Honeywell Lyric Controller Installation and Setup Guide
Honeywell Lyric Controller Installation and Setup Guide
TM
Controller
Ref: LCP500-L/LCP500-LC
800-18076
11/15 Rev. B
The Following Recommendations for the location of fire and burglary detection devices help provide proper
coverage for the protected premises.
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations
contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and
areas of the household as follows: For minimum protection a smoke detector should be installed outside of
each separate sleeping area, and on each additional floor of a multi-floor family living unit, including
basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not
normally recommended.
For additional protection the NFPA recommends that you install heat or smoke detectors in the living room,
dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and
attached garages.
In addition, we recommend the following:
Install a smoke detector inside every bedroom where a smoker sleeps.
Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely
closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up
the sleeper if the door is closed.
Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air
conditioners or humidifiers) are used.
Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
Install smoke detectors in any room where an alarm control is located, or in any room where alarm control
connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room
could prevent the control from reporting a fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE
SOUNDING OF FIRE NOTIFICATION APPLIANCES.
For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
premises. This would include any skylights that may be present, and the upper windows in a multi-level
building.
In addition, we recommend that radio backup be used in a security system. This will ensure that alarm signals
can be sent to the alarm monitoring station in the event that the communications are out of order (if
connected to an alarm monitoring station).
This Honeywell security system is designed for use with devices manufactured or approved by Honeywell for use with the
system. The security system is not designed for use with any device that may be attached to the system's control or other
communicating bus if Honeywell has not approved such device for use with the system. Use of any such unauthorized device
may cause damage or compromise the performance of the security system and affect the validity of the end users Honeywell
limited warranty. When you install devices that have been manufactured or approved by Honeywell, you give the end user
the assurance that these devices have been thoroughly tested to ensure optimum performance when used with this
Honeywell security system.
-2-
Table of Contents
System Features ............................................................................................................................................................................................ 5
Installing the Control ....................................................................................................................................................................................7
Battery Installation ..........................................................................................................................................................................................7
Battery Selection .....................................................................................................................................................................................7
Installing the Rechargeable Backup Battery .................................................................................................................................7
Replacing the Rechargeable Backup Battery ...............................................................................................................................7
Wall Mounting .................................................................................................................................................................................................. 8
Desktop Mounting .......................................................................................................................................................................................... 9
Replace the Back Plate......................................................................................................................................................................... 9
Install the Desk Stand ........................................................................................................................................................................... 9
AC Power ..........................................................................................................................................................................................................10
Wiring Overview ............................................................................................................................................................................................10
Make Electrical Connections .............................................................................................................................................................10
Communications Modules ........................................................................................................................................................................... 11
Communications Module 24-Hour Standby power ................................................................................................................... 11
Install and Configure Communications Module .................................................................................................................................. 11
Installing the Cellular Module ............................................................................................................................................................. 11
Checking Signal Strength ................................................................................................................................................................... 12
Wireless Zones .............................................................................................................................................................................................. 13
General Information ...................................................................................................................................................................................... 13
Zones.......................................................................................................................................................................................................... 13
Range ......................................................................................................................................................................................................... 13
Transmitters............................................................................................................................................................................................. 13
House Identification .............................................................................................................................................................................. 13
Transmitter Supervision ...................................................................................................................................................................... 13
Transmitter Input Types...................................................................................................................................................................... 13
Transmitter Battery Life ...................................................................................................................................................................... 13
RF Transmitter Loop Numbers.........................................................................................................................................................14
Mechanics of Programming .................................................................................................................................................................... 15
Navigating Menus .......................................................................................................................................................................................... 15
Touch-screen Display........................................................................................................................................................................... 15
Navigation Keys ..................................................................................................................................................................................... 16
Home Screen ........................................................................................................................................................................................... 16
Security Screen ...................................................................................................................................................................................... 17
Master User Tools Screen ................................................................................................................................................................... 17
Programming .................................................................................................................................................................................................. 18
Enter Installer Programming Mode ................................................................................................................................................. 18
Loading Factory Defaults ........................................................................................................................................................................... 19
Select a Default Configuration ......................................................................................................................................................... 19
Exit Programming Mode ............................................................................................................................................................................. 19
Zone Response Type Definitions .........................................................................................................................................................20
General Information .....................................................................................................................................................................................20
System Operation ....................................................................................................................................................................................... 22
Key/Touchscreen Operation .................................................................................................................................................................... 22
Panic Key/Icons............................................................................................................................................................................................. 22
Security Codes............................................................................................................................................................................................... 22
Installer Code ......................................................................................................................................................................................... 22
Master Code ........................................................................................................................................................................................... 22
Enter/Change the Master Code by Installer ............................................................................................................................... 22
Secondary User Codes ....................................................................................................................................................................... 22
Reset Master Code ............................................................................................................................................................................... 23
Security Code Notes ........................................................................................................................................................................... 23
System Displays ............................................................................................................................................................................................24
Zone Status Displays ...................................................................................................................................................................................24
Audio Alarm Verification (Two-Way Voice Feature) ..................................................................................................................... 25
Activation ................................................................................................................................................................................................ 25
Operator Commands .......................................................................................................................................................................... 25
Event Log ........................................................................................................................................................................................................ 26
Contact ID Event Log Codes............................................................................................................................................................ 26
Central Station Messages .......................................................................................................................................................................... 27
Testing the System .................................................................................................................................................................................... 28
-3-
Lyric Lock
This system supports Lyric Lock, an advanced feature designed to keep it functioning optimally. Lyric Lock
capabilities include: the ability to interact with Honeywell and your companys network for the setup and
programming of system features, support for remote software updates and the ability (when enabled) to
enhance the end users security by preventing unauthorized takeover of the system by another monitoring
company.
In the event that the end user wishes to authorize another company to take over the system, the end user may
request that Honeywell remotely disable Lyric Lock. Honeywell will require documentation that the end user
has attempted to contact your company three times and that your company has failed to respond, or failed to
agree to the end users request.
-4-
System Features
The Lyric Controller is a self-contained, rechargeable wireless control/communicator that features easy
installation and usage. A built-in speaker provides voice annunciation of system status along with voice
descriptors of each zone. An internal module allows the controller to communicate with the Central Station via
the Internet or (if installed) Cellular Wireless.
ETL
Lyric Controller is not intended for UL985 Household Fire applications unless a 24-hour backup
battery (p/n 300-03866-AIO) is installed.
System Features
Home Automation
Communication
ADEMCO Contact ID
Integrated WiFi Support
Cellular (GSM or CDMA) Central Station communication
WiFi Central Station communication
Two-way Voice Communication
TM
Remote Services
-5-
Primary Power: Plug-in Power Supply, 110VAC to 9VDC, 2.7A output p/n 300-04705V1 (300-4063V1 in
Canada)
Backup Battery: Rechargeable Nickel-metal Hydride Battery Pack rated at 7.2Vdc. (p/n 300-03864-AIO
or 300-03866-AIO
Alarm Output
Built-in Sounder
Steady Output for burglary/panic
Temporal (3) Pulse Output for fire alarms
Temporal (4) Pulse Output for carbon monoxide alarms
Audio Alarm Verification (AAV)
Programming
Other Features
Exit Error feature (detects difference between an actual alarm and exit alarm caused by leaving a door
open after the exit delay expires)
Event Log Storage (total 6,000 events)
RF Jam Detection
Advanced Protection Logic (APL) (Minimizes the likelihood of the system being disabled before
notification can be sent to the Central Station indicating that the premises have been compromised.)
