Auto Ground Design
Auto Ground Design
Page 1 of 15
AutoGroundDesign: An Overview
AutoGroundDesign is the only fully automated software package that can analyze and design grounding / earthing systems without the intervention of the user between various phases of the design thanks to its intelligent database driven algorithms. It offers powerful and intelligent functions that help electrical engineers design safe grounding installations quickly and efficiently.
First, a grounding system consisting of a buried metallic plate is used as a reference. This gives the minimum ground impedance achievable with a grid of a given size, and determines whether the desired ground impedance and safety limits can be achieved with a solid plate. If not, then the whole process is stopped and the user is informed that the design process is impossible without additional mitigation
measures.
Second, a grounding system consisting of a minimum number of conductors, for example, the conductors along the grid periphery with or without a few conductors inside the grid is analyzed to see whether the desired ground impedance and safety limits can be achieved with a sparse grid. If yes, the design process is completed quickly without the need to refer to the reference design database and smart
iterative techniques.
Third, an appropriate preliminary grid design is selected based on SES reference database and other intelligent rules or as specified manually by the user. The use of the reference database is based on the input data provided by the user, such as the size and the geometrical proportions of the grid, the soil structure type, the fault current injected, and the required safety criteria.
Finally, the initial design is refined recursively using rule-based techniques and smart algorithms to improve its performance and meet safety constraints, while reducing the overall cost of the grid.
Practicing electrical engineers are often faced with the necessity of having to design a grounding grid to meet certain protection objectives with regards to personnel safety or to equipment around electrical installations. The design procedure often starts with a preliminary grid which is usually determined based on practical considerations and engineering experience. This grid is then submitted to the
grounding engineering module to determine if all design requirements are met. If not, then the grid is refined and analyzed again until a satisfactory grid is obtained.
The design of grounding systems is often based on rough guidelines, derived from engineering experience. A grounding system design requires several iterations before obtaining a safe configuration. Therefore, it and can be quite time consuming. It is difficult to account for the large number of variables (topology and dimensions of the grounding system, burial depth, type and characteristics of the soil
structure and material used for the grids conductors (horizontal wires and grounding rods, etc. ) that can affect the grounding system performance. Thus, AutoGroundDesign uses a database and rule-based automated grounding system design method to meet design requirements (such as ground potential rise, touch voltage, step voltage, and ground resistance limits), given the soil structure, dimensions of
the grid area, characteristics of conductors, configuration of the grid, and fault current discharged by the grid. The ultimate objective is to complete a grid design that meets the mentioned design requirements.
The goal of AutoGroundDesign is to allow researchers and engineers to quickly and accurately find out which grid (if any) can satisfy the provided constraints. AutoGroundDesign has unique features that set it apart from previous implementations:
Generates grounding system designs based on a simple description of the substation site. The data entry requirements are reduced to a minimum: environment settings, soil data, grounding grid zone, fault current in the grid, safety related data, and automated design parameters & controls.
Models grounding systems and evaluates their performance; it is suited to analyze and design a grounding grid as long as the longitudinal impedances of the ground conductors can be neglected.
Analyzes and designs horizontal arbitrary grounding grids consisting of horizontal and vertical arrangements of bare conductors buried in uniform and multilayered soils.
Carries out automated design with several procedures, such as Automatic, Midpoint, Linear, and User-Defined methods. These procedures will specify the performance and progress of the automated design process appropriately and use ground grid databases, smart search algorithms and techniques, and user-supplied criteria and constraints more efficiently.
Allows users to specify if ground rods are to be used in the design of the final grid and ground rod characteristics. If yes, the rods can be distributed along the edges of the grid or over the whole grid area, as desired.
Computes earth potentials at specific soil locations called observation points that may be determined automatically by the program or user-defined.
Offers three other modes of operations, namely, the Estimator, Configuration and Dimension Predictor modes that allow users to quickly and accurately estimate the resistance of various grounding systems (such as grids, plates array of rods, star electrodes, circular rings, etc.) or predict the size (dimension) or configuration of the grounding system that meets that resistance. Please see the topic
entitled Using the Grounding System Estimator and Predictor modes for details.
Automated System Design Central Module. This core and controlling module has a simple interface that allows a user to establish an automated grounding system design quickly and efficiently. The ultimate objective of this module is to manage and coordinate input data, safety criteria and progress decisions in order to obtain a grid design that meets all requirements. The overall automated design
parameters are controlled by this module to select the methodology used to obtain the initial design of the grounding systems, specify which grid database methodology is to be used for the automated design, and specify the maximum number of design iterations as well as the rate at which the design of the grid evolves.
Grounding Analysis Module. The main mode of operation of this module is used to analyze power system ground networks subjected to DC or AC currents discharged into soil. It computes the safety performance of the grounding grid, in terms of GPR, touch and step voltages. Furthermore, the Estimator, Configuration and Dimension Predictor modes allow users to quickly and accurately estimate the
resistance of various grounding systems (grids, plates array of rods, star and hemispherical electrodes, circular rings, etc.) or determine the size (dimension) or configuration that meets a target resistance value.
Soil Analysis Module. This module is dedicated to the development of equivalent earth structure models based on measured soil resistivity data. It can generate models with many horizontal layers, as well as vertically and exponentially layered soil models.
Fault Current Distribution and Line Parameter Analysis Module. This module calculates the fault current distribution in multiple terminals, transmission lines and distribution feeders using minimum information and a simple set of data concerning the network. It provides the actual fault current flowing into a grounding grid, as well as currents in the shield wires, tower structures and cable sheaths.
Self and mutual impedances of shield wires and cable sheaths are also computed by a built-in line constant module.
Safety Module. This module generates safety threshold values based on IEEE Standard 80, IEC Standard 479, users own standard or a hybrid combination of these standards. The computed safety voltage limits are used to decide whether to stop or continue the design process. The safety voltage limits are: fault clearing time, earth surface covering layer (e.g., crushed rock) resistivity, earth surface
covering layer thickness, equivalent subsurface layer resistivity (this is the resistivity of the soil beneath the earth surface covering layer), body resistance, optionally specified foot resistance and resistance of protective wear, such as gloves or boots, and fibrillation current threshold computation method.
View, Plot and Report Tools. A CAD-based module is used to view or edit three-dimensional grounding grids consisting of straight-line segments. The line segments represent either metallic conductors or observation profiles. They can be viewed from any direction, in a variety of ways. A powerful and flexible report and graphics module serves as an integrated output processor to display the
computation results in various graphical or print formats. This module also has the capability to view the input data and even launch the grounding analysis module.
1. First, you can use the Help | Help Topics menu item to load the help file.
2. You can get context sensitive help from almost anywhere in the program by pressing the F1 key. This will bring up a help topic describing the part of the program that currently has the focus.
3. The status bar of the input screen displays helpful messages and the input text color will change based on the validity of the entered data (black if the data is sound, red if the data is not of the expected type, i.e., numeric or integer and dark red if the data is simply invalid). Out of range data brings a suitable message box indicating the acceptable range.
4. You can also obtain help on the SES Input Command language by selecting the Help | Command Mode Help menu item. This help document is useful to advanced users who are familiar with the SES SICL Commands and prefer to edit directly the input files
5. You can also go to the SES Web site at www.sestech.com. This web site offers a discussion group for grounding-related topics and a lot more information.
2. You can also contact SES by phone or fax using the coordinates available on the Web site at www.sestech.com/SES/coordinates.asp.
1. Starting AutoGroundDesign. To start the program, simply double-click the AutoGroundDesign icon in the tools of the SES Software Program Group.
2. Specifying Your Input Data. One single Windows screen consisting of three tabbed regions allows you to define all the input data and parameters controlling the program's behavior as a whole. These are regrouped in the following categories.
Computation settings
file://C:\Users\aivanov\AppData\Local\Temp\~hh4231.htm
13/02/2016
AutoGroundDesign: An Overview
Page 2 of 15
3. Processing the Grid Design, Electrode Estimation, or Electrode Prediction. When you have finished entering all the necessary input data, the automated grounding design, estimation, or prediction analyses can begin.
4. Viewing the Computations Results and the Final Grid Design. You can use any CDEGS or AutoGrid Pro tools or programs to do this. The plots and reports are displayed using the SESCAD, GRServer and FileView utilities.
5. Ending an AutoGroundDesign Session. To quit the application and terminate the AutoGroundDesign session, click the Exit button.
Starting AutoGroundDesign
To start the program, simply double-click the AutoGroundDesign icon in the SES Software Program Group. The information and data necessary to define the design automation process are described in section entitled Specifying Input Data.
In fact for every command button, there is a corresponding menu item that can be accessed from the menu bar. The following describes the role or function of each button or menu item.
Start Design / Start Automated Design: If all your data are valid, the button will be enabled and by selecting the button or the menu item, the automated design computation process will be launched.
View Designed Grid: The preceding button will change to this one as shown above if the run is successfully launched. In this case, selecting this button or the corresponding menu item will load the SESCAD tool and you will be able to view and modify the final version of the grid design.
View Design Summary File / View Design Summary Output File: This button or menu item will start a file viewer that displays the most relevant design computation information and results.
View Plots and Reports: Pressing this button or selecting this menu item launches the GRSERVER graphics viewer that will allow you to display the computation results as dedicated plots or as specialized reports.
View Messages: Some error or warning messages that were issued during your session will be stored and can be accessed by pressing this button or by selecting the corresponding menu item from the File drop down menu bar.
