Refrigerant Inventory TechNote
Refrigerant Inventory TechNote
August 2004
2004
Class I refrigerants are pure component or mixtures of chlorofluorocarbons (CFCs). Class II refrigerants
are pure component or mixtures of hydrochlorofluorocarbons (HFCs).
2004
Technically, section (d)(2)(C) of the PSM Standard requires maintaining estimates of the maximum
intended inventory. For refrigeration, the process is closed so that the system inventory is synonymous
with maximum intended inventory. However, the maximum intended inventory of individual components is
important and useful information as input to process hazards analyses.
2004
44
43
42
20F subcooling
41
Saturated liquid
30F subcooling
10F subcooling
40
39
38
37
36
-40
-20
20
40
60
80
100
2004
0.7
Anydrous Ammonia
0.6
0.5
Saturated vapor
0.4
10F Superheat
0.3
0.2
20F Superheat
0.1
0
-40
-20
20
40
60
80
100
Anhydrous ammonia
1000
100
10
-40
-20
20
40
60
80
100
2004
A corollary to density is its inverse, specific volume. The specific volume represents the volume
of a substance occupied by a unit mass (ft3/lbm). Because the density of refrigerant in a vapor
state can be quite small, specific volume is often used as an alterative measure to establish the
relationship between the refrigerants volume and mass.
What can we conclude from looking at the density of anhydrous ammonia in both the liquid and
vapor phase? The major conclusion is that we need to focus our attention on those places in a
refrigeration system that hold liquid phase refrigerant in order to obtain the best estimate of
overall system charge. Why? Well the relative mass of refrigerant associated with vapor phase
refrigerant will be very small. We underscore this point by comparing mass of refrigerant
associated with vapor vs. liquid in the examples provided the Appendix.
Inventory Estimation
Now that we know to focus our attention on those areas of a refrigeration system containing liquid
refrigerant, lets consider prioritizing those portions of the system and review methods for
determining the quantity contained within those parts of the system.
Figure 4 shows a simplified flow diagram illustrating the major components of a multi-temperature
level two-stage compression refrigeration system. Most industrial refrigeration systems will have
the single greatest mass of refrigerant contained within the systems vessels; however, end-users
with systems that have a footprint covering a large area may find that the mass in liquid piping
exceeds the refrigerant inventory in vessels. Heat exchangers (condensers and evaporators) and
liquid piping will also contain appreciable inventories of refrigerant mass as well. Based on the
properties of ammonia, expect to find minimal refrigerant inventory in the vapor spaces of vessels
and vapor piping.
Evaporative
Condenser(s)
DX Evap
Equalizer
line
3
8
Low
Temperature
Evaporator(s)
High
Pressure
Receiver
Medium
Temperature
Evaporator(s)
Medium
Temperature
Recirculator/
Intercooler
6
Low
Temperature
Recirculator
4
1
High-Stage
Compressor(s)
Booster
Compressor(s)
2004
Vessels
As an equipment category, vessels will often contain the largest
fraction of refrigerant inventory for most industrial refrigeration
systems. We are particularly interested in those vessels that
contain liquid refrigerant including: high pressure receiver(s),
thermosiphon pilot receivers, low pressure accumulators,
controlled-pressure receivers, intercoolers, suction traps, transfer
drums, and oil pots.
Determining the inventory of a vessel requires gathering physical
dimensions of the vessel as well as operating levels and refrigerant
state within the vessel. The complexity of the inventory calculation
depends on whether the vessel is oriented vertically or horizontally.
Lets look at the vertical orientation first it is the easiest.
Vertical Orientation
The first step in determining the inventory of a vessel is to calculate the volume of the
vessel that contains only refrigerant in the liquid phase. A simplified approach would
assume that the vessel is a vertical cylinder i.e. we ignore the vessels heads. Figure 5
below illustrates the key dimensions associated with the volume calculation assuming the
vessel is a simple vertical cylinder. This approach greatly simplifies the volume
calculation and provides a conservative estimate of liquid volume assuming that the
vessel length is taken from the vessels end and not at the girth weld. The volume of
liquid in a simple vertical cylinder is given by
Vliquid ,cylinder
2
Dvessel
=
H liquid
4
(1)
where Vliquid,cylinder is the volume of liquid assuming a simple cylinder (ft3), Dvessel is the
vessel diameter in ft, and Hliquid is the normal operating height of liquid in the vessel.
Hliquid
Dvessel
Figure 5: Illustration of key dimensions for approximating a vertical vessel.
2004
The inventory can then be approximated by the product of the liquid volume and the
liquid refrigerant density for the given operating pressure/temperature in the vessel.