Lyric Lock (Customer Retention Logic) Dealer selectable Lockout (anti-takeover) feature
Displays web content including Local News, Weather and Traffic (requires Total Connect Service)
Dealer/Central Station Messages (requires Total Connect Service)
-6-
The Lyric Controller is equipped with an integral, replaceable, rechargeable battery pack rated at 7.2Vdc. In the
event of an AC power loss, the system is supported by the long life backup battery that is supervised for
connection and for low voltage conditions. If the battery is missing, or a low battery condition is detected, a
low battery message is displayed and a report is sent to the Central Station. In addition, the system will beep
once every 45 seconds to audibly indicate a low battery condition (press any key to stop the beeping). Select
the appropriate battery pack, based on the installations requirement, and install the battery pack. Follow the
steps and refer to the figure below to install and connect the battery.
Battery Selection
Select the appropriate battery pack, based on the installations requirement, and install the battery pack.
Battery Part Number
300-03864-AIO
300-03866-AIO
Battery StandbyTime
4-hours (minimum)
24-hours (minimum)
Rechargeable batteries may take up to 48-hours to fully charge. The Low Battery message
should clear within four hours or by entering Test Mode.
When battery replacement is required, at the Installer Programming Tools Menu select Test OR at the
Master User Tools Menu screen select the Advanced icon.
2. Select Install Backup Battery and follow the displayed steps to replace the battery or follow the steps
below.
Remove the battery
1. Unscrew the screw securing the controller to the wall mount (if used).
2. Release the catch that secures the controller to the wall mount.
3. Rotate the controller away from the wall and lift it from the wall mount, being careful not to damage the
wiring.
-7-
Disconnect the battery pack connector from the receptacle on the back of the controller.
Remove the screw that secures the battery retainer and remove the battery retainer.
Remove the battery pack from the back case.
Wall Mounting
NOTE: When selecting a location for the Lyric Controller, be sure to provide a separation of at least 10 feet
between 2.4GHz devices such as Wi-Fi Routers/Access Points.
For wall mounting follow the steps and refer to the figure below.
1.
2.
3.
4.
5.
Feed the field wiring through the appropriate openings in the wall mount.
Attach the wall mount to a sturdy wall using the four provided screws.
If required, install an additional mounting screw in the case tamper.
Align the slots on the back of the controller with the hooks on the wall mount as shown below.
Once attached, insert the screw to secure the Lyric to the wall mount.
-8-
Desktop Mounting
NOTE: When selecting a location for the Lyric Controller, be sure to provide a separation of at least 10 feet
between 2.4GHz devices such as Wi-Fi Routers/Access Points.
For desktop mounting the Lyric Desk Stand (LCP500-DK) is installed in place of the wall mount. The desk Stand
can be installed in two positions that provide a viewing angle of 30 degrees or 60 degrees. Follow the steps and
refer to the figures below.
Replace the Back Plate
1. Remove the screw securing the rear cover to the controller.
2. Remove the rear cover.
NOTE: If using the high-capacity (24-hour) backup battery (Kit LCP500-24B, battery p/n 300-03866-AIO),
remove the battery retainer clip. The clip is not required when the desk mount is installed.
3. Feed the field wiring through the appropriate openings in the rear cover included with the Lyric Desk Stand
(LCP500-DK).
4. Install the new rear cover.
5. Install the screw to secure the rear cover to the Lyric Controller.
-9-
The Lyric Controller is powered by a 110VAC, 60 Hz/9 Volt DC, 2.7 Amp Plug-in Power Supply, 300-04705V1
(300-04063V1 in Canada). Refer to the wiring table below for wire gauge and length.
Use only the 300-04705V1 (300-04063V1 Canada) Power Supply. Do not plug the power supply
into the AC outlet until after all wiring connections have been made.
WIRING TABLE
MAXIMUM DISTANCE BETWEEN
POWER SUPPLY AND CONTROLLER
WIRE
GAUGE
Up to 8 feet (2.44 m)
# 22
Up to 13 feet (3.96 m)
# 20
Up to 20 feet (6.1 m)
# 18
Wiring Overview
The following summarizes the electrical connections associated with the Lyric Controller. Follow the steps and
refer to the figure below when making connections. Refer to the Summary of Connections diagram for
additional information.
4.
5.
6.
Temporarily hang the controller from the hook on the wall mount.
If used, connect the hardwire sensors/contacts to the HWZ1/HWZ2 (+) and GND (-) terminals.
Connect the Power Supply (p/n 300-04705V1 or 300-04063V1) to the +9VDC and GND terminals on the
controller.
Align the slots on the back of the controller with the hooks on the wall mount as shown below.
Once attached, insert the screw to secure the controller to the wall mount.
Plug the power supply into a 24-hour, 110VAC unswitched outlet. Upon power-up, the System Standby!
screen will be displayed.
- 10 -
Communication Modules
The Lyric Controller supports Central Station reporting using wireless/cellular and WiFi communications
devices. They also support upload/download programming capability via the Internet. This allows site
maintenance independent of Central Station monitoring, and modification to sites globally via the Internet. Refer
to the Programming Guide (p/n 800-18077) for information regarding programming and registration.
Additionally, an internal Z-Wave module allows the Lyric Controller to support Home Automation functions.
(refer to the Lyric User Guide (p/n 800-16078 for additional information.) The controllers are compatible with
the following AlarmNet Communication Modules:
Model
LYRIC-3G
LYRIC-CDMA
Description
GSM Cellular Communications Module
CDMA Cellular Communications Module
If 24-hour standby is required, the Super High Capacity battery (p/n 300-03866-AIO) must be installed.
RF Exposure
WARNING: The Lyric Controller must be installed to provide a separation distance of at least 7.8
in (20 cm) from all persons and not co-located or operated in conjunction with any other
transmitter except in accordance with FCC multi-transmitter product procedures.
Follow the steps and refer to the figure below to install the Communications Module.
At the Installer Programming Tools Menu screen select Test OR at the Master User Tools Menu
Programming screen select Advanced.
2. Select Install Cellular Module and follow the prompts displayed on the controller or follow the steps below.
3. Remove controller side cover (bezel).
4. Remove the screw securing the module to the controller (if installed).
5. Remove the existing Cellular Communications Module (if installed).
6. Install the Cellular Communications Module into the controller.
7. Ensure that the Communications Module is properly seated into the controller and secure the module with
the provided screw (if required).
8. Insert the side cover (bezel) into the controller.
9. Slide the side cover (bezel) down to lock it in place and secure the Communications Module.
10. Select OK to complete the installation.
NOTE: The Communication Path will be dynamically adjusted when a Cellular Communication Module is
installed or removed.
11.
Enable the Communications Module, configure alarm reporting and module supervision and register the
device. Refer to the Program Communicator and Communications Diagnostics sections in the
Programming Guide (p/n 800-18077). OR Log on to the AlarmNet 360TM website (http://alarmnet360.com).
