CIRED2015 0415 Final
CIRED2015 0415 Final
Ignaz HBL
KNG-Krnten Netz GmbH Austria
[email protected]
ABSTRACT
This paper describes a new digital sensitive method for
the directional detection of ground faults in resonantgrounded or isolated networks. The method evaluates the
transient response which occurs due to the state change
after the ground fault ignition.
In the past such methods were implemented in an analog
way, with disadvantages like limited sensitivity, no fault
recordings and others. The analog implementation was
caused by the fact that the frequency range of the
transient response is large, including frequencies up to
approximately 4 kHz (for the charging oscillation). Such
high signal frequencies require a respectively high
sampling frequency by the protection device which was
usually not available in the past. With constantly
increasing performance of modern digital protection
devices such high sampling frequencies are now possible,
allowing the implementation of fully digital algorithms
for the directional detection of transient ground faults.
The basis of the direction determination is the evaluation
of the discharging and charging oscillation of the
networks capacitance to ground, which occurs during the
first ms after the fault entry. However, due to the
frequency range and the energy content mainly the
charging oscillation of the sound phases is taken into
account.
The criterion for direction determination is the active
energy of the zero sequence system during the transient
response. By means of the sign of the active energy the
fault direction is determined. Especially for high
resistance ground faults the new method shows a
significant better sensitivity compared to analog methods
which depend only on comparing the signs of neutral
voltage and current.
The new method was tested and verified under different
conditions. Since static testing is not applicable due to
the required dynamic processes, different testing
approaches were chosen.
Testing was carried out a) by means of dynamic
simulations of the transient response, b) by use of ground
fault recordings from the field and c) finally by a
prototype application under real conditions in a meshed
110 kV network.
By the integration of this transient ground fault detection
method into a modern digital multifunctional protection
device all advantages of such a device (e.g. high sampled
fault recording) are provided, as well as the option for
CIRED 2015
Klaus BHME
Siemens AG Germany
[email protected]
INTRODUCTION
Various methods are being used for the detection of
ground faults in resonant-grounded or isolated networks.
The simplest method evaluates the zero sequence voltage
U0 (displacement voltage) or the zero sequence current
3I0. With these methods, only the detection of a ground
fault is possible. The localization of the fault via the
direction is not possible. Extension of the method to
include evaluation of the phase difference between U0
and 3I0 makes it possible to obtain the direction of the
ground fault; e.g. the watt-metric ground fault detection
falls into this category. With such methods it is only
possible to determine the ground fault direction under
stationary fault conditions, as the direction measurement
requires steady state values. In the event of nonstationary ground faults of short duration, it is not
possible to obtain the direction by evaluation of the phase
angle difference. Consequently, other methods based on
the transient ground fault signals are applied, e.g. the
transient ground fault method used in the device 7SN60.
During a ground fault in a system with compensated star
point grounding, the transient ground fault effect is
present during the initial ms of the fault. This is caused
by the discharge of the line capacitance in the faulted
phase, and the charging of the capacitance in the sound
phases [1][2]. These are then followed by the fault
extinction or the steady state fault current and voltage.
The transient ground fault effect is typically only of a
short duration (a few ms to a few network periods). The
duration is primarily dependent on the system
capacitance, the type of fault (high resistance, low
resistance) and the duration of the fault. Low resistance
faults are easier to detect than high resistance faults and
generally dont present any problems to the measuring
methods. The new directional transient ground fault
function evaluates this transient ground fault effect within
a short interval after the ground fault ignition and
determines the fault direction also in the event of highresistance faults.
The algorithm described here and tested in operation
significantly increases the sensitivity e.g. as compared
1/5
MEASURING PRINCIPLE
The measuring principle evaluates the signals in a short
interval after the ground fault ignition. At this point, the
signal components resulting from charging and
discharging the ground capacitance of the network are of
particular interest. The discharge oscillation (frequency
range 500 Hz to 1000 kHz) in the faulted phase typically
ends within the first cycle of the charging oscillation. The
charging oscillation (frequency range 70 Hz to 4 kHz) in
the sound phases typically terminates within the first
power system frequency cycle [3]. The discharge
oscillation can therefore not be reliably detected, even
with relatively high sampling rates (e.g. 8 kHz). The
charging oscillation on the other hand can reliably be
measured with higher sampling rates (e.g. 8 kHz). An
important feature of these charging and discharging
cycles is that they are resistive and dependent on the fault
direction. This characteristic was already used by analog
transient ground fault relays to determine the fault
direction [2]. After detecting the fault ignition, the ground
current and displacement voltage are evaluated to
determine if they are in-phase or in other words have the
same sign or not. This is done in a small time window
following the instant of detecting the fault ignition. If the
signs are not equal the fault is in the forward direction
and alternatively the fault is in reverse direction.
This principle has been applied for a number of decades
and provides reliable results for faults with low resistance
(see Figure 1). The reason for this is that the resistive
current components (charging of the network
capacitance) dominate compared to the static ones in
systems with resonant grounded star point these are
shifted by approx. 90. Using this, the co-phase or
opposite phase condition of the zero sequence current and
zero sequence voltage will reliably determine the fault
direction. In the case of high resistance faults (see Figure
2) on the other hand, the static component is dominant.
As a result there is only a small phase shift between the
charging transient and the static component.
During high resistance ground faults the transfer of
CIRED 2015
p0 (k ) = u0 (k )i0 (k )
(1)
2/5
pa ( k ) =
1
p0 (k ) dt
T k T
(2)
E0 (k ) = pa (k ) dt
(3)
+E0>
Tmax
unknown
-E0<
forward
CIRED 2015
3/5
Testing Methodology
The new measuring method was developed and tested
using approximately 200 fault recordings from a medium
voltage ring network N1 (Figure 4) and simulation data
from a radial network. The fault recordings have a high
sampling rate and were classified according to the fault
nature, so that they were suitable for the tests. The
implementation was done in a prototype, which had to
detect all the faults correctly. The prototype performance
was permanently compared with the MATHLAB
simulation during the entire testing process. The resulting
prototype was then installed in network N2.
110 kV
20 kV
Y
Y
Infeed
BB1
Y
Y
Infeed
BB2
BB=busbar
BB1
BB2
Coupling,
Normaly open
BB
BB
Closed ring
BB
Closed ring
CIRED 2015
SUMMARY
Simulation results
The network N2 that was used for testing is shown in
Figure 6. It was transferred into a simulation. This
allowed further investigation of the transient ground fault
function. Of particular interest is the boundary presented
by the detection of high resistance ground faults. For this
purpose the fault location and the fault resistance can be
varied.
REFERENCES
[1] Gernot Druml, 2012, Innovative Methoden zur
Erdschlussortung und Petersen-Spulen Regelung,
Dissertation TU Graz, Graz, Austria, 19-27
[2] Ungrad, Winkler, Wiszniewski, 1991, Schutztechnik
in Elektroenergiesystemen, Springer-Verlag, Berlin
Heidelberg, Germany, 16-19, 165-167
[3] H.
Pundt,
1965,
"Untersuchung
der
Ausgleichsvorgnge
bei
Erdschlu
in
Energieversorgungsnetzen", Energietechnik 15. Jg.,
Heft 10, 469-477
[4] Tengg, Schoa, Schmaranz, Marketz, Druml, 2011,
"Neue Erdschluss-Ortungsverfahren im Praxistest",
ETG-Fachtagung Sternpunktbehandlung
CIRED 2015
5/5