(2)
Vellipsoid =
D1 D2 D3 =
3
Dvessel
(3)
6 RD
where the diameters are shown in Figure 6 and RD is the ratio of the smaller diameter to
the vessel diameter. Typically the RD is 2 for most commercially available vessels
(commonly referred to as 2:1 ellipsoidal heads).
D3 = D/RD
D1 = D2 = Dvessel
Vliquid ,vertical =
Dvessel
D
H liquid vessel
6 RD
(4)
Note, this equation is only valid if the liquid level is between the vessels girth welds
where the heads are attached. The product of the liquid volume and the liquid density in
the vessel determines the actual liquid inventory for the vessel:
(5)
How much of an improvement is equation 5 (which includes effects of the vessel head)
over that given by equation 2 (a simple cylinder)? The answer to this question can be
found using Figure 7. Figure 7 shows the ratio of the actual volume of a vessel with
elliptic heads (2:1) to the volume of a simple cylinder of equal overall length and diameter
for several vessel aspect ratios (L/D) over a range of liquid levels. For vessels with high
liquid levels and large L/D ratios (long and narrow vessels), the simple cylinder estimate
2004
compares well with the actual cylinder inventory i.e., volume fraction is near 1. For lower
liquid levels and short-stocky vessels, the simple cylinder assumption substantially
overestimates the refrigerant inventory in a vertical vessel.
Figure 7 can also be used to correct the simple cylinder volume estimate found using
equation (1). For a given fraction of liquid refrigerant height in the vessel (Hliquid/L) and
the vessels aspect ratio (L/D), a correction factor (fvertical) can be read directly from the yaxis on the graph. The corrected liquid volume for the vessel is then calculated by
multiplying the simple cylinder volume calculated using equation (1) by the volume
correction factor, (fvertical) as shown in equation (6). Once the vertical vessel volume is
corrected, equation (5) can be used with corrected volume to determine the mass of
liquid refrigerant in the vessel including the effect of the dished head.
Vliquid ,vertical =
2
Dvessel
H liquid f vertical
4
(6)
[fvertical]
0.8
L/D = 8
L/D = 6
L/D = 4
0.6
L/D = 3
L/D = 2
L/D = 1
0.4
0.2
Vertical Vessel
2:1 Ellipsoidal Heads
0
0.01
0.1
Horizontal Orientation
Horizontal vessels are more complicated than their vertical counterparts because we
need to determine the fraction of the vessels cross-sectional area that contains liquid
refrigerant. Figure 8 shows the dimensions of importance in estimating the liquid volume
in a horizontal vessel.
10
2004
Dvessel
Hliquid
Aliquid ,cylinder =
2
Dvessel
f liquid
4
(7)
where fliquid is taken from the y-axis of Figure 9 for the liquid height to diameter ratio
(Hliquid/Dvessel) in the vessel.
1
0.8
0.6
0.4
0.2
Horizontal Vessel
0
0
0.2
0.4
0.6
0.8
11
2004
Once the cross-sectional area of liquid in the vessel is known, the liquid volume can be
determined using the following equation:
(8)
where Aliquid,cylinder is the vessel cross-sectional area that contains liquid and is either
determined equation (7).
A more detailed method for determining the cross-sectional area of liquid in a horizontal
method is outlined in Figure 10. Figure 10 illustrates geometry and corresponding
equations to determine the cross-sectional area of a partially filled horizontal cylinder.
The cross-sectional area for a given liquid level is determined by first calculating the area
of a pie-shaped element formed by two projections from the center of the circle to the
vessel diameter at a point intersecting the liquid level. The triangular area above the free
surface is subtracted to arrive at the cross-sectional area of the liquid-only.
2
1
2
Atri = ( Dvessel 2) Dvessel 2Hliquid ( Dvessel 2Hliquid )
2
Dvessel 2 H liquid
Dvessel 2
= 180 2
= sin 1
2
Apie = ( Dvessel
4 ) ( 360 )
Dvessel /2
Hliquid
Figure 10: Partially full horizontal cylinder equations for liquid cross-sectional area.
The analytical solution for the volume, including the effect of the heads, developed from
the equations in Figure 10 and the volume of liquid in a partially liquid filled head is given
by equation (9)
Aliquid ,cylinder =
0.5
180
( Dvessel 2 )
Vliquid ,vessel
Dvessel
D
= Aliquid ,cylinder L vessel
RD
12
(9)
2
3
( H liquid Dvessel 2 H liquid 2 )
+
RD
2004
Regardless of the method used for determining the volume of liquid in a horizontal
vessel, the mass of liquid in the vessel is determined with the following equation:
(10)
Similar to the vertical vessels, Figure 11 shows the ratio of volume of a partially-filled
horizontal vessel (with 2:1 elliptical heads) to that of simple horizontal cylinder. For large
aspect ratios (L/D=4 or higher), the simple cylinder approximation is within 10% of the
actual volume for a vessel with elliptical heads.