Reset Session: This button will clear all warning and error flags and will force the session status to become valid although errors are still present. This is sometimes useful to enable buttons or fields that are otherwise inaccessible.
Save Session / Save Session Input File: Pressing this button or selecting this menu item will immediately save all your input session data, selections and settings to the pertinent files or locations.
Restore Default Data: If you wish to populate your input data fields with default values and select default options, just press this button or select the corresponding menu item.
New / New Session: If you wish to start a new session, simply press this button or select the corresponding menu item. This will clear the Job ID and Working Directory path and will populate all data fields with default values. All options will be set to their default values. Note that you must specify a valid Job Id and Working directory before you can save and submit your input session for
processing.
Open... / Open Input File: This button or menu item allows you to browse to and load any existing AutoGroundDesign input session file.
Folder...: This button allows you to browse and select any folder path that you wish to specify as your Working Directory path. This is particularly convenient when the path name is long and you are starting a new session (i.e., you cannot browse to an existing input file).
View Edit Comments / View and Edit Comment Lines: This button or menu item is normally used to view or edit comment lines that you wish to insert in your input session file for future reference. The rich text box editor is loaded to allow you to edit these comment lines.
Job Identification (JobID): This is a text string identifying uniquely the various output files produced by the AutoGroundDesign engineering program run. This string will be appended to the name of the file just before its extension and will be printed on every plot and report. For example the most relevant input, output and database files are the following:
1. AD_ JobID.F05: This is the AutoGroundDesign command input file that is produced by your input session and that will be used to start the automated design process. It is an editable file. However, it is strongly recommended that you avoid editing this file if you are not familiar with the SES Input Command Language (SICL) environment.
2. AD_ JobID_Backup.F05: This is a backup copy of the input data file that was loaded at the beginning of your session. It contains a processed input file that is identical to the contents of your input data file. If for any reasons you modify and save the data, you can recover your original data by loading or editing the contents of this file.
3. AD_ JobID.F09: This is the AutoGroundDesign Summary results file that is produced by the automated design process. It is an editable file. That can be opened by any text browser such as Notepad or WordPad. SES FileView utility can be used by pressing the View Design Summary File button.
4. MT_JobID.F05, MT_JobID.F09, MT_JobID.F21: These are the corresponding MALT input, results and database files that are produced by the automated design process. They are identical to what is produced when you use the CDEGS or AutoGrid Pro software packages and can be accessed using the same tools and methods.
5. Other files that are normally produced when the MALT, FCDIST, and RESAP engineering modules are used. Please consult the CDEGS or AutoGrid Pro documentation for further details.
Working Directory Path Specification: The Working Directory is the location where these input, output and database results files are produced. You can define the working directory by entering or choosing through the Open... or Folder... (for a new session) button to select the directory of your choice in the Working Directory field.
System of Units
AutoGroundDesign stores all data internally using the metric (SI) system of units. When data is displayed as text (in a dialog or any other place), the data is first converted to the user-specified system of units. The program saves the data in the user-specified system of units.
Choose between the Metric or Imperial System of units. The radius can be specified in centimeters (cm) when using the metric system. When using the British system of units, the radius can be specified in inches.
Metric: This is the default choice. The data is specified in meters (m) or centimeters (cm), as indicated in the screen.
Imperial: This option selects the Imperial (old British) units. The data is specified in feet or inches, as indicated in the screen.
When the system of units is changed, you can choose whether all appropriate values are converted or not. However, the overhead shield/neutral wire characteristics will be converted in any case.
Complete: This is the default and recommended option. This option uses the extended two-layer soil grid database. More...
Basic: This option selects the uniform and equivalent two-layer soil grid database. This is a simplified database that can be used for comparison purposes or in some rare and unusual cases where the Complete database is unable to find a suitable initial grid. More...
None / Manual (User-Defined Initial Grid): The method provides further flexibility to a user that wishes to define an initial grid design based on the number of conductors along the grid sides, characteristics of the conductors and rods. The program will then refine this grid automatically. This is a very useful feature that allows a user to start where a previous automated design was interrupted or
failed rather than starting all over again . When this option is selected, the following two new input fields become enabled and should be defined in the Initial Number of Conductors along Zone panel:
Length
Width
For example, there are five remaining issues in the above list: two input errors and three warnings.
Select the first item in the list and double click on it. This will bring you to the location where the input error happens.
Double click on the right bottom of the status bar on the AutoGroundDesign main screen to open this window. If no error or warning is detected, the list is empty.
The user will need to clear all errors/warnings before the design can be started.
This list will be updated automatically whenever there is any change made by the user in the input data.
A complete specification of the data related to a grounding grid requires the following data.
Grounding System
Soil Data. Two options are possible, the Specify Soil Characteristics option where you must specify the structure and characteristics of the soil directly and the Determine Soil Characteristics option where you specify the measured apparent soil resistivity (or resistance) values in order to determine the equivalent soil structure model and characteristics
file://C:\Users\aivanov\AppData\Local\Temp\~hh4231.htm
13/02/2016
AutoGroundDesign: An Overview
Page 3 of 15
Fault Current Contribution Data. Two options are possible, you can specify the magnitude of this current in amperes by selecting the option Specify Grounding System Current, or you can simply select the Determine Grounding System Current option to calculate the appropriate current based on the fault current distribution in the multiple terminal electric network connected to the target grounding
system.
Computations
Safety Criteria. Two options are possible, the Specify Safe Voltages option where you must specify the Touch Voltage and Step Voltage and the Determine Safe Voltages option where you specify the network fault, surface layer data, and equivalent human circuit safety thresholds to compute touch and step voltages.
The type of automated analysis and the type of grounding system design should be determined first before any grounding system specifications.
If a Horizontal Arbitrary Shape Grid and Vertical Ground Rods is to be analyzed, the grounding zone vertices are specified on the following screen by clicking on the Define ... button.
More information on the above screen is available in the Horizontal Arbitrary Shape Grid Vertex Definitions topic.
For other selections of analysis and grounding grid types, you need to specify the following parameters:
Length: This is the length, in m or feet, of the grounding zone. This dimension is assumed to be along the X axis.
Width: This is the width, in m or feet, of the grounding zone. This dimension is assumed to be along the Y axis.
Depth: This is the depth, in m or feet, of the grounding grid in that zone. This dimension is assumed to be along the Z axis.
Conductor Radius: This is the radius of the grid conductor, in cm or inches.
(Initial) Number of Conductors along Zone: This defines the (initial) number of conductors along both zone directions of
Length
Width
Length
Width
Add Rods: This option specifies if ground rods are to be used in the design of the final grid and if required, the way they will be distributed over the whole grid area. The available options are:
n No
j
k
l
m
n Yes
j
k
l
m
If Yes is selected, then the following Rod Placement and Distribution and Rod Specification and Options are available in the Ground Rod Specification and Options tab.
Length: This is the length of the ground rod in m or feet. This value must be positive and must be larger than the radius of the ground rod.
Depth: This is the depth of the ground rod in m or feet. This value must be positive.
Radius: This is the radius of the ground rod in cm or inches. This value must be positive and must be smaller than the radius of the ground rod.
(Initial) Number of Rods along Zone: This defines the (initial) number of rods along both zone directions of
Length
file://C:\Users\aivanov\AppData\Local\Temp\~hh4231.htm
13/02/2016
AutoGroundDesign: An Overview
Page 4 of 15
Width
Place at Conductor Intersections: The rods will be placed at the intersection of two grid conductors.
Place anywhere along Conductors: The rods will be placed anywhere along conductors.
For the Horizontal Rectangular Grid and Vertical Ground Rods option:
Place at Conductor Intersections: The rods will be placed at the intersection of two grid conductors.
Place anywhere within Grid: The rods will be placed anywhere within the grid area.
and
Distribute over Entire Zone: The rods will be distributed over the whole grid area.
Distribute along Zone Periphery: The rods will be placed along the grid periphery.
Illustrate Model
Show Data
The first type of graphics consists of a static illustration of the grounding grid zone to help visually relate the items that are being edited. This static illustration can be displayed by clicking the Illustrate Model button.
The second type of graphics is the data graphics that gives a dynamic two dimensional (2D) visual representation of the horizontal arbitrary shape grid vertices. The vertices can be defined easily by filling in the data in the data grid and when the data is filled, the drawing is updated dynamically. Also, the vertex on the graphic can be dragged easily to change its position and the data is updated
immediately in the data grid.
To display the dynamic graphic, you must click the Show Data.
Click the Refresh button to redraw the grounding grid zone.
Vertex Coordinate:
X_VertexCoordinate: <Real value, default = 0>. X-coordinate of vertex (meters or feet).
Y_VertexCoordinate: <Real value, default = 0>. Y-coordinate of vertex (meters or feet).
Z_VertexCoordinate: <Real value>. Z-coordinate of vertex (meters or feet).
Note that if the vertex coordinate is greater than 10E+6, then the scale is showing.
Hint:
1. The vertex can be selected more easily by clicking on the data grid than by clicking on the display picture.
2. When entering values in the data grid, it is better to have the Show Data (i.e., to have the Illustrate Model button enabled). The data graphics refreshes with each new entry in the grid.
If the Specify Soil Characteristics is selected, the available soil options are:
Uniform: This model consists of two semi-infinite regions of constant electrical properties: the air and a soil layer.
Two-Layer: This model consists of three horizontal regions of constant electrical properties: the air, the top soil and the bottom soil layers.
Three-Layer: This model consists of four horizontal regions of constant electrical properties: the air, the top soil layer, a central layer and the bottom soil layer.
