Design Air Systems
Design Air Systems
com/MANUALS/AIRSYSTEMDESIGN/DESIGNAIRSYST
EMS.HTM
A theoretical and practical guide to the basics of designing air flow systems.
1.
Air Flow
1.1. Types of Flow
1.2. Types of Pressure Losses or Resistance to Flow
1.3. Total Pressure, Velocity Pressure, and Static Pressure
2.
Air Systems
2.1. Fan Laws
2.2. Air Density
2.3. System Constant
3.
4.
5.
Pressure Calculations
5.1. Methodology
5.2. Assumptions and Corrections
6.
7.
8.
9.
Appendix 1 Equations
1. Air Flow
Flow of air or any other fluid is caused by a pressure differential between two points. Flow will originate from an area of
high energy, or pressure, and proceed to area(s) of lower energy or pressure.
P1
FLOW
P0
P1>P0
Duct air moves according to three fundamental laws of physics: conservation of mass, conservation of energy, and
conservation of momentum.
Conservation of mass simply states that an air mass is neither created nor destroyed. From this principle it
follows that the amount of air mass coming into a junction in a ductwork system is equal to the amount of air mass
leaving the junction, or the sum of air masses at each junction is equal to zero. In most cases the air in a duct is
assumed to be incompressible, an assumption that overlooks the change of air density that occurs as a result of
pressure loss and flow in the ductwork. In ductwork, the law of conservation of mass means a duct size can be
recalculated for a new air velocity using the simple equation:
V2 = (V1 * A1)/A2
Where V is velocity and A is Area
The law of energy conservation states that energy cannot disappear; it is only converted from one form to
another. This is the basis of one of the main expression of aerodynamics, the Bernoulli equation. Bernoulli's
equation in its simple form shows that, for an elemental flow stream, the difference in total pressures between any
two points in a duct is equal to the pressure loss between these points, or:
(Pressure loss)1-2 = (Total pressure)1 - (Total pressure)2
Conservation of momentum is based on Newton's law that a body will maintain its state of rest or uniform motion
unless compelled by another force to change that state. This law is useful to explain flow behavior in a duct
system's fitting.
Page 2
Only total pressure in ductwork always drops in the direction of flow. Static or dynamic pressures alone do not
follow this rule.
The measurement of the energy level in an air stream is uniquely represented by total pressure only. The
pressure losses in a duct are represented by the combined potential and kinetic energy transformation, i.e., the
loss of total pressure.
The fan energy increases both static and dynamic pressure. Fan ratings based only on static pressure are
partial, but commonly used.
Pressure loss in ductwork has three components, frictional losses along duct walls and dynamic losses in fittings
and component losses in duct-mounted equipment.
Component Pressure
Due to physical items with known pressure drops, such as hoods, filters, louvers or dampers.
Dynamic Pressure
Dynamic losses are the result of changes in direction and velocity of air flow. Dynamic losses occur whenever an air
stream makes turns, diverges, converges, narrows, widens, enters, exits, or passes dampers, gates, orifices, coils,
filters, or sound attenuators. Velocity profiles are reorganized at these places by the development of vortexes that
cause the transformation of mechanical energy into heat. The disturbance of the velocity profile starts at some
distance before the air reaches a fitting. The straightening of a flow stream ends some distance after the air passes
the fitting. This distance is usually assumed to be no shorter then six duct diameters for a straight duct. Dynamic
losses are proportional to dynamic pressure and can be calculated using the equation:
Dynamic loss = (Local loss coefficient) * (Dynamic pressure)
where the Local loss coefficient, known as a C-coefficient, represents flow disturbances for particular fittings or for
duct-mounted equipment as a function of their type and ratio of dimensions. Coefficients can be found in the
ASHRAE Fittings diagrams.
A local loss coefficient can be related to different velocities; it is important to know which part of the velocity profile
is relevant. The relevant part of the velocity profile is usually the highest velocity in a narrow part of a fitting cross
section or a straight/branch section in a junction.
Frictional Pressure
Frictional losses in duct sections are result from air viscosity and momentum exchange among particles moving
with different velocities. These losses also contribute negligible losses or gains in air systems unless there are
extremely long duct runs or there are significant sections using flex duct.
The easiest way of defining frictional loss per unit length is by using the Friction Chart (ASHRAE, 1997); however,
this chart (shown below) should be used for elevations no higher of 500 m (1,600 ft), air temperature between 5C
and 40C (40F and 100F), and ducts with smooth surfaces. The Darcy-Weisbach Equation should be used for
non-standard duct type such as flex duct.