Figure 11 allows correction of the estimated liquid volume from equation (8) to account
for 2:1 ellipsoidal heads. The corrected liquid volume is calculated by multiplying the
simplified volume determined in equation (8) by the correction factor taken from Figure 11
(fhorizontal) for vessels length to diameter ratio (L/D) and the liquid height to diameter ratio
(Hliquid/D).
(11)
1
L/D = 8
[fhorizontal]
L/D = 6
L/D = 4
0.9
L/D = 3
L/D = 2
0.8
L/D = 1
0.7
0.6
Horizontal Vessel
2:1 Ellipsoidal Heads
0.5
0.01
0.1
Figure 11: Ratio of actual liquid volume to that of a partially filled horizontal cylinder.
13
2004
Condensers
Operators understand that evaporative
condensers are capable of holding up
significant quantities of liquid refrigerant
particularly under abnormal operating
conditions. During normal operation,
condensers freely drain condensed
high pressure liquid out the bottom of
the condensers heat exchanger
through a drain pipe connected to the
heat exchangers header box. For the
purposes of determining refrigerant
inventory in a system, we will focus on
the normal operation and not the
abnormal operation; however, the
inventory under abnormal operation
should be considered in the context of
risk assessments and condenser siting.
Virtually all evaporative condenser manufacturers catalog two key pieces of information that
aid in determining the refrigerant inventory: condenser heat exchanger volume and condenser
normal operating charge. Knowing the internal volume of the heat exchanger and average
density of the condensing refrigerant within the heat exchanger provides enough information
to estimate the refrigerant inventory. The internal volume, coupled with the density of high
pressure saturated liquid can also be used to estimate the worst-case inventory should the
condenser completely fill with liquid. In this section, we also provide you with a rule-of-thumb
condenser charge estimate based on the condensers heat rejection rating. The most
accurate estimate of refrigerant inventory is given by the operating charge data cataloged by
condenser manufacturers.
Figure 12 below shows an excerpt from one manufacturers catalog for evaporative
condensers. The tenth column from the left notes the operating charge of ammonia for each
condenser model. By knowing each model of condenser you have, this type of information
allows you to quickly estimate of the operating charge for each condenser in your system.
14
2004
The second rule-of-thumb was developed based on evaluating operating charge data for a
range of evaporative condenser types and sizes from which we concluded that a reasonable
average charge is 90 lbm per million Btu/hr of rated heat rejection at a manufacturers-specified
condition of 105F saturated condensing and 70F ambient wet-bulb temperature. In this
case, the operating condenser operating charge can then be conservatively estimated by:
lb m
mmBh
(12)
If the rating of the condenser is expressed in evaporator tons, the corresponding rule-ofthumb is 1.85 lbm/evaporator ton (rated at 96.3F saturated, 78F wet-bulb and +20F suction).
Determining the maximum inventory of a condenser involves determining the density of liquid
at the prevailing condensing pressure and multiplying that density by the cataloged condenser
coil volume.
Because the information provided by current condenser manufacturers is rather complete,
rules-of-thumb need rarely be applied and condenser refrigerant inventory determination is
straight forward.
Evaporators
Evaporators in industrial refrigeration
systems come in all shapes, sizes, and
styles. The majority of evaporators in
industrial refrigeration service are aircooling plate-finned type heat exchangers.
Other heat exchanger designs in use
include: shell-and-tube, plate-and-frame,
corrugated plate, plate-and-shell, scraped
surface and others.
The refrigerant-side of evaporators for industrial refrigeration systems are, generally,
configured in one of three ways: liquid overfed, flooded, direct-expansion (DX). Unfortunately,
evaporator manufactures do not catalog operating charge information for air-cooling
evaporators. As a result, we have structured some basic guidelines to estimate the normal
operating charge of refrigerant in evaporators depending on their method of refrigerant feed
and prevailing operating conditions.
The mass of refrigerant in an evaporator will be the product of the heat exchangers internal
volume and the average density of refrigerant within the evaporator.
(13)
Most evaporator manufacturers do catalog internal volumes for each model they produce.
Two operating states are generally of interest for refrigerant inventory determination: normal
and abnormal. Methods for estimating the density of refrigerant during normal operation are
presented in this section. The density of refrigerant in an abnormal situation is usually
assumed to be saturated liquid at the evaporator pressure.
