Voltage Control Scheme Using Fuzzy Logic
Voltage Control Scheme Using Fuzzy Logic
I. INTRODUCTION
raditionally, the distribution network of the power system
is a passive network with a radial configuration.
Electricity flows one way from a substation to a large
distribution network. During normal operation or planning
period, a steady-state analysis of voltage regulation, system
losses, protection coordination, power quality, and system
reliability must be performed to ensure proper operation
within appropriate operating voltage range. Each utility has its
own operation and planning criteria depending on distribution
system characteristics and design criteria.
Currently, in Saudi Arabia, the exploitation of solar energy
as an alternative source of electric power is being considered
because of the abundant amount of irradiation and long hours
of sunshine. One way to achieve this is by using GridConnected
Photovoltaic systems (GCPV) on domestic dwellings directly
connected to the distribution network. This means that in the
2010 IEEE
1/
Bus#1
| |
12
Bus#2
Where:
cos
cos
(1)
sin
sin
(2)
| |
(5)
TABLE I
From Bus
To Bus
Lenghth (m)
Impedance (/km)
ISK11
I1
1875
0.128+j0.1344
I1
I2
15
0.128+j0.1344
I2
I3
327
0.128+j0.1344
I3
I4
153
0.128+j0.1344
I4
I5
513
0.128+j0.1344
I5
I6
396
0.128+j0.1344
I6
I7
132
0.128+j0.1344
I7
I8
648
0.128+j0.1344
I8
I9
255
0.128+j0.1344
Fig. 3 shows the average daily load profile for this area
during each month. This area includes 5000 residential
properties.
Average Daily load for a residential Area
Jan
100.0
90.0
Peak Load
Feb
Mar
Laod (MW)
80.0
Apr
70.0
May
60.0
Jun
50.0
Average Load
Aug
40.0
Sep
30.0
Oct
20.0
10.0
Jul
Nov
Dec
Light Load
0.0
Average
8 10 12 14 16 18 20 22 24
Time (hour)
There are 6 load nodes tapped off from each feeder. Each
branch is equipped with on-load tap changing transformer
(LTCT) that has the ability of changing the voltage level of
the branch at the main substation bus in small steps (0.5% of
nominal voltages), adjusted by the automatic voltage
controller (AVC). The main branches can be interconnected
through normally-open circuit breakers in the case of outage
of one of the 110/11 kV transformers.
Since this study is concentrating on the effect of GCPV on
the voltage regulation in the network under normal operation
(no faults), the longest branch which is ISK11 will be the most
sensitive because it will have the largest variations for the
different load and irradiation scenarios. The line parameters of
this branch are shown in Table I.
A.
Load Conditions
Real load data for the selected residential area has been
collected from the Saudi Electricity Company in the Western
Region (SEC-WR) who has also provided details of the
transformers and lines of the network. Based on this
information a detailed model of the distribution network has
been created in ETAP.
Feb
Mar
Apr
Minimum Midday
Radiation
May
Jun
Jul
Aug
No Radiation
Sep
Oct
Nov
8 10 12 14 16 18 20 22 24
Dec
Time (hour)
Fig 4. Monthly average solar radiation, Jedddah 2002.
Voltage % of Nominal
Solar Radiation(W/m^2)
1100
1000
900
800
700
600
500
400
300
200
100
0
I1
I2
I3
I4
I5
I6
I7
I8
I9
Upper limit
Lower Limit
3
4
5
6
Customer Nodes
Fig. 5.Voltage profile of all feeders co
onnected to ISK11 branch.
