Type Test Report
Type Test Report
D. W. Lenk P.E.
Principal Engineer
M. G. Comber
Manager, Engineering
Date: 1/16/2006
Separate reports provide details of each test, according to the following table:
Report No.
EU1344-HR-01
EU1344-HR-02
EU1344-HR-03
EU1344-HR-04
EU1344-HR-05
EU1344-HR-06
EU1344-HR-07
EU1344-HR-08
EU1344-HR-09
EU1344-HR-10
EU1344-HR-11
EU1344-HR-12
EU1344-HR-13
Description
Insulation Withstand Test
Residual Voltage
Long Duration Current Withstand
Accelerated Aging Procedure
Heat Dissipation Behavior of Test Section
Switching Surge Operating Duty
Partial Discharge
Power Frequency Voltage Versus Time
Short Circuit
Bending Moment
Moisture Ingress
RIV
Weather Ageing
Clause
10.8.2
10.8.3
10.8.4
10.8.5
10.8.5
10.8.5
10.8.8
Annex D
5.11
10.8.9
10.8.13
10.8.12
10.8.14
Issue date
1/16/2006
1/16/2006
1/16/2006
1/16/2006
1/16/2006
1/16/2006
1/16/2006
1/16/2006
1/16/2006
1/16/2006
1/16/2006
1/16/2006
1/16/2006
This report records the results of this type test made on IEC 10 kA Class 3 arresters
rated 3 thru 228 kV in accordance with IEC Standard 60099-4, 2004, Surge
arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems.
To the best of our knowledge and within the usual limits of testing practice, tests
performed on IEC 10 kA Class 3 arresters demonstrate full compliance with the
relevant clause of the referenced standard.
M.G. Comber
Manager, Engineering
Date: 1/16/2006
Arrester
MCOV
2.55
5.1
7.65
8.4
10.2
12.7
15.3
17
19.5
22
24.4
29
31.5
36.5
39
42
48
57
70
76
84
88
98
106
115
131
140
144
152
180
Leakage
Distance
(mm)
584
584
584
584
787
787
787
1168
1168
1168
1168
1168
1575
1575
1575
1981
1981
2337
3150
3150
3962
3962
3962
3962
4724
5944
5944
5944
5944
7925
Imp w/s
Reqd
(KVc)
9.9
19.8
29.5
32.9
39.4
49.3
59.2
66.6
75.5
86.2
95
113
123
143
152
171
193
227
286
304
341
341
386
412
456
532
545
569
607
723
Imp w/s
Actual
(KVc)
120
120
120
120
161
161
161
241
241
241
241
241
321
321
321
401
401
450
639
639
700
700
660
660
817
1050
1050
1050
1050
1520
-2-
60 HZ
1 Minute Wet w/s
Reqd
(kVrms)
4.7
9.4
14
15.6
18.7
23.4
28.1
31.6
35.9
41
45.2
53.9
58.5
68
72
81
92
108
136
145
162
162
184
196
217
253
259
271
288
343
60 HZ
1 Minute Wet w/s
Actual
(kVrms)
57
57
57
57
74
74
74
109
109
109
109
109
145
145
145
182
182
200
295
295
320
320
306
306
385
410
410
410
410
500
M.G. Comber
Manager, Engineering
Date:1/16/2006
Current
magnitude
kA
10
5
10
20
0.25
1
Waveshape
s
1/2
8/20
47/91
Residual Voltage
kV
13.695
11.895
12.754
13.879
9.938
10.505
p.u.
1.074
0.933
1.000
1.088
0.779
0.824
Oscillogram
number
28
7
10
13
19
25
Current
magnitude
kA
10
5
10
20
0.25
1
Waveshape
s
1/2
8/20
47/91
Residual Voltage
kV
13.707
11.868
12.746
13.854
9.875
10.484
p.u.
1.075
0.931
1.000
1.087
0.775
0.823
Oscillogram
number
29
8
11
14
20
26
Current
Waveshape
Residual Voltage
Oscillogram
Steep current
Lightning
impulse
Switching
impulse
magnitude
kA
10
5
10
20
0.25
1
s
1/2
kV
13.504
11.697
12.547
13.683
9.706
10.295
8/20
47/91
p.u.
