Switchgear
Switchgear
The apparatus used for switching, controlling and protecting the electrical circuits and
equipment is known as switchgear.
The switchgear equipment is essentially concerned with switching and interrupting
currents either under normal or abnormal operating condition. For circuits of higher
rating, a high-rupturing capacity (H.R.C) fuse in conjunction with a switch may serve the
purpose of controlling and protecting the circuit.
Equipment
Function
1. Bus-bar
2. Circuit Breaker
3. Isolator
4. Earthing Switch
5. Current Transformer
6. Voltage Transformer
7. Lightning Arrestor
132KV
Incoming lines
Earthling
Switch
132KV busbar
132/33KV
33KV busbar
Substation
Auxiliary
3)
4)
5)
6)
Isolator
Earthling switch
CT and PT
Lighting arrester
11KV/400V
CT
PT
CB
400V
Busbar
The Circuit Breaker is found in an electrical service panel and is an electrical device used
to protect the electrical wiring from an overloaded (over current) condition when
exposed to more electrical current than it is designed to handle.
Type of Circuit Breaker is usually identically according to the medium of arc extension
and classified as
I.
II.
III.
IV.
V.
VI.
VII.
VIII. (a) MCB (Miniature Circuit Breaker)rated current not more than 100
A. Trip characteristics normally not adjustable. Thermal or thermal-magnetic
operation. Breakers illustrated above are in this category.
IX.
In its simplest form the process of separating the current carrying contacts was carried
out under oil with no special control over the resulting arc other than the increase in
length caused by the moving contact's as the power systems began to develop resulting in
higher voltages and higher fault levels, plain break type breaker could no longer keep
pace with the requirements. Various methods of controlling the breaking process were
investigated and developed.
120-GTR-40
138KV
14.7KA
50HZ
3s
0.288s
DC110V
400
1400
23000KG
A00683
1981
3.6.4 SF6 circuit breaker: Sulphur hexafluoride (SF6) is an inert, heavy gas having
good dielectric and arc extinguishing properties.
In this circuit breaker, sulphur hexafluoride (SF6) gas is used as the arc quenching
medium. The SF6 gas is an electro negative gas and has a strong tendency to absorb free
electrons. The contacts of the breaker are opened in a high pressure flow of SF6 gas and
an arc is struck between them.
3.2.2 Working:
In the closed position of the breaker the contacts remained surrounded by SF6 gas at a
pressure of about 2.8 kg/cm2. When the breaker operates the moving contact is pulled
apart and an arc is struck between the contacts. The movement of the moving contact is
synchronized with the opening of a valve which permits SF6 gas at 14 kg/cm2 pressure
from the reservoir to the arc interruption chamber.
The high pressure flow of SF6 rapidly absorbs the free electrons in the arc path to form
immobile negative ions which are ineffective as charge a carriers. The result is that the
medium between the contacts quickly builds up high dielectric strength and causes the
extinction of the arc. After the breaker operation the valve is closed by the action of a set
of springs.
.Type
LW11-145/2000A-40kA
b .Rated voltage
145kV
2000A
d .Rated frequency
50Hz
3s
f Rated Sequence
0-0.3s-co-180s-co
0.5Mpa20oC
h wind pressure(Max)
700pa
145v
27.8Mpa
25.8Mpa
m .Opening time
40ms
n .Closing time
135ms
70
150ppm(V/V)
275kV
2) Between phases
275KV
3) Phase to earth
275KV
3.6.5 Vacuum Circuit Breaker: Vacuum Circuit Breakers are specially suited in
industrial applications, where the Switching frequency is high combined with high
degree of pollution. The manufacturing range of M/s Driescher Panicker covers Vacuum
Circuit Breakers up to rated voltage of 36 kV. Current of a lesser value is chopped prior
to current zero, causing unduly high voltages, as may happen during interruption of no
load magnetizing currents of unloaded Transformers. The rapid build up of the dielectric
strength in the break enables the arc to be safely extinguished even if contact separation
occurs immediately prior to current zero the maximum arcing time for the last pole to
clear is stated to be 15 ms.
PROTECTIVE RELAY
3.7.2 Protective Relaying:
AC power system is covered by several protection zones. Each protective zone covers
one or two components of the system. The neighboring protective zones overlap so that
no part of the system is left unprotected. During the abnormal situation, the protective
relaying senses the condition and closes the trip circuit of the circuit breaker.
The protective schemes for large electrical equipment comprise several types of
protective systems. For low voltage equipment of relatively small ratings, fuses and
thermal relays are generally adequate. The protective schemes for large power system
equipment is generally designed with due regards to power swings, power system
stability and associated problems.
Types of Protective Relays:
1. Differential Relay
2. Directional Relay
3. Over current/ earth fault Relay
4. Frequency Relay
5. Trip Relay
6. Lockout Relay
7. Distance Relay
8. Gas accumulator Relay
9. Time Relay
In these two connections, the primary and secondary currents are in phase, but their
magnitudes are different. The difference in the current magnitude must be balanced out
by the current transformer ratios.
3.7.6 Some part of the Relay panel of Khulna 110MW power plant:
the current to first operate it. The "returning ratio" or "differential" is the measure of how
much the current must be reduced to reset the relay.
Distance relay
The most common form of protection on high voltage transmission systems is distance
relay protection. Power lines have set impedance per kilometer and using this value and
comparing voltage and current the distance to a fault can be determined. The ANSI
standard device number for a distance relay is 21.