MultiLayer (4 Layers): The soil model consists of four horizontal layers of soil with constant electrical properties. Presently, the input screen interface restricts the number of central layers to two.
MultiLayer (5 Layers): The soil model consists of five horizontal layers of soil with constant electrical properties.
MultiLayer (any number): Presently, the input screen interface restricts the number of soil layers to five.
The following naming conventions are used to define each horizontal layer.
Top: This represents the top soil layer if the soil is horizontally layered.
Central: This represents one of the central layers if the soil is horizontally layered.
Bottom: This represents the infinite bottom layer if the soil is horizontally layered.
Resistivity: This is the resistivity value of the specified layer or region (ohm-meters). This value must be positive.
Thickness: This value represents the thickness of the specified layer in m or feet (no value is available or required for the uniform soil resistivity or the bottom layer one). This value must be positive.
If the Determine Soil Characteristics is selected, The Define Initial Values of Soil Characteristics will be enable and the available soil options are
file://C:\Users\aivanov\AppData\Local\Temp\~hh4231.htm
13/02/2016
AutoGroundDesign: An Overview
Page 5 of 15
Uniform
Two-Layer
Three-Layer
MultiLayer (4 Layers)
MultiLayer (5 Layers)
Automatic
The last option Automatic indicates that the total number of layers in a horizontally layered soil is determined by the program based on the measured apparent resistances/resistivities. For more information on this method, see the topic entitled Automatic Determination of Total Number of Layers in Horizontally Layered Soils.
The initial values of soil characteristics can be specified in the Resistivity and Thickness fields:
Resistivity of Layer n: <Real value, default = 0, valid range of values = [0, ...) >. The initial resistivity of the layer n which will be used in the interpretation of measured apparent earth resistivity (or resistance). The program will automatically select the initial resistivity of layer n if a zero value is assigned to this variable.
Thickness of Layer n: <Real value, default = 0, valid range of values = [0 ,...) >. The initial thickness of the layer n which will be used in the interpretation of measured apparent earth resistivity (or resistance). The program will automatically select the initial thickness of layer n if a zero value is assigned to this variable.
Resistance: <Default value>. Indicates that soil data will be specified as apparent resistance measurements.
Resistivity: Indicates that soil data will be specified as apparent resistivity measurements.
Spacing C1-P1: Distance between current electrode C1 and adjacent potential probe P1 (in meters or feet). For Wenner measurements, this is the distance between any pair of adjacent pins.
Spacing P1-P2: Distance between potential electrode P1 and adjacent potential probe P2 (in meters or feet). For Wenner measurements, this is the distance between any pair of adjacent pins.
Spacing P2-C2: Distance between potential electrode P2 and adjacent current probe C2 (in meters or feet). For Wenner measurements, this is the distance between any pair of adjacent pins.
Spacing C1-C2: Distance between the two current electrodes C1 and C2 (in meters or feet). Required only for Unipolar and Dipole-Dipole measurements.
Apparent Resistance or Resistivity: <Real value, valid range of values = [0,...]>. Measured apparent resistivity (in ohm-m) or apparent resistance (in ohms) depending on the Type option selected.
Convert to General: Click this button to convert measurements specified using the Wenner, Schlumberger or Unipolar method into equivalent measurements specified with the General method. Note that this operation is not reversible, in general.
Notes:
1. Only one traverse or set of measurements should be specified per run, resulting in one apparent resistivity or resistance value per electrode spacing.
2. The apparent resistance is the voltage difference between the potential probes divided by the injection current. The apparent resistivity can be calculated from the following general formula:
R = (K*V/I)/(1/C1P1 + 1/C2P2 - 1/C1P2 - 1/C2P1),
where R is the apparent resistivity (in ohm-m), K is 6.283... (i.e., 2 pi), V/I is the apparent resistance (in ohms), and CiPj is the distance (in meters) between current electrode i and potential probe j.
Measurement Methods
The measurement configuration most widely used in the electric power industry is a four-electrode (probe) method developed by Wenner.
As shown in the figure below, four electrodes (probes) are used, with the outer pair being used as current input probes and the inner pair as potential references.
In AutoGroundDesign, you may specify not only the type of soil model, but also the number of layers and even the initial resistivities and thicknesses of any layers that the user believes are close to those that should be obtained in the computed soil model. In this way, the user can sometimes guide the program to a more satisfactory solution.
On the other hand, it is rare that you will need to specify any parameters other than the soil type (i.e., Horizontally Layered Soils versus Exponential Soils versus Vertically layered Soils ) and the number of layers desired in the computed soil model.
file://C:\Users\aivanov\AppData\Local\Temp\~hh4231.htm
13/02/2016
AutoGroundDesign: An Overview
Page 6 of 15
In the process of soil measurement interpretation, AutoGroundDesign will adjust the characteristics (resistivity) of the uniform soil so that the computed apparent resistivity curve matches the measured apparent resistivities.
Resistivity: <Real value, valid range of values = [0, ...)>. This value is an initial estimate of the resistivity of the uniform soil (ohm-meters). If this value is not specified (default setting), the resistivity is best averaged by the program based on the measured apparent resistances / resistivities.
In the process of soil measurement interpretation, AutoGroundDesign will adjust the characteristics (resistivities and thicknesses) of horizontally layered soils so that the computed apparent resistivity curve matches the measured apparent resistivities. If the real earth structure can be approximated by a multilayer soil model then the total number of layers of the target multiplayer soil and, optionally, initial
guesses of the soil layer characteristics must be specified unless the Automatic layer selection option is selected to determine automatically the most appropriate values. If the automatic determination of the number of soil layers is selected, then the initial guessed values of the layer characteristics are also automatically performed by the program. Otherwise, the user must specify how many layers the target
equivalent (or reconstructed) soil model should have and optionally an initial estimate of the characteristics of each layer. The program will then optimize the soil layer characteristics of the target equivalent soil model.
Possible settings:
Air: <Inactive>. The characteristics of the air above the earth's surface are being specified.
Top: <Default value>. The characteristics of the surface earth layer are being specified.
Central: The characteristics of one of the central earth layers, if any, are being specified.
Bottom: The characteristics of the bottom layer (which extends to infinite depth) are being specified.
The variables are as follows:
Resistivity: <Real value, valid range of values = [0,...)>. Initial resistivity of the specified layer (ohm-meters). If this data is omitted or values are set to 0, then the program determines suitable initial values based on the measurement data.
Thickness: <Real value, valid range of values = [0,...)>. Initial thickness of the layer specified (meters or feet). If this data is omitted or values are set to 0, then the program determines suitable initial values based on the measurement data.
2. Schlumberger Method
3. General Method
4. Unipolar Method
5. Dipole-Dipole Method
Optionally, the lengths of the current and potential electrodes may also be specified. The main block of data consists of a sequence of n data lines (j=1,n) containing the following values:
where
S, Se, Se1: Spacing between a current (outer) electrode C1 and its adjacent potential (inner) electrode P1 (see above figure). For the Dipole-Dipole method, this is the spacing between the current electrodes (C1 and C2).
R: Apparent soil resistance in ohms (i.e., R = V / I) or apparent soil resistivity in ohm-m corresponding to the electrode spacings (i.e., (2piV/I) (1/C1P1+1/C2P2-1/C1P2-1/C2P1) with all spacings specified in meters). When the RESISTIVITY setting is specified in the Measurements module, the measured data should be entered as apparent resistivities. When the RESISTANCE setting or no setting is
specified, the apparent resistance values should be entered.
Do: Is the average length of current electrodes (meters or feet). If this field is blank or zero, then the program assumes a negligible length and will use appropriate formulas (depending on the length of the potential electrodes) to compute the apparent resistivity. Otherwise, it will compute the apparent resistivity based on a more accurate formulation for handling cylindrical spikes.
Di: Is the average length. of potential electrodes (meters or feet). If this field is blank or zero, then the program assumes a negligible length of the current electrodes) to compute the apparent resistivity. Otherwise, it will compute the apparent resistivity based on a more accurate formulation for handling cylindrical spikes.
Si: Spacing between two potential (inner) electrodes (see figure above). For the Dipole-Dipole method, this is the spacing between the inner current and potential electrodes (C1 and P1).
Se2: Spacing between the remaining (outer) electrode C2 and its adjacent potential (inner) electrode (see figure). For the Dipole-Dipole method, this is the spacing between the two potential electrodes (P1 and P2).
C1-C2: Spacing between the two current electrodes C1 and C2.
Properties of the apparent resistivity curve and correspondence between the total number of layers and measured resistivity data
Based on the study of theoretical resistivity curves (also known as sounding curves) of Wenner or Schlumberger configuration, the following properties are generally observed [1,2], regardless of the number of layers or resistivity distribution with depth. For the convenience of the reader, the properties in [1] are included as follows:
1.
2.
3.
4.
5.
Figure 1, Figure 4 and Printouts 1 to 4 better illustrate these properties (in particular No. (4)). Figure 1 to Figure 4 show four typical measured resistivity points (dots) superposed with the resulting computed apparent resistivity curve (line) which corresponds to horizontal two-layer, three-layer, four-layer and five-layer soil models, respectively. Printouts 1 to 4 provide their corresponding soil models that
are obtained by the program.
