Automatic Tuning Method For The Design of Supplementary Damping Controllers For Exible Alternating Current Transmission System Devices
Automatic Tuning Method For The Design of Supplementary Damping Controllers For Exible Alternating Current Transmission System Devices
org
Published in IET Generation, Transmission & Distribution
Received on 29th August 2008
Revised on 9th June 2009
doi: 10.1049/iet-gtd.2008.0424
ISSN 1751-8687
Electromechanical Engineering Department, Federal Technological University of Parana, CEP 85503-390, Pato Branco,
PR- Brazil
2
Engineering School of Sao Carlos, University of Sao Paulo, CEP 13566-590, Sao Carlos, SP- Brazil
E-mail: [email protected]
Abstract: The design of supplementary damping controllers to mitigate the effects of electromechanical oscillations
in power systems is a highly complex and time-consuming process, which requires a signicant amount of
knowledge from the part of the designer. In this study, the authors propose an automatic technique that takes
the burden of tuning the controller parameters away from the power engineer and places it on the computer.
Unlike other approaches that do the same based on robust control theories or evolutionary computing
techniques, our proposed procedure uses an optimisation algorithm that works over a formulation of the
classical tuning problem in terms of bilinear matrix inequalities. Using this formulation, it is possible to apply
linear matrix inequality solvers to nd a solution to the tuning problem via an iterative process, with the
advantage that these solvers are widely available and have well-known convergence properties. The proposed
algorithm is applied to tune the parameters of supplementary controllers for thyristor controlled series
capacitors placed in the New England/New York benchmark test system, aiming at the improvement of the
damping factor of inter-area modes, under several different operating conditions. The results of the linear
analysis are validated by non-linear simulation and demonstrate the effectiveness of the proposed procedure.
Introduction
www.ietdl.org
3. the action of the damping controllers must vanish in
steady state, so the controllers do not change the operating
point dened by the load ow;
4. a control structure based on dynamic output feedback
must be used due to difculties in obtaining measurements
of all state variables of the system;
5. whenever possible, it is preferable to use local control
input signals, because the use of remote signals generally
increases the cost of the control scheme [wide-area control
systems (WACS) have been recently proposed and are still
under development, but they are still not widely available
and satisfactorily reliable at a reasonable cost].
It is an usual practice to employ classical phase compensation
to design SDCs for FACTS devices. These controllers consist
basically of a static gain, a washout lter and a phase
compensation network [4]. Such a control structure satises
the requirements (iii)(v). However, in order to fulll the
requirements (i) and (ii), a careful selection of the phase
compensators has to be made, which is not a trivial task.
The experience accumulated over years of practice has
generated a number of guidelines for the selection of these
parameters. The rst widely used set of guidelines for this
purpose is reported in [5], and the application of them to
power system stabiliser (PSS) design is usually called a
tuning process. The advent of selective modal analysis [6],
and later on the introduction of residue analysis [7] and
induced torque coefcients [8] have signicantly improved
the efciency of the tuning methods. However, these
problems are still very difcult to handle, because they
involve several variables and degrees of freedom, and
therefore only highly skilled engineers are able to perform
an effective tuning of controller parameters for several
operating conditions.
A number of alternative techniques, based on robust control
theories, have been proposed to address these issues. H1 mixedsensitivity formulation [9] and regional pole placement using
linear matrix inequalities (LMIs) [1012] can be cited as
examples. These approaches generate very efcient
controllers, but most of them provide high-order controller
structures. The industry seems to prefer conventional phase
compensation structures, as several industry-based researchers
adopt them as their structures of choice ([13] is an example).
Based on this consideration, this paper proposes an
algorithm that aims at relieving the engineer in charge of the
controller design from the burden of the trial-and-error
process involved in this problem. The designer only has to set
up a proper range of controller parameters, based on welldened equations, and to supply this range as input data to
the algorithm, which then applies an iterative method (based
on the solution of LMIs) to nd an acceptable tuning
considering all the operating conditions of interest.
920
& The Institution of Engineering and Technology 2009
(1)
(2)
y~ h(~x, u~ , z, l)
(3)
(4)
yj C j xj Dj uj
(5)
www.ietdl.org
into a single one, given by
2
Ac1
^ ^
^
6 .
^
_
x c A c x c Bc y j 6
4 ..
(6)
0
gi
ai
6
x_ ci 4 gi ai bi
ai b2i bi gi
uji 0 0
gi bi gi
3
2 3
1
0
7
6 7
0 5xci 4 bi 5y ji (7)
g i
b2i
(8)
Ki xci
where
..
.