A very common example of a differential current relay is the ground fault current
interrupter (GFCI), or Residual-current device.
float. The lower element contains a mercury switch mounted on a hinged type flap
located on the direct path of flow of oil from the transformer to the conservator. The
upper element closes an alarm circuit during slow developing faults whereas the lower
element is arranged to trip the circuit breaker in case of seve re internal faults.
5.9.2Operation
The operation of buchholz relay is as follows:
In case of slow developing faults within the transformer, the heat due to the fault
Causes decomposition of some transformer oil in the main tank. The products of
decomposition mainly contain 70 % of hydrogen gas. The hydrogen gas being
light tries to go into the conservator and in the process gets trapped in the upper
part of the relay chamber. When a predetermined amount of gas gets
accumulated, it exerts sufficient pressure on the float to cause it to tilt and close
the contacts of mercury switch attached to it. This completes the alarm circuit to
sound an alarm.
Vacuum Circuit Breakers are specially suited in industrial applications, where the
Switching frequency is high combined with high degree of pollution. The manufacturing
range of M/s Dresher Picnicker covers Vacuum Circuit Breakers up to rated voltage of 36
kV. Current of a lesser value is chopped prior to current zero, causing unduly high
voltages, as may happen during interruption of no load magnetizing currents of unloaded
Transformers. The rapid buildup of the dielectric strength in the break enables the arc to
be safely extinguished even if contact separation occurs immediately prior to current
zero the maximum arcing time for the last pole to clear is stated to be 15ms.
Further the arc voltage developed in vacuum interrupter is low (say between 20 to 200
V) due to high conductivity of metal vapor plasma.
For their reasons the arc energy developed in the break is very small. High Switching life
is claimed on this account. Performance is claimed to be immune to pollution because of
interrupters being hermetically sealed.
422010
36PV25A
RATING TO
IE62271-100
SR NO:
39170VP
VOLTAGE:
3600V
CURRENT
1250AMP
FREQUENCY
50HZ
NO OF POLE:
l3
BREAKING CAPACITY
25 KA
MAKING CAPACITY:
62.5KAP
DC COMPONENT
SHUNT TRIP
110 DC
CLOSING COIL
110VDC
Terminal Plate
Insulator (Ceramic)
Insulator (Ceramic)
Metal below
CURRENT TRANSFORMER
The instrument current transformer (CT) steps down the current of a circuit to a lower
value and is used in the same types of equipment as a potential transformer. This is done
by constructing the secondary coil consisting of many turns of wire, around the primary
coil, which contains only a few turns of wire. In this manner, measurements of high
values of current can be obtained. A current transformer should always be short-circuited
when not connected to an external load. Because the magnetic circuit of a current
transformer is designed for low magnetizing current when under load, this large
increase in magnetizing current will build up a large flux in the magnetic circuit
and cause the transformer to act as a step-up transformer, inducing an excessively
high voltage in the secondary when under no load. CT's may be accommodated in one of
six manners:
TYPE IB-145THW1
CODE NAME 1FT.760.575.5
ITH 21-42KA
IDHN 54-108KA
1S1-1S2
3S1-3S2
2S1-2S2
100-200/1A
1S1-1S3
3S1-3S3
2S1-2S3
200-400/1A
Class
Rated output, VA
SWRIAL NO
5p20
25
98LI2232-2
0.5
50
5p20
30
DATE
0.5
50
1-1999
a. Type:
: ES 132
b. Serial number
: 7032-1
: 145kV
d. Rated voltage
: 132V
e. Level
: 0.511/3P
f. Rated frequency
: 50Hz
g. Maximum output
: 2000VA
h. Technique standard
: IEC60044-2:1998
i.Total Weight
:450KG
Lighting arrester is a protective device for electrical equipments which reduces excessive
voltage resulting from lightning to a safe level by grounding the discharge.
Metal oxide varistors (MOVs) have been used for power system protection since the mid
1970s. The typical lightning arrester also known as surge arrester has a high voltage
terminal and a ground terminal. When a lightning surge or switching surge travels down
the power system to the arrester, the current from the surge is diverted around the
protected insulation in most cases to earth.
Overhead lines are exposed to atmosphere in accordingly they may suffer from lighting
strikes which calls very high voltage to be induce in overhead lines. These induced over
voltages may cause rupture of overhead insulators or other power system equipment. In
order to protect them from failure of insulator due to over voltages lighting arrester are
employed such that over voltages met lighting arresters first before meeting any of power
system equipments.
PT
CT
CB
Busbar
OH lines
Isolator
Earthling
switch
Lighting
Arrester
1) Specialization of busbar:
In thus arrangement there are a number of sections which can be interconnected in each
other hence for repair maintained or fault in any of section to the shutdown is not needed
Section A
CB
CB
Section B
CB
CB
CB
CB
3.13 Isolator:
Isolator (disconnecting switch) operates under no load condition. It does not have any
specified current breaking capacity or current making capacity. Isolator is not even used
for breaking load currents. Isolators are used in addition to circuit breakers, and are
provided on each side of every circuit breaker to provide isolation and enable
maintenance. While opening a circuit, the circuit breaker is opened first, then isolator.
While closing a circuit, the isolator is closed first, then circuit breaker. Isolators are
necessary on supply side of circuit breakers in order to ensure isolation (disconnection)
of the circuit breaker from live parts for the purpose of maintenance. Automatic
switching of isolators is preferred.
bond the fence to its own earthing rod system. This earthing rod system is not coupled to
the main substation earthing grid.