The Communications Module must be registered with AlarmNet 360TM before downloading or
alarm reporting can take place.
- 11 -
- 12 -
Wireless Zones
General Information
Zones
The Lyric Smart Control supports up to 128 total wireless zones using 5800 and SiX Series transmitters, and
wireless keys.
Range
The built-in RF receiver can detect signals from wireless transmitters within a nominal range of 200 feet.
Transmitters
5800 and SiX Series transmitters have built-in serial numbers that must be entered into the system using the
Zones programming section, or input to the controller via AlarmNet 360TM. Each transmitter's zone number is
also programmed into the system in the Zones programming section. Some transmitters, such as the 5816 can
support more than one "zone" (referred to as loops or inputs). On the 5816, for example, the wire connection
terminal block is loop 1; the reed contact is loop 2. Each loop must be assigned a different zone number.
For 5800 Series wireless keys such as the 5804E, 5834-4 and 5878, you must assign a unique zone number to
each individual button used on the transmitter. Each button on the transmitter also has a pre-designated loop
or input number, which is automatically displayed.
ETL
The 5816 Transmitters do not have EOL supervision of their loop wiring, which must not exceed 3
feet.
The 5800PIR-OD, 5800SS1, 5804E, 5814, 5821, 5877 and 5878 wireless transmitters have not been
evaluated by ETL.
House Identification
If a RF House ID (RF House Code) is required to establish proper communication, the same two-digit code (01
31) must be programmed in the Lyric, and the device. Refer to the System Type programming section in the
Lyric Controller Programming Guide (p/n 800-18077). An RF House ID is not necessary for 5800 Series
transmitters and the entry should be left at 0 (default) in those cases.
Transmitter Supervision
With the exception of some transmitters/keypads that may be carried off-premises (5804E, 5834-4 and
SiXFOB), each transmitter is supervised by a check-in signal that is sent to the receiver at 7090 minute
intervals. If at least one check-in is not received from each supervised transmitter within a 12-hour period, the
"missing" transmitter zone number(s) and "Supervision" will be displayed. The supervision for a particular
transmitter in the system that may also be carried off the premises may be turned off by entering it as an
Unsupervised type. For additional information, refer to the Zones programming section in the Lyric
Controller Programming Guide (p/n 800-18077). 5800 and SiX Series transmitters have built-in tamper
protection and will annunciate as a fault condition if covers are removed. In Canada the RF supervision period
is 3-hours for Fire zones and 12 hours for all other zone types.
Each transmitter has one or more unique factory-assigned input (loop/5800 Series or service/SiX Series) ID
codes. Each of the inputs requires a programming zone (e.g., a 5804E's four inputs require four button zones).
Transmitters can be entered as one of the following types (see transmitters instructions for appropriate
Supervision type):
Type
Supervised
Unsupervised
Button
Description
Sends periodic check-in signals, as well as fault, restore, and low battery signals. The
transmitter must remain within the receiver's range.
Sends all the signals that the Supervised type does, but the controller does not supervise the
check-in signals. The transmitter may therefore be carried off-premises.
Sends only fault signals. Do not send low battery signals until being activated. The
transmitter is unsupervised and may be carried off-premises.
Batteries in the wireless transmitters may last from 47 years, depending on the environment, usage, and
the specific wireless device being used. Factors such as humidity, high or low temperatures, as well as large
swings in temperature may all reduce the actual battery life in a given installation. The wireless system can
identify a true low battery situation, thus allowing the dealer or user of the system time to arrange a change
of battery and maintain protection for that point within the system.
Button-type transmitters should be periodically tested for battery life. The 5804E, 5834-4, 5878 and SiXFOB
button transmitters have replaceable batteries.
- 13 -
Notes: (1) The 5806W3 smoke detector must be used in SIA applications.
(2) Button type devices send only fault and low battery signals; no restore or check-in signals.
Supervised RF devices send periodic check-in signals, faults, restore and low battery signals.
(3) The 5804E and 5834-4 encrypted (High-Security) devices must be activated while the system is in
Go/No-Go Test Mode. Refer to the transmitters Installation Instructions for complete details. The
system will confirm the enrollment of the encrypted device by beeping two times.
(4) The 5800PIR-OD, 5800SS1, 5804E, 5814, 5821, 5877, and 5878 wireless transmitters have not been
evaluated by ETL.
- 14 -
Mechanics of Programming
Navigating Menus
Touch-screen Display
The LYRIC Controllers Liquid Crystal Display (LCD) touch-screen displays variable icons and text on screens.
The screen displays status icons and associated text, the current time and date, system status information and
menu choices. The Menu area includes a list of commands, or choices that apply to the current selection. The
status area provides information about various system events and a colored bar also provides an indication of
system status. A Home Screen is displayed whenever power is applied to the system. In addition, the Home
Function key is lit Green when the system is ready or flashes when it is not. When the system is armed the Home
Function key is lit Red.
LYRICTM Controller
Key
Description
Panic key - Initiates panic alarm options when selected for 4 seconds.
Home key - Used to exit from a screen or return to the home screen
- 15 -
Navigating through the screens is accomplished by lightly touching the icons or menu items on the touchscreen. Once activated, the controller advances to the next screen. Selecting the Home (cancel) key or the
key will return you to the previous screen at any time unless System Programming mode is active. By touching
(selecting) an icon or key the system, depending on the function, advances to another screen, toggles between
options or scrolls through multiple options that can be selected. The system provides a prompt when a specific
input is required.
Note: You may find it convenient to adjust the volume setting before entering the Program Mode. This will
allow you to clearly hear the feedback announcements or system beeps from the systems built-in
speaker. To adjust the volume, select Settings on the Home screen. Adjust the volume using the slide
displayed on the Settings screen and then select Save to accept.
Home Screen
System Status is displayed at the top of screen. In addition to the system status, the Home Screen displays the
current date and time and Security, Automation, Video, Smart Scenes, Notices Settings and Help Videos icons
on two pages. When Total Connect Services are connected and web content is enabled, News and Traffic icons
are displayed along with the current weather forecast and a 5-Day Forecast button. Selectable options are
displayed on two pages. Select the > and <to navigate between the two home screen pages.
Function
Provides access to Security Screen
Provides access to Automation Screen
Provides access to Video Screen
Provides access to Smart Scenes Programming Screen
Provides access to Dealer Notification Message Screen
Provides access to System Settings Screen
Provides access to Help Videos
Provides access to News Screen
Provides access to Traffic Screen
Provides access to local 5-Day Weather Forecast Screen
(displayed on both pages)
Provides local forecast and severe weather alerts
(displayed on both pages)
- 16 -
Function
Used to Arm the system in Away mode (displayed on both Home Screen pages).
Used to Arm the system in Stay mode (displayed on both Home Screen pages).
Used to Arm the system in Custom mode (displayed on both Home Screen pages).
Provides information about system status.
Provides access to Installer and User Programming Menus (Master User Code required for
access).
Provides access to Message Center (displayed on both Home Screen pages).
Provides access to Zone information and options.
- 17 -
If the system is Armed or in Alarm, the Tools icon will not be functional. The system must first
be disarmed.
ACTION
1.
2.
3.
4.
5.
6.
7.