15
2004
ref
(14)
(see table below), ref,two-phase,outlet is the two-phase refrigerant density at the coil outlet, and
ref,sat,in is the density of saturated refrigerant liquid at the evaporator inlet. Estimates for the
empirical constant are provided by the following table.
Overfed
0.25
Flooded
0.5
The density of the two-phase refrigerant at the evaporator outlet is dependent on the quality of
refrigerant at the coil outlet and the quality will be dependent on the liquid overfed ratio for the
coil.
x=
1
(1 + OR )
(15)
where x is the mass fraction of vapor (i.e. quality) at the evaporator outlet and OR is the
overfeed ratio (ratio of mass of liquid to mass of vapor leaving the evaporator). For liquid
overfed evaporators, OR can be approximated by using the manufacturers-recommended
overfeed rate for each evaporator. Alternatively, OR can be estimated by calculating the ratio
of the liquid refrigerant supply flow rate to the evaporator over the minimum required flow rate
just to meet the evaporators rated thermal performance. In this case, the liquid supply flow
rate can be estimated based on the pressure difference across the hand-expansion valve and
the valves Cv for the given number of turns open on the valve. For flooded evaporators, the
OR is assumed to be 1.
The specific volume of the mixed phase refrigerant out of the evaporator and corresponding
density are given by
16
2004
where x is quality, ref,two-phase,outlet is the mixed phase density leaving the evaporator,
vref,two-phase,outlet is the mixed phase specific volume leaving the evaporator, vvapor is the vapor
specific volume and vliquid is the liquid phase specific volume both evaluated at saturation
conditions for the pressure in the evaporator.
Direct-Expansion Evaporators
For direct-expansion evaporators, the average density of refrigerant in the evaporator is:
(17)
where ref,inlet is the density of refrigerant downstream of the expansion device and ref,outlet is
the refrigerant density at the outlet of the coil but upstream of any evaporator pressure
regulator. The refrigerant density at the coil inlet is given by
ref ,inlet
(18)
where fflash represents the flash gas (mass fraction of vapor) generated downstream of the
expansion device. The flash gas fraction is calculated by
f flash =
(h
(h
high pressure
vapor ,evap
hliquid ,evap )
hliquid ,evap )
(19)
where hhigh-pressure is the enthalpy of high pressure liquid upstream of the expansion device,
hliquid,evap is the enthalpy of saturated liquid at the evaporator pressure and hvapor,evap is the
enthalpy of saturated vapor at the evaporator pressure.
For other evaporator types such as shell-and-tube chiller heat exchangers, manufacturers
often provide operating charge data similar to that provided for condensers. As an example,
Figure 13 shows a catalog sheet for a line of flooded shell-and-tube heat exchangers by one
manufacturer. The seventh column from the left shows operating charge data for each chiller
size. Because the volume of internal components in a chiller can vary significantly from
manufacturer to manufacturer, we recommend that you contact the chiller manufacturer to
obtain operating charge information for your particular model.
In the absence of operating charge detailed data from the chiller manufacturer, a rule-of-thumb
assumes the operating charge for a shell-and-tube chiller is 20 lbm per ton of refrigeration
capacity per approach. Equation 20 includes an approximation for correcting the operating
charge based on the design approach temperature for the chiller.
M chiller
20 Capacity
(To SET )
(20)
Where Capacity is the chiller capacity in tons, To is the design leaving fluid temperature from
the chiller to the load [F], and SET is the corresponding saturated evaporator temperature [F]
of the ammonia in the chiller.
Welded (or nickel brazed) plate pair heat exchangers may be approximated using the methods
for an air-cooling evaporator using the appropriate liquid feed type (gravity flooded or DX) with
the volume determined by obtaining the volume of the refrigerant containing passages in the
17
2004
plate pair and the number of plate pairs. This information will require contact with the
manufacturer of the plates.
18
2004
Piping
Industrial refrigeration system piping carries
refrigerant that circulates through a system. In
general, the phase of refrigerant circulating
through segments of refrigerant piping can be
determined with a high degree of certainty with
one exception: wet suction return piping. When
refrigerant is in a single phase (vapor or liquid),
the total inventory in a pipe segment can be
accurately determined. Usually, uncertainties in
piping inventories are associated with
uncertainties in the physical size of the piping
segment. Estimating the inventory for piping
with mixed phase refrigerant is much more
difficult.
In this section, we provide guidance for estimating the inventory for all phases of refrigerant in
piping. The following table refers to the diagram shown in Figure 4 which identifies the
segment of piping by number, name, and typical state of refrigerant in that piping segment.
Table 2: Refrigerant piping identification and state.