0
3
3
0
.. 7
. 7
5xc
Acnc
0
.. 7
. 7
5y j
Bcnc
2
3
0
C c1
^ ^
6 .
^
^
.. 7
..
.
uj C c x c 6
. 7
.
4 .
5xc
0 C cnc
Bc1
6 .
6
4 ..
0
..
.
(12)
(13)
Aj
A j 4 ^
BC C j
Bj C C
^
j CC
A C BC D
(14)
1
ai
,
Twi
T
bi 1i ,
T2i
1
gi
T2i
(9)
(10)
uji C ci xci
(11)
Since we have one set of Equations (10) and (11) for each
SDC, we can lump all these nc sets of equations (nc being
the number FACTS in the system equipped with SDCs)
IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 10, pp. 919 929
doi: 10.1049/iet-gtd.2008.0424
www.ietdl.org
as a search problem in Rcc Rcp Rqc , where
c c, c p and q c are, respectively, the dimensions of
^
Pj Pj 0
^ ^
^T ^
and P j A j Aj P j 0
^T
(15)
T
^ ^
^ ^
6 sin u Aj P j P j Aj
6
6
T
T
^ ^
^ ^
4
cos u Aj P j P j Aj
T
T
3
^ ^
^ ^
^ ^
^ ^
u
A
P
P
A
u
A
P
P
A
cos
sin
j j
j j
j j
j j 7
6
6
7
6
T
T
T
7 sI 0
^ ^
^ ^
^ ^
^ ^
4
5
cos u Aj P j P j Aj
sin u Aj P j P j Aj
(17)
Step 3: Check whether s , 0; if yes, stop; if not, freeze the
T
3
^ ^
^ ^
cos u A j P j P j Aj 7
7
T
70
^ ^
^ ^
5
sin u Aj P j P j Aj
P j P j 0 and (17);
Step 4: Check whether s , 0; If yes, stop; if not, return to Step 2.
(16)
The proof of this statement can be traced from [15, 16] and
will not be repeated here due to space limitations. The
existence of cross products between the entries of the matrix
variables makes this search problem quite complex, because
the set of feasible solutions to it is not convex. In the next
section, an algorithm to deal with this kind of search will be
depicted and tailored to the SDC parameter tuning problem.
www.ietdl.org
3.2 Dening the ranges of acceptable
SDC parameters
As previously mentioned, it is necessary to include additional
constraints to the search problem presented in Section 3.1 to
restrict the set of possible solutions to physically and
practically meaningful ones. The phase compensation range
that provides additional damping for a particular set of
electromechanical modes can be determined by means of
residue analysis [7] or induced torque coefcients [8], for
example. In this paper, we chose to apply the former,
although similar results could be achieved with the latter.
In order to enable the application of residue analysis, we
initially set the parameters ai and bi , i 1, . . . , nc,
appearing in (7), to constant, pre-determined values.
The determination of the values for parameters ai follows
well-known industry rules, since these parameters are related
to the washout lters as can be seen in (9) and dened
according to typical values used in most SDC and PSS
designs. Common values for the washout time constant are
in the range of 3 20 s [5], which leads to
ai ai
where ai
const
const ,
0:05 , ai
const
, 0:33
(18)
(19)
gi
min
, gi , gi
max
(20)
gi
max
p
vk bi
1 j vi bi g1
i min
arg
1 j vi g1
i min
wi
min
(22)
or, equivalently
min ) gi min(vi
vi bi ) v2i bi tan(wi
min )
(23)
The static gains Ki , i 1, . . . , nc, are then the only
remaining parameters in (7) and (8) to be constrained.
According to [19], using residue analysis it is possible to
calculate the gain Ki residue of an SDC as a function of the
desired location for the eigenvalue corresponding to lk by
Ki
residue
l
lk
k des
Ri HLD (lk )
(24)
HLD
sGwi
1 sGwi
1 sG1i
1 sG2i
n
(25)
min
, Ki , Ki
max
(26)
for i 1, . . . , nc.
With the xed values for ai and bi and the bounded ranges
for gi and Ki given by (20) and (26), respectively, the set of
feasible solutions to the SDC tuning problem is now closed
and practically meaningful, and therefore we are ready to
present our proposed algorithm to tune SDCs for FACTS
devices, which will be done in the next section.