Page 3
Page 4
Page 5
2. Air Systems
For kitchen ventilation applications an air system consists of hood(s), duct work, and fan(s). The relationship between
the air flow rate (CFM) and the pressure of an air system is expressed as an increasing exponential function. The graph
below shows an example of a system curve. This curve shows the relationship between the air flow rate and the
pressure of an air system.
Page 6
Fan Law 1
SP x
CFM2 x
RPM2x
------ = ------- = ------SP known CFM2known RPM2known
Fan Law 2
BHPx
CFM3x
RPM3x
------ = ------- =
------BHPknown CFM3known RPM3known
Fan Law 3
Other calculations can be utilized to maneuver around a fan performance curve. For example, to calculate BHP from
motor amp draw, use the following formula:
1 phase motors
BHP = V * I * E * PF
746
3 phase motors
BHP = V * I * E * PF * 1.73
746
where:
BHP = Brake Horsepower
V = Line Voltage
I = Line Current
E = Motor Efficiency (Usually about .85 to .9)
PF = Motor Power Factor (Usually about .9)
Once the BHP is known, the RPM of the fan can be measured. The motor BHP and fan RPM can then be matched on
the fan performance curve to approximate airflow.
Page 8
Gather input data: air flow, duct shape, duct size, roughness, altitude, air temperature, and fittings;
The following is a simple example of how duct pressure accumulates and is totaled in a section.
Page 9
3.3. System
Effect
Page 10
The diagrams below show system effect factors for straight through elements and turning elements. For rectangular
ductwork, D = (2HW)/(H+W). The following formula should be used to calculate the pressure caused by system effect:
Turning Elements
The following diagrams show proper and improper methods of constructing ductwork:
Page 11
t loss
+ P v system outlet + (P
s system outlet
) =0
v entry
v system outlet
outlet
- P v discharge
P s fan = P t loss
For exhaust system: P v system outlet = P v discharge
For Supply Systems with resistance on the outlet side, the fan static pressure is:
Page 12
5. Pressure Calculations
5.1. Methodology
Break the system into sections.
A new section occurs at:
1) Changes in duct size.
2) Change in air volume
Calculate losses for each section.
Begin at the section farthest from the fan and work towards the fan. For each section:
1.
2.
3.
Sum up the Component, Dynamic, and Frictional Pressure for the section.
4.
Page 13
Section 1
Air Flow Rate Q = 4000 cfm
Cross-Sectional Area A = 10 x 36/144 = 2.5 ft2
Center Line Distance L = 2 + 6 = 8
Velocity V = 4000/2.5 = 1600 ft/min
Velocity Pressure = Pv1 = (V/4005)2 = (1600/4005) 2 = 0.16
Loss Calculations
Component Losses
Hood Loss
Phood1 = -0.688
Look up from manufacturer hood static pressure curves. Here is a link to the Hood Static Pressure Calculator.
Frictional Losses
Use the Friction Chart to look up the pressure loss per 100 ft of duct.
Pfr1 = -(.16/100 ft) * (8) = -0.013
Dynamic Losses
Mitered Elbow. Look up Fitting 3-6 in Appendix 2 - ASHRAE Fittings. The dynamic coefficient C0 = 1.3
Pelbow1 = - Pv1 = -(1.3)*(0.16) = -0.208
Bullhead Tee. Look up coefficient from Appendix 3 - Bullhead Tee Curves.
Page 14
Since Section 1 has a larger duct size, this section is the u side of the bullhead tee. The following describes
how to use the bullhead tee curves to find Ku for the u side of the bullhead tee.
Since AU /AD = (10x36)/(20x30) = .6, we find the bullhead tee curves for which AU /AD is .6 and the y-axis
represents KU.
We know that Qb /Q D = 4000/(4000+3400) = .54. For simplicity and ease of graphing, we round .54 to the
nearest 10th giving us .5.
We also know that Ab /AD = (10x30)/(20x30) = .5.
Equipped with these ratios, can draw a line from the point on the x-axis where Q b /Q D is .5 up to where it
intersects the curve for which Ab /AD is .5
We find Ku = 1.6
NOTE: Due to human error resulting from manually graphing the value of KU , the number you graph may be
slightly different than the value show above. The important thing is to know how to use the curves and get a
reasonable value for KU.