Pipe Segment3
Description
Liquid
Two-phase
Vapor
19
2004
For the piping segments in Table 2 shown to contain liquid, those segments become the
highest priority to quantify first followed by the two-phase piping segments. The inventory in
vapor-containing piping will be extremely small and should be considered last.
Determining the inventory of refrigerant for a given piping segment is as follows:
1. Determine internal cross-sectional area of pipe based on the pipe size (based on
nominal pipe size and schedule)
2. Estimate the pipe length of each size
3. Determine volume of pipe segment
4. Determine the state of refrigerant in the pipe segment
5. Determine the refrigerant density
6. Calculate mass (product of segment volume and density)
Step 1 involves determining the cross-sectional area of the pipe segment in question.
Refrigerant piping will have a nominal pipe dimension and a corresponding wall thickness
(standardized by its schedule). Pipe sizing information is available from several sources
including: pipe suppliers, IIAR (2000), ASHRAE (2004), and other reference handbooks. A
subset of pipe sizes is given below in Table 3.
Table 3: Steel pipe data (ASHRAE 2004).
i.d.
(in)
o.d.
(in)
Wall thickness
(in)
1 Schedule 80
0.957
1.315
0.179
2 Schedule 40
2.067
2.375
0.154
4 Schedule 40
4.026
4.500
0.237
10 Schedule 40
10.020
10.750
0.365
Size
Across section =
dinside
2
12 = d inside
4
183.3
(21)
where Across-section is the pipe cross-sectional area (ft2), dinside is the inside pipe diameter in
inches. The volume of the pipe segment is calculated as
(22)
where Vpipe is the pipe volume (ft3) and Lpipe is the pipe segment length (ft). Note, equations
(21) and (22) should be applied only to those piping sections with constant cross-section. In
situations where pipe size changes, apply both equations (21) and (22) consecutively.
Once the volume of piping is determined, the next step involves determining the density of the
20
2004
refrigerant occupying each pipe segment. As previously discussed, the refrigerant density is
dependent on the pressure and temperature of the refrigerant. Properties of ammonia are
available from sources such as IRC (2001), ASHRAE (2001), and IIAR (1992). An excerpt
from the IRC ammonia property tables is given below in Table 4. As an example, a high
pressure liquid line with saturated liquid at 95F would be carrying refrigerant at a density of
36.67 lbm/ft3.
Table 4: Anhydrous ammonia properties at saturation conditions (IRC 2001).
The mass of refrigerant occupying the pipe segment is the product of the pipe segment
volume (ft3) and the refrigerant density (lbm/ft3).
(23)
For liquid lines, the following correlation can be used to estimate the refrigerant inventory
given inside pipe diameter and refrigerant saturation temperature.
2
M ref , pipe ,est = 4.441 3.353 dinside + 23.0282 dinside
(24)
21
2004
somewhat of a challenge. The mixed phase density of refrigerant in a wet return can be
estimated by the following.
(25)
1
v ref ,two phase
where x is quality, ref,two-phase is the mixed phase density, vref,two-phase is the mixed phase specific
volume, vvapor is the vapor specific volume, and vliquid is the liquid phase specific volume
evaluated at saturation conditions for the pressure in the pipe segment. The quality can be
estimated based on the overfeed ratio as follows.
x=
1
(1 + OR )
(26)
where OR is the average overfeed ratio for evaporators contributing return refrigerant to the
wet-suction return.
Compressors
Oftentimes, we do not consider compressors as an
equipment category capable of holding a large
refrigerant inventory. The compressor itself will not
contain any appreciable amount of refrigerant;
however, it is important to consider the additional
components that makeup the compressor
package. The compressor-related components
that warrant consideration in a refrigerant inventory
calculation include: oil separator, thermosiphon oil
cooler, and thermosiphon piping. Lets look at the
inventory associated with each of these key
compressor package components.
Oil Separators
The majority of screw compressors in industrial refrigeration systems utilize a vessel to
separate oil from compressor discharge vapor (Jekel, et al. 2001). The state of refrigerant in
the oil separator is superheated vapor at the prevailing discharge pressure and temperature.
Recall from our discussion of refrigerant properties that as the pressure of the vapor
increases, the density of the vapor will also increase; consequently, an oil separator operating
in high stage duty will hold more mass of vapor than an equal sized oil separator operating in
booster service. A conservative estimate of the refrigerant mass in an oil separator will
neglect the volume associated with its internal components such as coalescing filter elements,
piping, baffles, heating elements, and the accumulated oil itself. These internal components
can reduce the gross internal volume of the oil separator by 20-30%.