(21)
www.ietdl.org
the maximum and minimum phase compensations wi
and wi min , i 1, . . ., nc, using residue analysis;
max
denite matrices P j , j 1, . . . , L;
^
T
T
3
^ ^
^ ^
^ ^
^ ^
cos u Aj P j P j Aj 7
6 sin u Aj P j P j Aj
6
7
6
T
T
T
7 sI 0
^ ^
^ ^
^ ^
^ ^
4
5
cos u Aj P j P j Aj
sin u Aj P j P j Aj
(27)
IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 10, pp. 919 929
doi: 10.1049/iet-gtd.2008.0424
www.ietdl.org
The results of the eigenvalue analysis show that two interarea modes are not adequately damped in all considered
operating conditions without the inclusion of SDCs, as can
be seen in Table 1. This table shows that modes 3 and 4
are well damped, while mode 1 is poorly damped in the
operating conditions from 7 a.m. to 10 p.m. Mode 2 is
poorly damped for all points in the entire load curve.
Table 1 Damping ratios (%) of inter-area modes for the system without the proposed SDCs
Hour (a.m.)
Inter-area modes
Hour (p.m.)
#1
#2
#3
#4
6.02
3.66
7.86
8.50
7.40
3.75
7.80
6.30
3.74
6.21
Inter-area modes
1
12
4.73
3.10
8.76
9.87
8.34
4.66
3.08
8.79
9.87
7.76
8.39
4.63
3.06
8.82
9.93
3.68
7.77
8.15
4.51
3.00
8.91
10.01
6.27
3.61
7.46
8.33
4.24
2.90
9.05
10.13
6.05
3.12
7.71
8.56
3.84
2.72
9.29
10.31
5.43
3.38
8.33
9.23
3.58
2.62
9.44
9.53
4.97
3.21
8.61
9.65
3.73
2.68
9.31
10.30
4.44
2.50
8.16
9.50
3.99
2.79
9.20
10.25
4.40
2.98
8.94
10.04
4.33
2.94
8.99
10.10
10
4.54
3.03
8.88
9.98
10
4.77
3.12
8.73
9.83
11
4.82
3.14
8.70
9.77
11
5.27
3.33
8.42
9.45
IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 10, pp. 919 929
doi: 10.1049/iet-gtd.2008.0424
925
www.ietdl.org
nearest decade, resulting in 21208 , wSDC_1 , 2608 and
21408 , wSDC_2 , 2808.
After that, the maximum allowed phase compensations
(w1 max 120 and w2 max 140) were employed to
calculate the bi parameters using (19), which resulted in
b1 0:072 and b2 0:031 . The bounds on the gi variables
were calculated from (21) and (23), using the frequencies of
the inter-area modes of interest in the operating point at
3 p.m. (which are, respectively, v1 4:63 rad/s and
v2 3:53 rad/s). The ranges 0:95 , g1 , 5:86 and
0:82 , g2 , 5:22 were obtained from these calculations.
Based on (24), and again using the data corresponding to
the operating point at 3 p.m., it was possible to conclude
and
that
gains
around
KSDC 1 1:28 p.u./p.u.
KSDC 2 0:41 p.u./p.u. would be necessary to provide a
damping ratio of 5% for the two inter-area modes of
interest, under these operating conditions. The maximum
values for the gains were set to be at most twice the values
given for the operating point at 3 p.m., and the minimum
values were set to at least half these values, resulting in
0:65 , KSDC 1 , 2:6 and 0:2 , KSDC 2 , 0:8, respectively.
The time constants of the washout lters were set as 10 s
for both SDCs (Twi 10, i 1, 2), so they do not
interfere signicantly with the phase compensation.
A minimum damping ratio of 5% for all modes in all 24
operating conditions was specied as the objective of the
tuning algorithm, which was performed using the mincx
solver (available in Matlab LMI Control Toolbox) in a
laptop with an Intel Dual Core 1.6 GHz processor and
1024 MB of RAM memory. The whole design process
took about 15 h and 20 min, nishing after four iterations.
Table 2 Damping ratios (%) of inter-area modes for the system with the designed SDCs
Hour (a.m.)
Inter-area modes
Hour (p.m.)
