Manual MPS-PA Compact Workstation en
Manual MPS-PA Compact Workstation en
MPS PA Compact
Workstation
Manual
MPS PA Compact
Workstation
EN
12/08
Intended use
This station has been developed and produced solely for vocational and further
training purposes in the field of automation and communication. The company
undertaking the training and / or the instructors is / are to ensure that trainees
observe the safety precautions described in the manuals provided.
Festo Didactic herewith excludes any liability for damage or injury caused to
trainees, the training company and / or any third party, which may occur if the
system is in use for purposes other than purely for training, unless the said damage
/ injury has been caused by Festo Didactic deliberately or through gross negligence.
Order No.:
BE.TW.0004
Description:
Manual
Designation:
Status:
12/2008
Authors:
Graphics:
Layout:
Contents
1.5
Risks involved in dealing with the MPS PA Compact Workstation ______ 8
1.6
Warranty and liability ____________________________________________ 9
1.7
Use for intended purpose ________________________________________ 9
Notes on safety ________________________________________________________ 11
2 Technical data_____________________________________________________ 13
3 Transport / Unpacking / Scope of delivery _____________________________ 15
4 Design and function ________________________________________________ 17
4.1
Level monitoring_______________________________________________ 20
4.2
Pump ________________________________________________________ 24
4.3
Proportional valve _____________________________________________ 25
4.4
Heating ______________________________________________________ 26
4.5
2W ball valve with pneumatic rotary drive __________________________ 28
4.6
Level control function___________________________________________ 29
4.7
Flow rate control function _______________________________________ 31
4.8
Pressure control function________________________________________ 33
4.9
Temperature control system _____________________________________ 35
4.10
I/O-board __________________________________________________ 37
4.11
Mouting frame ______________________________________________ 38
5 Commissioning ____________________________________________________ 39
5.1
Workstation___________________________________________________ 40
5.2
Visual check __________________________________________________ 40
5.3
Cable connections _____________________________________________ 41
5.3.1
Simulation box digital/analog and MPS PA Compact Workstation 41
5.3.2
Easyport digital/analog and MPS PA Compact Workstation______ 43
5.3.3
EduTrainer Siemens S7-300 and MPS PA Compact Workstation __ 45
5.3.4
EduTrainer Logo and MPS PA Compact Workstation ____________ 47
5.3.5
EduTrainer Festo CPX-FEC IT and MPS PA Compact Workstation __ 49
5.3.6
EduTrainer Allen Bradley and MPS PA Compact Workstation_____ 52
5.4
Pneumatic connection __________________________________________ 55
5.5
Voltage supply ________________________________________________ 55
5.6
Adjusting sensors ______________________________________________ 56
5.6.1
Capacitive proximity sensor B113/B114 _______________________ 56
5.6.2
Float switch S111/S112/S117 _______________________________ 57
6.6.3
Ultrasonic sensor B101 _____________________________________ 58
5.7
Choosing controlled system _____________________________________ 59
5.8
Allocation list of inputs and outputs ______________________________ 61
5.9
Loading the PLC program________________________________________ 62
Contents
5.9.1
Siemens S7 300 CPU 313C __________________________________ 62
5.9.2
Festo FEC-CPX _____________________________________________ 63
5.9.3
Allen Bradley controller _____________________________________ 64
5.10
Filling and deaeration ________________________________________ 65
5.11
Start sequence S7 programm Level ___________________________ 66
5.12
Notice _____________________________________________________ 67
6 Maintenance ______________________________________________________ 69
7 Appendix _________________________________________________________ 71
Designation of equipment _____________________________________________ 71
Parts lists___________________________________________________________ 71
Process flowsheets___________________________________________________ 71
EMCS block diagrams_________________________________________________ 71
EMCS ______________________________________________________________ 71
Electrical circuit diagrams _____________________________________________ 72
Electropneumatic circuit diagrams ______________________________________ 72
Program listings _____________________________________________________ 72
Data sheets _________________________________________________________ 72
Introduction
The Festo Didactic Learning System for process automation and technology is
designed to meet a number of different training and vocational requirements. The
systems and stations of the MPS PA Compact Workstation facilitate industryorientated vocational and further training and the hardware consists of didactically
suitable industrial components.