- 18 -
To load the factory defaults, enter the Installer Programming Mode and advance to second page of the System
Programming and refer to following procedure. Refer to the Programming Default Values section of this manual
to view the Default Values.
If a default configuration is loaded, any data that has already been programmed into the system
will be changed according to the default configuration selected!
ACTION
1. Select Default Configuration to display the following
options:
Default Config 1
Default Config 3
Default Config 2
Default Config 4
- 19 -
During programming, you must assign a zone type to each zone, which defines the way in which the system
responds to faults in that zone. Zone types are defined below.
Type
Not Used
Entry/Exit 1
(Burglary)
Function
Characteristics
Entry/Exit 2
(Burglary)
Perimeter
(Burglary)
Interior, Follower
24-hour Silent
Alarm
24-hour Audible
Alarm
24-hour
Auxiliary
Alarm
Trouble by Day/
Alarm by Night
Silent Burglary
Local Alarm
24-hour Carbon
Monoxide Monitor
Trouble
Fire No
Verification
None
Entry delay #1 is programmable.
Exit delay is independently programmable.
Exit and entry delays when armed in Away, Stay or Night
Stay mode.
No entry delay when armed in Stay or Away Instant modes.
Exit delay regardless of the arming mode selected.
Entry delay #2 is programmable.
Exit delay is independently programmable.
Secondary entry delay, if armed in the Away or Stay mode.
No entry delay when armed in the Stay Instant or Away
Instant mode.
Exit delay begins regardless of the arming mode selected.
Instant alarm, when armed in Away, Stay, Stay No Delay,
Night Stay or Away Instant mode.
Delayed alarm (using the programmed entry/exit time) if
entry/exit or interior-with-delay zone is faulted first.
Instant alarm in all other situations.
Active when armed in Away or Away Instant mode.
Bypassed automatically when armed in Stay, Night Stay or
Stay Instant mode.
- 20 -
Characteristics
Fire with
Verification
Type
ArmStay
ArmAway
Alarm sound will pulse (Temporal Fire) when this zone type is
alarmed and the alarm has been verified.
System verifies alarm by delaying reporting and alarm
sounding for 30 seconds after alarm is detected. If the zone
remains faulted after 30 seconds a fire alarm is provided. If
any other fire zone is faulted during the 30 second delay
window a fire alarm is immediately provided for that zone.
An alarm for original fire zone will also be provided, if that
zone is still faulted. If there are no fire alarms after the 30
second delay expires, the system will open a 60 second
window. If any fire zone is faulted during that window a fire
alarm will immediately be provided for that zone.
Exit delay regardless of the arming mode selected.
System is armed in the Stay mode when the zone is
activated.
System is armed in the Away mode when the zone is
activated.
Disarms the system when the zone is activated.
Disarm
No Alarm
Response
Monitor
General Monitor
General
Response
Resident Monitor
Resident
Response
Garage
(Burglary)
Garage Monitor
- 21 -
System Operation
Key/Touchscreen Operation
The touchscreen icons allows the user to arm and disarm the system, and perform other system functions, such
as bypassing zones. Zone and system conditions (alarm, trouble, bypass) are displayed on the LCD. When an
alarm occurs, the console and external sounder (if installed) will sound, and the zone(s) in alarm will be
displayed. Pressing any key will silence the keypad sounder for 10 seconds (only once). Disarming the system
will silence both console and external sounders. When the system is disarmed, any zones that were in an alarm
condition during the armed period will be displayed (memory of alarm). To clear this display, simply repeat the
disarm sequence by selecting the Disarm button and entering the Security Code. The console also features
chime annunciation, and three panic key icons for silent, audible, fire or personal emergency alarms. These keys
can notify the Central Station of an alarm condition, if that service is connected.
Panic Key/Icons
There are four panic icons that are displayed (if programmed) when the Panic key is selected for
approximately four seconds. The panic key screen will timeout if a selection is not made within ten seconds.
The keys can be used to manually initiate alarms and send a report to the Central Station. Each can be
individually programmed for 24-hour silent, audible, personal or fire emergency responses. The panic function is
activated when the respective keys is pressed. The panic functions are identified by the system as follows:
Zone
995
996
998
999
Function
Fire Emergency
Medical Emergency
Local Alarm
Police Emergency
Important: For the silent panic functions to be of practical value, the system must be connected to a Central
Station.
Security Codes
Installer Code
The installer programs the 4-digit Installer Code initially as part of the programming procedure. The
factory default Installer Code is 4-1-1-2, but may be changed in the Installer Code programming field.
The Installer Code is the only code that allows entry into Installer Programming mode.
Master Code
In normal operation mode, the Master (Security) Code is used to enter the 4-digit User Security Codes and enter
the Master User Tools Menu mode.
The factory default Master Code for the Lyric Controller is set to 1-2-3-4. The Master Code is used to enter the
4-digit User Security Codes.
SCREEN
ACTION
1.
In normal operation mode, the Master (Security) Code can be used to assign up to 46 secondary 4-digit security
codes, including a Guest Code and a Duress Code. The Master Code can also be used to individually remove
secondary codes from the system. Refer to the Lyric Controller User Manual for additional information.
- 22 -
System Operation
Reset Master Code
1.
After Entering the Installer Programming Mode, select Reset Master Code from the second page of the
Installer Programming Tools menu.
The system displays a confirmation screen. Select the Yes key to reset the Master User Code to 1234.
If confirmed, the Master Code will be reset back to 1-2-3-4. This will be logged in the System Event Log as
User: 1 Reset Master Code, E655. The system returns to the second page of the Installer Programming
Tools menu.
OR
If the reset failed, the system will display: Command Failed. Unable to Reset Master Code. This will only
occur if the code 1-2-3-4 has been assigned to another User in the panel.
2.
3.
- 23 -
System Operation
System Displays
The following icons will be displayed on the Home screen along with specific zone status information (if
applicable) to indicate system status.
DISPLAY
DEFINITION
DISPLAY
DEFINITION
DISPLAY
DEFINITION
AC Loss
901 Expansion
Temperature
Module Tamper
Alarm
(Intrusion)
950 Comm.
Trouble
Other
Ready To Arm
988 RF Jam
Automation
Icon
(5800 Series
Wireless Device)
Armed Away
990 RF Jam
(SiX Series
Wireless Device)
(Z-Wave Node
Failure OR ZWave Controller
Not Ready)
Garage Door
Open
Armed Stay
998 Local
Alarm
WiFi source
present and
signal strength
Armed Night
Stay
Door Open
No WiFi source
Armed Custom
Window Open
Restart Timer
Fire
OR
Heat Sensor
Environmental
Battery Low
Bypassed
Zones
Flood
CO Alarm
Glass Break
Reporter
Failure
Medical Alarm
Low Batt
850 Keypad
Keypad
900 Cover
Tamper
Motion
The icons associated with the programmed zones are displayed on the Zones screen. The icons color
indicates the zone status (i.e.; yellow icon indicates the zone is faulted and a red icon indicate the zone
is in alarm). In addition a bypass icon is displayed alongside the icon for a bypassed zone.
- 24 -
This feature allows the Central Station operator to listen, talk to or conduct a two-way conversation with an
individual(s) at the premises. It also assists the operator in gathering information about the nature and location
of the alarm that may be helpful in responding to police and fire departments. All Lyric Controllers are capable
of supporting the Two-Way Voice feature. The Lyric Controller does not make system announcements when the
Two-Way Voice feature is active.