1.076
0.932
1.000
1.091
0.774
0.821
number
30
9
12
15
21
27
The results are shown graphically in the following chart. When expressed in terms of per
unit of the residual voltage at nominal discharge current, the residual voltages of Type
PVN arresters for steep front, lightning impulse and switching impulse do not exceed
values shown in this chart.
1.1
Steep front
Lightning impulse
0.9
0.8
Switching impulse
0.7
0
10
15
20
Current - kA
Annex
Oscillograms
Annex
Oscillograms
Oscillogram 7
Sample 1
6
Oscillogram 8
Sample 2
Oscillogroam 9
Sample 3
Oscillogram 10
Sample 1
Oscillogram 11
Sample 2
10
Oscillogram 12
Sample 3
11
Oscillogram 13
Sample 1
12
Oscillogram 14
Sample 2
13
Oscillogram 15
Sample 3
14
Oscillogram 19
Sample 1
15
Oscillogram 20
Sample 2
16
Oscillogram 21
Sample 3
17
Oscillogram 25
Sample 1
18
Oscillogram 26
Sample 2
19
Oscillogram 27
Sample 3
20
Oscillogram 28
Sample 1
21
Oscillogram 29
Sample 2
22
Oscillogram 30
Sample 3
23
This report records the results of this type test made on 10 kA Class 3 arresters
rated 3 thru 228 kV in accordance with IEC Standard 60099-4, 2004 Surge
arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems.
To the best of our knowledge and within the usual limits of testing practice, tests
performed on 10 kA Class 3 arresters demonstrate full compliance with the
relevant clause of the referenced standard.
D. W. Lenk P.E.
Principal Engineer
M.G. Comber
Manager, Engineering
Date: 1/16/2006
Sample #1
Sample #2
Sample #3
22.343 kV
16.996 kV
1 mA
12.944 kV
7.763 kV
9.502 kV
10 kA
3
2400 S
12.35
26.606 kV
22.311 kV
16.983 kV
1 mA
12.902 kV
7.738 kV
9.471 kV
10 kA
3
2400 S
12.31
26.519 kV
22.408 kV
17.061 kV
1 mA
12.914 kV
7.745 kV
9.480 kV
10 kA
3
2400 S
12.32
26.544 kV
Before the transmission line discharge test, the 10 kA, 8/20 S discharge voltage of the
test sample was measured.
The procedure was performed per Section 7.4.2 of the IEC 99-4 Standard. The procedure
consisted of eighteen rectangular wave shape discharges applied to each sample. These
discharges were arranged in six groups of three consecutive operations with a time
interval between consecutive operations of 50 to 60 sec. The samples were allowed to
cool to near ambient temperature between groups of discharges.
-2-
Test Results
Figure No.1 measures the surge impedance and confirms the virtual duration of the
transmission line generator. The samples were exposed to the air at still air temperature
of 20 oC during the tests. A summary of data recorded during this test is shown in Table
1.
Figure 1
Zg = 10451 V / 850.2 A
Zg = 12.29 Ohms
Time Duration = 2400 S
Table 1
Summary Data - Long Duration Current Impulse Withstand Test
Impulse
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
I (A)
740
721
709
729
710
702
727
715
704
720
705
711
730
711
704
737
718
692
Sample 1
V (kV)
17.79
17.95
18.08
17.84
18.00
18.13
17.87
18.01
18.14
17.89
18.05
18.19
17.87
18.01
18.16
17.90
18.06
18.14
E (kJ)
34.23
33.70
33.32
33.72
33.22
32.97
33.66
33.44
33.16
33.40
33.02
33.54
33.85
33.22
33.15
34.25
33.62
32.60
I (A)
735
722
711
728
714
703
728
712
703
729
706
694
727
713
698
723
710
695
Sample 2
V (kV) E (kJ)
17.81
33.96
17.95
33.61
18.08
33.31
17.84
33.70
17.98
33.28
18.13
33.04
17.85
33.72
18.01
33.27
18.11
33.02
17.87
33.80
18.03
32.96
18.13
32.61
17.87
33.69
18.03
33.29
18.13
32.88
17.87
33.61
18.01
33.16
18.12
32.69
-3-
I (A)
725
711
700
720
706
696
721
706
698
712
711
695
714
697
689
717
700
692
Sample 3
V (kV)
E (kJ)
17.87
33.64
18.03
33.25
18.16
32.97
17.92
33.47
18.08
33.12
18.19
32.82
17.95
33.58
18.11
33.20
18.20
33.04
17.94
33.17
18.11
33.41
18.22
32.80
17.93
33.23
18.09
32.69
18.20
32.53
17.97
33.36
18.09
32.89
18.20
32.75
Figure 2 is an oscillographics record of the first, ninth and eighteen transmission line
discharge through the test sample No. 1.