The MPS PA Compact Workstation station provides you with an appropriate system
for practice-orientated tuition of the following key qualifications
Social competence,
Technical competence and
Methodological competence
Moreover, training can be provided to instill team spirit, willingness to cooperate
and organisational skills.
Actual project phases can be taught by means of training projects, such as:
Planning,
Assembly,
Programming,
Commissioning,
Operation,
Maintenance and
Trouble shooting.
Introduction
1.1
Training contents
Introduction
The basic requirement for safe use and trouble-free operation of the
1.2
Important notes
These operating instructions contain important notes concerning the safe operation
prevention and who have received instructions in the handling of the MPS PA
Compact Workstation,
have read and understood the chapter on safety and the cautionary notes in
these operating instructions and confirmed this by signing,
are regularly vetted to ensure safe working.
Prior to commencing work, all persons assigned to working on the MPS PA Compact
Workstation have a duty to:
1.4
Duty of trainees
observe the basic regulations regarding operational safety and the prevention of
accidents,
read the chapter on safety and the cautionary notes in these operating
instructions and to confirm that they have understood these by signing.
Introduction
1.5
Risks involved in dealing
Introduction
1.6
Warranty and liability
In principle all of our Terms and Conditions of Sale apply. These are available to
the operating authority upon conclusion of the contract at the latest. Warranty and
liability claims for persons or material damage are excluded if these can be traced
back to one or several of the following causes
Use of the machine not in accordance with its intended purpose
Incorrect assembly, commissioning, operation and maintenance of the machine
Operation of the machine using faulty safety equipment or incorrectly fitted or
non operational safety or protective devices
Non observance of notes in the operating instructions regarding transport,
storage, assembly, commissioning, operation, maintenance and setting up of the
machine
Unlawful constructional modifications on the machine
Inadequate monitoring of machine components subject to wear
Incorrectly carried out repairs
Catastrophes as a result of foreign objects and acts of force major.
Festo Didactic herewith rules out any liability for damage or injury to trainees, the
training company and /or other third parties which may occur during the use /
operation of the system other than purely in a training situation, unless such
damage has been caused intentionally or due to gross negligence by Festo Didactic.
1.7
Use for intended purpose
This system has been developed and produced exclusively for vocational and further
training in the field of automation and communication. The training authority and /
or the instructors is / are to ensure that trainees observe the safety precautions
described in the manual provided.
The use of the system for its intended purpose also includes:
following all advice in the operating instructions and
carrying out inspection and maintenance work.
Introduction
10
Notes on safety
General
Trainees must only work on the station under the supervision of an instructor.
Observe the data in the data sheets for the individual components, in particular
all notes on safety!
Electrics
Electrical connections are to be wired up or disconnected only when power is
disconnected!
Use only low voltages of up to 24 V DC.
The heating is using 230 V AC. Work on components using electrical connections
of 230 V AC must be carried out by qualified personnel. Please refer to safety
regulations for commissioning (DIN VDE 0113, EN 60204).
Pneumatics
Do not exceed the permissible pressure of 8 bar (800 kPA).
Do not switch on compressed air until you have established and secured all
tubing connections.
Do not disconnect air lines under pressure.
Particular care is to be taken when switching on the compressed air. Cylinders
may advance or retract as soon as the compressed air is switched on.
Mechanics
Securely mount all components on the plate.
No manual intervention unless the machine is at rest.
The pump can be mounted horizontally or vertically. If mounted, the ouput of the
pump must point upwards. The pump must be mounted so that is is flooded (see
also data sheet).
11
Notes on safety
Process engineering
Before filling the tanks with water switch of power supply!
Switch of power supply 24 VDC and 230 VAC (110 VAC)!
The use of tap water in quality of drinking water (recommended), ensures a
prolonged maintenance-free operation of the system (proportional valve and
pump).
The maximum operating temperature of the tanks must not exceed +65 C.
Do not operate the heating unit unless the heating element is fully immersed in
fluid.
Do not operate the piping system with a system pressure higher than 0,5 bar.
Do not operate the pump without fluid, running dry or used for sea water or
contaminated fluids.
