T400 Ang Synch App Note
T400 Ang Synch App Note
SPA440
June 2000
Page 0
MASTERDRIVE T400
Application Guide #1
Angular Synchronization SPA440 with 6SE70, 6RA70
June 2000
June 2000
Page 1
2. Equipment Requirements:
2.1
2.2
2.3
2.4
2.5
2.6
June 2000
Page 2
Variable
On / Off Command
Off2
Off3
Setpoint Enable
Fault Acknowledge
Jogging 1
Jogging 2
External Fault 1
Speed Controller Enable
Speed Setpoint (see note1)
Suppl. Speed Setpoint from
Angular Controller
Pre-Control value for the
Speed Controller
Status Word 1
Speed Actual Value
Torque
Status Word 2
Drive Output Current
Word
Bit
W1.0
W1.1
W1.2
W1.6
W1.7
W1.8
W1.9
W1.15
W4.9
W2
W5
CUVC
Parameter
Value
P554
3100
P555
3101
P558
3102
P564
3106
P565
3107
P568
3108
P569
3109
P575
3115
P585
3409
P443
3002
P224
3005
DC-Master
Parameter
Value
P654
3100
P655
3101
P658
3102
P664
3106
P665
3107
P668
3108
P669
3109
P675
3115
P685
3409
P644
3002
P634
3005
W8
P262
3008
P501
3008
W1
W2
W3
W4
W5
P734.01
P734.02
P734.03
P734.04
P734.05
32
91
182
33
22
U734.01
U734.02
U734.03
U734.04
U734.05
32
40
142
33
116
Drive#2 will have the following Digital Inputs / Outputs available as default.
Terminal
46
47
48
49
51
Description
Output-Sychronism Reached
Output Angular Controller at limit
Output Enable Status of Ang. Contr.
Output - Fault
Output - Alarm
53
54
55
56
57
BICO Parameter
H631
H632
H633
H634
H635
Enable
H637
H638
H639
H640
N/A
June 2000
Page 3
Line Speed
Reference
CUV
C
T40
0
CUV
C
Drive #2
Encoder
Feedback
connection to
CUVC
Drive #2
Reference from
Drive #1
Drive
Drive
Drive
Drive
Drive
Drive
Drive
Drive
Description
#1 Encoder Feedback
#1 Encoder Feedback
#1 Encoder Feedback
#1 Encoder Feedback
Description
#2 Encoder Feedback
#2 Encoder Feedback
#2 Encoder Feedback
#2 Encoder Feedback
Description
T400 Terminal 66
T400 Terminal 62
T400 Terminal 63
T400 Terminal 64
Note that the T400 Terminals 85, 86 and 87 need to have an external jumper installed if
using Single-Ended Encoders. In the case of this Demo Unit, the jumpers did have to
be installed.
5. Ready to Start:
June 2000
Page 4
5.1 Power to the Drive#2 Demo Unit was cycled to ensure the parameter values
on the T400 card were updated.
5.2 Power to both Demo Units were restored.
5.3 Since this is a simulation, P554 on Drive#2 was changed to B0018 to allow
the slave drive to start and be ready for when the speed change was
detected on the Reference encoder.
5.4 Drive#1s motor was manually turned and the motor shaft on Drive#2 was
observed.
5.5 Drive#1 was started and the speed reference (speed pot#1) was adjusted.
5.6 If specific additional tuning was required refer to main instruction manual
contained on the 6SE70 VC Documentation CD, part number DRMS-02051
Version 3.0
Additional Notes:
Note#1: If H140 is set to 0 then the speed controller is active on the CUVC
board.
If H140 is set to 1, then the speed controller is active on the T400 board.