Substation Earthing
Substation Earthing
CONTRACT NO.
TENDER NO.
PROJECT
REVISION
Probe Spacing A
(m)
0.31
0.92
1.52
4.57
6.10
9.15
15.24
21.34
27.44
33.54
39.63
45.73
DATE
0.02
0.05
0.08
0.23
0.30
0.46
0.76
1.07
1.37
1.68
1.98
2.29
56.98
88.15
95.48
110.64
120.71
143.11
182.01
209.21
227.60
242.36
251.55
258.64
30.00
Resistance W
25.00
20.00
15.00
10.00
5.00
0.00
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
45.00
50.00
45
50
250
Resistivity Wm
200
150
100
50
0
0
10
15
20
25
30
35
40
0
0
10
15
20
25
30
35
40
45
50
SUBSTATION
CONTRACT NO.
TENDER NO.
PROJECT
REVISION
DATE
INPUT PARAMETER
Symmetrical Earth Fault Current, If
31,500.00 A
0.50 sec
3.00 sec
Soil Resistivity,
112.20 m
Fence Perimeter
0.00 m
Body Weight
50.00 kg
1.00
0.70
Crushed Rock
Crushed Rock Resistivity, s
Thickness of Crushed Rock, hs
3,000.00 m
0.150 m
Earth Rod
Number of Earth Rod Point
Length of Earth Rod, Lr
165.00
1.80 m
3.00
891.00 m
300.00 mm2
0.30 m
1.00 m
70.00 m
3.00 m
3.00 m
3,406.67 m
4,900.00 m2
280.00 m
4,297.67 m
3,312.35 m
70.00 m x
3.00 m x
SUBSTATION
CONTRACT NO.
TENDER NO.
PROJECT
REVISION
DATE
0.78
3,330.81 V
999.23 V
0.74
22,050.00 A
22,050.00 A
16,232.91 V
GPR vs Etouch50
GPR
Etouch50
16,232.91 V
999.23 V
GPR > TOLERABLE TOUCH VOLTAGE
MESH VOLTAGE, EM
na
nb
nc
nd
n = na x nb x nc x nd
24.33
1.00
1.00
1.00
24.33
Ki
Kii
kh
Km
Em
4.25
1.00
1.14
0.35
770.48 V
EM vs Etouch50
EM
Etouch50
770.48 V
999.23 V
MESH VOLTAGE < TOLERABLE TOUCH
VOLTAGE, DESIGN OK
STEP VOLTAGE, Es
Es
2,324.48 V
Es vs Estep50
Es
Estep50
2,324.48 V
3,330.81 V
STEP VOLTAGE < TOLERABLE STEP
VOLTAGE, DESIGN OK
Legend
s
A
Cs
d
Dm
Df
Em
Es
Estep50
Etouch50
h
hs
IG
Ig
kh
Ki
Kii
Km
Ks
n
Soil resistivity.
Surface layer resistivity.
Total area enclosed by earth grid.
Surface layer derating factor.
Diameter of grid conductor.
Maximum distance between any two points on the grid.
Decrement factor for determining IG.
Mesh voltage at the centre of the corner mesh for the simplified method.
Step voltage between a point above the outer corner of the grid and a point 1m diagonally outside the
grid for the simplified method.
Tolerable step voltage for human with 50kg body weight.
Tolerable touch voltage for human with 50kg body weight.
Depth of earth grid conductors.
Surface layer thickness.
Maximum grid gurrent that flows between earth grid and surrounding earth.
Symmetrical grid current.
Corrective weighting factor that emphasizes the effects of grid depth, simplified method.
Correction factor for grid geometry, simplified method.
Corrective weighting factor that adjusts for the effects of inner conductor on the corner mesh,
simplified method.
Spacing factor for mesh voltage, simplified method.
Spacing factor for step voltage, simplified method.
Geomatric factor composed of factors na, nb, nc and nd.
Equation 29
Equation 32
Equation 52
Assumption Ig = IG
MESH VOLTAGE, EM
Equation 81
Equation 83
Equation 82
Equation 85
Equation 86
Equation 87
Equation 88
Equation 84
STEP VOLTAGE, Es
Equation 89
Equation 93
Equation 94
Equation 92
nt above the outer corner of the grid and a point 1m diagonally outside the
d.
that adjusts for the effects of inner conductor on the corner mesh,