Please empty fluids from the system (tanks, piping, close valves) before you
make changes at the piping system.
It is possible to drain the fluids inside the MPS PA Compact Workstation by
opening hand valve V105
Do not left the water inside the tanks for a longer time. It is possible, that
bacteria as legionella grow up, which can cause diseases.
12
Technical data
Parameter
Value
24 V DC
profile plate
700 x 700 x 32 mm
dimensions
Weight
(volumetric) flow rate of the pump
~5 l/min
tank volume
10 l max.
DN10 (a 15mm)
digital inputs
digital outputs
analog inputs
analog outputs
amount of tanks
voltage 0...10 V
2/2W-proportional valve
voltage 0...10 V
On/Off
(power 1000 W)
0...10 l mm
09 l
current 4...20 mA
0...7 l/min
0,3...9,0 l/min
frequence 0...1200 Hz
voltage 0...10 V
0...60 C
-50 C+150 C
resistance PT100
13
Technical data
14
Transport
15
16
The MPS PA Compact Workstation combines 4 closed-loops with digital and analog
sensors and actuators. With a PLC or a controller it is possible to use them
individually or cascaded:
17
18
The functions of each closed-loop system result in the specified combination of the
(manual-) valves. Also they depend on the programming, configuration or
parametrizing of the PLC/ controlling system.
19
4.1
Level monitoring
Following technical examples for level monitoring are integrated into the MPS PA
Compact Workstation:
proximity switches
float switch for overflow savety
float switch for threshold function
Proximity switches
Two capacitive proximity switches B113 (1) and B114 (2) are located on the side of
the lower tank B101 and mounted on a profile plate. The proximity switches can be
mechanically adjusted. The sensing distance through the tank wall can be adjusted
with a screw. The binary 24 V input signals are connected to the I/O-terminal XMA1.
The minimum level of the tank B101 is indicated by the lower sensor B113. At
minimum level the heating element E104 should be totally immersed into the liquid.
The maximum level of the tank B101 is indicated by the upper sensor B114.
At reset position of the system both sensors have to be activated.
20
The overflow at tank B101 is monitored with float switch S111 (1). If the level in the
tank exceeds the maximum level the transparent float cylinder is pushed upward.
Inside the float cylinder are magnets which activate a reed contact.
Overflow savety
The binary 24 V input signals (no) is connected to the I/O-terminal XMA1. The signal
of the overflow switch should activate a alarm function in the PLC-program and has
effect on ball valve V102 and pump P101.
If changed electrically the overflow switch also can be used to turn off the pump or
valve with a relay circuit or for signal indication to a emergency relay.
21
Threshold function
The increasing fluid level into the upper tank B102 is monitored at a certain
minimum level by float switch S112 (1). If the mounting position is changed the
switch can also indicate the decreasing level.
The binary 24 V input signals (nc) is connected to the I/O-terminal XMA1. The cable
of the switch has a plug connection for easy connect/disconnect on changing the
mounting position.
22
The float switch is monitoring the decreasing filling level in tank. It avoids continuing
heating if filling level undershoots the critical point. The heating must be
sourrounded completely by the fluid.
The cable of the switch has a plug connection and is connected directly to the
heating and to the connecting cable for the I/O- connecting board.
23
4.2
Pump
The centrifugal pump P101 (1) is the controlling equipment used in all controlled
systems. The pump is delivering fluid from a reservoir tank B101 through the piping
system.
The pump must not be operated running dry. Before commissioning the reservoir
tank or piping system to/from the pump should be filled with fluid.
The pump is driven by the motor controller A4 and relay K1. With a digital output
(O2 at XMA1) it is possible to switch from digital binary control to analog control
variable from 0 to 24 V. At digital binary control (O2 = 0) the pump is turn on/off
with a additional output (O3 at XMA1). At analog control (O2 = 1) the drive voltage
from analog output signal channel 0 (UA1 at X2) is setting the speed of the pump
from 0 to 10 V.
Please also see the data sheet of the pump for further savety instructions!
24
4.3
Proportional valve
The proportional valve V106 (1) is a directly actuated 2/2-way valve for flow control
of fluids. It can be used as a adjustable remote element in open- or closed-loops.