For example, Figure 1 shows a two-layer soil model in which the soil resistivities vary from high to low. The asymptotical value at smaller spacings corresponds truly to the top layer resistivity, while the asymptotical value at larger spacings corresponds truly to the bottom layer resistivity. Such one-to-one correspondence does not apply to any other layers between the top and bottom layers. The reason is
very simple: the measured apparent resistivities corresponding to any layers between the top and bottom layers are influenced by the top and bottom layer resistivities during the measurement (assuming a 4-pin electrode method). For a three-layer soil shown in Figure 2, the middle layer soil resistivity 792 W-m (see Printout 2) is slightly higher than the highest measured apparent resistivity data 780 W-m,
simply because the top and bottom layer resistivities are lower. For the same reason, the true middle layer resistivity is always lower than the measured apparent resistivity data if a High-Low-High three-layer soil type is encountered. Such effects are even more pronounced in Figure 3 and Figure 4 and their corresponding soil models in Printouts 3 and 4. Furthermore, a minimum total number of layers
can be obtained by counting the number of extreme (maximum or minimum) on the measured apparent resistivity curve. Figure 3 is a four-layer soil since the data exhibit one peak and one valley, while Figure 4 exhibits one peak and two valleys which leads to a five-layer soil model, and so on.
It is obvious that for a given set of soil resistivity measurement, there are a number of electrically equivalent soil models. For instance, a five-layer or six-layer soil models would also fit the measured data in Figure 3. However, a smaller number of layers will consume usually less computation time in MALT or MALZ. Besides, since they are all electrically equivalent, the computation results from MALT
or MALZ should be very similar. Therefore, for a given set of soil measurements, we should look for the electrically equivalent soil model with the least number of layers possible.
Figure 1: Computed
file://C:\Users\aivanov\AppData\Local\Temp\~hh4231.htm
13/02/2016
AutoGroundDesign: An Overview
Layer Number
1
2
-
Page 7 of 15
Resistivity (ohm-m)
364.5703
63.76699
-
Thickness (Meters)
0.6672840
Infinite
-
Layer Number
1
Resistivity (ohm-m)
273.8638
792.3849
114.4890
269.4607
Infinite
Thickness (Feet)
2.317178
Layer
Number
1
2
3
4
Resistivity
(ohm-m)
206.2624
3239.253
67.99847
582.0868
Thickness
(Feet)
2.806843
2.179909
7.562907
Infinite
Thickness
(Meters)
1.013675
5.708103
19.78955
36.22168
Infinite
Basis of Method
The task of the automatic determination of the total number of layers is to determine the total number of layers based on measured resistivity data. As demonstrated in the preceding section, the basis of the method lies in a fact that the total number of layers is best reflected by the number of extreme or bends on measured apparent resistivity curves. The key point of the method is thus to determine the
number of extreme or bents on the measured resistivity curve which always contains noise on the data points. To overcome this difficulty, a data-smoothing step is carried out first using a Windows Median technique [3]. Using the smoothed data, the number of extremes is then obtained using the modified Brent's method [3]. The properties of sounding curves listed in the preceding section have also been
incorporated as guidelines in both the data smoothing and the second step that determines the number of extremes. Note that the smoothed data is only used to determine the total number of layers. The original measurement data is still used to obtain the final soil model.
References
1. Zohdy, A. A. R., "A new method for the automatic interpretation of Schlumberger and Wenner sounding curves", Geophysics, Vol. 54, No. 2, pp.245-253, 1989
2. Esparza, F. J., "1-D inversion of resistivity and induced polarization data for the least number of layers", Geophysics, Vol. 62, No. 6, pp.1724-1729, 1997
3. Press, W. H., Flannery, B. P., Teukolsky, S. A., and Vetterling, W. T., Numerical Recipes, Cambridge University Press, Cambridge, 1989
file://C:\Users\aivanov\AppData\Local\Temp\~hh4231.htm
13/02/2016
AutoGroundDesign: An Overview
Page 8 of 15
For each new terminal, you may type new terminal name in the New Terminal Name and choose the type for this new terminal from the following terminals:
The Add Terminal button is used to create the new terminal. The Edit Terminal button is used to input or edit the characteristics of the terminal.
The Copy Terminal button will copy the chosen one of the existing terminals to the new terminal. This new terminal will automatically inherit the characteristics of the former. In order to erase all data you have entered for the terminal currently being displayed and start over, click the Delete Terminal button.
The Editing Terminal screen is used to introduce a terminal whose data is to be specified.
The circuit model of a transmission line network consists of three basic elements: i) a central site, ii) terminal stations, and iii) transmission lines connecting the central site to the terminal stations. These elements, and the data required by the program to specify them, are explained in more detail below:
Central Site. This is a node that connects to all arms of the network. The user must specify the central site ground impedance (i.e., shunt impedance). Typically this site represents a faulted substation or transmission line structure and the shunt impedance is set equal to the ground impedance (resistance) of the faulted site. Only one central site can exist in a given circuit run.
Terminal Stations. At least one, and possibly several, terminal stations may exist in each circuit model. The terminal station consists of a ground impedance representing the impedance of the terminating station ground network and a current source that energizes the transmission line. The data specified by the user are as follows:
Terminals: each arm of the transmission line ends in a terminal section. You must create the terminal by specifying the terminal name. In this version, you can not select an arbitrary ground impedance for the terminal. Only a small or very large value can be selected by opening or closing a switch.
Sources: each arm of the network is energized by a current source whose current can be specified with a user-defined magnitude and phase angle (or as a complex number) relative to the current sources of the other terminals. Each source is connected to the transmission line ground (or neutral or static) wire group through a switch that can be opened or closed. In this version this connection can not
have a user-defined mutual impedance with respect to the phase wire (the default value of the mutual is set to 0 ohm).
Transmission Lines or Power Cables. The transmission line is modeled as a single faulted phase and a single ground (or neutral or static) wire group. Each transmission line or cable is made up of sections (i.e., spans) that are all of the same length. Each span is terminated by a ground shunt connected to the ground wire group. This represents the ground impedance of the transmission line towers (or cable
man holes) connected to the ground wire group (or sheath and armour group). Each section of the ground wire group has a series impedance and mutual impedance with respect to the faulted phase. Data entered by the user is given below:
Faulted Phase: the location of the faulted phase is specified in terms of its cross-sectional location in the right-of-way.
Ground (or Neutral or Static) Wire Group: the circuit model also includes a single ground (or neutral or static) wire group. It can be composed of several conductors regularly arranged on the perimeter of a circle. Its location is specified in terms of the position of the group's center and the number of conductors, and the position of the first conductor. The ground wire group has a series impedance
and a mutual impedance with respect to the faulted phase that can be calculated by the program or specified by the user. More details are provided in the conductor-data help topic.
Section (Span) Shunt: each section (or span) of the transmission line has a ground shunt impedance located at its extremity which is furthest away from the central site. The section shunt represents the ground impedance of the transmission line structures. This ground shunt is a complex-valued quantity which is the same for all structures in a given arm of the transmission line network.
The user must also specify the span length and the total length of all spans in each transmission line arm.
Note that terminal, source, ground wire group, section and phase parameters must be specified separately for each transmission line arm, i.e. for each specified terminal.
To fully describe the transmission line network, it is also necessary to specify the electrical characteristics (resistivity and permeability) of the soil in which the network is located. A uniform soil model is used. The user must also specify the power system frequency. This value is specified in the Safety specification tab.
The span (section) length is the same for all sections in a given arm of the transmission line (or power cable) network. When the impedances are specified directly, the span length is not required.
Distance between the ground wire group center to the center of each ground wire.
Relative permeability of members of the ground wire group. Alternatively, this value can also be specified as the geometric mean radius or the 60 hertz reactance at 1 foot spacing of the conductor (the option selected depends on the setting of a flag specified by the user). This value can be retrieved automatically from a conductor database (see Note 2).
Relative resistivity of members of the ground wire group. Alternatively, the user can specify this parameter in terms of the conductor dc resistance or the conductor ac resistance (the option selected depends on the setting of a flag specified by the user). This value can be retrieved automatically from a conductor database (see Note 2).
External radius of members of the ground wire group. This value can be retrieved automatically from a conductor database (see Note 2).
Internal radius of the members of the ground wire group, in the case of hollow conductors (this is 0 for solid conductors). This value can be retrieved automatically from a conductor database (see Note 2).
Notes:
1. All members of a ground wire group must be identical and arranged along the perimeter of a circle at regular intervals (i.e., at the vertices of a regular polygon).
2. If the conductor does not exist in the supplied default databases, a new database can be used to add the conductor data for subsequent use.
For the faulted phase, the coordinates must be specified in order to calculate the mutual impedance between the faulted phase and the ground wire group.
Further Details
The user must specify the magnitude and phase angle of the power source current energizing each terminal (arm) of the transmission line network. Typically, this value represents the current in the faulted phase. If the currents in the non-faulted phases are not negligible, the current flowing in the phase conductor is specified as the total vector sum of the three phase currents. This improves the accuracy of
the calculation of the currents in the central site and in each tower.
The program accepts source currents in Cartesian or Polar notation. By default, the program uses the Cartesian notation.
Network Configuration
The Shield Wire Coordinates and Phase Wire Coordinates are used to specify the characteristics of neutral (or ground or shield) and phase conductors belonging to a given terminal.
1. Distribution Line (DL) with 1 Neutral or Overhead Transmission Line (or DL) with 1 Shield Wire
Ys <Real value, default = 0>: Y-coordinate of the neutral/ground/shield wire, in meters or feet.
Zs <Real value, default = 35>: Z-coordinate of the neutral/ground/shield wire, in meters or feet.
