MPC
MPC
Features
Maintenance personnel can open station for inspection and
address setting without causing an alarm condition.
Built-in bicolor LED, which is visible through the handle of
the station, flashes in normal operation and latches steady
red when in alarm.
Handle latches in down position and the word ACTIVATED
appears to clearly indicate the station has been operated.
Captive screw terminals wire-ready for easy connection to
SLC loop (accepts up to 12 AWG/3.25 mm wire).
Can be surface mounted (with SB-10 or SB-I/O) or semiflush mounted. Semi-flush mount to a standard singlegang, double-gang, or 4" (10.16 cm) square electrical box.
Smooth dual-action design.
Meets ADAAG controls and operating mechanisms guidelines (Section 4.1.3[13]); meets ADA requirement for 5 lb.
maximum activation force.
Highly visible.
Attractive shape and textured finish.
Key reset.
Includes Braille text on station handle.
Optional trim ring (BG12TR).
Meets UL 38, Standard for Manually Actuated Signaling
Boxes.
Up to 99 S464G1007 stations per loop on CLIP protocol
loops.
Up to 159 S464G1007 stations per loop on FlashScan
protocol loops.
Dual-color LED blinks green to indicate normal on
FlashScan systems.
Construction
Shell, door, and handle are molded of durable polycarbonate
material with a textured finish.
Specifications
The S464G1007
Addressable Manual Pull Station
Installation
The S464G1007 will mount semi-flush into a single-gang, double-gang, or standard 4" (10.16 cm) square electrical outlet
box, or will surface mount to the model SB-10 or SB-I/O surface backbox. If the S464G1007 is being semi-flush mounted,
then the optional trim ring (BG12TR) may be used. The
BG12TR is usually needed for semi-flush mounting with 4"
(10.16 cm) or double-gang boxes (not with single-gang boxes).
Operation
Pushing in, then pulling down on the handle causes it to latch
in the down/activated position. Once latched, the word ACTIVATED (in bright yellow) appears at the top of the handle,
while a portion of the handle protrudes from the bottom of the
station. To reset the station, simply unlock the station with the
key and pull the door open. This action resets the handle; closing the door automatically resets the switch.
Each manual station, on command from the control panel,
sends data to the panel representing the state of the manual
switch. Two rotary decimal switches allow address settings
(1 159 on FlashScan systems, 1 99 on CLIP systems).
Architectural/Engineering
Specifications
Manual Fire Alarm Stations shall be non-coded, with a keyoperated reset lock in order that they may be tested, and so
designed that after actual Emergency Operation, they cannot
be restored to normal except by use of a key. An operated station shall automatically condition itself so as to be visually
detected as activated. Manual stations shall be constructed of
red-colored polycarbonate material with clearly visible operating instructions provided on the cover. The word FIRE shall
appear on the front of the stations in white letters, 1.00 inches
(2.54 cm) or larger. Stations shall be suitable for surface
mounting on matching backbox SB-10 or SB-I/O; or semi-flush
mounting on a standard single-gang, double-gang, or
4" (10.16 cm) square electrical box, and shall be installed
within the limits defined by the Americans with Disabilities Act
(ADA) or per national/local requirements. Manual Stations
shall be Underwriters Laboratories listed.
Manual stations shall connect with two wires to one of the control panel SLC loops. The manual station shall, on command
from the control panel, send data to the panel representing the
The loop poll LED shall be clearly visible through the front of
the station. The LED shall flash while in the normal condition,
and stay steadily illuminated when in alarm.
This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific
applications or anticipate all requirements. All specifications are subject to change without notice.
FlashScan is a trademark and Eclipse is a registered trademark of Honeywell International Inc.
2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.