Abb Drive
Abb Drive
Please check the status in CDP, if it is showing Ready on, this means the
drive is ready for switched on.
If Ready On is not coming in CDP please check followings.
1. Ensure all the MCB/MPCB should be on.
2. The drive shall not be in fault/alarm condition.
3. The corresponding breaker of drive should be in service position, Spring
charge healthy, Trip circuit healthy, relay healthy.
4. The earthing switch should be in open condition.
5. The doors of converter and transformer section must be in closed.
Now Press the ON Push Button for energising the Drive, After Precharge completes the main breaker closed. Now the Drive status will be
updated to drive ready run from Ready to Switch ON.
Donts
The breaker of corresponding VFD should never close manually
(TNC/MANUAL) from 6.6KV Switchboard. There may be severe
damage occurred in the drive.
from Control
its discharge
earth switch
entire blower
Donts
1. Dont open the doors of converter and transformer section of drive when
the drive is energised condition and blowers are running condition.
2. Never switch of the control power during DC link Voltage (Earth switch
unlock indication not Glow) present in the drive.
POWER FAILURE.
1. In case of power failure first ensure all breaker must be opened and if not
opened then trip the breaker manually from 6.6Kv Switch-board.
2. Before restore power in the drive the control power must be recycled, if
the control power not recycled then the redundant fan may be operated.
FAULT EXAMPLE
Log
11
Log
12
Log
13
Log
14
Log
{0}
{1}FL.L1
1
{0}
{1}FL.L1
2
{0}
{1}FL.L1
3
{0}
{1}FL.L
14
{0}
15
Log
16
Log
17
Log
18
Log
19
Log
20
{1}FL.L1
5
{0}
{1}FL.L1
6
{0}
{1}FL.L1
7
{0}
{1}FL.L1
8
{0}
{1}FL.L1
9
{0}
{1}FL.L
20
15:33:29.7060
Active Fault INT2 VLU ShortCirc at 2015-05-22
15:33:29.7060
Active Fault INT1 VLU ShortCirc at 2015-05-22
15:33:29.7060
Active Fault INT3 VLU Control at 2015-05-22
15:33:29.7060
Active Fault INT2 VLU Control at 2015-05-22
15:33:29.7060
Active Fault INT1 VLU Control at 2015-0522 15:33:29.7060