The valve pistons lifted of its seat as a function of the solenoid coil current and
releases the flow through the valve.
The control electronic of the proportional valve is activated with a binary output
(O4 at XMA1). A analog signal from channel 1 (UA2 at X2) is driving the signal input
of the proportional valve with a standard analog signal from 0 to 10 V.
The standard analog signal is transformed into a pulse-width modulation (PWM) and
the opening of the valve is infinitely adjustable. The frequence of the PWM can be
adapted for different valve types.
25
4.4
Heating
Heating
Notes on safety:
The maximum operating temperature of the tanks must not exceed +65 C.
Do not operate the heating unit unless the heating element is fully immersed in
fluid.
Critical temperature at the heat element: at temperature around 50-60 C the
heating is internal automatically switched off. If the temperature value drops
below 45 C the heating is switched on again.
Critical temperature at the micro controller of the heating: at a semiconductor
temperature of around 90C the heating is internal automatically switched off. If
the temperature value drops below 85 C the heating is switched on again.
26
MPS PA Compact Workstation the heating is controlled binary only. To use the
heating as a continous output element a pulse-width-modulation (PWM) is used.
The control is clocking the ON- and OFF- time of the heating. The time periode T is
constant (e.g. 10s). By changing the ON-time t1 of the heating the thermal power Q
is manipulated. Is the ON-time raised, also the thermal power is.
t1
t2
Key
t1
t2
T
Q
OFF-time
ON-time
time periode
thermal power
27
4.5
2W ball valve with
pneumatic rotary drive
The 2-way ball valve V102 is opened and closed by a pneumatical rotary drive. The
controlled equipment consists of a brass ball valve (1) with
rotary drive type SYPAR (4), using scotch yoke principle. A solenoid (2) 5/2 way
valve (3) with port pattern to NAMUR and sensor box (5) are flange mounted onto
the rotary drive. The flow of the fluid from upper tank B102 into the lower tank B101
is controlled with the ball valve of the rotary drive.
4
2
3
Key
1
2
3
4
5
The end position sensing attachment (5) consists of two electrical micro switches
with roller lever. The two binary 24 VDC signals (S115 and S116) are connected as
inputs to the I/O-terminal XMA1. There is also a visual indication of the drive
position for the operator.
28
4.6
Level control function
The function of the level controlled system is to regulate the filling level of a fluid in
a reservoir tank.
The controlled filling level system can be used as an I- or PT1 controlled system.
Controlled level system upper container B102 with ultrasonic sensor B101 (measuring point LIC B102)
29
LIC
B101
V102
B102
LA+
V112
S111
LSS112
LS+
B114
V101
B101
V110
LSB113
P101
V105
M
The pump P101 delivers a fluid from a storage tank B101 to a reservoir tank B102 (1)
via a piping system. The level of the fluid inside tank B102 is monitored with a
analog ultrasonic sensor B101 (2) at measuring point LIC B101 and read as actual
value. The actual value should be kept on a certain level also if disturbances or
set point changes occur. For function and characteristic curve of the ultrasonic
sensor please see data sheet.
The fluid quantity of the pump P101 can be a binary or manipulated value. For
controlling system a two-position or a continuous element can be used
(see also EMCS block diagrams).
For disturbance is it possible to partly or totally open/close the ball valve V102 to
drain the upper into the lower tank or open/close hand valve V104.
The analog current signal (4...20 mA) of the ultrasonic sensor is connected a as a
standard signal to analog terminal X2 (IE1) as channel 0. The current signal is
connected to the measuring transformer A1, too. The transformer changes the
analog current signal into a standard voltage signal (010 V). The standard voltage
signal is also connected to the analog terminal X2 (UE1).
30
4.7
Flow rate control function
In a piping system or a filter unit the flow velocity of a fluid shall be regulated.
The system used is a controlled system with self-regulation (P-controlled system). It
does not have a time delay. The control loop in combination with the pump (PT1
behaviour) creates a easily controllable system.
