41
2.95
2.66
Maximum Current/1-ft Length for 20-Year Design Life of .325 in. Dia. Rod
10
15
20
2.37
1.85
1.56
3.06
2.63
2.37
5.11
4.42
3.99
Maximum Current/1ft Length for 20-Year Design Life of .5 in. Dia. Rod
10
15
20
3.16
2.47
2.08
4.08
3.51
3.16
6.81
5.90
5.33
Maximum Current/1-ft Length for 20Year Design Life of .625 in. Dia. Rod
10
15
20
3.95
3.09
2.60
5.10
4.39
3.95
8.52
7.37
6.66
Maximum Current Per 1-ft Length for 20Year Design Life of .75 in. Dia. Rod
10
15
20
4.74
3.71
3.12
6.12
5.27
4.74
121
10.22
8.85
7.99
ETL 1110-9-10(FR)
5 Jan 91
Tubular Anodes (Bare)
25
50
15
30
amp
amp
amp
amp
6 amp
12 amp
4.00
8.00
2.50
5.00
amp
amp
amp
amp
Life
(years)
Coke
Fresh Water
Brackish Water
10
19
24
31
52
15
15
19
27
45
20
13
16
24
41
_________________
* Anode packaged in coke breeze
122
Seawater
ETL 1110-9-10(FR)
5 Jan 91
Tubular Anodes
Anode Life Versus Maximum Current Density (ampere/sq ft)
Life
(years)
Coke
Fresh Water
Brackish Water
Seawater
20
9.3
9.3
9.3
56 **
_________________
*Anode packaged in coke breeze
**15-Year Design Life
Size:
Active Area:
Weight:
0.84
5.0
20.0
10.0
50.0
_______________
*Standard Coating
123
Salt Water
2.5
10.0
ETL 1110-9-10(FR)
5 Jan 91
Table 34. Shape functions (K) for impressed current cathodic
protection anodes where L is effective anode/backfill length and
d is anode/backfill diameter.
L/d
L/d
5
6
7
8
9
10
12
14
16
18
0.0140
0.0150
0.0158
0.0165
0.0171
0.0177
0.0186
0.0194
0.0201
0.0207
20
25
30
35
40
45
50
55
60
0.0213
0.0224
0.0234
0.0242
0.0249
0.0255
0.0261
0.0266
0.0270
2
3
4
5
6
7
8
9
10
12
0.00261
0.00289
0.00283
0.00268
0.00252
0.00237
0.00224
0.00212
0.00201
0.00182
14
16
18
20
22
24
26
28
30
0.00168
0.00155
0.00145
0.00135
0.00128
0.00121
0.00114
0.00109
0.00104
124
ETL 1110-9-10(FR)
5 Jan 91
Table 36. Resistance and other parameters for stranded copper
conductors.
Size **
AWG
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250 MCM
EPR/HY-50*
EPR/HY-16*
Overall
Diameter
Not Incl.
Insulation
(in.)
0.0726
0.0915
0.1160
0.1460
0.1840
0.2320
0.2600
0.2920
0.3320
0.3730
0.4190
0.4700
0.5280
0.5750
0.3730(1)
0.1840(2)
Approximate
Maximum
Weight
Maximum
Allowable
Not Incl.
Maximum DC Resistance DC Current
Insulation Breaking
at 20 EC
Capacity
(lb/M ft) Strength (lb)(ohms/M ft)
(ampere)
12.68
20.16
32.06
50.97
81.05
128.90
162.50
204.90
258.40
325.80
410.90
518.10
653.30
771.90
75.0(1)
87.0(2)
130
207
329
525
832
1320
1670
21.10
2660
3350
4230
5320
6453
7930
1896
628
2.5800
1.6200
1.0200
0.6400
0.4030
0.2540
0.2010
0.1590
0.1260
0.1000
0.0795
0.0631
0.0500
0.0423
0.1183
0.3658
15
20
30
45
65
85
100
115
130
150
175
200
230
255
150
50
___________
(1)
With insulation: Overall diameter = 0.88 in.; weight 610 lb/l000 ft.
(2)
With insulation: Overall diameter = 0.51 in.; weight - 200 lb/1000 ft.
* Data from Dow Chemical
** Data from Rome Cable Company
125
ETL 1110-9-10(FR)
5 Jan 91
Table 37. suggested number of anode rings for various size
tanks.
Tank Diameter
(ft)
24
30
36
42
48
54
60
66
72
78
84
Bare
1
1
1
1
1
1
2
2
2
2
2
1
1
1
1
2
2
2
2
2
3
3
24
30
36
42
48
54
60
66
72
78
84
6
6
6
6
6
8
8
8
10
10
10
126
ETL 1110-9-10(FR)
5 Jan 91
Table 3-9. Adjusting factors for parallel anodes.
No. of Anodes
in Parallel
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
22
24
26
28
30
Adjusting Factors
5 ft
10 ft
Anode
15 ft
0.652
0.586
0.520
0.466
0.423
0.387
0.361
0.332
0.311
0.292
0.276
0.262
0.249
0.238
0.226
0.218
0.209
0.202
0.194
0.182
0.171
0.161
0.152
0.145
0.551
0.418
0.340
0.289
0.252
0.224
0.204
0.185
0.170
0.158
0.143
0.139
0.131
0.124
0.117
0.112
0.107
0.102
0.098
0.091
0.085
0.079
0.075
0.070
0.576
0.460
0.385
0.333
0.295
0.265
0.243
0.222
0.205
0.192
0.180
0.169
0.160
0.152
0.144
0.138
0.132
0.127
0.122
0.114
0.106
0.100
0.094
0.089
Spacing in Feet
20 ft
25 ft
0.538
0.397
0.318
0.267
0.231
0.204
0.184
0.166
0.153
0.141
0.132
0.123
0.116
0.109
0.103
0.099
0.094
0.090
0.086
0.079
0.074
0.069
0.065
0.061
0.530
0.384
0.304
0.253
0.218
0.192
0.172
0.155
0.142
0.131
0.122
0.114
0.107
0.101
0.095
0.091
0.086
0.082
0.079
0.073
0.067
0.063
0.059
0.056
System
Current (I)
(amp)
5
10
20
30
40
60
80
127
5
3
2
1.3
1.0
0.6
0.4
ETL 1110-9-10(FR)
5 Jan 91
SECTION 4
IDENTIFICATION OF VARIABLES
A
AR
AS
ASB =
CC
CE
Tank diameter.
DA
DE
DR
FADJ =
IA
Shape function.
128
ETL 1110-9-10(FR)
5 Jan 91
LAVG =
LB
LF
ln
LW
NS
PF
Paralleling factor.
RA
RADJ =
Adjusted resistance.
RC
Structure-to-electrolyte resistance.
RH
RL
RMFT =
RN
RNEG =
Rs
RT
ETL 1110-9-10(FR)
5 Jan 91
RN
VREC =
130