Figure 2
Figure 3 is an oscillographics record of the first, ninth and eighteenth transmission line
discharge through the test sample No. 2.
Figure 3
Figure 4
-6-
After successful completion of the eighteen-shot test, the 10 kA, 8/20 S discharge
voltage of each test sample was measured. The results of the residual voltage
measurements are given in the following table and they show that all three samples had
less than the permissible 5% change.
Summary Data - Residual Voltage Measurement Comparisons 10 kA, 8/20 S Impulse
SAMPLE NO.
1
2
3
PERCENT
CHANGE
-0.14
0.22
0.29
Test Summary
The three prorated test samples successfully completed the Long Duration Current
Impulse Withstand Test per Clause 10.8.4 of IEC 99-4, 2004 Standard. In all cases, the
change in 10 kA, 8/20 S residual voltage was less than the allowed 5% limit.
Disassembly revealed no evidence of physical damage to the three test samples.
Therefore, the three test samples have successfully fulfilled the Long Duration Current
Impulse Withstand requirement of a PVN Line Discharge Class 3 Arrester.
-7-
Michael G. Comber
Manager, Engineering
Date: 1/16/2006
EU1516-H-04
Sample
Number
Power
dissipation
at 2 h
P1ct (W)
Power
dissipation
at 1000 h
P2ct (W)
Minimum
power
dissipation
P3ct (W)
1
2
3
2.57
2.40
2.49
2.12
2.06
2.07
2.12
2.02
2.04
-2-
This report records the results of this type test made on IEC 10 kA Class 3
arresters rated 3 thru 228 kV in accordance with IEC Standard 60099-4, 2004
Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c.
systems.
To the best of our knowledge and within the usual limits of testing practice, tests
performed on IEC 10 KA Class 3 Arresters demonstrate full compliance with the
relevant clause of the referenced standard.
-2-
This report records the results of this type test made on 10 kA Class arresters rated
3 thru 228 kV in accordance with IEC Standard 60099-4, 2001 Surge arresters Part 4: Metal-oxide surge arresters without gaps for a.c. systems.
To the best of our knowledge and within the usual limits of testing practice, tests
performed on 10 kA Class 3 Arresters demonstrate full compliance with the
relevant clause of the referenced standard.
D. W. Lenk P.E.
Principal Engineer
M.G. Comber
Manager, Engineering
Date:
At room temperature, the reference voltage was measured at 1mA reference current
for each test sample.
At room temperature, the initial residual voltage was measured at 10 kA, 8/20 S for
each test sample also.
2) Conditioning:
While assembled into an open air test fixture, each sample was next subjected to two
100 kA 4/10 uS current impulses with the samples cooled to ambient between shots.
The samples were assembled into the prorated models, placed in an oven and heated
to 60 0C +/- 3 0C. Within 3 minutes after removal from the oven, each section was
subjected to two transmission line discharge, 50 to 60 seconds apart. Then, within 90
msec. of the last long duration impulse, rated voltage (Ur) was applied for 10 seconds
immediately followed by MCOV (Uc) for 30 min. During the recovery period, the
power dissipation was monitored.
After the complete test sequence each test section was cooled to near ambient
temperature and the 10 kA, 8/20 S discharge voltage test was repeated. The
percentage change in 10 kA, 8/20 S residual voltage measured before and after the
test was calculated .
