Catalogo KAVS
Catalogo KAVS
T&D
Energy Automation & Information
Type KAVS
Check Synchronising Relay
Features
Introduction
Application
Models Available
KAVS 100
Functions
Check synchronising
The relay checks that the two part of
the system are in synchronism by
measuring the angle and the slip
frequency between the line voltage
and the bus voltage. Auto-reclose is
blocked if these values exceed the
phase angle and slip frequency
settings. Manual closure is blocked if
these values exceed the system angle
and system slip settings.
Selectable undervoltage and
differential voltage measurements are
available to block closure if the line
and bus voltages are not compatible.
To allow the circuit breaker to be
closed onto an uncharged line, live
line/dead bus, dead line/dead bus
and dead line/live bus detectors are
included. These allow reclosure when
the voltage on the line and/or the bus
VT is below a preset value.
Scheme logic
The KAVS uses ladder logic (Figure 2)
to implement the scheme. It presents
this in the form of contacts, coils,
counters and timers that are
implemented in the software. In
operation, the left side of the ladder is
analogous to a positive supply rail,
with the right side being negative. The
program then acts as an imaginary
current flowing left to right, acting
upon the components on the rungs of
the ladder as appropriate. Changes
to the scheme can be made through a
user interface by opening or closing
software function links, to match the
scheme to a particular application.
Full details of the scheme logic used
are included in the relevant scheme
description. (See Additional
Information.)
External inputs
Software
relay coil
Break
Make
Function link
Software
relay contact
Timer
Output
Make
Disturbance records
Ancillary Functions
Measurement
The relay can display the magnitude
of the line and bus voltages, line
voltage frequency and slip frequency.
The measurements can be selected by
the user to be displayed as either
primary or secondary quantities.
Primary display quantities are based
on the VT ratios set in the relay. These
quantities can provide a default
setting on the LCD situated on the
relay frontplate.
Event records
Fifty events are stored in a non-volatile
buffer. Software is available to enable
the events to be downloaded to a PC.
Any change of state of a control inpu
or output relay, local setting change or
operation of a control function, is
stored in the relay with a resolution of
1ms. Alarms are also stored as events.
3
Test features
A number of features are provided to
enable the relay to be thoroughly
tested during commissioning, routine
maintenance and fault finding
operations:
The measurement functions allow the
analogue input and its associated
wiring to be checked.
The on/off states of the digital inputs
and relay outputs can be displayed.
Power-on diagnostics and
self-monitoring
Power-on diagnostic tests are carried
out by the relay when it is energised.
These tests include checks on the timer,
microprocessor, memory and the
analogue input circuitry. Continuous
self-monitoring, in the form of
watchdog circuitry, memory checks
and analogue input module tests, is
also performed. In the event of a
failure, the relay will either stop
operating, which resets the watchdog
contact, or will attempt a recovery,
depending on the type of failure
detected.
Hardware Description
K bus screened
2 core cable
Relay 32
Relay 4
Relay 3
Relay 2
Relay 1
User Interface
Front panel user interface
The features of the relay can be
accessed through a menu driven
system. The menu is arranged in the
form of a table, into each column of
which, related items (menu cells) are
grouped.
Protocol
converter
KITZ
RS232
Desktop
computer
PC
K-Bus
Relay interconnection
Communications protocol
Technical Data
Contacts
Ratings
Phase angle
5 to 90
Output relays
Inputs:
Contact ratings
Make: 30A and carry for 0.2s
AC voltage
System angle
5 to 90
Vn (nominal)
57V to 120V
System split
90 to 175
Operating range
0 to 440V
Carry: 5A continuous
25W inductive
Maximum withstand
375V
Durability
Loaded contact
10,000 operations minimum
Auxiliary voltage Vx
24/125V or 48/250V ac or dc
Time settings
Unloaded contact
100,000 operation minimum
Frequency
50/60Hz
Frequency range
45Hz to 65Hz
Output:
Field voltage
48V dc (current limit: 60mA)
Burdens
Transmission mode
Synchronous
Signal levels
RS485
Message format
HDLC
AC voltage
0.02VA at 110V phase/neutral
Voltage settings
Data rate
64 kbits/s
Auxiliary voltage
The burden on the auxiliary supply
depends upon the number of output
relays and control inputs
energized.
Undervoltage
22V to 132V
Connection
Multidrop (32 units)
Differential voltage
0.5V to 22V
K-Bus cable
Screened twisted pair
K-Bus loading
32 units (multi-drop system)
Transformer ratios
Connector
Screw terminals
DC
supply
AC
supply
No. of
output
relays
No. of
control
inputs
Typical
burden
0
2
8
0
2
8
2.5 - 6.0W
4.0 - 8.0W
5.5 - 12W
0
2
8
0
2
8
6.0 - 12VA
6.0 - 14VA
13 - 23VA
Voltage transformers
1:1 to 9999:1
Digital inputs
Opto-isolated inputs
Eight- energized from 48V field
voltage
Nominal rating
50V dc
Off voltage
12V
On voltage
35V
7
Isolation
2kV rms for 1 minute
Electrostatic discharge
IEC 255-22-2: 1996 Class III
8.0kV discharge in air with
cover in place.
Class II 4.0kV point contact
discharge with cover
removed.
No additional tolerances are
required for the operating time or
the units thresholds.
Temperature
IEC 68-2-1: 1990 (cold)
Storage and transit 25C to
+70C
IEC 68-2-2: 1974 (dry heat)
Operating 25C to +55C
Humidity
IEC 68-2-3: 1969
56 days at 93% RH and +40C
EMC Compliance
89/336/EEC
Compliance to the European
Commission Directive on EMC is
claimed via the Technical
Construction File route.
Enclosure Protection
IEC 529: 1989
IP50 (dust protected)
Mechanical environment
Vibration
IEC255-21-1: 1988
Response Class 1
Endurance Class 1
EN 50081-2: 1994
EN 50082-2: 1995
Generic Standards were used to
establish conformity.
Product safety
73/23/EEC
Compliance with European
Commission Low Voltage
Directive.
Seismic
IEC255-21-3: 1993 Class 1
Case
The relay is housed in a size 4
Midos case as shown in Figure 7.
52
4 holes 4.4
97
23.5
Atmospheric environment
159
Push button
projection 10 max.
99
Panel cut-out:
Flush mounting fixing details.
32
Flush mounting.
25 min.
157 max.
177
103
212
11
Additional Information
KAVS 100 service manual
R8506
KAVS 100
Configuration
Standard
Case size
Size 4 Midos flush mounting
Auxiliary voltage
24/125V
48/250V
Ratings
J
Vn = 57.7/120V
Language
English
Glossary
Courier
K-Bus
KITZ
PC
Personal computer
Transmission & Distribution Energy Automation & Information, Le Sextant, 3 avenue Andr Malraux, 92300 Levallois-Perret. France
Tel: +33 (0) 1 41 49 20 00
Fax: +33 (0) 1 41 49 24 85
[email protected]
www.tde.alstom.com
Contact Centre on line 24 hours a day : +44 (0) 1785 25 00 70
ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.
MiCOM is a registered trademark of ALSTOM. Other names mentioned, registered or not, are the property of their respective companies.
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this
brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product
referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.