Assuming the separator as a simple cylinder, the following equation gives the gross volume of
the oil separator:
22
2004
2
Dseparator
(27)
The mass of refrigerant vapor in the separator can be conservatively estimated using:
(28)
where vapor is the density of vapor refrigerant at the compressor discharge pressure and
temperature. Further refinement of the volume to account for dished heads can be done as
previously discussed in the section on vessels.
Thermosiphon Oil Coolers
Thermosiphon oil coolers utilize high pressure saturated liquid as the heat sink for oil cooling
on a screw compressor package. The most common oil cooling configuration consists of a
shell-and-tube heat exchanger where oil circulates on the shell-side while high pressure liquid
refrigerant is supplied to the tube-side. As the liquid refrigerant absorbs heat from the oil, it
boils and the resulting vapor is vented back to the thermosiphon pilot receiver. During normal
operation, the return vapor will entrain some liquid refrigerant from the cooler and deliver a
mixture of liquid and vapor back to the pilot receiver.
Determining the refrigerant inventory of thermosiphon oil coolers is similar to condensers.
Most compressor manufacturers publish data for both refrigerant and oil inventory for the oil
coolers integrated into their compressor packages as part of the technical documentation that
is included with the compressor purchase.
23
2004
For a high stage compressor, saturated liquid ammonia at 181 psig has a density of 36.67
lbm/ft3. The maximum refrigerant inventory for a model 6074 oil cooler would then be the
product of the listed refrigerant volume (0.5 ft3) and the refrigerant density (36.67 lbm/ft3)
resulting in an estimated operating charge of 33.34 lbm.
Recently, plate-type heat exchangers have found growing application for thermosiphon oil
cooling. An primary advantage of the plate-type heat exchanger is its compact size (which
leads to low operating charge) for a given oil cooling load. For example, a flat plate-type heat
exchanger capable of rejecting 881 mBh of oil cooling load has a refrigerant-side internal
volume of approximately 0.2 ft3. If we assumed that the oil cooler in this example was
completely filled with saturated liquid at a design condensing temperature (181 psig), the
refrigerant charge would be just over 7 lbm (the product of 0.2 ft3 and the refrigerant density of
36.67 lbm/ft3).
Thermosiphon Piping
The methods presented in the piping portion of this TechNote should be applied to estimate
inventory of thermosiphon piping. The refrigerant state in the thermosiphon supply piping will
be saturated liquid while the thermosiphon return piping will contain a mixture of liquid and
vapor.
The refrigerant inventory for the thermosiphon supply piping can be estimated using equations
(21)-(23) or equation (24). The refrigerant inventory for thermosiphon return piping can be
estimated by equations (21)-(23) where the refrigerant density for equation (23) is estimated
using equations (25)-(26). Typically, the ratio of liquid mass to vapor mass in the return
piping is 3:1 (FES, 1998 and Welch, 2003); consequently, a value for OR in equation (26) can
be assumed to be 3 for inventory estimating purposes.
Systems
The total inventory of a refrigeration
system will be the summation of the
estimates of refrigerant inventory for
each component that makes up the
system. Keep in mind that refrigerant in
the liquid state will usually account for
more than 98% of the total charge of the
system with two-phase mixtures of liquid
and vapor accounting for an additional
1%. In doing these calculations
yourself, you will likely find that vapor
accounts for less than 1%.
Consider developing a summary table of refrigerant for your system. Table 5 provides a
simple example of the minimum information that should be included in a system summary of
refrigerant inventory. The Description column breaks out each of the main components for
the system and provides the component inventory estimate (second column) and a running
total of cumulative inventory (third column).
4
The model for the oil cooler data is related to the physical size of the oil cooling heat exchanger. The first number or
second digit represents the shell diameter (6 inch for the 600 series, 8 inch for the 800 series, 10 inch for the 1000
series, etc.). The last one or two digits represents the length of the oil cooler in ft (5 ft for the 05 coolers, 10 ft for the
10 coolers). Such information is helpful for determining the specific oil cooler in the absence of a positive
identification from the manufacturers original documentation for the package.
24
2004
Estimated on 2/24/1992
Equipment Description
Component
Inventory
(lbm)
Cumulative
Inventory
(lbm)
6,200
6,200
Intercooler (IC-050)
4,250
10,450
2,725
13,175
2,840
16,015
600
16,615
30
16,645
570
17,215
2,640
19,855
3,180
23,035
1,200
24,235
840
25,075
990
26,065
Chiller (CH-510)
1,808
27,873
Chiller (CH-511)
2,480
30,353
Chiller (CH-512)
1,808
32,161
341
32,502
648
33,150
1,372
34,522
280
34,802
Vessels
Evaporators
Piping
Plant Total
25
34,802
2004
Conclusion
Accurately estimating the refrigerant charge in a system is the first step in determining whether or
not your plant falls within the scope of OSHAs Process Safety Management Standard and EPAs
Risk Management Program. For ammonia refrigeration systems having inventories in excess of
the threshold quantity (10,000 lbm), end-users are required to develop and implement both a
process safety management and risk management program. The process safety information
portion of the PSM Standard requires maintaining up-to-date information on the inventory of a
refrigeration system. Component level inventories also provide useful data for other facets of
safety such as evaluating risk through a formal process hazard analysis.