Controlled flow rate system pump P101 with flow sensor B102 (measuring point FIC B101)
The pump delivers a fluid from the reservoir via a piping system. The flow rate is
detected by means of an optoelectronic vane sensor B102 (2) in the form of an
actual value. The actual value should be kept on a certain flow rate also if
disturbances or set point changes occur.
For controlling system a continuous element can be used (see also EMCS block
diagrams). There are two operation modes:
flow rate control by the means of the pump P101 as controlled system.
Manipulated value is the voltage of the pump, which sets the revolution speed.
flow rate control by the means of the proportional valve V106 as controlled
system. Manipulated value is the voltage of the valve coil, which sets the stroke
of the valve piston. The pump P101 is running with a constant revolution speed.
For disturbance is it possible to partly or totally open/close the hand valve V104.
31
V104
LA+
S111
LS+
B114
V109
V106
LSV103
FIC
B113
B102
P101
V105
M
A steady square wave signal of the flow rate sensor is connected to a binary input at
I/O terminal XMA1 (I0).
Please see the manual of the PLC for maximum input frequency of binary inputs.
The signal level is depending on the applied supply voltage (8...24 V). The pulse
signal can be processed with a PLC with integrated counter inputs. The frequency
signal is connected to the measuring transformer A2, too. The transformer changes
the frequency signal into a standard voltage signal (010 V). The standard voltage
signal is also connected to the analog terminal X2 (UE2).
32
4.8
Pressure control function
Controlled pressure system pressure tank B103 with pressure sensor B103 (measuring point PIC B103)
Via a piping system, the pump P101 delivers a fluid from a resevoir into a gasprefilled pressure tank B103 (1). The pressure of the gas (air) in the pressure tank is
detected by means of a piezoresistive relative pressure sensor in the form of an
actual value. The actual value should be kept on a certain pressure also if
disturbances or set point changes occur.
Setup for controlling
As controlling system a continuous element can be used (see also EMCS block
diagrams). During control a pressure is build up and controlled from liquid to
gaseous medium in the pressure container B103. The amount of liquid inside of the
pressure tank can be increased by opening/closing of the exhaust valve V107 if the
pump P101 is running before using closed-loop control. It is recommended to setup
the water level of the pressure tank at half level with V107 for a opmtimal work
range during closed-loop control.
33
V107
PI
105
LA+
B102
S111
LSB103
S112
LS+
B114
V109
V108
B101
V110
V106
LSB113
PIC
B103
V103
P101
V105
M
34
2
1
Controlled temperature system reactor container B101 with temperatur sensor B104 (measuring point TIC B104)
The water in the reactor container B101 of the heat exchanger E104 is heated by
means of a heating element and is recirculated by means of the pump P101.
A PT100 sensor B104 (2) is used for measuring the system temperature at
measuring point TIC B104 in the form of an actual value. The actual value should be
kept on a certain temperature also if disturbances or set point changes occur.
35
V104
LA+
S111
LS+
B114
B101
LSTIC
S117
B104
E104
LSB113
P101
V105
M
The on/off switching period of the heating element E104, which is the manipulated
variable, determines the heat output of the heat exchanger. For controlling system a
two-point element can be used (see also EMCS block diagrams). For disturbance is it
possible to use cold fluid or (f.g. ice cubes) or mix with water from the upper tank.
The resistance of the temperature sensor is connected to the measuring transformer
A3. The transformer changes the resistance into a standard voltage signal 0 to 10 V.
The standard voltage signal is connected to the analog terminal X2 (UE4).
The heating is controlled by a internal relay. With a digital ouput (O1 at XMA1) the
relay can be switched on/off.
36
The connection board serves as an interface for analogue and digital input and
output signals. All analogue signals are converted into 0 - 10 V and applied to the
analogue terminal. Binary signals max. 8 inputs and 8 outputs per station are
applied to the I/O terminal. This ensures compatibility with EasyPort, SimuBox,
EduTrainern and PLC boards.
4.10
I/O-board
45
I/U
f/U
PT
100
/U
10
11 12
I/O-board
Mounting plate
I/O terminal (Syslink station): Connection of inputs, e.g. capacitive proximity sensor
and connection of outputs, e.g. pumps. Proportional valve, 2way-ball valve.