Now we can calculate the pressure drop contributed by the bullhead tee for Section 1:
Pbulltee1 = -Ku * Pv1 = -(1.6)*(0.16) = -0.256
The total pressure loss for Section 1 is:
P t loss 1 = Phood1 + Pfr1 + Pelbow1 + Pbulltee1
P t loss 1 = -0.688 -0.013 -0.208 -0.256 = -1.165
Section 2
Air Flow Rate Q = 3400 cfm
Cross-Sectional Area A = 10 x 30/144 = 2.1 ft2
Center Line Distance L = 2 + 7 = 9
Velocity V = 3400/2.1 = 1619 ft/min
Velocity Pressure = Pv2 = (V/4005) 2 = (1619/4005) 2 = 0.16
Loss Calculations
Component Losses
Hood Loss
Phood2 = -0.688
Frictional Losses
Use the Friction Chart to look up the pressure loss per 100 ft of duct.
Pfr2 = -(.18/100 ft) * (9) = -0.016
Dynamic Losses
Mitered Elbow. Look up Fitting 3-6 in Appendix 2 - ASHRAE Fittings.
The dynamic coefficient C0 = 1.3
Pelbow2 = - Pv2 = -(1.3)*(0.16) = -0.208
Bullhead Tee. Using the methodology described for the bullhead tee in Section 1, we can find the value of the
coefficient, Kb, for the b side of the bullhead tee. Use the bullhead tee curves for which AU /AD is .6 and the yaxis represents Kb.
We find that Kb = 1.75 and the resulting pressure loss is:
Pbulltee 2 = -Kb * Pv2 = -(1.75)*(0.16) = -0.280
Page 15
Balance by Design
Note that the pressure loss of Section 2 is greater than the loss of Section 1. To balance the system by design
increase the air flow rate in Section 1 to bring it up to the higher pressure loss of Section 2.
To correct the air flow rate for Section 1 use the Fan Laws:
Q 1 new = Q 1 old * (P t loss 1 new / P t loss 1 old)1/2
Q 1 new = 4000 * (1.192/1.165) 1/2 = 4046 cfm
Section 3
Air Flow Rate Q = 3400 cfm + 4046 cfm = 7446 cfm
Cross-Sectional Area A = 20 x 30/144 = 4.17 ft2
Center Line Distance L = 9
Velocity V = 7446/4.17 = 1785 ft/min
Velocity Pressure = Pv3 = (V/4005) 2 = (1785/4005) 2 = .20
Loss Calculations
Component Losses
None
Frictional Losses
Use the Friction Chart to look up the pressure loss per 100 ft of duct.
Pfr2 = -(.15/100 ft) * (9) = -0.014
Dynamic Losses
None
Total pressure loss for Section 3 is:
P t loss 3 = Pfr3
P t loss 3 = -0.014
Page 16
Section 1
There is no change.
P t loss 1 = -1.165
Section 2
Air Flow Rate Q = 3000 CFM
Cross-Sectional Area A = 10 x 30/144 = 2.1 ft2
Center Line Distance L = 2 + 7 = 9
Velocity V = 3000/2.1 = 1429 ft/min
Velocity Pressure = Pv2 = (V/4005) 2 = (1429/4005) 2 = 0.13
Loss Calculations
Component Losses
Hood Loss. Use the Fan Laws to calculate a new Hood Loss or look it up in the Hood S.P. chart.
Phood2 = -(0.688)*((3000 CFM)2/(3400 CFM)2)
Phood2 = -0.536
Frictional Losses
Use the Friction Chart to look up the pressure loss per 100 ft of duct.
Pfr2 = -(.15/100 ft) * (9) = -0.014
Dynamic Losses
Mitered Elbow. Look up Fitting 3-6 in Appendix 2 - ASHRAE Fittings.
The dynamic coefficient C0 = 1.3
Pelbow2 = - Pv2 = -(1.3)*(0.13) = -0.169
Bullhead Tee. Since Section 2 is the b side, we use the set of bullhead tee curves for which AU /AD is .6 and
the y-axis represents Kb.
We find that Kb = 1.65
Pbulltee 2 = -Kb * Pv2 = -(1.65)*(0.13) = -0.215
Total Section Loss:
P t loss 2 = Phood2 + Pfr2 + Pelbow2 + Pbulltee2
P t loss 2 = -0.536 -0.014 -0.169 -0.215 = -0.93
Using the Fan Laws to calculate the new total pressure loss for Section 2:
P t loss 2 = -(1.192)*((3000 CFM)2/(3400 CFM)2) = -0.93
Balance by Design
Note that the pressure loss of Section 1 is now greater than the loss of Section 2. To balance the system by
design we must increase the air flow rate in Section 2 to bring it up to the higher pressure loss of Section 1.