Yc <Real value, default = 0>: Y-coordinate of the geometric center of the neutral/ground/shield wire(s), i.e., conductor center (if only one) or midpoint between conductors (if two) or bundle center (if one bundle), in meters or feet.
Zc <Real value, default = 35>: Z-coordinate of the geometric center of the neutral/ground/shield wire(s), in meters or feet.
Number of Wires (N) <Integer value, default = 1, valid range of values = [1,...]>: Number of neutral or shield or overhead ground conductors.
Starting Angle S (Degrees) <Real value, default = 0, valid range of values = [0,360]>: Angle (in degrees) between the positive y-axis and a ray traced from the geometric center of the neutral/shield overhead ground conductors to one of these conductors. Angle is always positive and is measured counterclockwise from the positive y-axis.
Bundle Radius <Real value, default = 0, valid range of values = [0,...]>: Distance of neutral or shield or overhead ground conductors from their geometric center, in meters or feet.
Note:
Specify the external (re) and internal (ri) radii of each individual neutral or shield or overhead ground wire conductor. For a solid conductor, specify 0. These values are automatically retrieved when the wire is selected from the conductor database.
file://C:\Users\aivanov\AppData\Local\Temp\~hh4231.htm
13/02/2016
AutoGroundDesign: An Overview
Page 9 of 15
Yc <Real value, default = 0>: Y-coordinate of the cable shield center, i.e., conductor center (if only one) or midpoint between conductors (if two) or bundle center (if one bundle), in meters or feet.
Zc <Real value, default = 35>: Z-coordinate of cable shield center, in meters or feet.
Further Details
The coordinate system used assumes the z-axis to be vertical, the y-axis to be at ground level, and the y-z plane to be such that the transmission line conductors pierce it at right angles.
Sections
Total Line Length (Dt) <Real value, , valid range of values = [0,...)>: Total line length of the power line associated with the terminal. The units are in meters or feet depending on the Units selected in the Main screen.
Section Length (Ds) <Real value, default = 1000, valid range of values = [0,...)>: Section or span length. This is a constant (average) value for all sections. The units are in meters or feet depending on the Units selected in the Main screen.
Tower Ground Impedance or Power Cable Man Hole Ground Impedance (Ohms):
Rt <Real value, default = 10>: Resistive component of the (average) shunt impedance to earth of the neutral (or shield or overhead ground) wires per section (in ohms). Typically, this value represents the structure ground resistance.
Further Details
The shunt impedance is modeled as a lumped impedance at one end of each section (at the end furthest away from the central station).
The following parameters for the characteristics of the neutral conductors must also be defined or imported automatically from the conductor database.
Internal Reactance (select and enter one of the three following values):
1. Relative permeability (relative to 1.2566 E-06 henries/meter - free space) <default value is 1>
2. Geometric mean radius (in feet or meters)
3. 60 hertz reactance at 1 foot spacing (in ohms/mile or ohms/km)
Internal Resistance (select and enter one of the three following values):
1. Relative resistivity (relative to 1.7241 E-08 ohm-meters - annealed copper) <default value is 1>
2. DC resistance (in ohms/mile or ohms/km)
3. AC resistance (in ohms/mile or ohms/km). This resistance value should correspond to the specified power system frequency. The AC resistance should only be used for frequencies below 2 kHz.
Note that the above data can be automatically imported from the built-in database, rather than being typed in. Click the Define... button to do so.
Computations
The Computations tabbed region specifies the frequency and settings for a group of equally spaced observation points where earth potentials are to be computed.
Frequency: The system frequency in Hertz is used for calculating the electric line parameters. It is also used to calculate the Decrement Factor at the corresponding fault duration, which accounts for the asymmetrical current component. The default value is 60 Hertz.
Observation Points: Specific soil locations where the program carries out earth potential calculations. The following options are used to select the observation point settings:
Automatic: Instructs the program to select the most appropriate observation point settings.
User-Defined: The observation point preferred settings are defined by users. They must be equally spaced and lying on the same line profile. This option is available only for horizontal arbitrary shape Grid.
Preferred Point Spacing during Iteration: Defines the preferred spacing between the points in the potential profiles during iterations (meters or feet).
Preferred Point Spacing for Final Results: Defines the preferred spacing between the points in the potential profiles for the final computation (meters or feet).
Notes:
Efficient and intelligent techniques have been developed to generate different types of observation points in order to accurately carry out computations and at the same time minimize the computation time during the iterative design steps and the final results computation steps. There are two ways to create observation points.
Safety Criteria
Use the Safety Criteria Specification tabbed section to define the data that control the safety analysis carried out by the program. It allows you to select which quantities should be analyzed, the region where they should be analyzed and the values that are considered safe for these quantities.
The automated design process requires the following three values in order to decide if a specific grid design meets the target safety criteria.
1. Maximum acceptable GPR: This is the maximum acceptable ground potential rise of the grid in volts. The default value is 5000 V. This value must be positive.
2. Touch Voltage: This is the maximum allowable safe touch voltage within the grid zone in volts. This value must be positive.
3. Step Voltages within and outside Grid: These are the maximum allowable safe step voltages within the substation area and outside where the surface insulating material (crushed rock or asphalt). These values must be positive. More ...
The user should specify a very large value for any of these parameters if they are not to be used during the automated design process.
The Maximum acceptable GPR must be specified directly by typing the applicable value if it is relevant in the context of the automated design session. The last two values, namely the allowable touch and step voltages can be specified directly as well or can be determined based on the IEEE or IEC standards. The two options are:
i Determine
j
k
l
m
n
j Specify
k
l
m
n
Safe Voltages
Safe Voltages
Surface Layer Data: The resistivity and thickness (in cm or inches) of the layer covering the soil surface above the grid is specified in this panel. This high resistivity material is used to provide a semi-insulating layer (i.e., earth surface covering layer) to protect the assumed bare-footed person. The applicable data fields are:
Resistivity: This is the surface layer resistivity (ohm-m) that will be used to determine the safe voltage values. This value must be positive.
Thickness: This is the surface layer thickness (cm or inches) that will be used to determine the safe voltage values. This value must be positive.
Within Grid: This indicates the resistivity and thickness (in cm or inches) of the surface layer within the substation area.
Outside Grid: This indicates the resistivity and thickness (in cm or inches) of the surface layer outside the substation area (where it may be an insulating material like crushed rock or asphalt).
Network Fault Data: The parameters in this panel represents data used to calculate the asymmetrical magnitude of the fault current. The available fields are described hereafter.
Default Value (based on X/R=20): The decrement factor is automatically calculated on the assumption that the system X/R ratio equals 20.0.
Computed from X/R Ratio: The decrement factor is automatically calculated based on the specified system X/R ratio.
file://C:\Users\aivanov\AppData\Local\Temp\~hh4231.htm
13/02/2016
AutoGroundDesign: An Overview
Page 10 of 15
X/R Ratio: The computed decrement factor that derates the fibrillation current threshold to account for the asymmetrical current component associated with short duration faults is based on this ratio. The decrement factors are automatically calculated on the basis of a user-specified system X/R Ratio (the default value is 20.0). This value must be positive. It is accessible only if Computed from X/R Ratio
is selected.
Decrement Factor: This value represents the decrement factor used to derate the fibrillation current threshold to account for the asymmetrical current component associated with short duration faults is a computed value based on a user-specified X/R ratio. This value must be greater than 1. It varies normally between 1 and 2. It is accessible only if User Defined is selected.
Note that the system frequency in Hertz is used for calculating the Decrement Factor at the corresponding fault duration, which account for the asymmetrical current component. The default value is 60 Hertz.
Please refer to the topic entitled Equivalent Human Circuit Safety Thresholds for more options.
The ANSI/IEEE Standard 80 formula suggested for 50 kg body weight, based on Dalziel's studies, is used to calculate the fibrillation current threshold
The ANSI/IEEE Standard 80 alternative formula for 70 kg body weight, based on Dalziel's studies, is used to calculate the fibrillation current threshold.
The fibrillation current threshold is calculated according to fibrillation current versus current flow duration curves published in IEC Report 479-1.
Use the Fibrillation Current Calculation Method dropdown box to select the calculation method for the maximum acceptable current (typically the fibrillation current). Six methods are available as well as a manual definition method as listed hereafter.
50KG-IEEE: This is the default value. It selects the IEEE Standard 80 method for a 50 kg human to calculate the fibrillation current based on Dalziels formula.
70KG-IEEE: This option selects the IEEE Standard 80 method for a 70 kg human to calculate the fibrillation current based on Dalziels formula.
C1-IEC: This option selects the IEC (curve C1) method to calculate the fibrillation current. The C1 curve suggests a negligible probability of ventricular fibrillation to occur. The more rigorous definition is that the probability of fibrillation between the C1 and C2 curves increases progressively from a very low value (about 0.5% or less) to 5%, once C2 is reached.
C2-IEC: This option selects the IEC (curve C2) method to calculate the fibrillation current. The C2 curve represents the limit at which the probability of ventricular fibrillation reaches 5%.
C3-IEC: This option selects the IEC (curve C3) method to calculate the fibrillation current. The C3 curve represents a 50 % probability of ventricular fibrillation to occur.
B-IEC: This option selects the IEC (curve b) method to calculate the maximum body current for long fault exposures. The "b" curve suggests a likelihood for muscular contractions, difficulty in breathing and transient cardiac arrest without ventricular fibrillation.
User-Defined: This option uses the user-defined fibrillation current (in A). When this selection is picked, a text box (with the Current label) appears to let the user enter the desired value in amps. This value must be positive.