If a WiFi connection is being used for Two-Way Voice (AAV), sufficient bandwidth must be available.
AAV requires a continuous WiFi upload/download bandwidth of 90kbps for proper operation.
Activation
Fire and CO alarms will prevent the Lyric Controller from starting an AAV session. A new Fire or
CO alarm will end an AAV session that is in progress.
The controller sends the alarm message followed by a Listen-in-to-Follow message (Contact ID code 606)
to the Central Station. The Listen-in-to-Follow message causes the Central Stations digital receiver to
temporarily hold the phone line for approximately 1 minute. When the controller receives the kissoff from the
Central Station, indicating that the alarm message has been received, the Two-Way Voice (AAV) feature is
activated in the (default) Listen Mode and sirens and keypad sounds are discontinued. The controller transmits
a beep acknowledgment to the Central Station, once per second. The beep alternates between two tones and
indicates that the controller is waiting for a session command from the Central Station operator. Once a
command is issued the beep acknowledgement is discontinued, however, if a command is not issued within two
minutes the system will time out and the call will be terminated.
Operator Commands
The Central Station operator begins the session, which last 5 minutes, by entering one of the valid AAV
commands shown in the table below. The session may be extended 5 minutes, without changing the operating
mode, by pressing the [7] key on the touch-tone phone. Selecting another operating mode also resets the
session an additional 5 minutes. During the last minute of the 5 minute, session, the controller generates two
beeps every 30 seconds to alert the Central Station operator that the session is about to time out. The Central
Station operator may then extend the session by pressing the [7] key on the touch-tone phone. If the session is
not extended, the phone line is disconnected and the session is ended. Sessions may be ended at any time by
pressing the [9] key on the touch-tone phone. The AAV modes are described as follows:
Note: When entering AAV commands make sure the Central Station receiver has been disconnected
from the phone line, otherwise AAV commands may not go through.
Key
1
Function
Talk Mode: Pressing the [1] key on the touch tone phone, enables one-way voice communication
from the Central Sation to the violated premises, and allows the operator to communicate through
the controllers built-in speaker. In this mode the controllers Panic and Home buttons blink
alternately.
VOX (Voice) Mode: Pressing the [2] key on the touch-tone phone, enables two-way voice
communications between the Central Station and the violated premises via the controllers built-in
speaker and microphone. In this mode the controllers Panic button is lit Red and the Home button is
alternately lit Red and Green.
Listen Mode: Pressing the [3] key on the touch-tone phone, Enables one-way audio from the violated
premises to the Central Station. The Listen Mode is the start up default mode of the voice feature and
allows the operator to listen through the controller microphone. This mode does not affect the existing
LED pattern.
- 25 -
System Operation
Event Log
The Lyric Controller Series event log is capable of recording and displaying up to 6,000 system events. These
events are stored locally in the controller, in chronological order, and transmitted to the Central Station. When
the maximum number of events is reached in the Event Log, the system will overwrite the oldest event first. The
type of events that can be recorded is selectable and is programmed in the System Type programming field.
The event log can be reviewed by entering the Installer Programming or Master User Programming mode and
selecting Events. Refer to the Lyric Controller User Manual for additional information. The Events and CID
Codes displayed vary according to the options that are programmed. The tables below provide definitions of
the events/codes that may be transmitted to the Central Station and/or displayed by the controller.
Note: In the unlikely condition that the backup battery becomes fully discharged when AC power is lost, any system activity
performed after the low battery notification will not be saved in the event log. Additionally, the controller will revert to
the status condition as before the low battery notification.
CID Code
110
121
122
123
131
132
134
135
137
145
146
150
162
301
302
305
308
316
341
344
350
353
354
373
374
380
381
383
384
401
403
406
407
408
441
455
459
461
570
601
602
606
607
623
627
628
654
655
Definition
Alarm, Fire
Alarm, Duress
Alarm, Silent
Alarm, Audible
Alarm, Perimeter
Alarm, Interior
Alarm, Entry/Exit
Alarm, Day/Night
Alarm, Tamper
Expansion Module Tamper
Silent Burglary
24-Hour Non-Burglary
Carbon Monoxide Detected
Trouble, AC Loss
Trouble, Low System Battery
Trouble, System Reset
System shutdown
System Tamper*
Trouble, Case Tamper
Trouble, RF Receiver Jam Detect
Long Range Radio Reset
Trouble, Long Range Radio Transmitter Fault
Failure to Communicate Event
Trouble, Fire Trouble
Trouble, Exit Error Alarm
Trouble, Sensor
Trouble, Loss of Supervision RF
Trouble, Sensor Tamper
RF Low Battery
Open/Close by User
Open/Close Automatic
Cancel
Remote Arm/Disarm
Quick Arm
Armed Stay
Auto-Arm Failed
Recent Close
Wrong Code Entry
Zone/Sensor Bypass
Manual Trigger Test Report
Periodic Test Report
Listen-in to follow
Walk Test
Event 90% Full
Program Mode Entry
Program Mode Exit
System Inactivity
Reset Master Code
*If APL is enabled, AlarmNet 360TM will generate a special comm. fail message (E316) if it does not hear from a unit within 15 minutes
after a delayed alarm is delivered. This message is meant to alert the Central Station that the system has been tampered with and may
have been compromised.
- 26 -
System Operation
Contact ID Event Log Codes
CID Code
759
760
761
762
1401
3000
3001
3100
3101
3200
3201
3300
3301
3302
3400
3401
3402
3403
3404
3405
3406
3407
3408
3409
3410
3411
3412
3500
3501
4000
4001
4002
4003
5000
Definition
The following messages are sent by the controller internal cellular or WiFi devices for the conditions listed
below.
Alarm Condition
Power On / Reset
Primary Communication Path Supervision
Secondary Communication Path Supervision
Test
Alarm Code
E33900950
E350C0951
E350C0952
555555559
- 27 -
Restore Code
R350C0951
R350C0952
Test Modes
The Test button provides access to the following functions and test modes:
Option
Walk Test
RF Sniffer Test
Go-No-Go Test
Diagnostics
Zone Discovery
Install Cell
System
Information
Install Backup
Battery
Function
Refer to the User Manual for additional information
Refer to the Programming Guide (p/n 800-18077) for additional information.
Refer to the Programming Guide (p/n 800-18077) for additional information.
Provides access to the Reboot Feature. Refer to the paragraph in this section for additional
information regarding this feature.
Provides access to the Zone Discovery mode. Refer to the paragraph in this section for
additional information regarding the Zone Discovery feature.
User feature that allow the Master User to install or replace a Communications Module.
Refer to the User Guide (p/n 800-18078) for additional information.
System Information is displayed. Select OK to return to the previous screen.
User feature that allow the Master User to replace the backup battery. Refer to the User
Guide (p/n 800-18078) for additional information.
After installation is completed, the security system should be carefully tested, as follows:
1.
With the system in the disarmed state, check that all zones are intact. If the ready LED or Home button
is not lit, select the Zones icon to display the faulted zone(s). If necessary, restore faulted zone(s) so that
the ready LED or Home button lights. Fault and restore every sensor individually to assure that it is
being monitored by the system.