TABLE II
ALNPV
Average
No
98.19
+22.0%
+2.5%
ALAPV
Average
Min
100.12
00.0%
0.0%
ALMPV
Average
Max
102.71
-22.5%
-2.5%
XLNPV
Extreme
No
94.39
+55.0%
+5.0%
XLAPV
Extreme
Min
96.51
+33.5%
+2.5%
XLMPV
Extreme
Max
99.33
+00.5%
0.0%
LLNPV
Light
No
99.56
+00.5%
0.0%
LLAPV
Light
Min
101.43
-11.5%
-2.5%
LLMPV
Light
Max
103.94
-44.0%
-5.0%
NLMPV
No
Max
104.35
-44.5%
-5.0%
PLNPV
Peak
No
96.32
+33.5%
+5.0%
PLAPV
Peak
Min
98.34
+22.0%
+2.5%
PLMPV
Peak
Max
101.04
-11.0%
0.0%
R1LNPN
Random1
No
97.48
+22.5%
+2.5%
R1LAPV
Random1
Min
99.44
+00.5%
0.0%
R1LMPV
Random1
Max
102.07
-22.0%
-2.5%
R2LNPV
Random2
No
96.92
+33.0%
+2.5%
R2LAPV
Random2
Min
98.91
+11.0%
0.0%
R2LMPV
Random2
Max
101.58
-11.5%
-2.5%
R3LNPV
Random3
No
97.33
+22.5%
+2.5%
R3LAPV
Random3
Min
99.31
+00.5%
0.0%
R3LMPV
Random3
101.95
-22.0%
-2.5%
106
105
104
103
102
101
100
99
98
97
96
95
94
Voltage % of Nominal
Max
I1
Centralized
system
+5.0%
+2.5%
Avr V
Fuzzy Logic
Controller
Tap position
0.0%
-2.5%
Average Voltage
+5.0%
I2
I3
I4
I5
I6
I7
I8
I9
Upper limit
Lower Limit
Voltage % of Nominal
Customer Nodes
Fig. 6. Voltage profile of XLNPV scenario with prefferred position of tap
106
105
104
103
102
101
100
99
98
97
96
95
94
I1
I2
I3
I4
I5
I6
I7
I8
I9
Upper limit
Lower Limit
3
4
5
6
Customer Nodes
Fig. 7. Voltage profile of LLMPV scenario with preferrred position of tap
TABLE IV
POWER FLOW MEASUREMENTS @ ISK11 FOR
F
SCENARIOS USING ETAP
mentation of FLC
Fig. 10. Output membership function for 1st implem
Numerical
Fuzzy
94
95
96
97
98
Scenario
P@ISK11(kW)
Q@ISK1
11(kVar)
Preferred tap
ALNPV
805
479
+2.5%
ALAPV
-915
486
0.0%
ALMPV
-3382
638
-2.5%
XLNPV
2444
1549
+5.0%
XLAPV
-670
1480
+2.5%
XLMPV
-1859
1540
0.0%
LLNPV
200
99
0.0%
LLAPV
-1502
130
-2.5%
LLMPV
-3946
315
-5.0%
NLMPV
-4134
208
-5.0%
PLNPV
1619
1004
+5.0%
PLAPV
-127
974
+2.5%
PLMPV
-2624
1082
0.0%
R1LNPN
1122
691
+2.5%
R1LAPV
-609
683
0.0%
R1LMPV
-3088
818
-2.5%
R2LNPV
1327
824
+2.5%
R2LAPV
-411
805
0.0%
R2LMPV
-2899
927
-2.5%
R3LNPV
1168
720
+2.5%
R3LAPV
-565
709
0.0%
R3LMPV
-3046
841
-2.5%
+5.0%
+2.5%
P @ ISK11
Q @ ISK11
Fuzzy Logic
Controller
Tap position
0.0%
-2.5%
+5.0%
where:
1) The membership of input and output
o
signals:
Input1: Reactive power (Q) @ ISK11; extreme and peak
load high Q (HL), average load medium Q (ML) and
light load light Q (LL) as shown in
n Fig.13.
mentation of FLC
Fig. 14. Input membership function 2 for 2nd implem
Output: Tap changer setting (TC); Very Highh (VH), High (H),
Normal (N), Low (L), Very low (VL) as show
wn in Fig.15.
[2]
5.0%
2.5%
0.0%
2010
470
-1070
-2.5%
1400
-4150
1550
950
1250
1100
650
800
350
[4]
[5]
[6]
-2610
500
50
200
-5.0%
[3]
Fig. 16. Fuzzy Logic set for LTC based on powerr flow @ ISK11
Raed A. Shalwala
a received the B.S. degree from
King AbdulAziz Un
niversity, Jeddah, Saudi Arabia,
in 2002 and the M.S.
M
degree from University of
Nottingham, Nottin
ngham, U.K., in 2006, both in
electrical engineerin
ng. He is currently pursuing the
Ph.D. degree at Un
niversity of Leicester, Leicester,
U.K.
His research interessts are in power system planning
and operation, ren
newable energy resources and
distribution network
k.
Johannes (Hans) Bleijs
B
received his MSc degree in
Electrical and Electronic
E
Engineering from
Eindhoven Univeersity of Technology, The
Netherlands, in 198
82. In 1983 he joined Imperial
College in London as
a a Research Associate working
on integration off wind turbines with diesel
generators. He wass awarded a PhD degree from
Imperial College in 1990. Since 1991 he has been a
Lecturer in Electricaal Engineering in the Department
of Engineering at th
he University of Leicester, where
he teaches Electrical Machines and Power Systems. His field of research
covers a wide range of subjects in Renewablee Energy Conversion and Energy
Storage, from electrical generators and pow
wer electronics to power systems
and advanced controllers.