Relay K1: Control of the pump. If K1 is active, the pump can be controlled with a
continous manipulation voltage of 0-10V.
Measuring transducer I/U: signal of the ultrasonic sensor for level measurement will
be converted from 4-20 mA current signal into 0-10 V standard voltage signal.
Measuring transducer f/U: signal of the flow rate sensor for flow measurement will be
converted from a frequency rectangle-pulse signal into 0-10 V standard voltage
signal.
10
Staring current limiter: limits the maximum starting current of the motor controller to
prevent voltage drops at the controller.
37
4.11
Mouting frame
The mounting frame of the MPS PA Compact Workstation consists of a two-row ERframe for EduTrainers and a 19 base frame for 19 units. The ER frame can be used
for:
3 wide EduTrainer (h x w X d = 145 x 240 x 170 mm),
e.g. EduTrainer SIMATIC S7
1 small EduTrainer (H x B X T = 85 x 240 x 170 mm),
e.g. control panel
Mounting frame
The 19" control panel is suitable for following operation or indication units :
19 power supply 24 V DC/4,5A
19 control panel with 3 push buttons, 1 key switch and 4 indicator
19 Communication panels with 4 inputs and 4 outputs available at 4 mm safety
sockets (only use with 19 control panel)
19 EMERGENCY STOP panel
38
Commissioning
For running the MPS PA Compact Workstation all commissioning steps have to be
obeyed according to the rules of operation:
Commissioing
Visual check
Connect cables
Fill tank
Start controller
Choose setpoint
Run closed-loop
39
Commissioning
completely assembled
operationally adjusted
commissioned
tested
5.2
Visual check
40
Commissioning
5.3
Cable connections
5.3.1
All cable connections are described for a MPS PA Compact Workstation with
Simulationbox.
Simulation box D/A station: connect the Syslink plug of the simbox with the
XMA1 socket of the I/O terminal (2) of the station with a SysLink cable (3).
Simulation box D/A station: connect the analog plug of the simbox with the X2
socket of the analog terminal (4) of the station with analog cable (5).
Simulation box D/A power supply unit: connect 4 mm safety plugs (red and
blue) of the simbox and power supply unit with 4 mm safety plugs
cable (red = + / blue = ).
Notice
By using the crossover analoge cable with the simulation box only the first two
analog cannels (0 = Level; 1 = Flow) can be displayed.
41
Commissioning
3
5
X2
XMA1
2
1
Key
42
Analog terminal
24 V DC power supply
Commissioning
5.3.2
43
Commissioning
XMA1
X2
2.32
1
3
Key
44
Easyport USB
Analog terminal
24 V DC power supply
USB cable
Commissioning
5.3.3
45
Commissioning
6
7
8
3
XMA1
X2
4
5
1
3
Cable connections MPS PA Compact Workstation EduTrainer Compact with S7-300 CPU 313C
Key
Analog terminal
24 V DC power supply
Connector Syslink-cable on the right side of the control panel from the backside
46
Commissioning
5.3.4
47
Commissioning
6
7
X2
XMA1
4
5
1
3
Key
48
Logo EduTrainer
Analog terminal
24 V DC power supply
Commissioning
5.3.5
All cable connections are described as an example for a EduTrainer Festo CPX-FEC IT
with the Compact Workstation.
CPX-FEC station: connect the XMA plug of the PLC /controller with the XMA1
socket of the I/O terminal (2) of the station with a SysLink cable (3).
CPX-FEC station: connect the analog plug of the PLC /controller with the X2
socket of the analog terminal (4) of the station
with the analog cable (5).
CPX-FEC power supply unit: connect 4 mm safety plugs (red, blue and yellow) of
the PLC /controller to power supply unit
with 4 mm safety plugs cable (red = + / blue = /yellow = ground).
CPX-FEC PLC: Connect your PC to the PLC by means of a programming cable. For
usage of visualization please connect PLC and PC via Ethernet cable (crossover)
or connect both to an Ethernet switch or network.
49
Commissioning
Notice
50
Commissioning
8
6
9
5
3
Key
Analog terminal
24 V DC power supply
51
Commissioning
5.3.6
All cable connections are described as an example for an Allen Bradley controller
with the Compact Workstation.
