Chapter 5.2r PDF
Chapter 5.2r PDF
N-S
section
60 m
NE-SW
section
36 m
NW-SE
section
60 m
45 m
60 m
85 m
Lu = 36 m. x = 10 m.
H
0.83
2 Lu
10
M h ,S 1 0.711
1.68
240
(Equation 4.4(3))
Lu = 45 m. x = 16 m.
H
0.67
2 Lu
M h, SE 1 0.711
1.66 (Equation 4.4(3))
240
Lu = 85 m. x = 15 m.
H
0.35
2 Lu
60
15
M h ,SW 1
1
1.47 (Equation 4.4(2))
3.54.35 30.6 306
V500
(m/s)
45
45
45
45
45
45
45
45
Md
Mz,cat
Ms
Mt
Vsit, (m/s)
0.90
0.80
0.80
0.80
0.85
0.95
1.00
0.95
0.91
0.91
0.91
0.91
0.91
0.91
0.91
0.91
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.47
1.68
1.66
1.0
1.0
36.9
32.8
32.8
48.2
58.5
64.6
41.0
38.9
East wall.
As windward wall (east wind direction):
Cfig (external) = +0.7 (1.0) (1.0) = 0.7
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (48.2)2 (0.7)(1.0) = 976 Pa = 0.98 kPa
Cfig (internal) = -0.3 (1.0) = -0.3
pint = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (48.2)2 (-0.3)(1.0) = -418 Pa = -0.42 kPa
Net pressure across wall surface = 0.98-(-0.42) = 1.40 kPa
As side wall north wind direction:
For first 4.35 m from north edge:
Cfig (external) = -0.65 (1.0) (1.0) = -0.65
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (38.9)2 (-0.65)(1.0) = -590 Pa = -0.59 kPa
Cfig (internal) = 0.0 (1.0) = 0.0
pint = 0 kPa
Net pressure across wall surface = -0.59 kPa (ignore - leeward wall case governs)
For 4.35 m to (9.75-4.35=)5.4 m from north edge of west wall:
Cfig (external) = -0.5 (1.0) (1.0) = -0.5
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (38.9)2 (-0.5)(1.0) = -454 Pa = -0.45 kPa
pint = 0 kPa
Net pressure across wall surface = -0.45 kPa (ignore - leeward wall case governs)
As side wall south wind direction:
For first 4.35 m from south edges :
Cfig (external) = -0.65 (1.0) (1.0) = -0.65
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.65)(1.0) = -1628 Pa = -1.63 kPa
pint = 0 kPa
Net pressure across wall surface = -1.63 kPa (acting outwards)
As leeward wall west wind direction:
Cfig (external) = -0.3 (1.0) (1.0) = -0.3
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.3)(1.0) = -751 Pa = -0.75 kPa
pint = 0 kPa
Net pressure across wall surface = -0.75 kPa (acting outwards)
West wall.
As windward wall (west wind direction):
South wall.
As windward wall (south wind direction):
Cfig (external) = +0.7 (1.0) (1.0) = 0.7
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (0.7)(1.0) = 1753 Pa = 1.75 kPa
Cfig (internal) = -0.3 (1.0) = -0.3
pint = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.3)(1.0) = -751 Pa = -0.75 kPa
Net pressure across wall surface = 1.75-(-0.75) = 1.50 kPa
As leeward wall (north wind direction):
Cfig (external) = -0.3 (1.0) (1.0) = -0.3
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (38.9)2 (-0.3)(1.0) = -272 Pa = -0.27 kPa
pint = 0 kPa
Net pressure across wall surface = -0.27 kPa (ignore - side wall case governs)
As side wall west wind direction:
For first 4.35 m from west edge:
Cfig (external) = -0.65 (1.0) (1.0) = -0.65
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.65)(1.0) = -1628 Pa = -1.63 kPa
pint = 0 kPa
Net pressure across wall surface = -1.63 kPa (acting outwards)
Roof
north wind direction
north roof slope (surface 8).
Cfig (external) = -0.59 (1.0) (1.0) = -0.59
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (38.9)2 (-0.59)(1.0) = -536 Pa = -0.54 kPa
Cfig (internal) = 0.0 (1.0) = 0.0
pint = 0 kPa
Net pressure across roof surface = -0.54-(0.0) = -0.54 kPa
South roof slope (surface 9) and hip end (surface 7).
Cfig (external) = -0.5 (1.0) (1.0) = -0.5
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (38.9)2 (-0.5)(1.0) = -454 Pa = -0.45 kPa
pint = 0 kPa
pint = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.3)(0.8) = -601 Pa = -0.60 kPa
Net pressure across roof surface = +0.20-(-0.60) = +0.80 kPa
(note use of Kc equal to 0.8 in this case)
west wind direction
west roof slopes (surfaces 7 and 11).
Cfig (external) = -0.59 (1.0) (1.0) = -0.59
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.59)(1.0) = -1477 Pa = -1.48 kPa
pint = 0 kPa
Net pressure across roof surface = -1.48-(0.0) = -1.48 kPa
crosswind roof slopes (surfaces 8 and 9).