Alarm messages will be sent to the Central Station during the following tests 1 and 2.
Station in advance that tests will be in progress.
1.
2.
3.
4.
Arm the system and fault one or more zones. After 15 seconds (if optional Alarm Report Delay is selected),
silence alarm sounder(s) by disarming the system. Check entry/exit delay zones.
Check the keypad-initiated alarms that are in the system by selecting the Panic key. If the system has been
programmed for audible emergency, the keypad will emit a steady alarm sound, and ALARM and zone
number will be displayed. Silence the alarm by entering the Security Code.
If the system has been programmed for silent emergency, there will be no audible alarms or displays, but a
report will be sent to the Central Station.
Notify the Central Station when all tests are finished, and verify results with them.
To test the wireless part of the system and the RF receiver, perform the two additional tests described in
the Programming Guide (p/n 800-18077): Sniffer mode and Go/No Go Test.
Note:
System Test mode and Go/No Go Test will be automatically terminated after 3-1/2 to 4 hours if the
installer or user does not manually terminate it. This ensures that fire and panic zones will not remain
disabled. However, Sniffer mode does not automatically expire. You must manually exit Sniffer mode by
selecting the Home key and entering the Master Code, to return to normal operation. During the final 5
minutes the system will emit double beeps indicating that the end of Test mode is nearing.
- 28 -
With the System in the Installer Programming mode, select the Test button and then select the Zone
Discovery button. The Zone Discovery button will be highlighted indicating that the mode is active.
Select the Home key and enter the Master Code. If you do not exit Zone Discovery mode manually, the
system will automatically exit zone discovery mode in approximately 1-4 minutes dependent upon the
number of zones that are programmed. The system beeps once and returns to the home screen.
The Reboot function allows you to restart the system if required. To reboot the system perform the following:
1.
2.
3.
With the System in the Installer Programming mode, select the Test button and then select the
Diagnostics button.
The system advances to the next screen. Select the Reboot button. A confirmation screen appears.
Select Yes. The system will restart.
Note: After the reboot sequence is complete it is recommended that you perform a Walk Test to verify that
all transmitters are operational in the system.
.
- 29 -
Configuration 1
4112
Configuration 2
4112
Configuration 3
4112
Configuration 4
4112
RF Jam Log
0
Disabled
Press to Log All
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Disabled
RF Jam Log
0
Disabled
Press to Log All
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Disabled
RF Jam Log
0
Disabled
Press to Log All
Enabled
Disabled
Disabled
Enabled
Disabled
Disabled
Disabled
RF Jam Log
0
Disabled
Press to Log All
Enabled
Disabled
Disabled
Enabled
Disabled
Disabled
Disabled
January 1, 2013
12:00 PM
Eastern (EST)
Yes
March
Second
November
First
January 1, 2013
12:00 PM
Eastern (EST)
Yes
March
Second
November
First
January 1, 2013
12:00 PM
Eastern (EST)
Yes
March
Second
November
First
January 1, 2013
12:00 PM
Eastern (EST)
Yes
March
Second
November
First
WiFi
Disabled
Blank
Blank
Blank
30 days
10 Minutes
Disabled
Disabled
WiFi
Disabled
Blank
Blank
Blank
30 days
10 Minutes
Disabled
Disabled
00
00
Yes
60
No
No
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
See
See
Yes
60
No
No
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
Zone Programming
Zone Programming
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
- 30 -
WiFi
Disabled
Blank
Blank
Blank
30 days
10 Minutes
Disabled
Disabled
WiFi
Disabled
Blank
Blank
Blank
30 days
10 Minutes
Disabled
Disabled
00
00
Yes
Yes
60
60
No
No
No
No
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
255.255.255.255
Default Configurations
Default Configurations
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Configuration 1
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Configuration 2
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Configuration 3
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Configuration 4
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
2 Reports
30 Sec.
6 Hrs
Never
2 Reports
30 Sec.
12 Hrs
30 Days
2 Reports
30 Sec.
12 Hrs
Never
2 Reports
30 Sec.
12 Hrs
Never
Yes
4 Minutes
4 Minutes
RF Key Fob
Yes
4 Minutes
4 Minutes
RF Key Fob
Yes
4 Minutes
4 Minutes
RF Key Fob
Yes
4 Minutes
4 Minutes
RF Key Fob
30 Seconds
30 Seconds
60 Seconds
30 Seconds
30 Seconds
60 Seconds
30 Seconds
30 Seconds
60 Seconds
30 Seconds
30 Seconds
60 Seconds
No
No
No
No
Yes
Yes
Yes
No
Yes
Yes
Disabled
Yes
Yes
Yes
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled
Yes
Yes
Yes
No
Yes
Yes
Disabled
Yes
Yes
Yes
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled
Yes
Yes
Yes
No
Yes
Yes
Disabled
Yes
Yes
Yes
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled
Yes
Yes
Yes
No
Yes
Yes
Disabled
Yes
Yes
Yes
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled
None
Disabled
Disabled
- 31 -
Configuration 1
Configuration 2
Configuration 3
Configuration 4
Enabled
Fahrenheit
Enabled
Fahrenheit
Enabled
Fahrenheit
Enabled
Fahrenheit
English
English
English
English
English
English
See Zone Programming Default Configurations
English
English
Device Type
Response Type
New
New
Door
Door
Window
Motion Sensor
New
New
New
New
Key Fob
Key Fob
Key Fob
Key Fob
Key Fob
Key Fob
Key Fob
Key Fob
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Fire
Medical
Local Alarm
Police
Not Used
Not Used
Entry Exit 1
Entry Exit 1
Perimeter
Interior With Delay
Not Used
Not Used
Not Used
Not Used
Arm Away
Disarm
Arm Stay
No Response
Arm Away
Disarm
Arm Stay
No Response
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Fire No Verification
Not Used
Local Alarm
24-Hour Silent
Alarm
Report
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Yes
Yes
Yes
Yes
- 32 -
Chime
Supervision
Disabled
Disabled
Standard
Standard
Standard
Disabled
Standard
Standard
Standard
Standard
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Disabled
Disabled
Disabled
Disabled
End of Line
End of Line
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Button
Button
Button
Button
Button
Button
Button
Button
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Panic Trigger
Panic Trigger
Panic Trigger
Panic Trigger
Arm
Night
n/a
n/a
n/a
n/a
n/a
No
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Zone Descriptor
n/a
n/a
Front
Back
n/a
n/a
Main
Main
Main
Main
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Device Type
New
New
Door
Door
Door
Motion Sensor
Smoke Detector
New
New
New
New
Key Fob
Key Fob
Key Fob
Key Fob
Key Fob
Key Fob
Key Fob
Key Fob
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Fire
Medical
Local Alarm
Police
Alarm
Report
Not Used
Yes
Not Used
Yes
Entry Exit 1
Yes
Entry Exit 1
Yes
Entry Exit 1
Yes
Interior With Delay
Yes
Fire No Verification
Yes
Not Used
No
Not Used
No
Not Used
No
Not Used
No
Arm Away
Yes
Disarm
Yes
Arm Stay
Yes
No Response
No
Arm Away
Yes
Disarm
Yes
Arm Stay
Yes
No Response
No
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
Monitor
Yes
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Fire No Verification
Yes
24-Hour Auxiliary
Yes
Local Alarm
Yes
24-Hour Audible
Yes
Response Type
- 33 -
Chime
Supervision
Disabled
Disabled
Standard
Standard
Standard
Disabled
Disabled
Standard
Standard
Standard
Standard
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Disabled
Disabled
Disabled
Disabled
End of Line
End of Line
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Button
Button
Button
Button
Button
Button
Button
Button
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Panic Trigger
Panic Trigger
Panic Trigger
Panic Trigger
Arm
Night
n/a
n/a
n/a
n/a
n/a
No
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Zone Descriptor
n/a
n/a
Front
Back
Garage
n/a
n/a
Main
Main
Main
Main
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Device Type
Response Type
New
New
Door
Door
Window
Window
Window
Window
Motion Sensor
Smoke Detector
New
New
New
New
Key Fob
Key Fob
Key Fob
Key Fob
Key Fob
Key Fob
Key Fob
Key Fob
