HVDC Protection System
HVDC Protection System
PROTE
CTION
SYSTE
M AND
ITS
DESIG
N
S.THIRUMAL
1.
2.
3.
4.
CONTENT
HVDC Protection Principle
Types of HVDC Protection
HVDS Protection SLD
HVDC Protection System
This is the mainly based to isolate the major equipment to remove the
Energized system in the HVDC also have similar kind of DC Instrument
Transformer and DC breakers and the Advanced protection systems.
The HVDC control and protection system is divided to two redundant systems A and B, based on
an Active Standby concept. Both systems include a complete set of control and protection systems.
Each protection system consists of both set1 and set2 protections.
As soon as a protection operates a fast changeover is executed from the active system to the
standby system, to ensure that the protection action is based on a correct external measurement. The
concept is equal for both the DC and the AC protections .
The protective scheme is designed to meet the following general requirements:
a. Fault or other abnormal conditions, that might expose the equipment to hazards are detected.
Also, the cause of an unacceptable disturbance should be detected and the faulty or
overstressed equipment should either be taken out of service or relieved from stresses in a
controlled
way.
b. The aim of the protection design is to detect every condition according to above with at least
two protective functions.
c. The protection setup should be arranged into overlapping protective zones. For each fault
case, there should be a fast main protection with a limited protective zone. The main
protective function should normally be supported with a slower or less sensitive backup
protective function. The backup
d. protective function should, if possible, be based on a different measuring principle and when
applicable, with a more extended protective zone. For those cases where the main/backup
philosophy can not be applied without difficulties, essential protective functions should be
doubled.
e. Steps shall be taken to minimize the possibility of a fault in one converter causing protective
f. actions in other converters.
g. The protection system shall be provided with recording facilities. All signals used by the
protection system shall be recorded and time marked. The recording facility shall always
h. save the latest event, even if there already are information stored.
i.
Where applicable, the alarm and trip references shall be set so as to give level and time
separated operation.
j.
The protection system shall be active/standby as long as the power supply is OK and there
is no fault on the system.
k. Tripping paths to the breaker should be redundant and fed by two different auxiliary
voltage supplies.
l.
The protections shall be arranged so that testing and maintenance can be carried out
without affecting the operation of the transmission.
Bipole aspects
The aim with the overall protection philosophy, especially for bipole related protective functions
shall be to avoid any undue bipole outage during any circumstances. Examples of possible faults and
disturbances
which shall be covered by the protection philosophy:
Common mode disturbances and faults e.g. in the AC system causing disturbances to both
poles.
DC side disturbances related to common bipole equipment i.e. the bipole neutral bus,
station ground, metallic return, electrode line/cable and transfer breakers.
Domino effect i.e. faults in one converter causing a protective action in the other
converter.
According to the above philosophy:
a) Protective functions related to equipment within a pole shall be separated between
a) the poles and have separate measuring devices.
b) There shall be a set of protective functions for equipment common for both poles in a
c) bipole, called bipole protections. Each pole shall have a separate set of bipole protections,
using separate measuring devices.
d) No protective function, pole related or bipole related, is allowed to trip the other pole in a
bipole.
e) There shall be no single protective actions for bipole related faults or disturbances which can
lead to a bipole outage.
f) A bipole related protective function should not initiate protective actions on a single criterion.
3. DC PROTECTIONS
Converter protections
with DC currents IDL and IDNE. During commutation failures the DC current is higher than the AC
conductor current, which is detected by the protection.
Back up UD Supervision
The back up UD supervision calculates the DC voltage out of UDI0 , , and the neutral bus
current IDNE. The calculated DC voltage is compared with the measured DC voltage and the
difference is used to detect and prevent transmission disturbances due to abnormal control or
measuring circuit conditions. The function is coordinated with the UD calculation in the control
system.
Thyristor monitoring
The thyristor valve monitoring system is a self supervising system. In every valve control
unit there is a function, detecting if the voltage is picked up within a specified time by the
corresponding thyristor. At the time the thyristor picks up the voltage an indication pulse IP is sent on
an optical fiber to the valve control. A failed thyristor does not pick up voltage and this condition is
detected.
system. It includes a theoretical model of the valve damping circuits, the arresters across the
valve and the valve reactor.
DC overcurrent protection
The DC overcurrent protection protects the valves and the converter equipment. The AC conductor
currents IVY and IVD, the neutral bus current IDNE and the cooling water temperature are
measured. The protection contains two parts, one for the overcurrent and the other for the thyristor
over temperature detection.
Pole protections
Figure-2
DC harmonic protection
DC harmonic protection detects abnormal harmonics in the converter current, generated at
control equipment malfunction or during valve and AC network disturbances. The direct current
is filtered for the fundamental and second harmonic frequencies.
DC differential protection
The protective zone of the DC differential protection is from the converter transformer secondary
bushings to the measurements of both the line and electrode currents, at the DC side of the converter.
To detect ground faults within the protective zone the direct currents IDL and IDNE are measured in
combination with the AC conductor currents IVY and IVD neutral bus currents IANC and ICN in
addition with the DC filter currents IF1 and IF2.
DC switchyard protections
Figure-3
The Station ground overcurrent protection protects the station ground, converter transformer and the
bus between the electrode line and the pole neutral bus.