PLC /controller station: connect the XMA plug (1/A) of the PLC /controller with
the XMA1 socket of the I/O terminal (2) of the station with a SysLink cable (3).
PLC /controller control console: connect the XMG plug (1/B) of the
PLC /controller with the X1 socket (4) of the control console (if available)
with with the corresponding data cable.
PLC /controller station: connect the analog plug (1/C) of the PLC /controller
with the X2 socket of the analog terminal (6) of the station
with a analog cable (7).
PC /controller PLC: Connect your PC to the PLC by means of an serial data cable
(9).
52
Commissioning
8
6
9
12
11
10
5
3
Key
Analog terminal
24 V DC power supply
10
11
12
53
Commissioning
AB
Allen-Bradley
Communication Cable connection between HMI PanelView Plus 600 and PLC Micrologix 1500
54
Commissioning
2
Panel View 600+ - back view
Base configuration unit with Ethernet port for communication to PLC (Compact
Logix)
5.4
Pneumatic connection
5.5
Voltage supply
The stations are supplied with 24 V DC voltage (max. 5 A) via a power supply
unit. Connect the 230 VAC shock proof plug of the power supply with the main
cable to the main power supply.
The voltage supply of the complete station is provided via the PLC or controller.
Heating element: Connect the 230 VAC shock proof plug of the power supply with
the main cable to the fast circuit breakter with main power supply.
55
Commissioning
5.6
Adjusting sensors
5.6.1
The two capacitive proximity sensors are used to determine liquid level in the lower
tank and are to be adjusted such as to enable the contactless sensing of the liquid in
the container, but not the wall of the container. The liquid changes the capacity of a
capacitor integrated into the proximity sensor.
Notes
The capacitive proximity sensors are used to sense the liquid level of both the lower
and upper liquid levels of the tanks.
Prerequisites
The tank and a profile for the attachment of the mounting bracket are assembled
The electrical connection of the capacitive proximity sensor is established
The power pack is switched on.
Procedure
1.
2.
3.
Mount the proximity sensors onto the mounting bracket so that they do not
touch the tank, each at a distance of 5 mm from the tank.
Fill the tank with liquid.
The proximity sensors are set at the following values:
2 l (bottom); 6 l (top)
Move the switches up or down until the switching status display (LED)
switches
on at the respective volume level.
Note
The proximity sensors must be triggered by the liquid in the tank. If there is no liquid
in the tank, there must be no signal available.
4. Check the positioning and setting of the proximity sensor by repeatedly filling
and emptying the tank.
56
Commissioning
5.6.2
The float switch is to be fitted into the tank. The float switch opens if the maximum
level of liquid in the tank is exceeded and switches off the pumps via the relay.
Prerequisites
The tank is mounted
Electrical connection of the float switch is established
The power pack is switched on.
Procedure
1.
The float switch is to be fed from the inside of the tank through the opening in
the tank cover an.d the screw tightened externally.
2. Connect the float switch. The switch must emit a signal without any liquid.
3. Fill the tank and establish whether the float switch interrupts the signal if the
maximum liquid level is exceeded. The float must turn upwards
4. Check the positioning and setting of the sensor by repeated filling and emptying.
Note
Make sure that the flow always moves freely and is not stuck due to dirt.
57
Commissioning
Procedure
The LED must be illuminated even if the level of liquid is minimal. The sensor must
be re-adjusted via the securing nuts if this is not the case.
Note
Make sure that the emitter side of the sensor is always clean.