More information on the safety parameters related to the equivalent electrical model of a person and methods to determine this equivalent model is given hereafter.
IEEE Std. 80 Method: This default option selects the IEEE 80 Standard as the reference for calculating the body resistance.
IEC 479 Method: This option selects the IEC 479 standard to select the suggested body resistance value of 1000 ohms. The body resistance is calculated according to stress voltage versus body resistance curves published in IEC Report 479-1. The applicable body resistance as a function of the computed or estimated applied voltage is determined. The user selects one of the three following curves
that encompass different proportions of the population.
1. Body Resistance of 95% of Population Exceeds Curve. This is the default value that encompasses the majority of the population.
2. Body Resistance of 50% of Population Exceeds Curve. This value encompasses half of the population.
3. Body Resistance of 5% of Population Exceeds Curve. This value encompasses a minority of the population.
User-Defined: This option allows you to specify your own value of body resistance of the prospective victim. This option is useful to study problems involving a typical scenarios and environment conditions. When this option is selected, a textbox field is enabled to allow you to enter the applicable value in ohms.
100% (hand-to-hand): This, typically corresponds to a hand-to-hand contact or a single-hand-to-single foot contact
User Defined: This option allows you to specify any percentage that corresponds to your scenario. In this case, a text box field, Percentage, is enabled that allows you to enter the appropriate percentage value (in %)
IEEE Std.80-2000: This is the default method. It selects the IEEE Standard 80 (2000 edition) method which uses an exact series expansion that calculates the foot resistance (and the Cs correction factor, see the following for more information) based on a two-layer soil model consisting of the surface covering layer and the native top soil layer (assumed to be of infinite thickness).
IEEE Std.80-1981: This option selects the older IEEE Standard 80 (1981 edition) method that assumed a very thick layer of surface covering material. In other words, it assumes that the Cs factor is 1.0 to calculate the foot resistance.
User-Defined: This option uses the user-defined foot resistance in ohms (based on a 1 ohm-m infinitely thick surface covering layer) to estimate the foot resistance for the selected surface layer resistivity requested in the safety panel. Note that when this option is selected, values for the Foot Resistance R-1 (for a 1 ohm-m soil) and Surface Covering Layer Resistivity must be entered.
The foot resistance Rfoot value used in the safety criteria calculations is automatically determined if you select the first two options. If you select the User-Defined option you must specify its value directly. If you specify the value, provide the resistance of one foot in a 1 ohm-m uniform soil (typically, 3 ohms). When computed by the program, the equivalent feet ground resistance is calculated as follows:
where Rhos is the surface covering layer resistivity, Rfeet-touch is the parallel resistance of both feet for touch voltages, Rfeet-step is the series resistance of two feet for step voltages, Cs is a reduction factor for derating the nominal value of surface layer resistivity, and Rextra is an optional extra resistance which can be included, for example, to model the resistance of a boot as explained hereafter. Cs is a
function of surface layer resistivity, surface layer thickness, and equivalent subsurface layer resistivity. When the IEEE Std. 80-2000 is selected, Cs is calculated using an accurate expression of the foot resistance in a two-layer soil. When the IEEE Std.80-1981 is selected, Cs is simply set to 1.
Extra Resistance: It is possible to specify an additional resistance that is inserted in series with the body resistance and feet resistance to emulate the effects of gloves, shoes or any insulated tool. This resistance is shown as Extra Resistance in the Safety panel. This value is in ohms and must be greater or equal to zero. This component of the persons body current path is not proportional to the surface
material. For example, this value may represent the resistance of insulating boot.
IEC Options
The following options are available when the Determine Safe Voltages option is selected and an IEC-based method is selected for the Fibrillation Current Calculation Method or the Body Resistance Data in the Equivalent Human Circuit Safety Thresholds tab. Depending on the options that are specified, some fields or options may not be accessible for editing.
IEC Standard Revision: Identifies the revision of the IEC standard to be used.
Contact Moisture: Specifies the moisture level of the contact surfaces for the calculation of the body resistance using the 2005 revision of the IEC standard.
Dry (Default): Dry contact surfaces. Corresponds to normal indoor environmental conditions.
Water Wet: "Water Wet" contact surfaces. Corresponds to skin exposed for 1 minute to water of average resistivity 35 Ohm-m and pH from 7 to 9.
Salt-Water Wet: "Salt-Water Wet" contact surfaces. Corresponds to skin exposed for 1 minute to water of average resistivity 0.3 Ohm-m and pH from 7 to 9.
The safety module is independent from the rest of the software. Thus, the computed safety voltage limits, which are displayed on screen and stored to the report file, are not used by the grid performance computation modules. They are used to decide whether to stop or continue the design process until the maximum number of iteration steps is reached.
By default, the touch and step voltage limits are computed based on the following parameter values:
file://C:\Users\aivanov\AppData\Local\Temp\~hh4231.htm
13/02/2016
AutoGroundDesign: An Overview
Page 11 of 15
Maximum Number of Design Iterations: The iterative process will continue until either a design is found which meets all of the safety criteria, or this maximum number of iterations is exceeded. This value must be positive and should not exceed 99. This upper limit was selected for practical reasons to guard against typing errors and is not based on any other considerations.
Minimum Number of Grid Segments: The minimum total number of conductor segments desired in the Main-Ground electrode after subdivision has been performed. Specification of this value is optional. If the value specified is zero or is left blank, then an automatic subdivision process may take place if the following condition is true. All conductors are examined sequentially and if the [(conductor
length/(average conductor length) + 0.75] is equal to or larger than two, then the conductor is subdivided in two or more segments depending on the calculated (integer) value . The average length is also calculated sequentially, first, for the main electrode and then by adding the total length of each additional electrode being considered. Note that this number may be exceeded in some cases due to
subdivision at nodes (i.e., locations where conductors contact each other), at soil boundaries, or according to user-specified presubdivision numbers associated with each conductor. Note also that if the program's arrays are completely filled at any time during the subdivision process, no further subdivision takes place.
Design Evolution Method: This evolution method specifies the performance and progress of the automated design process. The following methods can be used:
AUTOMATIC: This option selects the most appropriate method that will be used to determine the mesh numbers in the next iteration. This is the default option.
MIDPOINT: Select the MIDPOINT option to instruct the program to use the midpoint of two previous iterations of the mesh numbers as the next mesh number for the next iteration.
LINEAR: Select the LINEAR option to instruct the program to use a simple linear curve fit approximation to compute the mesh numbers of the next iteration based on previous iterations.
USER-DEFINED: The control parameters of the iteration process are defined by the user.
BINOMIAL: Select the BINOMIAL option to instruct the program to use a binomial curve fit
approximation to compute the mesh numbers of the next iteration. (not active presently)
CUBIC: Select the CUBIC option to instruct the program to use a cubic curve fit approximation to compute the mesh numbers of the next iteration. (not active presently)
POLYNOMIAL: Select the POLYNOMIAL option to instruct the program to use a polynomial curve fit approximation to compute the mesh numbers of the next iteration. (not active presently)
The Mesh Growth Factor controls the rate at which a given grid is enhanced to yield the next grid configuration to be analyzed in the following design iteration. More precisely, when a grounding system is found to be unsatisfactory during an iteration cycle, the number of horizontal conductors is increased by this "mesh growth factor" to produce the grounding system to be modeled in the next iteration.
For example, specifying a grid mesh growth factor of 50% means that a grid with 16 horizontal conductors in the current iteration will acquire 8 additional horizontal conductors in the next iteration. This variable is also used to control the number of horizontal conductors that need to be removed during the refinement procedure. This value must be positive and should not exceed 100%. This upper limit
was selected for practical reasons to guard against typing errors and is not based on any other considerations. In most cases, this mesh growth factor should be based on economical considerations. It should represent the acceptable over design margin that can be tolerated as economically acceptable. In fact, presently, the design iteration process will stop if an acceptable grid is found and the difference
between this acceptable grid and the one in the previous iteration is less than 50% of this mesh growth factor.
The Design Refinement Level specifies the type of design refinement process to apply. If None is selected, no design refinement will be applied to the automated design process. In other words, the mesh growth factor is used only to proceed from one design to the next until either a design is found which meets all of the safety criteria, or the maximum number of iterations is exceeded. The refinement
process consists of removing or adding grid conductors in an efficient way as appropriate in order to avoid over designed grounding grids. If Basic is selected, then the basic refinement process will proceed by removing or adding grid conductors based on the mesh growth factor. If Advanced is selected, then the advanced refinement process will proceed by removing or adding one conductor at a time
based on the mesh size.
Soil Weighting Factor (Basic Database): This option is enabled only if the Basic reference database radio button option that specifies which grid database is to be used for the automated design has been selected. It specifies the soil layer weighting coefficient to be used for the automated design that references the Basic database. Two options are available.
Automatic: The soil layer weighting coefficient is to be used for automated design is automatically selected by the software algorithms. This is the default option.
User Defined: The soil layer weighting coefficient is defined by entering the appropriate value in the prescribed field that has been enabled.
The program uses either a user-specified or automatically calculated soil layer weighting
coefficient to elaborate an initial grounding system design when a two-layer soil is involved.
This coefficient indicates the relative importance (weight) to be given to each soil layer
when estimating the performance of the initial design. When only the bottom layers are to
be considered (e.g. when the grid and rods are confined to the bottom layers), the coefficient
value should be 0.0; when only the top layers are to be considered, the coefficient value
should be 1.0. Intermediate values indicate that both shallow depth layers and deep layers
should be considered to a greater or lesser extent. The computation equation is as follows:
When the soil is multilayered, the user must regroup the soil layers according to shallow or
deep depth categories. This approach should be made based on the equivalent two-layer soil
that represents the best fit.