For first 4.35 m
Cfig (external) = -0.9 (1.0) (1.0) = -0.9
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.9)(1.0) = -2253 Pa = -2.25 kPa
pint = 0 kPa
Net pressure across roof surface = -2.25-(0.0) = -2.25 kPa
For 4.35 m to 8.7m from windward edge
Cfig (external) = -0.5 (1.0) (1.0) = -0.5
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.5)(1.0) = -1252 Pa = -1.25 kPa
pint = 0 kPa
Net pressure across roof surface = -1.25-(0.0) = -1.25 kPa
For 8.7 m to 13.05 m from windward edge
Cfig (external) = -0.3 (1.0) (1.0) = -0.3 (negative case)
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.3)(1.0) = -751 Pa = -0.75 kPa
pint = 0 kPa
Net pressure across roof surface = -0.75-(0.0) = -0.75 kPa
Cfig (external) = +0.1 (1.0) (1.0) = +0.1 (positive case)
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (+0.1)(0.8) = +200 Pa = +0.20 kPa
Cfig (internal) = -0.3 (1.0) = -0.3
pint = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.3)(0.8) = -601 Pa = -0.60 kPa
Net pressure across roof surface = +0.20-(-0.60) = +0.80 kPa
For 13.05 m to 24 m from windward edge
Cfig (external) = -0.2 (1.0) (1.0) = -0.2 (negative case)
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.2)(1.0) = -501 Pa = -0.50 kPa
pint = 0 kPa
Net pressure across roof surface = -0.50-(0.0) = -0.50 kPa
Cfig (external) = +0.2 (1.0) (1.0) = +0.2 (positive case)
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (+0.2)(0.8) = +401 Pa = +0.40 kPa
Cfig (internal) = -0.3 (1.0) = -0.3
pint = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.3)(1.0) = -751 Pa = -0.75 kPa
Net pressure across roof surface = +0.40-(-0.75) = +1.15 kPa
east roof slopes (surface 10).
Cfig (external) = -0.5 (1.0) (1.0) = -0.5
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.5)(1.0) = -1252 Pa = -1.25 kPa
pint = 0 kPa
For windows less than 1.44 m2 in area on east and west walls within a distance of 1.2 m
from south corners, and on north and south walls within a distance of 1.2 m from west
corners:
Cfig (external) = -0.65 (1.0) (2.0) = -1.3 (negative case)
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-1.3)(1.0) = -3255 Pa = -3.26 kPa
pint = 0 kPa
Net pressure across window = -3.26-(0.0) = -3.26 kPa
For windows (or doors) more than 1.44 m2 in area on north wall:
Cfig (external) = +0.7 (1.0) (1.0) = +0.7 (positive case)
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (38.9)2 (+0.7)(1.0) = +636 Pa = +0.64 kPa
Cfig (internal) = -0.3 (1.0) = -0.3
pint = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (38.9)2 (-0.3)(1.0) = -272 Pa = -0.27 kPa
Net pressure across window = +0.64-(-0.27) = +0.91 kPa
For windows (or doors) more than 1.44 m2 in area on east wall:
Cfig (external) = +0.7 (1.0) (1.0) = +0.7 (positive case)
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (48.2)2 (+0.7)(1.0) = +976 Pa = +0.98 kPa
Cfig (internal) = -0.3 (1.0) = -0.3
pint = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (48.2)2 (-0.3)(1.0) = -418 Pa = -0.42 kPa
Net pressure across window = +0.98-(-0.42) = +1.40 kPa
For windows (or doors) more than 1.44 m2 in area on south and west walls:
Cfig (external) = +0.7 (1.0) (1.0) = +0.7 (positive case)
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (+0.7)(1.0) = +1753 Pa = +1.75 kPa
Cfig (internal) = -0.3 (1.0) = -0.3
pint = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.3)(1.0) = -751 Pa = -0.75 kPa
Net pressure across window = +1.75-(-0.75) = +2.50 kPa
For windows up to 5.76 m2 in area on east and west walls within a distance of 2.4 m from
north corners:
Cfig (external) = -0.65 (1.0) (1.5) = -0.975 (negative case)
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (38.9)2 (-0.975)(1.0) = -885 Pa = -0.89 kPa
pint = 0 kPa
Net pressure across window = -0.89-(0.0) = -0.89 kPa
For windows up to 5.76 m2 in area on north and south walls within a distance of 2.4 m
from east corners:
Cfig (external) = -0.65 (1.0) (1.5) = -0.975 (negative case)
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (48.2)2 (-0.975)(1.0) = -1359 Pa = -1.36 kPa
pint = 0 kPa
Net pressure across window = -1.36-(0.0) = -1.36 kPa
For windows up to 5.76 m2 in area on east and west walls within a distance of 2.4 m from
south corners, and on north and south walls within a distance of 2.4 m from west corners:
Cfig (external) = -0.65 (1.0) (1.5) = -0.975 (negative case)
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.975)(1.0) = -2441 Pa = -2.44 kPa
pint = 0 kPa
Net pressure across window = -2.44-(0.0) = -2.44 kPa
For any other windows or doors, loads for major framing members apply.