Test Results
-2-
Before the switching surge operating duty test, the initial measurements and prorated
section parameters are defined in Table 1:
Table 1
Test Parameters
Sample #1
Sample #2
Sample #3
Initial Residual Voltage @ 10 kA, 8/20 S
Reference Current: Iref
Reference Voltage (peak): Vref
Maximum COV (rms): Uc
Maximum Rating (rms): Ur (1.224Uc)
22.44 kV
1 mA
12.974 kV
7.78 kV
9.523 kV
22.42 kV
1 mA
13.028 kV
7.81 kV
9.562 kV
22.42 kV
1 mA
12.959 kV
7.77 kV
9.511 kV
A summary of data recorded for three samples during 20 shots conditioning test is
shown in Table 2. The samples were exposed to the air at still air temperature of 20 oC
during the tests.
Table 2
Summary Data - Conditioning
IMPULSE
SAMPLE NO. 1
SAMPLE NO. 2
SAMPLE NO. 3
NUMBER
I (KA)
I (KA)
I (KA)
1
10.456
10.408
9.981
2
10.368
10.443
10.057
3
10.271
10.404
10.769
4
10.372
10.421
10.535
5
10.460
10.444
10.564
6
10.414
10.440
10.890
7
10.333
10.385
10.978
8
10.352
10.395
11.043
9
10.385
10.404
10.958
10
10.303
10.349
10.802
11
10.404
10.300
10.509
12
10.316
10.267
10.515
13
10.212
10.408
10.421
14
10.180
10.310
10.290
15
10.251
10.232
10.336
16
10.261
10.313
10.546
17
10.232
10.228
10.590
18
10.189
10.271
10.466
19
10.225
10.297
10.486
20
10.261
10.261
10.440
After successful completion of the 20 shot test, each sample was subjected to two 100 kA
4/10 S impulses as specified in the Standard (figure 8). Following Table 3 shows the
first and second 100 kA impulses for all samples. Measured waveshape was 4.2/10.2 uS
SHOTS
Table 3
Summary Data - 100 kA 4/10 S
SAMPLE NO. 1
SAMPLE NO. 2
-3-
SAMPLE NO. 3
NUMBER
1
2
I (KA)
107.480
102.290
I (KA)
102.080
102.430
I (KA)
102.500
102.780
Figure 1 shows oscillograms of the 100 kA impulse duty on the three test sections.
Figure 1
Sample No. 1
First 100 kA Impulse
-4-
-5-
12.974 kV
9.523 kV
10 kA
3
2400 S
12.38
26.664 kV
13.028 kV
9.562 kV
10 kA
3
2400 S
12.43
26.774 kV
12.959 kV
9.511 kV
10 kA
3
2400 S
12.36
26.631 kV
Figure 2 measures the surge impedance and confirms the virtual duration of the transmission
line generator. A summary of data recorded during this test is shown in Table 5.
Figure 2
Zg = 10451 V / 850.2 A
Zg = 12.29 Ohms
Time Duration = 2400 S
Table 5
Summary Data - Energy Dissipation During the Long Duration Current Impulse:
-6-
Impulse
Number I (A)
1
712
2
691
Sample 1
V (kV) E (kJ)
18.06
33.56
18.29
32.93
Sample 2
I (A) V (kV) E (kJ)
745
18.14
35.21
720
18.35
34.39
Sample 3
I (A) V (kV) E (kJ)
743
18.14
35.09
698
18.33
33.36
The oscillograms during the Long Duration Current Impulse test are shown in Figure 3
Figure 3
Sample No. 1:
First LD Impulse
Sample No. 2:
First LD Impulse
-7-
-8-
SAMPLE NO. 1
POWER LOSS (W)
21.9
19.8
19.0
18.6
15.7
12.7
9.8
8.2
SAMPLE NO. 2
POWER LOSS (W)
24.1
20.6
19.4
17.1
14.4
11.2
9.6
7.8
SAMPLE NO. 3
POWER LOSS (W)
26.2
24.3
22.6
20.3
17.4
15.0
12.2
10.4
The results of the residual voltage measurements are given in Table 7 and they show that
all three samples had less than the permissible 5% change.
Table 7
Summary Data - Residual Voltage Measurement Comparisons 10 kA, 8/20 S Impulse
RESIDUAL VOLTAGE (KV)
PERCENT
SAMPLE NO.