If you are unsure of applying the inventory calculation methods presented in this TechNote, work
through some of the example problems provided in the Appendix. Check the IRC website for
computer-aided tools that will assist you in rapidly estimating the refrigerant inventory for
components in a refrigeration system.
26
2004
Summary
Table 6 provides a summary of the equations used in this TechNote for inventory calculations.
For each type of equipment, the relevant equations for both detailed and simplified methods are
identified.
Table 6: Summary equations for inventory calculations.
Equipment Type
Method
Equation
Page
Volume, liquid
(1)
Inventory, liquid
(2)
(4) or (6)
9 or 10
Inventory, liquid
(5)
(7)
11
(8)
12
Inventory, liquid
(10)
13
(9)
12
(9) or (11)
12 or 13
Inventory, liquid
(10)
13
Simplified
Inventory
(12)
15
Detailed
Inventory
Mfgrs Data
14
Air-cooling
Evaporators
Overfed/Flooded
Inventory
(13)-(16)
15-16
Direct-expansion
Inventory
(13), (17)-(19)
15, 17
Chillers
Flooded
Inventory
(20)
17
Area, cross-section
(21)
20
Volume
(22)
20
(23)
21
Inventory (two-phase)
(23), (25)-(26)
21-22
(24)
21
(27)
23
(28)
23
Thermosiphon supply
(21)-(23)
20-21
Thermosiphon return
(23), (25)-(26)
21-22
Simplified
Vertical Vessel
Detailed
Simplified
Horizontal Vessel
Detailed
Condensers
Piping
Detailed
Simplified
Simplified
Compressors
Quantity
Volume, liquid
Detailed
27
2004
Postscript
This TechNote outlines the principles and methods for inventory calculations applicable to
components that comprise a built-up industrial refrigeration system. The accuracy of an
inventory calculation is dependent on two factors: accuracy of the method and certainty of
inputs. Some of the methods presented are less developed; consequently, the uncertainty of
the estimated inventory derived from those less certain methods will be greater. In some
cases, details on the required inputs for a particular inventory calculation method may not be
well known. In this case, the result will be uncertain because the inputs are uncertain.
Below is a summary of two measures intended to provide you with a qualitative assessment of
each inventory calculation method presented in this TechNote. The first measure represents
the level of development for each particular method. The scale ranges from (1) not well
developed to (5) very well developed. The second measure represents the inventory
uncertainty estimate attributable to both the method and certainty of required inputs. The
scale ranges from (1) very uncertain to (5) very certain. Both measures are provided in
the bar charts below.
4
3
Detailed
Detailed
Flooded Overfed
Evap.
Evap.
Detailed
DX
Evap.
Detailed
Manufacturers
charge data
Detailed
Detailed
Vertical Vessel
Simple
cylinder
Detailed
Simple
cylinder
Detailed
Rule-of-thumb
Method Uncertainty
Liquid
lines
Vapor
lines
Wet
lines
4
3
28
Detailed
Detailed
Flooded Overfed
Evap.
Evap.
Detailed
DX
Evap.
Detailed
Detailed
Manufacturers
charge data
Detailed
Detailed
Vertical Vessel
Simple
cylinder
Detailed
Rule-of-thumb
Simple
cylinder
Overall Uncertainty
Liquid
lines
Vapor
lines
Wet
lines
2004
References
ASHRAE, HVAC Systems and Equipment Handbook, American Society of Heating, Refrigerating,
and Air conditioning Engineers, Atlanta, GA (2004).
ASHRAE, Fundamentals Handbook, American Society of Heating, Refrigerating, and Air
conditioning Engineers, Atlanta, GA (2001).
BAC, Series V Evaporative Condensers, Baltimore Aircoil, Bulletin S119/1-OB (2003).
29
2004
Appendix: Examples
30
2004
Vessels
Determine the mass of refrigerant in a -40 F pumped recirculator that measures 8 ft in diameter
and 12 ft high. Liquid refrigerant is maintained at the 4 ft level during normal operation. Assume
the vessel is a vertical cylinder and estimate the refrigerant inventory associated with both the
liquid and vapor.