Design loadings for roof cladding and battens (ultimate limit states)
(note: for permissible stress design divide loads by 1.5)
For roof cladding elements less than 1.44 m2 in area, on roof surface 8, up to 1.2 m from
east edge of roof:
Cfig (external) = -0.9 (1.0) (2.0) = -1.8
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (48.2)2 (-1.8)(1.0) = -2509 Pa = -2.51 kPa
pint = 0 kPa
Net pressure across element = -2.51-(0.0) = -2.51 kPa
For roof cladding elements less than 1.44 m2 in area, on roof surfaces 8 and 10, up to 1.2
m from the north-east corner of roof:
Cfig (external) = -0.59 (1.0) (3.0) = -1.77
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (48.2)2 (-1.77)(1.0) = -2467 Pa = -2.47 kPa
pint = 0 kPa
Net pressure across element = -2.47-(0.0) = -2.47 kPa
For roof cladding elements less than 1.44 m2 in area, on roof surfaces 8 and 9, up to 1.2 m
from west edge of roof, and on roof surfaces 10 and 11, up to 1.2 m from south edge of
roof :
Cfig (external) = -0.9 (1.0) (2.0) = -1.8
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-1.8)(1.0) = -4507 Pa = -4.51 kPa
pint = 0 kPa
Net pressure across element = -4.51-(0.0) = -4.51 kPa
For roof cladding elements less than 1.44 m2 in area, on roof surfaces 8 and 9, up to 2.4 m
from the north west or south west corners of the roof, and on roof surfaces 10 and 11, up
to 2.4 m from the corners on the south side of the roof :
Cfig (external) = Cp,e Kc,e K = -0.9 (1.0) (3.0) = -2.7
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-2.7)(1.0) = -6761 Pa = -6.76 kPa
pint = 0 kPa
Net pressure across element = -6.76-(0.0) = -6.76 kPa
For roof cladding elements less than 5.76 m2 in area, on roof surfaces 8 and 9, up to 2.4 m
from east edge of roof:
Cfig (external) = -0.9 (1.0) (1.5) = -1.35
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (48.2)2 (-1.35)(1.0) = -1882 Pa = -1.88 kPa
pint = 0 kPa
Net pressure across element = -1.88-(0.0) = -1.88 kPa
For roof cladding elements less than 5.76 m2 in area, on roof surfaces 8 and 9, up to 2.4 m
from west edge of roof, and on roof surfaces 10 and 11, up to 2.4 m from south edge of
roof :
Cfig (external) = -0.9 (1.0) (1.5) = -1.35
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-1.35)(1.0) = -3380 Pa = -3.38 kPa
pint = 0 kPa
Net pressure across element = -0.81-(0.0) = -3.38 kPa
For roof cladding elements less than 1.44 m2 in area, on roof surface 8, up to 1.2 m from
north edge of roof :
Cfig (external) = -0.59 (1.0) (2.0) = -1.18 (negative case)
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (38.9)2 (-1.18)(1.0) = -1071 Pa = -1.07 kPa
pint = 0 kPa
Net pressure across element = -1.07-(0.0) = -1.07 kPa
For roof cladding elements less than 1.44 m2 in area, on roof surface 7, up to 1.2 m from
west edge of roof, and on roof surface 9, up to 1.2 m from south edge of roof :
Cfig (external) = -0.59 (1.0) (2.0) = -1.18 (negative case)
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-1.18)(1.0) = -2955 Pa = -2.95 kPa
pint = 0 kPa
Net pressure across element = -2.95-(0.0) = -2.95 kPa
For roof cladding elements less than 5.76 m2 in area, on roof surface 8, up to 2.4 m from
north edge of roof :
Cfig (external) = -0.59 (1.0) (1.5) = -0.89 (negative case)
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (38.9)2 (-0.89)(1.0) = -808 Pa = -0.81 kPa
pint = 0 kPa
Net pressure across element = -0.81-(0.0) = -0.81 kPa
For roof cladding elements less than 5.76 m2 in area, on roof surface 7, up to 2.4 m from
west edge of roof, and on roof surface 9, up to 2.4 m from south edge of roof:
Cfig (external) = -0.59 (1.0) (1.5) = -0.89
pext = (0.5 air) Vdes,2 Cfig Cdyn = (0.5)(1.2) (64.6)2 (-0.89)(1.0) = -2228 Pa = -2.23 kPa
pint = 0 kPa
Net pressure across element = -2.23-(0.0) = -2.23 kPa
Loading on battens should be applied as moving patch loads with a tributary area equal
to the batten spacing times truss rafter spacing, with the appropriate local pressure factor
for that area. For example, in this case, if the batten spacing is 0.6 m, the tributary area
would be 1.2 0.6 = 0.72 m2. Since this area is less than 0.25a2, the local pressure
factor could be 1.0, 1.5 or 2.0, depending on the distance of the centre of the patch from
the roof edge.
Over the remainder of the batten, K should be taken as 1.0; i.e. the
loading should be the same as used for major structural members.