#1
#2
#3
#4
7.43
5.81
7.96
9.35
7.83
5.89
9.31
6.50
5.84
7.69
Inter-area modes
#1
#2
#3
#4
12
6.21
5.34
8.83
10.67
9.19
6.14
5.33
8.86
10.66
7.88
9.26
6.12
5.31
8.89
10.71
5.84
7.86
9.00
6.01
5.25
8.97
10.79
7.71
5.77
7.91
9.15
5.74
5.16
9.12
10.90
7.82
5.86
7.95
9.31
5.36
5.05
9.35
11.06
6.92
5.59
8.40
10.05
5.01
5.01
9.50
11.11
6.46
5.43
8.69
10.45
5.06
5.26
9.37
11.03
5.94
5.24
9.00
10.82
5.50
5.07
9.26
11.00
5.89
5.22
9.03
10.85
5.85
5.20
9.06
10.86
10
6.03
5.27
8.95
10.76
10
6.26
5.36
8.80
10.63
11
6.27
5.36
8.86
10.69
11
6.73
5.54
8.50
10.26
926
& The Institution of Engineering and Technology 2009
IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 10, pp. 919 929
doi: 10.1049/iet-gtd.2008.0424
www.ietdl.org
Figure 7 Comparative analysis between the SDCs from [21] and the ones tuned by the algorithm proposed in this paper
Figure 8 Operating conditions at 4 p.m.; solid line: system operating with SDCs; dashed line: without SDCs
It is important to remark that the best efforts of an
experienced designed could produce similar results in about
the same time taken by our procedure to tune the SDCs.
IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 10, pp. 919 929
doi: 10.1049/iet-gtd.2008.0424
www.ietdl.org
phase compensation for SDC tuning. The method chosen
for comparison was initially proposed for PSS design in
[10] and [11] and recently adapted to the design of SDCs
for FACTS devices in [21].
Fig. 7 presents this comparison, where it is possible to see
that, although the SDCs from [21] provide phase lead over
the entire range of possible electromechanical oscillations, they
do so at the expense of also providing large amplication of
signals in the high-frequency range. This is an important
drawback of the method proposed in [21], from the practical
viewpoint, since measurement noises and other highfrequency unmodelled dynamics will be substantially amplied
in the controller responses, deteriorating their performances.
In contrast, the SDCs tuned in this paper provide an
amount of phase compensation that is sufcient to enhance
the damping ratios of the electromechanical modes, and
their respective gains in the high-frequency range are
considerably lower than the ones of the controllers from
[21]. Given that both types of controllers fulll the desired
performance criterion and the ones tuned in this paper
have the mentioned practical advantage, the comparison is
clearly favourable to the controllers proposed in this paper.
Finally, to validate the conclusions taken from the linear
analyses and to ensure performance robustness for the
designed SDCs, non-linear simulations of the system
response to several perturbations were carried out. The
results of one of these simulations are shown in Fig. 8,
where a three-phase solid fault was applied to one of the
lines connecting buses 47 and 48, when the system
operates under the conditions corresponding to 4 p.m. in
Fig. 5. The fault was applied at t 2 s and lasted for
80 ms, being cleared by the disconnection of the faulted
line. Since the operating condition without this line was
not considered in the design stage, the good results shown
in Fig. 8 under these unpredicted conditions are an
indication that the controller performance is robust with
respect to variations in the operating point. Several other
simulations conrmed this statement.
Conclusions
Acknowledgment
References
928
& The Institution of Engineering and Technology 2009
IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 10, pp. 919 929
doi: 10.1049/iet-gtd.2008.0424
www.ietdl.org
[9] CHAUDHURI B., PAL B.: Robust damping of multiple
swing modes employing global stabilizing signals
with a TCSC, IEEE Trans. Power Syst., 2004, 19, (1),
pp. 499 506
[10] RAMOS R.A., ALBERTO L.F.C., BRETAS N.G.: A new methodology
for the coordinated design of robust decentralized power
system damping controllers, IEEE Trans. Power Syst.,
2004, 19, (1), pp. 444 454
[11] RAMOS R.A., MARTINS A.C.P., BRETAS N.G.: An improved
methodology for the design of power system damping
controllers, IEEE Trans. Power Syst., 2005, 20, (4),
pp. 1938 1945
[12] XUE C.F. , ZHANG X.P., GODFREY K.R.: Design of STATCOM
damping control with multiple operating points:
a multimodel LMI approach, IEE Proc. Gener. Transm.
Distrib., 2006, 153, (4), pp. 375 382
[13] KAMWA I., GRONDIN R., TRUDEL G.: IEEE PSS2B versus PSS4B:
the limits of performance of modern power system
stabilizers, IEEE Trans. Power Syst., 2005, 20, (2),
pp. 903 915
[14] ABDEL-MAGID Y.L., ABIDO M.A., AL-BAIYAT S., MANTAWY A.H. :
Simultaneous stabilization of multimachine power
systems via genetic algorithms, IEEE Trans. Power Syst.,
1999, 14, (4), pp. 1428 1439
Appendix
IET Gener. Transm. Distrib., 2009, Vol. 3, Iss. 10, pp. 919 929
doi: 10.1049/iet-gtd.2008.0424
SDC2 0:885
929