To correct the air flow rate for Section 2 use the Fan Laws:
Q 2 new = Q 2 old * (P t loss 2 new / P t loss 2 old)1/2
Q 2 new = 3000 * (1.165/0.93) 1/2 = 3357 CFM
Section 3
Page 17
Loss Calculations
Component Losses
None
Frictional Losses
Use the Friction Chart to look up the pressure loss per 100 ft of duct.
Pfr2 = -(0.14/100 ft) * (9) = -0.013
Dynamic Losses
None
Using the Fan Laws to calculate the new total pressure loss for Section 3:
P t loss 3 = -(0.014)*((7357 cfm) 2/(7446 cfm) 2) = -0.013
Page 18
The first part of the problem will show the pressure gains obtained from measuring the total pressure at 3 points shown in the
diagram above. It will provide some rules of thumb for estimating pressure for elbow and at the supply collar. The second
part of the problem will calculate the pressure gain of the system and compare it to the measured pressure gain.
The entire system satisfies the definition of a section since there are no junctions or duct size changes. The transitions off the
supply collars can be included in the section.
Point 3
after 2nd elbow
(in. wg)
0.260
0.910
How high air velocities greatly increase the pressure. When the air flow rate is raised to 1920 cfm, the
velocity through the duct about doubles and the pressure increases 3-1/2 fold.
The system effect of having 2 elbows close to each other and being close to the hood.
Using the pressure gains for 1000 cfm flowing through the system, we see that the pressure gain for the
first elbow is: 0.14 - 0.075 = 0.065. This reflects the system effect of having an elbow close to the
supply opening of a hood.
The pressure gain for the second elbow is: 0.26 - 0.14 = 0.12. This reflects the system effect of having
two elbows within close proximity to one another and being close to the hood.
Page 19
3)
Loss Calculations
Component Losses
Hood. Assume 1/16 pressure gain at the collar.
P hood = 0.063
Frictional Losses
Use the Friction Chart to look up the pressure loss per 100 ft of duct.
Pfr = -(0.095/100 ft) * (15) = 0.014
Dynamic Losses
12x 20 to 10 x 16 Rectangular Transition
Use ASHRAE fitting 5-1 in Appendix 2 ASHRAE Fittings.
To find the dynamic coefficient we calculate:
/2 = tan -1(2/6) = 18o Therefore: = 36 o
A0 / A1 = (12x20)/(10x16) = 1.5
Therefore C0 = 0.05
P trans1 = C0Pv1 = (0.05)(0.055) = 0.003
10x 16 Rectangular to 14 Round Transition
Use ASHRAE fitting 4-6 in Appendix 2 ASHRAE Fittings.
B = W/H(A0 / A1 )2 = (16/10)(1.069/1.111)2 = 1.48
Re = 8.56DV = (8.56)(14)(935 ft/min) = 11205
Therefore Re x 10-4 = 11. Use the value for Re x 10-4 = 10
L/D is not relevant in this case.
C0 = 0.11
P trans2 = C0Pv1 = (0.11)(0.055) = 0.006
Two 90 Radius Elbows
Use ASHRAE fitting 3-2. Assume a 3 piece elbow.
Assume r = 10. So, r/D = 10/14 = .71 therefore K = 1.
C0 = 0.54
o
Page 21
9. Appendix 1 - Equations
Total Pressure (P T)
P T = P v+ P s
P v = Velocity Pressure
P s = Static Pressure
Velocity Pressure (P v)
P v = (V/1097)2
For standard air P v equals:
P v = (V/4005) 2
V = Velocity through the duct.
A
0.0425
b
0.0465
c
0.602
0.0307
0.0311
0.533
0.604
0.612
0.639
Page 22
Fitting 3-6
Page 23
Fitting 3-14
Page 24
Fitting 4-6
Fitting 5-1
Page 25
Page 26
Au/Ad = 0.2, Ku
Page 27
Au/Ad = 0.3, Kb
Page 28
Au/Ad = 0.3, Ku
Page 29
Au/Ad = 0.4, Kb
Page 30
Au/Ad = 0.4, Ku
Page 31
Au/Ad = 0.5, Kb
Page 32
Au/Ad = 0.5, Ku
Page 33
Au/Ad = 0.6, Kb
Page 34
Au/Ad = 0.6, Ku
Page 35
Au/Ad = 0.8, Kb
Page 36
Au/Ad = 0.8, Ku
Page 37
Au/Ad = 1.0, Kb
Page 38
Au/Ad = 1.0, Ku
Page 39
Page 40