INITIAL
FINAL
CHANGE
1
22.44
22.55
0.49
2
22.42
22.52
0.45
3
22.42
22.55
0.58
Test Summary
The three prorated test samples successfully completed the operating duty test per Clause
10.8.5 of IEC 99-4, 2004 standard. There was no evidence of puncture, flashover or
-9-
cracking of the non-linear metal oxide resistors in any of the three samples. Also, all
three samples were thermally stable as demonstrated in Table 6. The change in the
residual voltage measured before and after the test was less than 5%. Therefore, the three
test samples have successfully fulfilled the operating duty test requirement of a Class 3
Type PVN Arrester.
- 10 -
This report records the results of this type test made on 10 kA Class 3 arresters
rated 3 thru 228 kV in accordance with IEC Standard 60099-4-2004 Surge
Arresters- Part 4: Metal oxide surge arresters without gaps for ac systems
To the best of our knowledge and within the usual limits of testing practice, tests
performed on IEC 10 kA Class 3 arresters demonstrate full compliance with the
relevant clause of the referenced standard.
-2-
This report records the results of this type test made on 10 kA Class 3 arresters
rated 3 thru 228 kV in accordance with IEC Standard 60099-4, 2004 Surge
arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems.
To the best of our knowledge and within the usual limits of testing practice, tests
performed on 10 kA Type PVN Class 3 arresters demonstrate full compliance with
the relevant clause of the referenced standard.
D. W. Lenk P.E.
Principal Engineer
____________________________
M. G. Comber
Manager, Engineering
Date: 1/16/2006
1.5
1.4
1.3
1.2
1.1
1
0.01
0.1
10
100
1000
OVERVOLTAGE DURATION-SECONDS
DEMONSTRATED WITHSTAND DATA POINTS PU*Uc
-2-
10000
This report records the results of this type test made on 10 kA Class 3 arresters
rated 3 thru 228 kV in accordance with IEC Standard 60099-4, 1998 Surge
arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems.
To the best of our knowledge and within the usual limits of testing practice, tests
performed on 10 kA Type PVN Class 3 arresters demonstrate full compliance with
the relevant clause of the referenced standard.
D. W. Lenk P.E.
Principal Engineer
M. G. Comber
Manager, Engineering
Date:
INTRODUCTION: The high current and low current pressure relief tests were
performed per Section 5.11 of IEC 60099-4-1998 Standard. For the high current tests, an
additional timed reclose was performed on each test specimen approximately 20 cycles
after completion of the required 12 cycle test. The high current tests were performed in
the IREQ High Power Laboratory in Montreal.
SAMPLE PREPARATION: The fuse wire was used to short out the mov disc elements.
Two shorting methods were used. The "shorted" mode of failure consisted of externally
locating a fuse wire along the outside contour of the stack of mov disc elements between
the mov discs and the fiberglass-epoxy wrap. The "puncture" mode of failure consisted of
drilling a 4 mm diameter hole through the center of each mov disc and then running a
wire through the center of the stack of discs. For the high current tests, the longest
available single unit arrester ( 48 kV MCOV ) was tested.
TEST PROCEDURE: To achieve the high levels of fault current, the high current
pressure relief tests were performed per Section 8.13.3.4 with a reduced voltage source of
11.1 kV rms. Since the arrester arc resistance can significantly affect the required
asymmetry, the claimable symmetrical rms current for the high current test procedure is
calculated by dividing the 1st loop peak current by 2.6. The low current pressure relief
tests were performed per Section 8.13.4.
TEST RESULTS: The following table summarizes the results of the pressure relief
testing. The low current sample successfully vented within .23 seconds after fault
initiation. The high current tests were performed on the longest arrester units. In addition
to the initial 12 cycle fault current duty required per the standard test procedure, both the
"punctured" and the "shorted" test samples were immediately subjected to a fault current
reclose condition. Both arresters successfully vented. The highest claimable symmetrical
fault current of 83.4 kA rms for 12.5 cycles, followed in 20 cycles by a claimable 81.5
kA rms 3 cycle reclose was recorded on the "shorted" design. The lower peak kA values
recorded on the "punctured" arrester configuration were the result of the high arc
resistance of that design when subjected to the reduced voltage test procedure.