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Temperature
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Keypad
Fire
Medical
Local Alarm
Police
Not Used
Not Used
Entry Exit 1
Entry Exit 1
Perimeter
Perimeter
Perimeter
Perimeter
Interior With Delay
Fire No Verification
Not Used
Not Used
Not Used
Not Used
Arm Away
Disarm
No Response
No Response
Arm Away
Disarm
No Response
No Response
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Fire No Verification
Not Used
Local Alarm
24-Hour Silent
Alarm
Report
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
Yes
Yes
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Yes
Yes
Yes
Yes
- 34 -
Chime
Supervision
Disabled
Disabled
Standard
Standard
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Standard
Standard
Standard
Standard
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Disabled
Disabled
Disabled
Disabled
End of Line
End of Line
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Supervised
Button
Button
Button
Button
Button
Button
Button
Button
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
High Temp
Low Temp
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Panic Trigger
Panic Trigger
Panic Trigger
Panic Trigger
Arm
Night
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
No
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Zone Descriptor
n/a
n/a
Front
Back
n/a
n/a
n/a
n/a
n/a
n/a
Main
Main
Main
Main
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Flood
Environmental
Medical
Fire
x
x
Police
Garage Door
x
x
x
Temperature
Other
Local Alarm
Trouble
Garage Monitor
Garage
Silent Burglary
Glass Break
No Response
Disarm
Arm Away
Arm Stay
Not Used
Monitor
Motion Sensor
24 Hour Silent
24 Hour Audible
24 Hour Auxiliary
Carbon Monoxide
General Response
Window
Interior Follower
General Monitor
Device Type
Door
Day/Night
Resident Response
Response Type
Resident Monitor
Perimeter
Heat Sensor
Entry Exit 2
Smoke Detector
Entry Exit 1
Fire No Verification
Description
Four Green Bars
Three Green Bars
Two Green Bars
One Green Bar
Four Red Bars
Signal Strength
Greater than -27dBm
Greater than -45 dBm
Greater than -63 dBm
Greater than -81 dBm
Less than -81dBm (below threshold)
- 35 -
FCC IC Statement
This device complies with Part 15 of FCC Rules and RSS-210 of Industry Canada. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference
that may cause undesired operation.
Cet appareil est conforme la partie 15 des rgles de la FCC & de RSS-210 des Industries Canada. Son fonctionnement est soumis aux
conditions suivantes: (1) Cet appareil ne doit pas causer d' interferences nuisibles. (2) Cet appareil doit accepter toute interference
reue y compris les interferences causant une reception indsirable.
RF Exposure Warning
The antenna(s) used for this transmitter must be installed to provide a separation distance of at least 7.8 in (20 cm)
from all persons and must not be co-located or operated in conjunction with any other transmitter except in
accordance with FCC multi-transmitter product procedures.
Mise en Garde
Exposition aux Frequences Radio: L'antenne (s) utilise pour cet metteur doit tre installe une distance de
sparation d'au moins 7,8 pouces (20 cm) de toutes les personnes.
- 36 -
Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm
sensor or disconnect an alarm warning device.
Intrusion detectors (e.g., passive infrared detectors), smoke detectors, and many other sensing devices will not
work without power. Battery-operated devices will not work without batteries, with dead batteries, or if the
batteries are not put in properly. Devices powered solely by AC will not work if their AC power supply is cut off for
any reason, however briefly.
Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver.
Even if the signal path has been recently checked during a weekly test, blockage can occur if a metal object is
moved into the path.
A user may not be able to reach a panic or emergency button quickly enough.
While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not
activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data
published by the Federal Emergency Management Agency. Some of the reasons smoke detectors used in
conjunction with this System may not work are as follows. Smoke detectors may have been improperly installed
and positioned. Smoke detectors may not sense fires that start where smoke cannot reach the detectors, such as
in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on
another level of a residence or building. A second floor detector, for example, may not sense a first floor or
basement fire. Finally, smoke detectors have sensing limitations. No smoke detector can sense every kind of fire
every time. In general, detectors may not always warn about fires caused by carelessness and safety hazards like
smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical
circuits, children playing with matches, or arson. Depending on the nature of the fire and/or location of the smoke
detectors, the detector, even if it operates as anticipated, may not provide sufficient warning to allow all
occupants to escape in time to prevent injury or death.
Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their
installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple
beams of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They
cannot detect motion or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass
doors, or windows. Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows
or any part of the optical system can reduce their detection ability. Passive Infrared Detectors sense changes in
temperature; however, as the ambient temperature of the protected area approaches the temperature range of
90 to 105F (32 to 40C), the detection performance can decrease.
Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located
on the other side of closed or partly open doors. If warning devices are located on a different level of the
residence from the bedrooms, then they are less likely to waken or alert people inside the bedrooms. Even persons
who are awake may not hear the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or
other appliance, or by passing traffic. Finally, alarm warning devices, however loud, may not warn hearingimpaired people.
Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of
service or temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.
Even if the system responds to the emergency as intended, however, occupants may have insufficient time to
protect themselves from the emergency situation. In the case of a monitored alarm system, authorities may not
respond appropriately.
This equipment, like other electrical devices, is subject to component failure. Even though this equipment is
designed to last as long as 10 years, the electronic components could fail at any time.
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate
maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working
properly. The security keypad (and remote keypad) should be tested as well.
Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating
conditions. Longevity of batteries may be as much as 4 to 7 years, depending on the environment, usage, and the
specific wireless device being used. External factors such as humidity, high or low temperatures, as well as large
swings in temperature, may all reduce the actual battery life in a given installation. This wireless system, however, can
identify a true low battery situation, thus allowing time to arrange a change of battery to maintain protection for that
given point within the system.
Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a
substitute for insurance. Homeowners, property owners and renters should continue to act prudently in protecting
themselves and continue to insure their lives and property.
We continue to develop new and improved protection devices. Users of 7
alarm systems owe it to themselves and their loved ones to learn about these developments.
- 37 -
Agency Notices
1.
2.
3.
4.
For Residential Burglar Alarm installations with line security, total exit delay time must not exceed 60
seconds. For Burglar Alarm installations without line security, total exit delay time must not exceed 120
seconds.
Periodic testing must be at least every 24 hours.