1.
Note that your input data will be saved automatically to AD_Jobid_backup.f05 if you have loaded a previously created session file named AD_jobid.f05. Therefore, if for any reasons you need to recover your previous session data, you can do it by opening the _backup?tagged file.
2.
When the processing begins, a small window (the Message Window) appears and displays information, warning or error messages regarding the progress of the computations. See computation message window style for more information.
file://C:\Users\aivanov\AppData\Local\Temp\~hh4231.htm
13/02/2016
AutoGroundDesign: An Overview
3.
Page 12 of 15
The program computes all necessary quantities, analyzes the grid design, and verifies the grid performance according to your safety criteria. The processing tasks include the following steps:
Selecting an appropriate set of observation points in the safety zone where the analysis should be conducted (this is done automatically in this release, future releases will allow users to select arbitrary observation points)
Determining an initial and appropriate grid within the AutoGroundDesign grid database
Computing the earth potentials and grid GPR at the fault site
Computing the safety limits for the touch and step voltages
Examining and comparing the computed touch and step voltages against the safe values
4.
Once the processing is finished, the plots and reports data that can be displayed using the View Designed Grid, View Design Summary File and View Plots and Reports buttons.
For information on the role or function of each button on the interface, see the topic entitled Using the AutoGroundDesign Windows Interface.
View Designed Grid: This starts the SESCAD program, a graphical utility for the development of conductor networks. This CAD program uses an object-oriented approach to network development. See SESCAD Help File for more information on SESCAD.
View Plots and Reports: This starts the GRServer program, a software that produces a large variety of plots and reports based on AutoGroundDesign computation results. See GRServer User Guide for more information on GRServer.
Note that you can use these programs to examine the computation results and print selected reports. The program creates a copy of all reports in the working directory folder for the processed scenario.
Ground Resistance Estimator: This option allows you to compute the ground resistance of the selected grounding system model based on the specified grounding system configuration and dimensions.
Electrode Configuration Predictor: This option determines the optimal configuration of the selected grounding system model that exhibits the Expected Resistance or less. In this case, the grounding zone (dimensions) will not change but the total number of conductors will be determined in order to meet the expected ground resistance value.
Electrode Dimension Predictor: This option computes the required dimensions of the selected grounding system model that exhibits the Expected Resistance or less. In this case, the grounding zone (dimensions) will be adjusted proportionally in order to meet the expected ground resistance value. However, the total number of conductors will not change.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Rectangular Horizontal Grid with or without Ground Rods : The grounding system is made of a number of horizontal conductors with or without rods forming a rectangular grid.
Horizontal Arbitrary Rectangular with or without Ground Rods : The grounding system is made of a number of conductors with or without rods forming a horizontal arbitrary rectangular grid.
One Horizontal Wire : The grounding system is made of a single straight horizontal conductor which is horizontally buried in the soil.
Array of Horizontal Parallel Wires (2 or more) : The grounding system is made of an array of horizontal parallel conductors without any perpendicular horizontal conductors.
Array of Horizontal Radial Wires : This type of grounding system consists of a number of conductors originating from the same point and forming a star-shaped array of conductors.
One Ground Rod (vertical wire) : The grounding system is made of a single straight vertical conductor buried in the soil.
Linear Array of Ground Rods (2 or more) : This grounding system is made of vertical conductors or rods equally spaced from each other and distributed along a straight line.
Rectangular Array of Ground Rods (vertical wires) : This grounding system is made of regularly spaced vertical conductors or rods distributed over the specified rectangular zone.
Circular Array of Ground Rods : This is a grounding system made of vertical conductors or rods equally spaced from each other and distributed along a circle.
Horizontal Rectangular Plate (approximation) : This is a grounding system which consists of a large number of horizontal conductors forming a very dense grid. It is almost equivalent to a metallic plate buried in the soil and having the same dimensions as the grounding system zone.
Vertical Rectangular Plate (approximation) : This is a grounding system which consists of a large number of conductors forming a very dense vertical grid. It is almost equivalent to a metallic plate buried in the soil and having the same dimensions as the grounding system zone.
file://C:\Users\aivanov\AppData\Local\Temp\~hh4231.htm
13/02/2016
AutoGroundDesign: An Overview
12.
13.
14.
15.
16.
Page 13 of 15
Horizontal Rectangular Plate: This is a horizontal metallic plate buried in the soil
Vertical Rectangular Plate: This is a vertical metallic plate buried in the soil.
Circular Ring (approximation) : This type of grounding system approximates metallic circle buried in the soil.
Circular Plate (approximation) : This is a grounding system which consists of a large number of horizontal circular and radial conductors forming a very dense circular electrode. It is almost equivalent to a metallic plate with the same dimensions.
Hemispherical (approximation) Electrode : The grounding system is made of a very dense circular electrode and a series of conductor rings with different ring radii buried at different depths as well as a large number of conductors connecting the rings together. All these conductors form a hemispherical volume of dense metal buried in the soil. It is used to emulate an hemispherical volume made of
metal.
Zone Length: The length of the grounding system in m or feet. This dimension is assumed to be along the X axis. Or Radius of Electrode: This is the radius of circular ground electrodes, such as hemispheres, circular plates, rings, etc.
Zone Width: The width of the grounding system in m or feet. This dimension is assumed to be along the Y axis.
(Initial)Number of Conductors along Zone Length: This number determines the number of horizontal conductors along the grid zone length.
(Initial)Number of Conductors along Zone Width: This number determines the number of horizontal conductors along the grid zone width.
Total number of Conductor Segments along Circumference: This number determines the density of metal used to model circular ring, hemispherical electrodes or circular plates (approximation).
Total number of Conductor Segments along Radial Direction: This number determines the density of metal used to model hemispherical electrodes or circular plates (approximation).
(Initial)Total Number of Radial Wires: This number determines the density of metal used to model the array of horizontal radial wires.
(Initial)Number of Rods along Zone Circumference: This number determines the number of ground rods along zone circumference.
(Initial)Number of Rods along Zone Length: This number determines the number of ground rods along zone length.
(Initial)Number of Rods along Zone Width: This number determines the number of ground rods along zone width.
Maximum Number of Ground Rods: This number restricts the total number of ground rods that can be added to the grounding grid. This value should be at least four and cannot exceed the program capacity (depends on the released version).
Minimum Rod Spacing: This spacing represents the minimum allowable spacing between rods (in m or feet). This value must be zero or positive. If a zero value is specified, the program will determine a suitable value.
Maximum Rod Spacing: This spacing represents the maximum allowable spacing between rods (in m or feet).
Environment
Color Preferences
Frequency: This is a convenient setting that allows a user to always start a new input session with the most frequently used network frequency.
Units System: This is a convenient setting that allows a user to always start a new input session with the most frequently used units system.
Computation Message Window Style: When the AutoGroundDesign computation process is launched, messages and information on the computation performance and progress are displayed in a window that can be one of the following two types:
1. CDEGS Style : This is exactly the type of window that is used by the CDEGS engineering modules such as RESAP or MALT.
2. AGP (AutoGrid Pro) Style : This is a window style that is very similar to the one displayed while the AGP module is processing the computations. It is based on a Rich Text window that can be edited and saved to a file.
Loading of Last Input Session File: If you wish to load the last input session file you were working on before you start a new AutoGroundDesign session file, select the appropriate radio button. Otherwise, you will always start a new session file whenever you launch an AutoGroundDesign session.
When Starting AutoGroundDesign: If you wish to load the last valid session file you were working on before you start a new AutoGroundDesign session file, select the appropriate radio button. Otherwise, you will always start a new session file whenever you launch an AutoGroundDesign session.
Display MessageBoxDialogues while Loading Data: If you wish to display each possible message, such as the error, warning, and information message, individually, you should select the option Yes. Otherwise, you will always display all possible messages together within one page.
The Windows XP Style: In this mode you have no direct control on the background colors of several areas of the AutoGroundDesign interface (the controls will be disabled). However, your interface will follow the style you have selected in your Windows XP environment settings. Note that when you select this style, it will not be effective immediately. It will be applied only when your session is
restarted.
The Normal Style: In this mode you have a direct control on the background colors of several areas of the AutoGroundDesign interface as indicated in the above screen. However, you should experiment with the colors before committing your choices because the character font colors will not be changed automatically to match the selected colors. Therefore, the text may be difficult to read if the
background color does not have a good contrast with the font color.
Sample Files
Three sample files are available to help you get familiar with the AutoGroundDesign program. The files are located in the folder "Examples\Tools\AutoGroundDesign" in your SESSoftware installation folder.
The files are:
AD_Uniform Soil.F05, located in the Uniform Soil folder: It corresponds to a 230 ft X 230 ft grounding grid in a uniform soil. The safety criteria are determined based on the IEC safety standard.
AD_Two Layer Soil.F05, located in the Two Layer Soil folder: It corresponds to a 100 m X 60 m grounding grid with four rods at the corners in a two-layer soil. The safety criteria are determined based on the IEEE safety standard.
AD_Multiple Layer Soil.F05, located in the Multiple Layer Soil folder: It corresponds to a 23 m X 20 m grounding grid in a multi-layer (five-layer) soil. The safety criteria are determined based on the IEEE safety standard.
These three examples are described in greater detail in the remaining topics of this section.