58
Commissioning
59
Commissioning
Component
Level controlled
system
Flow controlled
system
with pump P101
for manip. value
Flow controlled
system
with valve V106
for manip. value
Pressure
control. system
with pump P101
for manip. value
Measuring point
Sensor
LIC102
B101
Pump
P101
controlling
element
controlling
element
digital On
controlling
Element
digital On
On
Prop. valve
V106
Off
Off
controlling
element
Off
controlling
element
Off
Heating element
Off
Off
Off
Off
Off
switched
FIC101
B102
Pressure
control. system
with valve V106
for manip. value
PIC103
B103
TIC104
B104
E104
Hand valve
Temperature
controlled
system
controll. element
open
closed
closed
closed
closed
closed
open/closed
closed
closed
closed
closed
closed
closed
closed
closed
open
closed
open
Hand valve
V104
closed
open
closed
closed
closed
closed
Drainage valve
V105
closed
closed
closed
closed
closed
closed
Hand valve
closed
closed
closed
closed
closed
closed
closed
closed
closed
open
open
closed
closed
closed
open
open/closed
open/closed
open
closed
closed
closed
closed
closed
closed
open/closed
closed
closed
closed
closed
closed
V101
Ball valve
V102
Hand valve
V103
V107
Hand valve
V108
Hand valve
V109
Hand valve
V110
Hand valve
V112
60
Commissioning
5.8
Allocation list of
inputs and outputs
Symbol
PIN
EasyPort/
PLC
assignment
Simbox
address
address
Descritption
I0
I0
S111
I1
I1
S112
I2
I2
B113
I3
I3
B114
I4
I4
S115
I5
I5
S116
I6
I6
I7
I7
Not used
O0
Q0
E104
O1
Q1
K1
O2
Q2
M1
O3
Q3
M106
O4
Q4
O5
Q5
Not used
O6
Q6
Not used
O7
Q7
Not used
UE1
AI 0
FIC B102
UE2
AI 1
PIC B103
UE3
AI 2
TIC B104
UE4
AI 3
P101
UA1
AQ 0
V106
UA2
AQ 1
61
Commissioning
5.9
Loading the PLC program
5.9.1
62
Commissioning
5.9.2
Festo FEC-CPX
63
Commissioning
5.9.3
64
Commissioning
5.10
Filling and deaeration
4.
5.
6.
7.
8.
9.
10.
11.
12.
Before filling the system with water close drainage valve V105.
Before filling the system with water close all hand valves
Switch of power supply!
Fill container only if power supply is switched off!
Water spray can cause short circuits.
Turn off compressed air supply!
Fill the lower tank B101 up to a water level of 10 l in quality of drinking water.
Fill up lower tank B101 with water until the upper capacitive sensor B114 is
activated. Float switch S111 for overflow safety function must not be activated!
Clear of water spray!
Switch on power supply 24 VDC.
Switch on pump P101 and pump water to the upper tank B102. Therefore open
hand valve V101 (or RESET and START program).
Close hand valve V101 and open hand valve V103 and prop. valve V106.
Close hand valve V103 and prop. valve V106.
Switch of pump P101 (or STOP program)
There will be loss of water in the piping system visible in the lower tank after
deaeration. Refill lower tank and compensate the water (as described in 5.).
65
Commissioning
5.11
Start sequence
S7 programm Level
not activated
activated
activated
not activated
16. Start the sequence of the MPS PA Compact Workstation. The start is prompted
by the illuminated START pushbutton and executed when the push button has
been actuated.
17. It program is started operation mode logic control is running and indicated
with light Q1.
18. The pump P101 delivers process fluid from the lower storage tank B101 into the
upper reservoir tank B102. As soon as the level rise up to the float switch B112
is activated the PLC is changing operation mode from logic control to close-loop
control. Light Q2 is indicating operation mode close-loop control. Filling level is
monitored with the ultrasonic sensor B102 (actual value) and controlled up to
the setpoint (fixed value at startup of PLC). If the water level has reached the
setpoint and the steady-state of e.g. bottling pressure is reached ball valve
V102 is opened time controlled. After bottling time t the ball valve V102 is
closed and once again the water level controlled to setpoint. After setpoint is
reached again another bottling process is started, etc.
19. The program is stopped automatically if the water level in the lower storage
tank is lower than the limit switch B113 (deactivated).
By pressing STOP pushbutton the ball valve V102 is closed and the pump P101
switched off. The sequence program is stopped.
66
Commissioning
5.12
Notice
67
Commissioning
68
Maintenance
69
Maintenance
70
Appendix
Designation of equipment
Parts lists
Process flowsheets
EMCS
71
Appendix
Electropneumatic circuit
diagrams
Program listings
S7 Symbols table
S7 Overview
S7 Sequential function chart
S7 Function block diagram
Data sheets
72