Remote downloading without an alarm company technician on-site (unattended downloading) is not
permissible for ETL installations.
As SIA limits for delay of alarm reporting and sounding can exceed UL Standard limits for commercial and
residential applications, the following requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to a
remote monitoring location, or to delay the energizing of a local alarm sounding device to permit the
alarm system user to enter and disarm the system, or to arm the system and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.
Feature
Range
Shipping Default
SIA Requirement
Enabled
Enabled
Enabled
Enabled
Alarm Cancel
Enabled or Disabled
Enabled
Enabled
Number of
Reports
1 to 6 Reports
2 Reports
2 Reports
Alarm Report
Delay (Abort
Window)
30 seconds
30 seconds*
Entry Delay # 1
30 seconds
30 seconds minimum
Entry Delay # 2
30 seconds
30 seconds minimum
Exit Delay
60 Seconds
45 seconds minimum
Enabled or Disabled
Yes (Enabled)
Enabled
Exit Warning
Not selectable
Yes (Enabled)
Enabled
Auto Stay
Arming
Enabled or Disabled
Yes (Enabled)
Enabled
30 seconds and 2
minutes (in 30 second
increments), 3 minutes
None (Disabled)
Zones
Fire Alarms
Disabled
Disabled
User Guide
User Functions/
User Access
Duress
Duress Code is
Programmed by Master
User as User 48
Disabled
Disabled
System Test
n/a
n/a
Communications
Disabled
Disabled
Reporter/Options
System Settings
System Functions/
Testing the System**
* Combined Entry Delay and Alarm Report Delay (Abort Window) should not exceed 1 minute.
** Refer to the User Guide for procedures on Testing the System.
- 38 -
Specifications
Lyric Controller Series Residential Burglar and Fire Alarm Control Panel
Physical:
Dimensions:
8.5 (216mm) W x 6.65 (169mm) H x 1.3 (33mm) D
Electrical:
Voltage Input:
110VAC, 60 Hz/9 Vdc from plug-in 2.7A power supply
Rechargeable Backup Battery: Nickel-metal hydride battery pack rated at 7.2 Vdc
Communication:
Formats Supported:
ADEMCO Contact ID Reporting, 10 characters/sec
SIA/DCS Format, 2225Hz Handshake, Data Tones, 2025/2235Hz, baud
Hardwire Zones:
2K ohms, End of Line Resistor (EOLR), Normally Open (N/O) and Normally
Closed (N/C)
For patent information, see www.honeywell.com/patents
- 39 -
Glossary
AES Advanced Encryption Standard
APL Advanced Protection Logic
dBM decibels milliwatt (power ratio)
CDMA - Code Division Multiple Access is a channel access method used by various radio communication
technologies that allows many users to occupy the same time and frequency allocations in a given band/space.
DHCP Dynamic Host Configuration Protocol, which provides a mechanism for allocating IP addresses
dynamically so that addresses can be reused when hosts no longer need them.
DNS Domain Name System, which is a distributed hierarchical naming system used to resolve domain names
(e.g., www.yahoo.com) into numerical IP addresses (e.g., 204.17.25.1).
Ec/Io Signal to noise ratio of the current channel for CDMA (Measured in dB).
Eb/No Signal to noise ratio of the current channel for UTMS (3G) (Measured in dB).
ESN Electronic Serial Number (32 bit number that identifies a CDMA device)
Gateway IP Address A gateway (sometimes called a router) is a computer and/or software used to connect
two or more networks (including incompatible networks) and translates information from one network to the
other. The Gateway IP address is the IP address for the gateway.
GPRS General Packet Radio Service
GSM Global System for Mobile communications, which is an international standard for digital mobile phone
systems used for cellular communication.
HSDPA High-Speed Downlink Packet Access
HSPA High-Speed Packet Access
ICCID Integrated Circuit Card Identifier (SIM Card serial number)
IMEI International Mobile Equipment Identity number
IP Internet Protocol
IP Address A unique number consisting of four parts separated by periods, sometimes called a "dotted quad.,"
for example: 204.17.29.11, assigned to every computer/workstation connected to the Internet. IP numbers can
be "static" (assigned and unchanging) or "dynamic," assigned via DHCP at each and every startup.
ISP Internet Service Provider
KBPS Kilobits per second
MAC ID Media Access Code; located on the module label.
MEID Mobile Equipment Identifier (56 bit number that identifies a CDMA device)
NIC Network Interface Card
RSCP Received Signal Code Power (Ratio of RSSI and Ec/No)
RSSI Received Signal Strength Indication
SCID SIM Card ID
Subnet Mask A Subnet is a portion of a network that shares a network address with other portions of the
network, and is distinguished by a subnet number. The Subnet Mask is a 32-bit address mask used in IP to
indicate the bits of an IP address that are being used for the subnet address.
UMTS Universal Mobile Telecommunications Service
WEP Wired Equivalent Privacy
WPA WiFi Protected Access
WPS WiFi Protected Setup
- 40 -
Determine that the power supply and/or backup battery are supplying proper voltages.
Note the proper model number of this product, and the version level (if known) along with any
documentation that came with the product.
Having this information handy will make it easier for us to serve you quickly and effectively.
- 41 -
Index
24-Hour Silent ............................................................ 22
300-03864-AIO ........................................................... 7
300-03866-AIO ........................................................... 7
300-04063V1 .............................................................. 10
300-04705V1 .............................................................. 10
5800 Series Transmitter Loop Numbers .......... 14
5800 Series Transmitters ....................................... 13
5802MN ......................................................................... 13
5804E ............................................................................ 13
5816 ................................................................................. 13
5834-4 ........................................................................... 13
5878 ................................................................................ 13
AC Power...................................................................... 10
AC Power Loss ............................................................. 7
ADEMCO Contact ID ............................................... 39
Armed System Test ................................................. 28
Audio Alarm Verification (Two-Way Voice
Feature) ................................................................... 25
Babysitter Code ........................................................ 22
Backup Battery .................................................. 10, 39
Button Transmitters ................................................. 13
CDMA Cellular Communications Module .......... 11
Communication Modules ......................................... 11
Contact ID Event Log Codes ........................ 26, 27
Contact ID Reporting .............................................. 39
Contacting Technical Support ............................. 41
Devices ............................................................................2
Duress Code ............................................................... 22
Enter Installer Programming Mode .................... 18
Enter/Change The Master Code ......................... 22
Entry Delay ................................................................. 20
Entry/Exit Burglary .................................................. 20
Exit Delay ..................................................... 20, 28, 38
Exit Programming Mode ......................................... 19
GSM Cellular Communications Module .............. 11
Home Screen ............................................................... 16
House ID Code ............................................................ 13
House Identification ................................................. 13
Installer Code ............................................................. 22
Installer Tools Menu Screen................................... 18
Installing Wireless Zones ........................................ 14
Key/Touchscreen Operation................................ 22
Liquid Crystal Display (LCD) Touch-Screen ... 15
Loading Factory Defaults ....................................... 19
LYRIC-3G ....................................................................... 11
LYRIC-CDMA ................................................................ 11
Master Code ............................................................... 22
Master Security Code.............................................. 22
- 42 -
- 43 -
MyWebTech
800-18076X
800-18076
11/15 Rev. B
Warranty
Patents