Initial Fault
Arrest
MCOV
Mode of
Fail
Test
Volts
kVrms
1st
Loop
Peak
Act
Symm
Curr
Claimed
Symm
Curr
-2-
Reclose Fault
Fault
Durat
(Cyc)
1st
Loop
Peak
Act
Sym
m
Fault
Durat
(Cyc)
Condition
of Arrester
after
kAc
kA rms
kArms
kAc
48
Shorted
11.3
217
120
83.4
12.5
212
Curr
kArms
122
48
Punct
11.2
181
121
69.6
12.5
229
124
2.55
Shorted
15.0
.48
.48
60
Testing
3
Module
Intact
Housing
Separated
Module
Intact
Housing
Separated
Module
Intact
Housing
Split
CONCLUSION: The test arresters assembled with the longest mechanical unit met the
test evaluation criteria as specified. In all tests, the arrester module remained intact after
the completion of each test. The flexible polymer housing wall section split or separated,
as intended, on all samples to allow venting of internal arcing gases to the outside of the
arrester. In all cases, flames associated with the fault current test extinguished
immediately after completion of the test, well within the allowed 2 minute duration.
These tests have demonstrated the capability of the IEC 10 kA Type PVN Class 3 arrester
design to successfully discharge a maximum claimable 83 kArms symmetrical fault
current.
-3-
M. G. Comber
Manager, Engineering
Date: 1/16/2006
-2-
20000
Moment In-lbs
15000
Moment (in-lbs)
10000
5000
Residual deflection = .208"
0
0
50
100
150
200
250
Time- Seconds
Subsequent to the bending moment test, the test arrester was subjected to 42 hours
immersion in the specified salt water bath. After removal from the bath, the arrester was
electrically tested. The following table compares the initial versus the final electrical test
results.
Sample
Initial
Final
Initial PD
Final PD
Initial 17
Final 17
No.
Watts @
Watts @
@ 1.05
@ 1.05
ma
ma
Uc
Uc
times Uc
times Uc
Voltage
Voltage
(pC)
(pC
kVc
kVc
1
3.8
3.8
0
0
54.2
54.5
Test Conclusions
Visual inspection confirmed that there was no damage to the arrester as a result of the
bending moment test, followed by the water immersion test. The load-deflection plot
shows a smooth time load curve for the arrester. Electrical tests performed before and
after testing confirmed the electrical integrity of the test arrester. The 0 % watts loss was
below the allowed 20% increase. Partial discharge was 0 pC, below the allowed 10 pC
limit. The measured 17 ma voltage changed +0.5%, below the allowed 5% limit. The IEC
Class 3 Type PVN base mounted arrester design successfully passed the bending moment
test, as defined in IEC 60099-4 standard.
-3-
This report records the results of type tests made on Type PVN IEC 10 kA Class 3
arresters in accordance with IEC Standard 60099-4, 2004-05 Surge arresters - Part
4: Metal-oxide surge arresters without gaps for a.c. systems.
To the best of our knowledge and within the usual limits of testing practice, tests
performed on Type PVN IEC 10 kA Class 3 arresters demonstrate full compliance
with the relevant clauses of the referenced standard.
__________________________
D. W. Lenk P.E.
Principal Engineer
_____________________________
M. G. Comber
Manager, Engineering
Date: 1/16/2006
Watts Loss
@MCOV
Final
2.4
Watts
Loss
Change
-4.0%
1.5 kA IR
kVc
Initial
72.91
1.5 kA IR
kVc
Final
71.37
1.5 kA IR
kVc
Change
-2.1%
Partial disch
Pc
Initial
1.0
Partial
disch Pc
Final
1.0
CONCLUSION: Per the test results summarized above, the electrical characteristics of the
PVN arrester met the allowable limits specified in Clause 10.8.13.4. Visual examination revealed
no evidence of mechanical damage. The above tests validated the seal integrity of the PVN
arrester assembled with a 3-lug base end casting when loaded to the 10,000 inch-pound
continuous cantilever rating.
M. G. Comber
Manager, Engineering
Date: 1/16/2006
-2-
IEC
-2-