Solution:
Vliquid =
2
d vessel
82
H liquid = 4 = 201 ft 3
4
4
The density of saturated liquid at -40F is 43.08 lbm/ft3; consequently, the mass of liquid in the
vessel is
Vvapor =
2
d vessel
82
H vapor = 8 = 402 ft 3
4
4
31
2004
The density of saturated vapor at -40F is 0.04017 lbm/ft3; consequently, the mass of vapor in the
vessel is
M vapor = 0.04017
lbm
402 ft 3 = 24 lbm
3
ft
The following is a comparison between the above simplified analysis results and the IRCs Vessel
Inventory Calculator tool.
Inventory Type
Simplified Analysis
% Difference
8,659
7,219
+20
24
15
+60
8,683
7,234
+20
Total
The corrected result could also be determined using Figure 7 in the body of the report. The L/D
ratio for the vessel is 1.5 and the fraction of the vessel containing liquid is 0.33. Using Figure 7,
the correction factor is approximately 0.83 resulting in an adjusted liquid mass of 7,190 lbm.
32
2004
Condensers
Determine the refrigerant inventory for an Evapco ATC Model 3459B.
Solution:
The table below is an excerpt from Evapcos evaporative condenser product data catalog. From
the entry showing the model 3459B, we find the reported operating charge of 4,780 lbm.
This particular condenser has a nominal capacity of 50,848 mBh. Applying the rule-of-thumb of
90 lbm/mmBh yields an estimated operating charge of
M est = 90
lb m
mmBh
50,848 mBh
= 4,576 lb m
mmBh
1,000 mBh
The last rule-of-thumb we introduced suggested taking the reported internal coil volume and
using an average density of lbm/ft3. With this rule-of-thumb, the estimated inventory would be
M est ,2 = 532ft 3 10
lb m
= 5,320 lb m
ft 3
33
2004
Evaporator
Estimate the inventory for an overfed evaporator operating with a -20F liquid supply and a 3:1
overfeed ratio. The coil does not have an evaporator pressure regulator. The internal volume is
4 ft3.
Solution:
The density of liquid at -20F is 42.23 lbm/ft3 and the corresponding specific volume is 0.0237
ft3/lbm. The density of vapor at -20F is 0.06809 lbm/ft3 and the corresponding specific volume is
14.686 ft3/lbm.
The first step is to estimate the quality of refrigerant at the evaporator outlet, x.
xevap ,outlet =
1
1
=
= 0.25
(1 + overfeed ) (1 + 3)
Next, we estimate the specific volume and density of refrigerant at the coil outlet
ft 3
= 0.0237 + 0.25 (14.686 0.0237 ) = 3.689
lb m
1
vref ,two phase,outlet
1
lb
= 0.2711 m3
3.689
ft
lb m
ft 3
Finally, we have enough information to estimate the refrigerant inventory for the coil
34
lbm
= 42.5 lbm
ft 3
2004
Piping
Determine the mass of refrigerant in a 100 ft segment of 2 Schedule 40 pipe carrying minus 40F
saturated liquid refrigerant.
2 sch. 40
i.d. = 2.067
o.d. = 2.375
100 ft
Solution:
The density of -40F saturated liquid refrigerant is 43.08 lbm/ft3.
2
d inside
183.3
L pipe =
2.067 2
100 = 2.33 ft 3
183.3
lb m
= 100.4 lb m per 100 ft
ft 3
Determine the mass of refrigerant for the same pipe segment assuming it is carrying -40F
saturated vapor refrigerant.
The density for saturated vapor at -40F is 0.04017 lbm/ft3. The mass of refrigerant is then given
by
lb m
= 0.0936 lb m per 100 ft
ft 3
35
2004
Screw Compressor
Determine the mass of refrigerant for a twin screw compressor equipped with an oil separator 36
inches in diameter and 16 ft in length. The compressor will operate with a maximum discharge
pressure of 196 psia (181 psig) and a corresponding discharge temperature of 180F.
From equation (27) the gross volume of the oil separator is:
2
Dseparator
( 3 ft )
L =
4
16 ft = 113 ft 3
The density of ammonia at 196 psia and 180F is 0.5257 lbm/ft3. The corresponding estimate of
the refrigerant mass in the oil separator during normal operation can be found by using equation
(28) as follows:
lb m
= 59 lb m
ft 3
If this compressor were operating under booster duty, the discharge pressure would be
considerably lower, e.g. 45 psia. In this case, the density of the refrigerant would be in the range
of 0.12 lbm/ft3 and the corresponding refrigerant vapor inventory for the oil separator drops to
approximately 14 lbm.
36
2004