Safety Criteria
1. Safety is determined according to the IEC safety standard.
2. The crushed rock surface layer that will cover the surface of the substation and an area extending 23 feet outside the substation grounding grid is 6 inches thick and has an estimated resistivity (when wet) of 3000 ohm-m.
3. The fault clearing time is 0.5 s.
4. For a 0.5 s fault clearing time, the maximum acceptable GPR is 5000 V and the maximum allowable safe touch within the grid area is 428.6 V. The maximum acceptable safe step voltages in the substation and in an area extending 23 feet outside the substation grounding grid are 1469.4 V.
You can either enter the data yourself or simply click on the Open ... button on the main screen and load the AD_Uniform Soil.f05 file that was prepared in the "Example\Tools\AutoGroundDesign\Uniform Soil" folder of your SESSoftware installation folder. If you want to re-run the automated design process yourself with this file, remember to copy the file to another working directory, otherwise, you
file://C:\Users\aivanov\AppData\Local\Temp\~hh4231.htm
13/02/2016
AutoGroundDesign: An Overview
Page 14 of 15
To run the automated design process, please refer to the topic entitled Start Automated Design.
The resulting grid configuration plot and the computed quantities such as scalar potential, touch and safe step voltages values and plots are presented in the topic entitled Results: Grid in Uniform Soil.
The following plots show the grid configuration, scalar potentials, touch and step voltages throughout the grid as displayed using the GRServer plot and report program.
Grid Configuration
Scalar Potentials
Touch Voltages (2D Spot Plot)
Touch Voltages (3D Plot)
Step Voltages (2D Spot Plot)
Step Voltages (3D Plot)
Objectives
A new 230 kV substation (named East Central) is planned. It will be interconnected to the rest of the network via three transmission lines terminating at three different substations, namely terminal Greenbay, Newhaven and Hudson respectively. The objective of the analysis is to provide a new grid design for East Central Substation. The soil model is computed from the RESAP engineering module and
has the following structure:
Layer
Top
Bottom
Resistivity (ohm-m)
297.0809
65.84742
Thickness (m)
0.6741049
infinity
The ground grid specification and safety criteria are described hereafter:
Safety Criteria
1. Safety is determined according to the IEEE safety standard.
2. The crushed rock surface layer that will cover the surface of the substation only is 15 cm thick and has an estimated resistivity (when wet) of 3000 ohm-m.
3. The system X/R ratio is 20.
4. The fibrillation current method assumes a 50 kg person.
5. The fault clearing time is 0.3 s.
6. For a 0.3 s fault clearing time, the maximum acceptable GPR of the grid is 5000 V. The allowable maximum touch and step voltages within the grid area (i.e., 1 m outside the fence or less) and outside the grid are 933 V, 3147 V and 557.7 respectively based on the IEEE safety standard.
You can either enter the data yourself or simply click on the Open ... button on the main screen and load the AD_Two Layer Soil.f05 file that was prepared in the "Example\Tools\AutoGroundDesign\Two Layer Soil" folder of your SESSoftware installation folder. If you want to re-run the automated design process yourself with this file, remember to copy the file to another working directory, otherwise,
you will overwrite the existing reports and database files.
To run the automated design process, please refer to the topic entitled Start Automated Design.
The resulting grid configuration plot and the computed quantities such as scalar potential, touch and safe step voltages values and plots are presented in the topic entitled Results: Grid in Two-Layer Soil.
The following plots show the grid configuration, scalar potentials, touch and step voltages throughout the grid.
Grid Configuration
Scalar Potentials
Touch Voltages (2D Spot Plot)
Step Voltages (2D Spot Plot)
Layer
Top
Central 1
Central 2
Central 3
Bottom
Resistivity (ohm-m)
Thickness (m)
86
180
24
1083
62
0.7
1.8
1.6
3.7
infinity
The ground grid specification and safety criteria are described as follows:
file://C:\Users\aivanov\AppData\Local\Temp\~hh4231.htm
13/02/2016
AutoGroundDesign: An Overview
Page 15 of 15
Safety Criteria
1. Safety is determined according to IEEE safety standard.
2. The crushed rock surface layer that will cover the surface of the substation and an area extending 3 m outside the substation grounding grid is 18 cm thick and has an estimated resistivity (when wet) of 3000 ohm-m.
3. The system X/R ratio is 20.
4. The fibrillation current method assumes a 50 kg person.
5. The fault clearing time is 0.5 s.
6. For a 0.5 s fault clearing time, the maximum acceptable GPR of the grid is 5000 V and the allowable maximum safe touch within the grid area is 754 V . The maximum acceptable safe step voltages in the substation and in an area extending 3 m outside the substation grounding grid are 2549 V based on the IEEE safety standard.
You can either enter the data yourself or simply click on the Open ... button on the main screen and load the AD_Multiple Layer Soil.f05 file that was prepared in the "Example\Tools\AutoGroundDesign\Multiple Layer Soil" folder of your SESSoftware installation folder. If you want to re-run the automated design process yourself with this file, remember to copy the file to another working directory,
otherwise, you will overwrite the existing reports and database files.
To run the automated design process, please refer to the topic entitled Start Automated Design.
The resulting grid configuration plot and the computed quantities such as scalar potential, touch and safe step voltages values and plots are presented in the topic entitled Results: Grid in Multiple Layer Soil.
After a few iterations, the final design corresponds to a grid made of 5 equally spaced conductors along the X axis and the Y axis. The maximum GPR is 3883.8 V. The maximum computed touch voltage, and step voltages within and outside grid are 748.7 V, 457.1 V, and 650.1 V respectively. These values meet the safety requirements.
A snapshot of the computation process results progress screen is shown here .
The following plots show the grid configuration, scalar potentials, touch and step voltages throughout the grid.
Grid Configuration
Scalar Potentials
Touch Voltages (2D Spot Plot)
Step Voltages (2D Spot Plot)
In 2004, SES developed the first version of a Windows-based specialized package called AutoGroundDesign. This was more pertinent, since SES has developed a new and unique automated design method that promises to reduce considerably the time needed to determine an adequate design for grounding systems. However, AutoGroundDesign was restricted to rectangular grids buried in multilayered
soils. This version didnt have a soil resistivity measurement and fault current distribution analysis modules. The soil structure characteristics and grounding grid fault current had to be specified by the user. These steps were quite inconvenient.
In the 2005 release of AutoGroundDesign, the soil resistivity measurement analysis, fault current distribution analysis and safety computation assessment modules have been integrated into the AutoGroundDesign specialized package. A new iterative approach and improved observation point selection procedure that speed up computation time have been introduced into this package. Moreover, metallic
plates have been introduced and a robust and flexible grid and rod creation procedure that allows the specification of unequally spaced grids and rods were added as well. However, AutoGroundDesign was still restricted to rectangular grids.
Finally, SES is pleased to announce that in 2012, AutoGroundDesign can handle arbitrary shape horizontal grounding systems.
Program Highlights
With AutoGroundDesign, the data entry requirements are reduced to a minimum. The data includes:
Input session environment, Users' preference and regional settings, system of units and reference database
Grounding grid zone
Soil data
Fault current in the grid
Computation settings
Safety related data
Automated design parameters and controls
Once the input data is defined, simply click the Start Design/Automated Design button and let the program do the rest. The program will compute everything that is necessary, analyze the grid design, modify and improve it progressively in order to provide a safe grid design and produce the appropriate reports and grid configuration that you can display online.
First, an appropriate preliminary grid design is retrieved from a database of predefined grids, based on the provided input data, such as the size and the geometrical proportions of the grid, the soil structure, the fault current injected, and the safety criteria. These predefined grids have been previously analyzed and stored in the supplied databases. The multilayer soil is analyzed to obtain an equivalent twolayer soil that will be used to select the appropriate initial grid for the automated ground design.
This initial design will be refined automatically and dynamically using appropriate techniques and algorithms and by varying the number of horizontal and vertical conductors in the grid in an attempt to improve its performance and meet the safety constraints, while reducing the overall cost of the grid.
The data storage requirements for this database are unusual in that each grid is indexed by a large number of parameters (size, geometrical proportions, maximum touch voltage, maximum step voltage, soil structure, etc?. A specially designed database has been created and a suitable sampling strategy has been devised to make sure that it is possible to quickly find the most appropriate grid using any of
these indexes, while at the same time minimizing the size of the database.
An intelligent rule-based strategy has been devised to conduct the design refinement steps, since each design cycle can be computationally intensive. The families of predefined grids whose dimensions are the closest to the rectangular user-specified perimeter are examined, and the number of meshes in the grid with the most appropriate performance characteristics is chosen for the grid to be designed.
Ground rods are placed uniformly throughout the grounding system to mitigate the effect of frozen soil (or dry soil) conditions on the electrode's performance in winter or summer conditions, as appropriate.
The initial grounding grid is then analyzed and evaluated from a safety viewpoint by the program: the GPR, touch and step voltages are computed and compared against the maximum values specified by the user, i.e., IEEE, IEC standards or user-supplied thresholds. If any of the maximum values are exceeded, then the AutoGroundDesign module adds horizontal or vertical conductors and performs a new
analysis. Note that in the first version of the automated design, all horizontal conductors are parallel to the grid perimeter conductors while vertical conductors are placed in a symmetrical fashion along the horizontal conductors. The iterative process continues until either a grounding system satisfying the design criteria is found, or the maximum number of iterations or other restrictions specified by the
user are reached.
file://C:\Users\aivanov\AppData\Local\Temp\~hh4231.htm
13/02/2016